INTERNAL INSPECTION LOG
FLow Measurement
Date: 2/12/2010
Technician: ADS
ADS Environmental Services
16H3-009CA 16H3-076C
Downstream Line Depth 24 7
Sewer Plug Locations
None
Dyed-Water Flood Sketch None
Upstream Line Depth 7 10
ADDITIONAL INFORMATION
Type Of Sewer Combination
Harlem Baden Hebert
LOCATION: Esmt off Idadale Avenue
PROJECT:
Total Line Length 56
Type Of Pipe RCP
Joint Spacing 0
Pipe Diameter 72x96
Avg. Depth 16.2
Uncapped SC's
Comments: Dataview shows "16H3-076C to 16H3-238C" -- Should show "16H3-076C to 16H3-009CA"
TAPE NO. 15
Start Counter 14101
End Counter 15111 ft.
ft. in.
in.
l.f.
l.f.
in.
ft.TV Line Length 56 l.f.
TV against the direction of flow
Time: 10:40 AM
Precleaning N
Upstream Structure Downstream Structure
End Inspection Start Inspection
Capped SC's
Distance Defect Description Clock Ref.
GPM Photo No.
Defect
0 MH 16H3-076C 1BDMH
2-54 Less Than 1/8-Pipe Water Depth W 1
ALIGN
2-54 Sludge/Sand & Grit (10-25% dia.)
SGR 2
DEBRIS
2 72-inch RCP at startGCC
16 Pipe Material or Liner Change -- Changes to CON 2PSHP
16 Pipe Shape or Size Change -- Changes to 72x96PSIZ
21 9Tap - Break-in - Fair to Good Condition -- No protrusion -- 12-inch VCP -- Called SNP 16H3-076CA
TB 1
LAT'L
23 9Tap - Break-in - Fair to Good Condition -- No protrusion -- 12-inch VCP -- Called SNP 16H3-075C
TB 1
LAT'L
23 Light to Moderate Corrosion/Erosion
SR 2
DETER
30 Sludge/Sand & Grit (25-33% dia.)
SGR 3
DEBRIS
42 Bend to Right (slight-moderate -- 15-45 degrees) 5
BR 2
ALIGN
53 5Tap - Break-in - Cannot effectively evaluate 6
TBX 3
LAT'L
Page 1 of 4 From MH 16H3-009CA To 16H3-076C
Distance Defect Description Clock Ref.
GPM Photo No.
Defect
56 New Structure -- Not on Prints -- Visible -- Called 16H3-009CANEWV
56 MH 16H3-009CA 7EUMH
Page 2 of 4 From MH 16H3-009CA To 16H3-076C
LS 16H3-009CA to 16H3-076C
Harlem Baden Hebert TV PHOTOS
FLow Measurement TV against the direction of flow
0 l.f.PHOTO 1 MH 16H3-076C 16 l.f.PHOTO 2 Pipe Material or Liner Change -- Changes to CON
21 l.f.PHOTO 3 Tap - Break-in - Fair to Good Condition -- Called SNP 16H3-076CA -- No protrusion --
12-inch VCP
23 l.f.PHOTO 4 Tap - Break-in - Fair to Good Condition -- Called SNP 16H3-075C -- No protrusion --
12-inch VCP
42 l.f.PHOTO 5 Bend to Right (slight-moderate -- 15-45 degrees)
53 l.f.PHOTO 6 Tap - Break-in - Cannot effectively evaluate
Page 3 of 4 From MH 16H3-009CA To 16H3-076C
56 l.f.PHOTO 7 MH 16H3-009CA
Page 4 of 4 From MH 16H3-009CA To 16H3-076C