This document contains panel schedules and notes for the NAMA 216042 - Lincoln Memorial Rehabilitation project. The schedules provide circuit details for multiple new and existing panelboards, including circuit information, load calculations, and panel specifications. Panelboards will be installed at various locations within the Lincoln Memorial, such as the chamber level, attic level, and utility level. The project solicitation is for rehabilitation work at the Lincoln Memorial and seeks bids from contractors to perform electrical work including installing new panelboards and refeeding existing circuits as detailed in the panel schedules. The solicitation was issued by the National Park Service National Office and references solicitation number 140P2022R0046.
View the file
Other files
Show 40 more
Latest 50 of 171 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1. TURN ALL SPARE CIRCUIT BREAKERS TO "OFF" POSITION AT COMPLETION OF WORK.
2. AT COMPLETION OF THE PROJECT, PROVIDE TYPE WRITTEN SCHEDULES FOR ALL PANEL BOARDS
UTILIZED DURING THE CONSTRUCTION PROCESS INDICATING AS-BUILT CONDITIONS.
3. ALL UNGROUNDED AND GROUNDED CONDUCTORS OF EACH MULTI-WIRE BRANCH CIRCUIT ARE TO BE GROUPED BY WIRE TIES OR SIMILAR MEANS AT LEAST ONE LOCATION EITHER WITHIN THE PANEL
BOARD OR AT THE OTHER POINT OF ORIGINATION.
4. ALL REUSED CIRCUIT NUMBERS INDICATED ON PLAN ARE BASED ON EXISTING DOCUMENTS AND MAY NOT MATCH THE ACTUAL AS-BUILT CONDITION OF THE EXISTING CIRCUITS SERVING THE AREA.
CONTRACTOR TO VERIFY THE EXACT CIRCUIT NUMBERS DURING CONSTRUCTION.
5. ALL NEW CIRCUIT BREAKERS WHERE PROVIDED MUST BE COMPATIBLE WITH THE EXISTING PANEL
BOARD AND SHALL MATCH THE EXISTING UL LISTING, MANUFACTURER MAKE AND AIC RATING.
6. PROVIDE ARC FLASH WARNING LABELS FOR ALL NEW PANEL BOARDS.
PANELBOARD SCHEDULE NOTES
DATE:
DESIGNED:
TECH. REVIEW:
SUB SHEET NO.
PMIS/PKG NO.
DRAWING NO.
SHEET
TITLE OF SHEET
OF
132917
NAMA-216042
TITLE OF SHEETSEAL
B
IM
L in c o ln
M e m o ri a l U n d e rc ro ft L in c o ln
M e m o ri a l_ E le c v .r v t
DT
DT E72WJR
05/13/2022
PANEL SCHEDULES
LINCOLN MEMORIAL REHABILITATION
NATIONAL MALL AND MEMORIAL PARKS 125
3AH(N) 3BL(N) GR
ATTIC(X) AV(N) 4AL(N)
TOTAL AMPS 8 A 8 A
TOTAL LOAD 2.78 kVA 2.80 kVA
HEATING 0.00 kVA 125% 0.00 kVA RECEPTACLE 1.22 kVA 100% FIRST 10KVA, 50% OTHER 1.22 kVA
MOTOR 0.00 kVA 125% LARGEST, 100% OTHER 0.00 kVA LIGHTING 0.06 kVA 125% 0.08 kVA
POWER 1.50 kVA 100% 1.50 kVA
LOAD CLASSIFICATION CONNECTED (KVA) DEMAND FACTOR DEMAND (KVA)
PHASE SUBTOTAL (AMPS): 10 A 6 A 7 A
PHASE SUBTOTAL (kVA): 1.25... 0.75... 0.7...
