INTERNAL INSPECTION LOG
FLow Measurement
Date: 2/12/2010
Technician: ADS
ADS Environmental Services
16H3-007C 16H3-008C
Downstream Line Depth NA
Sewer Plug Locations
None
Dyed-Water Flood Sketch None
Upstream Line Depth NA
ADDITIONAL INFORMATION
Type Of Sewer Sanitary
Harlem Baden Hebert
LOCATION: Esmt off Idadale Avenue
PROJECT:
Total Line Length 149
Type Of Pipe RCB
Joint Spacing
Pipe Diameter 60x60
Avg. Depth
Uncapped SC's
Comments:
TAPE NO. 17
Start Counter 02330
End Counter 03121 ft.
ft. in.
in.
l.f.
l.f.
in.
ft.TV Line Length 149 l.f.
TV against the direction of flow
Time: 12:50 PM
Precleaning N
Upstream Structure Downstream Structure
End Inspection Start Inspection
Capped SC's
Distance Defect Description Clock Ref.
GPM Photo No.
Defect
0 MH 16H3-008CBDMH
2-147 Less Than 1/8-Pipe Water Depth W 1
ALIGN
2-147 Sludge/Sand & Grit (<10% dia.)
SGR 1
DEBRIS
8 11Tap - Break-in - Fair-Poor Condition -- No protrusion -- 6-inch VCP -- MD's
TB 3
LAT'L
14 Evidence of Leakage -- Slight to Moderate -- MD's at walls 2
EL 2
LEAK
50 General Condition Photo 3GCP
106 General Condition Photo 4GCP
149 MH 16H3-007C 5EUMH
Page 1 of 2 From MH 16H3-007C To 16H3-008C
LS 16H3-007C to 16H3-008C
Harlem Baden Hebert TV PHOTOS
FLow Measurement TV against the direction of flow
8 l.f.PHOTO 1 Tap - Break-in - Fair-Poor Condition -- MD's -- No protrusion -- 6-inch VCP
14 l.f.PHOTO 2 Evidence of Leakage -- Slight to Moderate -- MD's at walls
50 l.f.PHOTO 3 General Condition Photo 106 l.f.PHOTO 4 General Condition Photo
149 l.f.PHOTO 5 MH 16H3-007C
Page 2 of 2 From MH 16H3-007C To 16H3-008C