Text version
INTERNAL INSPECTION LOG
FLow Measurement
Date: 2/11/2010
Technician: ADS
ADS Environmental Services
16H3-004C 16H3-011C
Downstream Line Depth NA
Sewer Plug Locations
None
Dyed-Water Flood Sketch None
Upstream Line Depth NA
ADDITIONAL INFORMATION
Type Of Sewer Combination
Harlem Baden Hebert
LOCATION: Esmt off Cherry Avenue
PROJECT:
Total Line Length 109
Type Of Pipe RCB
Joint Spacing
Pipe Diameter 60x60
Avg. Depth
Uncapped SC's
Comments: Dataview shows "16H3-004C to 16H3-006C" -- Should show "16H3-004C to 16H3-011C"
TAPE NO. 15
Start Counter 11345
End Counter 11925 ft.
ft. in.
in.
l.f.
l.f.
in.
ft.TV Line Length 109 l.f.
Time: 1:10 PM
Precleaning N
Upstream Structure Downstream Structure
Start Inspection End Inspection
Capped SC's
Distance Defect Description Clock Ref.
GPM Photo No.
Defect
0 SNP 16H3-004C 1BAND
2-109 Less Than 1/8-Pipe Water Depth W 1
ALIGN
2-109 Sludge/Sand & Grit (<10% dia.)
SGR 1
DEBRIS
2-109 Evidence of Leakage -- Slight -- Mineral deposits
EL 1
LEAK
32 11Tap - Break-in - Fair to Good Condition -- No protrusion -- 8-inch
VCP
TB 1
LAT'L
39 9Tap - Break-in - Fair to Good Condition -- No protrusion -- 6-inch
VCP
TB 1
LAT'L
50 General Condition Photo 4GCP
73 12Tap - Break-in - Fair to Good Condition -- No protrusion -- 6-inch
VCP
TB 1
LAT'L
76 12Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 6
TC 2
LAT'L
99 9Tap - Break-in - Fair to Good Condition -- No protrusion -- 12-inch VCP
TB 1
LAT'L
109 SNP 16H3-011C 8EAND
Page 1 of 3 From MH 16H3-004C To 16H3-011C
LS 16H3-004C to 16H3-011C
Harlem Baden Hebert TV PHOTOS
FLow Measurement
0 l.f.PHOTO 1 Inspection Begins at Connection/Node --
SNP 16H3-004C
32 l.f.PHOTO 2 Tap - Break-in - Fair to Good Condition -- No protrusion -- 8-inch VCP
39 l.f.PHOTO 3 Tap - Break-in - Fair to Good Condition -- No protrusion -- 6-inch VCP
50 l.f.PHOTO 4 General Condition Photo
73 l.f.PHOTO 5 Tap - Break-in - Fair to Good Condition -- No protrusion -- 6-inch VCP
76 l.f.PHOTO 6 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP
Page 2 of 3 From MH 16H3-004C To 16H3-011C
99 l.f.PHOTO 7 Tap - Break-in - Fair to Good Condition -- No protrusion -- 12-inch VCP
109 l.f.PHOTO 8 Inspection Ends at Connection/Node --
SNP 16H3-011C
Page 3 of 3 From MH 16H3-004C To 16H3-011C