A B C
TOTAL PHASE SUMMARY
BUSSED SPACE -- -- -- 23 0.00 0.00 24 -- -- -- BUSSED SPACE
BUSSED SPACE -- -- -- 21 0.00 0.00 22 -- -- -- BUSSED SPACE
SPARE 20 A 1 19 0.00 0.00 20 1 20 A SPARE
-- -- -- -- 17 0.00 0.00 18 1 20 A SPARE
-- -- -- -- 15 0.00 0.00 16 1 20 A SPARE
MAIN BREAKER 70 A 3 13 0.00 0.00 14 1 20 A SPARE
SPARE 20 A 1 11 0.00 0.00 12 1 20 A SPARE
SPARE 20 A 1 9 0.00 0.00 10 1 20 A SPARE
U.C. REFR. 20 A 1 7 0.50 0.00 8 1 20 A SPARE
RECPTS-RM 203 20 A 1 5 0.72 0.06 6 1 20 A LTG-RMS 203 AND 203A
-- -- -- -- 3 0.50 0.25 4 -- -- -- --
FTR-3 20 A 2 1 0.50 0.25 2 2 20 A FTR-2
DESCRIPTION
BRKR
NOTES
BRKR
AMP,
POLES
CKT
NO
A B C A B C
CKT
NO
BRKR
AMP,
POLES
BRKR
NOTES
DESCRIPTION
LEFT SIDE, kVA RIGHT SIDE, kVA
REMARKS:
ENCLOSURE Type 1 CALCULATED AVAILABLE FAULT... 6 kA BUS RATING 125 A MOUNTING SURFACE SCCR 10 kA
MAIN RATING 50 A 3 PHASE 4 WIRE FED FROM 600A BUS...
MAIN TYPE MCB VOLTAGE 120/208 Wye LOCATION CHAMBER LEVEL POWER PLAN, 3AH(N)
TOTAL AMPS 16 A 17 A
TOTAL LOAD 5.88 kVA 6.14 kVA
HEATING 0.00 kVA 125% 0.00 kVA RECEPTACLE 0.00 kVA 100% FIRST 10KVA, 50% OTHER 0.00 kVA
MOTOR 5.60 kVA 125% LARGEST, 100% OTHER 5.80 kVA LIGHTING 0.28 kVA 125% 0.34 kVA
POWER 0.00 kVA 100% 0.00 kVA
LOAD CLASSIFICATION CONNECTED (KVA) DEMAND FACTOR DEMAND (KVA)
PHASE SUBTOTAL (AMPS): 14 A 16 A 20 A
PHASE SUBTOTAL (kVA): 1.64... 1.84... 2.4...
A B C
TOTAL PHASE SUMMARY
BUSSED SPACE -- -- -- 19 0.00 0.00 20 -- -- -- BUSSED SPACE
-- -- -- -- 17 0.00 0.00 18 -- -- -- BUSSED SPACE
-- -- -- -- 15 0.00 0.00 16 -- -- -- BUSSED SPACE
MAIN BREAKER 50 A 3 13 0.00 0.00 14 1 20 A SPARE
(X) CORE WALL RECEPTACLES (*) 20 A 1 11 0.80 0.00 12 1 20 A SPARE
(X) CORE WALL RECEPTACLES (*) 20 A 1 9 0.80 0.80 10 1 20 A EXISTING LOAD (*)
(X) CORE WALL LIGHTS (*) 20 A 1 7 0.80 0.80 8 1 20 A EXISTING LOAD (*)
(X) ATTIC WALL LIGHTS (*) 20 A 1 5 0.80 0.80 6 1 20 A (X) ATTIC WALL RECEPTACLES (*)
SPARE 20 A 1 3 0.00 0.24 4 1 20 A LTG RMS 151, 153, 154 AND ST1.1
SPARE 20 A 1 1 0.00 0.04 2 1 20 A LTG
DESCRIPTION
BRKR
NOTES
BRKR
AMP,
POLES
CKT
NO
A B C A B C
CKT
NO
BRKR
AMP,
POLES
BRKR
NOTES
DESCRIPTION
LEFT SIDE, kVA RIGHT SIDE, kVA
REMARKS: (*) EXISTING TO REMAIN BRANCH CIRCUITS REFEED FROM NEW PANELBOARD.
ENCLOSURE Type 1 CALCULATED AVAILABLE FAULT... 6 kA BUS RATING 125 A MOUNTING Surface SCCR 10 kA
MAIN RATING 70 A 3 PHASE 4 WIRE FED FROM 600A BUS...
