CONTRACTORS PLEASE NOTE - THESE ARE ADDITIONAL DOCUMENTS THAT BELONG WITH AMENDMENT 1. ALTHOUGH FBO TITLES THE DIFFERENT UPLOADS AS AMENDMENTS, THE ONLY AMENDMENT CURRENTLY POSTED IS AMENDMENT 1. THE SF30 (WHICH IS UNDER AMENDMENT 2 IN THE FBO SYSTEM) IS THE OFFICIAL GOVERNMENT DOCUMENT THAT MUST BE SIGNED, DATED AND RETURNED WITH YOUR PROPOSAL. Additional Information for Amendment 1.
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
INTERNAL INSPECTION LOG
FLow Measurement
Date: 2/11/2010
Technician: ADS
ADS Environmental Services
16G4-234C 16G4-250C
Downstream Line Depth NA
Sewer Plug Locations
None
Dyed-Water Flood Sketch None
Upstream Line Depth NA
ADDITIONAL INFORMATION
Type Of Sewer Combined
Harlem Baden Hebert
LOCATION: Easement Clara Avenue
PROJECT:
Total Line Length 564
Type Of Pipe RCP
Joint Spacing 0
Pipe Diameter 78x92
Avg. Depth
Uncapped SC's
Comments:
TAPE NO. 14
Start Counter 05810
End Counter 12935 ft.
ft. in.
in.
l.f.
l.f.
in.
ft.TV Line Length 564 l.f.
TV against the direction of flow
Time: 10:30 AM
Precleaning N
Upstream Structure Downstream Structure
End Inspection Start Inspection
Capped SC's
Distance Defect Description Clock Ref.
GPM Photo No.
Defect
0 MH 16G4-250C 1BDMH
2-562 Less Than 1/8-Pipe Water Depth W 1
ALIGN
2-562 Minimal to No Debris in Pipe
SGR
DEBRIS
2-562 Evidence of Leakage -- Slight
EL 1
LEAK
50 3Tap - Break-in - Fair Condition -- No protrusion -- 12-inch VCP 2
TB 2
LAT'L
50 General Condition Photo 3GCP
58 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 4
TC 2
LAT'L
87 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 5
TC 2
LAT'L
104-150 Bend to Right (slight -- <15 degrees)
BR 1
ALIGN
109 General Condition Photo 6GCP
148 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 7
TC 2
LAT'L
150 8Leak in Brickwork/Masonry (See I/I Severity Value) 8
LB
LEAK
Page 1 of 7 From MH 16G4-234C To 16G4-250C
Distance Defect Description Clock Ref.
GPM Photo No.
Defect
150 Leak - GW Infiltration (Moderate 1-5 gpm) 1
IGW 3
LEAK
169 General Condition Photo 9GCP
169 7Leak in Brickwork/Masonry (See I/I Severity Value) 10
LB
LEAK
169 Leak - GW Infiltration (Moderate 1-5 gpm) 1
IGW 3
LEAK
206 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 11
TC 2
LAT'L
235 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 12
TC 2
LAT'L
242 2Special Structure - Node Point/Junction 13STRJ
242 General Condition Photo 14GCP
262 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 15
TC 2
LAT'L
291 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP -- Deposits
TC 2
LAT'L
318 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP -- Deposits
TC 2
LAT'L
318 General Condition Photo 18GCP
346 11Tap - Capped - Fair-Poor Condition -- No protrusion -- 6-inch VCP -- Deposits
TC 3
LAT'L
355 3Tap - Break-in - Fair Condition -- No protrusion -- 8-inch VCP -- Deposits
TB 2
LAT'L
372 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP -- Deposits
TC 2
LAT'L
401 General Condition Photo 22GCP
401 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 23
TC 2
LAT'L
430 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP -- Deposits
TC 2
LAT'L
486 8Tap - Capped - Fair-Poor Condition -- No protrusion -- 21-inch VCP -- Deposits
TC 3
LAT'L
486 General Condition Photo 26GCP
501 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 27
TC 2
LAT'L
564 MH 16G4-234C 28EUMH
Page 2 of 7 From MH 16G4-234C To 16G4-250C
LS 16G4-234C to 16G4-250C
Harlem Baden Hebert TV PHOTOS
FLow Measurement TV against the direction of flow
0 l.f.PHOTO 1 MH 16G4-250C 50 l.f.PHOTO 2 Tap - Break-in - Fair Condition -- No protrusion -- 12-inch VCP
50 l.f.PHOTO 3 General Condition Photo 58 l.f.PHOTO 4 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP
87 l.f.PHOTO 5 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP
109 l.f.PHOTO 6 General Condition Photo
Page 3 of 7 From MH 16G4-234C To 16G4-250C
148 l.f.PHOTO 7 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP
150 l.f.PHOTO 8 Leak in Brickwork/Masonry (See I/I Severity Value)
169 l.f.PHOTO 9 General Condition Photo 169 l.f.PHOTO 10 Leak in Brickwork/Masonry (See I/I Severity Value)
206 l.f.PHOTO 11 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP
235 l.f.PHOTO 12 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP
Page 4 of 7 From MH 16G4-234C To 16G4-250C
242 l.f.PHOTO 13 Special Structure - Node Point/Junction 242 l.f.PHOTO 14 General Condition Photo
262 l.f.PHOTO 15 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP
291 l.f.PHOTO 16 Tap - Capped - Fair Condition -- Deposits -- No protrusion -- 6-inch VCP
318 l.f.PHOTO 17 Tap - Capped - Fair Condition -- Deposits -- No protrusion -- 6-inch VCP
318 l.f.PHOTO 18 General Condition Photo
Page 5 of 7 From MH 16G4-234C To 16G4-250C
346 l.f.PHOTO 19 Tap - Capped - Fair-Poor Condition -- Deposits -- No protrusion -- 6-inch VCP
355 l.f.PHOTO 20 Tap - Break-in - Fair Condition -- Deposits -- No protrusion -- 8-inch VCP
372 l.f.PHOTO 21 Tap - Capped - Fair Condition -- Deposits -- No protrusion -- 6-inch VCP
401 l.f.PHOTO 22 General Condition Photo
401 l.f.PHOTO 23 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP
430 l.f.PHOTO 24 Tap - Capped - Fair Condition -- Deposits -- No protrusion -- 6-inch VCP
Page 6 of 7 From MH 16G4-234C To 16G4-250C
486 l.f.PHOTO 25 Tap - Capped - Fair-Poor Condition -- Deposits -- No protrusion -- 21-inch VCP
486 l.f.PHOTO 26 General Condition Photo
501 l.f.PHOTO 27 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP
564 l.f.PHOTO 28 MH 16G4-234C
Page 7 of 7 From MH 16G4-234C To 16G4-250C