INTERNAL INSPECTION LOG
FLow Measurement
Date: 2/12/2010
Technician: ADS
ADS Environmental Services
16H3-009C 16H3-009CA
Downstream Line Depth 7 10
Sewer Plug Locations
None
Dyed-Water Flood Sketch None
Upstream Line Depth NA
ADDITIONAL INFORMATION
Type Of Sewer Combination
Harlem Baden Hebert
LOCATION: Esmt off Idadale Avenue
PROJECT:
Total Line Length 123
Type Of Pipe VAR
Joint Spacing
Pipe Diameter VAR
Avg. Depth
Uncapped SC's
Comments: Dataview shows "16H3-238C to 16H3-009C" -- Should show "16H3- 009CA to 16H3-009C"
TAPE NO. 17
Start Counter 00000
End Counter 01339 ft.
ft. in.
in.
l.f.
l.f.
in.
ft.TV Line Length 123 l.f.
TV against the direction of flow
Time: 11:10 AM
Precleaning N
Upstream Structure Downstream Structure
End Inspection Start Inspection
Capped SC's
Distance Defect Description Clock Ref.
GPM Photo No.
Defect
0 MH 16H3-009CA 1BDMH
2-121 Less Than 1/8-Pipe Water Depth W 1
ALIGN
2-121 Sludge/Sand & Grit (25-33% dia.)
SGR 3
DEBRIS
2 60 x 96-inch STN at startGCC
20 9Special Structure - Node Point/Junction -- Called SNP 16H3-238C 2STRJ
31 Pipe Material or Liner Change -- Changes to RCB 3PSHP
31 Pipe Shape or Size Change -- Changes to 60x60PSIZ
34 Unknown structure -- Not on map 4GCC
38 3Special Structure - Node Point/Junction 5STRJ
42 3Special Structure - Node Point/Junction 6STRJ
50 General Condition Photo 7GCP
59 Pipe Shape or Size Change -- Changes to 48x48 8PSIZ
Page 1 of 5 From MH 16H3-009C To 16H3-009CA
Distance Defect Description Clock Ref.
GPM Photo No.
Defect
74 7Special Structure - Node Point/Junction 9STRJ
94 10Tap - Break-in - Fair to Good Condition -- No protrusion -- 10-inch VCP
TB 1
LAT'L
104 9Tap - Factory - Cannot effectively evaluate 11
TFX 3
LAT'L
113 Evidence of Leakage -- Slight to Moderate -- MD's 12
EL 2
LEAK
123 MH 16H3-009C 13EUMH
Page 2 of 5 From MH 16H3-009C To 16H3-009CA
LS 16H3-009C to 16H3-009CA
Harlem Baden Hebert TV PHOTOS
FLow Measurement TV against the direction of flow
0 l.f.PHOTO 1 MH 16H3-009CA 20 l.f.PHOTO 2 Special Structure - Node Point/Junction -- Called SNP 16H3-238C
31 l.f.PHOTO 3 Pipe Material or Liner Change -- Changes to RCB
34 l.f.PHOTO 4 Unknown structure -- Not on map
38 l.f.PHOTO 5 Special Structure - Node Point/Junction 42 l.f.PHOTO 6 Special Structure - Node Point/Junction
Page 3 of 5 From MH 16H3-009C To 16H3-009CA
50 l.f.PHOTO 7 General Condition Photo 59 l.f.PHOTO 8 Pipe Shape or Size Change -- Changes to 48x48
74 l.f.PHOTO 9 Special Structure - Node Point/Junction 94 l.f.PHOTO 10 Tap - Break-in - Fair to Good Condition -- No protrusion -- 10-inch VCP
104 l.f.PHOTO 11 Tap - Factory - Cannot effectively evaluate 113 l.f.PHOTO 12 Evidence of Leakage -- Slight to Moderate -- MD's
Page 4 of 5 From MH 16H3-009C To 16H3-009CA
123 l.f.PHOTO 13 MH 16H3-009C
Page 5 of 5 From MH 16H3-009C To 16H3-009CA
File details come from the government source that posted it.