MAIN TYPE MCB VOLTAGE 120/208 Wye LOCATION BOH ACCESS 154
3BL(N)
TOTAL AMPS 153 A 158 A
TOTAL LOAD 55.25 kVA 56.79 kVA
HEATING 0.00 kVA 125% 0.00 kVA RECEPTACLE 0.90 kVA 100% FIRST 10KVA, 50% OTHER 0.90 kVA
MOTOR 16.90 kVA 125% LARGEST, 100% OTHER 18.43 kVA LIGHTING 0.05 kVA 125% 0.06 kVA
POWER 0.00 kVA 100% 0.00 kVA
LOAD CLASSIFICATION CONNECTED (KVA) DEMAND FACTOR DEMAND (KVA)
PHASE SUBTOTAL (AMPS): 161 A 155 A 147 A
PHASE SUBTOTAL (kVA): 19.1... 18.4... 17
A B C
TOTAL PHASE SUMMARY
-- -- -- -- 41 0.80 0.00 42 1 20 A SPARE
-- -- -- -- 39 0.80 0.00 40 1 20 A SPARE
(X) ATTIC FAN #5 (*) 20 A 3 37 0.80 0.00 38 1 20 A SPARE
EXISTING LOAD (*) 20 A 1 35 0.80 0.00 36 1 20 A SPARE
(X) TEMP "D" (*) 20 A 1 33 1.00 0.00 34 1 20 A SPARE
(X) TEMP "D" (*) 20 A 1 31 1.00 0.00 32 1 20 A SPARE
(X) NORTH MURAL LIGHTS (*) 20 A 1 29 1.00 0.00 30 1 20 A SPARE
(X) NORTH MURAL LIGHTS (*) 20 A 1 27 1.00 0.80 28 -- -- -- --
(X) NORTH MURAL LIGHTS (*) 20 A 1 25 1.00 0.80 26 -- -- -- --
(X) ATTIC CEILING LIGHTS (*) 20 A 1 23 1.00 0.80 24 3 20 A (X) ATTIC FAN #3 (*)
(X) ATTIC CEILING LIGHTS (*) 20 A 1 21 1.00 0.80 22 1 20 A EXISTING LOAD (*)
(X) ATTIC CEILING LIGHTS (*) 20 A 1 19 1.00 0.80 20 1 20 A EXISTING LOAD (*)
(X) SOUTH MURAL LIGHTS (*) 20 A 1 17 1.00 0.80 18 1 20 A EXISTING LOAD (*)
(X) SOUTH MURAL LIGHTS (*) 20 A 1 15 1.00 0.80 16 1 20 A EXISTING LOAD (*)
(X) SOUTH MURAL LIGHTS (*) 20 A 1 13 1.00 0.80 14 1 20 A EXISTING LOAD (*)
(X) ATTIC LTS EAST- STORAGE LTS... 20 A 1 11 1.00 0.80 12 1 20 A EXISTING LOAD (*)
(X) ATTIC FAN (*) 20 A 1 9 0.80 0.80 10 1 20 A EXISTING LOAD (*)
(X) ATTIC CEILING LIGHTS (*) 20 A 1 7 1.00 0.40 8 1 20 A (X) ATTIC RECEPTACLE EAST SIDE...
-- -- -- -- 5 9.63 0.00 6 -- -- -- --
-- -- -- -- 3 9.63 0.00 4 -- -- -- --
PANEL ATTIC (X) 100 A 3 1 9.63 0.95 2 3 70 A GR
DESCRIPTION
BRKR
NOTES
BRKR
AMP,
POLES
CKT
NO
A B C A B C
CKT
NO
BRKR
AMP,
POLES
BRKR
NOTES
DESCRIPTION
LEFT SIDE, kVA RIGHT SIDE, kVA
REMARKS: (*) EXISTING TO REMAIN BRANCH CIRCUITS REFEED FROM NEW PANELBOARD.
