INTERNAL INSPECTION LOG
FLow Measurement
Date: 2/11/2010
Technician: ADS
ADS Environmental Services
16G4-280C 16G4-237C
Downstream Line Depth NA
Sewer Plug Locations
None
Dyed-Water Flood Sketch None
Upstream Line Depth NA
ADDITIONAL INFORMATION
Type Of Sewer Combined
Harlem Baden Hebert
LOCATION: Easement Hamilton Avenue
PROJECT:
Total Line Length 523
Type Of Pipe RCP
Joint Spacing 0
Pipe Diameter 72x84
Avg. Depth
Uncapped SC's
Comments:
TAPE NO. 18
Start Counter 01355
End Counter 03020 ft.
ft. in.
in.
l.f.
l.f.
in.
ft.TV Line Length 523 l.f.
Time: 1:45 PM
Precleaning N
Upstream Structure Downstream Structure
Start Inspection End Inspection
Capped SC's
Distance Defect Description Clock Ref.
GPM Photo No.
Defect
0 MH 16G4-280C 1BUMH
2-521 Less Than 1/8-Pipe Water Depth W 1
ALIGN
2-521 Minimal to No Debris in Pipe
SGR
DEBRIS
2-521 Evidence of Leakage -- Slight
EL 1
LEAK
17 12Leak in Brickwork/Masonry (See I/I Severity Value) 2
LB
LEAK
67 9Special Structure - Node Point/Junction -- Called SNP 16G4-279C 3STRJ
99 General Condition Photo 4GCP
154 2Leak in Brickwork/Masonry (See I/I Severity Value) 5
LB
LEAK
154 Leak - GW Infiltration (Heavy 5-15 gpm) 5
IGW 4
LEAK
220 General Condition Photo 6GCP
246 Pipe Shape or Size Change -- Change to 94 x 92-inchPSIZ
276 8Tap - Factory - Cannot effectively evaluate -- No protrusion -- 15-inch VCP -- Full of deposits -- Possibly capped
TFX 3
LAT'L
Page 1 of 4 From MH 16G4-280C To 16G4-237C
Distance Defect Description Clock Ref.
GPM Photo No.
Defect
282 3Tap - Factory - Cannot effectively evaluate -- No protrusion -- 15-inch VCP -- Full of deposits -- Possibly capped
TFX 3
LAT'L
311 General Condition Photo 9GCP
402 General Condition Photo 10GCP
483 General Condition Photo 11GCP
523 MH 16G4-237C 12EDMH
Page 2 of 4 From MH 16G4-280C To 16G4-237C
LS 16G4-280C to 16G4-237C
Harlem Baden Hebert TV PHOTOS
FLow Measurement
0 l.f.PHOTO 1 MH 16G4-280C 17 l.f.PHOTO 2 Leak in Brickwork/Masonry (See I/I Severity Value)
67 l.f.PHOTO 3 Special Structure - Node Point/Junction -- Called SNP 16G4-279C
99 l.f.PHOTO 4 General Condition Photo
154 l.f.PHOTO 5 Leak in Brickwork/Masonry (See I/I Severity Value)
220 l.f.PHOTO 6 General Condition Photo
Page 3 of 4 From MH 16G4-280C To 16G4-237C
276 l.f.PHOTO 7 Tap - Factory - Cannot effectively evaluate -- Full of deposits -- Possibly capped -- No protrusion -- 15-inch VCP
282 l.f.PHOTO 8 Tap - Factory - Cannot effectively evaluate -- Full of deposits -- Possibly capped -- No protrusion -- 15-inch VCP
311 l.f.PHOTO 9 General Condition Photo 402 l.f.PHOTO 10 General Condition Photo
483 l.f.PHOTO 11 General Condition Photo 523 l.f.PHOTO 12 MH 16G4-237C
Page 4 of 4 From MH 16G4-280C To 16G4-237C