ENCLOSURE Type 1 CALCULATED AVAILABLE FAULT... 9 kA BUS RATING 225 A MOUNTING Surface SCCR 18 kA
MAIN RATING 200 A 3 PHASE 4 WIRE FED FROM 800A BUS...
MAIN TYPE MCB VOLTAGE 120/208 Wye LOCATION CHAMBER LEVEL POWER...
4AL(N)
TOTAL AMPS 80 A 84 A
TOTAL LOAD 28.90 kVA 30.43 kVA
HEATING 0.00 kVA 125% 0.00 kVA RECEPTACLE 0.00 kVA 100% FIRST 10KVA, 50% OTHER 0.00 kVA
MOTOR 16.90 kVA 125% LARGEST, 100% OTHER 18.43 kVA LIGHTING 0.00 kVA 125% 0.00 kVA
POWER 0.00 kVA 100% 0.00 kVA
LOAD CLASSIFICATION CONNECTED (KVA) DEMAND FACTOR DEMAND (KVA)
PHASE SUBTOTAL (AMPS): 80 A 80 A 80 A
PHASE SUBTOTAL (kVA): 9.63... 9.63... 9.6...
A B C
TOTAL PHASE SUMMARY
EXISTING LOAD 20 A 1 29 0.80 0.80 30 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 27 0.80 0.80 28 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 25 0.80 0.80 26 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 23 0.80 0.80 24 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 21 0.80 0.80 22 1 20 A EXISTING LOAD
EXISTING LOAD 20 A 1 19 0.80 0.80 20 1 20 A EXISTING LOAD
-- -- -- -- 17 0.90 0.80 18 1 20 A EXISTING LOAD
-- -- -- -- 15 0.90 0.80 16 1 20 A EXISTING LOAD
EF-6 20 A 3 13 0.90 0.80 14 1 20 A EXISTING LOAD
-- -- -- -- 11 0.90 2.03 12 -- -- -- -- -- -- -- -- 9 0.90 2.03 10 -- -- -- --
EF-4 20 A 3 7 0.90 2.03 8 3 35 A OA-1
-- -- -- -- 5 0.90 0.90 6 -- -- -- -- -- -- -- -- 3 0.90 0.90 4 -- -- -- --
EF-3 20 A 3 1 0.90 0.90 2 3 20 A EF-5
DESCRIPTION
BRKR
NOTES
BRKR
AMP,
POLES
CKT
NO
A B C A B C
CKT
NO
BRKR
AMP,
POLES
BRKR
NOTES
DESCRIPTION
LEFT SIDE, kVA RIGHT SIDE, kVA
REMARKS:
ENCLOSURE Type 1 CALCULATED AVAILABLE FAULT... 4 kA BUS RATING 125 A MOUNTING Surface SCCR 10 kA
MAIN RATING 100 A 3 PHASE 4 WIRE FED FROM 4AL(N)
MAIN TYPE MCB VOLTAGE 120/208 Wye LOCATION ATTIC LEVEL, ATTIC (X)
TOTAL AMPS 42 A 42 A
TOTAL LOAD 15.24 kVA 15.24 kVA
HEATING 0.00 kVA 125% 0.00 kVA RECEPTACLE 5.72 kVA 100% FIRST 10KVA, 50% OTHER 5.72 kVA
MOTOR 0.00 kVA 125% LARGEST, 100% OTHER 0.00 kVA LIGHTING 0.00 kVA 125% 0.00 kVA
POWER 7.22 kVA 100% 7.22 kVA
LOAD CLASSIFICATION CONNECTED (KVA) DEMAND FACTOR DEMAND (KVA)
PHASE SUBTOTAL (AMPS): 47 A 48 A 39 A
PHASE SUBTOTAL (kVA): 5.46... 5.60... 4.6...
A B C
TOTAL PHASE SUMMARY
-- -- -- -- 83 0.60 0.00 84 -- -- -- BUSSSED SPACE
-- -- -- -- 81 0.60 0.00 82 -- -- -- BUSSSED SPACE
SPD 30 A 3 79 0.60 0.00 80 -- -- -- BUSSSED SPACE
SPARE 20 A 1 77 0.00 0.00 78 1 20 A SPARE
SPARE 20 A 1 75 0.00 0.00 76 1 20 A SPARE
SPARE 20 A 1 73 0.00 0.00 74 1 20 A SPARE
SPARE 20 A 1 71 0.00 0.00 72 1 20 A SPARE
SPARE 20 A 1 69 0.00 0.00 70 1 20 A SPARE
SPARE 20 A 1 67 0.00 0.00 68 1 20 A SPARE
SPARE 20 A 1 65 0.00 0.00 66 1 20 A SPARE
SPARE 20 A 1 63 0.00 0.00 64 1 20 A SPARE
SPARE 20 A 1 61 0.00 0.00 62 1 20 A SPARE
SPARE 20 A 1 59 0.00 0.00 60 1 20 A SPARE
SPARE 20 A 1 57 0.00 0.00 58 1 20 A SPARE
SPARE 20 A 1 55 0.00 0.00 56 1 20 A SPARE
SPARE 20 A 1 53 0.00 0.00 54 1 20 A SPARE
SPARE 20 A 1 51 0.00 0.00 52 1 20 A SPARE
SPARE 20 A 1 49 0.00 0.00 50 1 20 A SPARE
SPARE 20 A 1 47 0.00 0.00 48 1 20 A SPARE
SPARE 20 A 1 45 0.00 0.00 46 1 20 A SPARE
SPARE 20 A 1 43 0.00 0.00 44 1 20 A SPARE
SPARE 20 A 1 41 0.00 0.00 42 1 20 A SPARE
SPARE 20 A 1 39 0.00 0.00 40 1 20 A SPARE
SPARE 20 A 1 37 0.00 0.00 38 1 20 A SPARE
SPARE 20 A 1 35 0.00 0.00 36 1 20 A SPARE
-- -- -- -- 33 0.25 0.00 34 1 20 A SPARE
RECEPT RM 017 20 A 2 31 0.25 0.00 32 1 20 A SPARE
RECEPT RM 017 20 A 1 29 0.36 0.00 30 1 20 A SPARE
-- -- -- -- 27 0.25 0.50 28 1 20 A T-COIL DRIVER EQUIPMENT
RECEPT RM 017 20 A 2 25 0.25 0.50 26 1 20 A T-COIL DRIVER EQUIPMENT
RECEPTS RM 017 20 A 1 23 0.72 0.00 24 1 20 A POWER FOR AV DEVICE RM 141
POWER FOR AV DEVICE RM 143 20 A 1 21 0.50 0.50 22 1 20 A POWER FOR AV DEVICE RM 141 POWER FOR AV DEVICE RM 143 20 A 1 19 0.50 0.50 20 1 20 A POWER FOR AV DEVICE RM 120 POWER FOR AV DEVICE RM 120 20 A 1 17 0.50 0.50 18 1 20 A POWER FOR AV DEVICE RM 120 POWER FOR AV DEVICE RM 120 20 A 1 15 0.50 0.50 16 1 20 A POWER FOR AV DEVICE RM 120 POWER FOR AV DEVICE RM 120 20 A 1 13 0.50 0.50 14 1 20 A POWER FOR AV DEVICE RM 120 POWER FOR AV DEVICE RM 120 20 A 1 11 0.50 0.50 12 1 20 A POWER FOR AV DEVICE RM 120 POWER FOR AV DEVICE RM 120 20 A 1 9 0.50 0.50 10 1 20 A POWER FOR AV DEVICE RM 120 POWER FOR AV DEVICE RM 120 20 A 1 7 0.50 0.50 8 1 20 A POWER FOR AV DEVICE RM 120 POWER FOR AV DEVICE RM 120 20 A 1 5 0.50 0.50 6 1 20 A POWER FOR AV DEVICE RM 120
POWER FOR AV DEVICERM 123 20 A 1 3 0.50 0.50 4 1 20 A POWER FOR AV DEVICE RM 120
POWER FOR AV DEVICE RM 123 20 A 1 1 0.36 0.50 2 1 20 A POWER FOR AV DEVICE RM 120
DESCRIPTION
BRKR
NOTES
BRKR
AMP,
POLES
CKT
NO
A B C A B C
CKT
NO
BRKR
AMP,
POLES
BRKR
NOTES
DESCRIPTION
LEFT SIDE, kVA RIGHT SIDE, kVA
REMARKS:
ENCLOSURE Type 1 CALCULATED AVAILABLE FAULT... 2 kA BUS RATING 125 A MOUNTING Surface SCCR 10 kA
MAIN RATING 100 A 3 PHASE 4 WIRE FED FROM 800A BUS...
MAIN TYPE MCB VOLTAGE 120/208 Wye LOCATION UTILITY LEVEL POWER...
AV(N)
TOTAL AMPS 3 A 3 A
TOTAL LOAD 0.95 kVA 0.96 kVA
HEATING 0.00 kVA 125% 0.00 kVA RECEPTACLE 0.90 kVA 100% FIRST 10KVA, 50% OTHER 0.90 kVA
MOTOR 0.00 kVA 125% LARGEST, 100% OTHER 0.00 kVA LIGHTING 0.05 kVA 125% 0.06 kVA
POWER 0.00 kVA 100% 0.00 kVA
LOAD CLASSIFICATION CONNECTED (KVA) DEMAND FACTOR DEMAND (KVA)
PHASE SUBTOTAL (AMPS): 8 A 0 A 0 A
PHASE SUBTOTAL (kVA): 0.95... 0.00... 0.0...
A B C
TOTAL PHASE SUMMARY
SPARE 20 A 1 17 0.00 0.00 18 1 20 A SPARE
SPARE 20 A 1 15 0.00 0.00 16 1 20 A SPARE
SPARE 20 A 1 13 0.00 0.00 14 1 20 A SPARE
SPARE 20 A 1 11 0.00 0.00 12 1 20 A SPARE
SPARE 20 A 1 9 0.00 0.00 10 1 20 A SPARE
SPARE 20 A 1 7 0.00 0.00 8 1 20 A SPARE
SPARE 20 A 1 5 0.00 0.00 6 1 20 A SPARE
3 0.00 4 1 20 A SPARE
RECEPTS RMS 204 AND 205 20 A 1 1 0.90 0.05 2 1 20 A LGT-RMS 204 AND 205
DESCRIPTION
BRKR
NOTES
BRKR
AMP,
POLES
CKT
NO
A B C A B C
CKT
NO
BRKR
AMP,
POLES
BRKR
NOTES
DESCRIPTION
LEFT SIDE, kVA RIGHT SIDE, kVA
REMARKS:
ENCLOSURE Type 1 CALCULATED AVAILABLE FAULT... 9 kA BUS RATING 100 A MOUNTING Surface SCCR 18 kA
MAIN RATING 70 A 3 PHASE 4 WIRE FED FROM 4AL(N)
MAIN TYPE MLO VOLTAGE 120/208 Wye LOCATION CHAMBER LEVEL POWER...
GR(N)
KEY NOTES
1. PANELBOARD SECTION 1 IS FROM 1 TO 42 POLES,
PANELBOARD SECTION 2 IS FROM 43 TO 84.
NO. REVISION DATE BY
B1 BID ADDENDUM 2 6/24/2022 AEI
B2 BID ADDENDUM 3 7/01/2022 AEI
B1 B1 B1
B1 B1 B1
B2
07/01/2022
| Sheets |
| E14 - EXHIBIT LEVEL - POWER - SE PARTIAL PLAN |
| E15 - EXHIBIT LEVEL - POWER - NE PARTIAL PLAN |
| E45 - EXHIBIT LEVEL - CEILING LIGHTING - SE PARTIAL PLAN |
| E46 - EXHIBIT LEVEL - CEILING LIGHTING - NE PARTIAL PLAN |
| E53 - EXHIBIT LEVEL - WALL/BACK LIGHTING - SE PARTIAL PLAN 2 |
| E54 - EXHIBIT LEVEL - WALL/BACK LIGHTING - NE PARTIAL PLAN 2 |
| E72 - PANEL SCHEDULES |
File details come from the government source that posted it. Updated .