16G4-234C_TO_16G4-250C_TVI_436891.pdf

PDF 43 KB Posted

Attached to
HARLEM BADEN PHASE 8
Solicitation number
W912P919R0023
Issued by

About this file

CONTRACTORS PLEASE NOTE - THESE ARE ADDITIONAL DOCUMENTS THAT BELONG WITH AMENDMENT 1. ALTHOUGH FBO TITLES THE DIFFERENT UPLOADS AS AMENDMENTS, THE ONLY AMENDMENT CURRENTLY POSTED IS AMENDMENT 1. THE SF30 (WHICH IS UNDER AMENDMENT 2 IN THE FBO SYSTEM) IS THE OFFICIAL GOVERNMENT DOCUMENT THAT MUST BE SIGNED, DATED AND RETURNED WITH YOUR PROPOSAL. Additional Information for Amendment 1.

View the file

Other files

File Type Posted
D03_SF30_Amendment_3.pdf PDF
A22_Revised_Bid_Schedule_Amendment_2.pdf PDF
A22_Rehab_Tables_Amendment_2.xlsx XLSX spreadsheet
A22_Amendment_2.pdf PDF
A22_Drawing_10722-S2.pdf PDF
A22_Amendment_1.pdf PDF
16H3-077CA_TO_16H3-077CB_TVI_908423.pdf PDF
16G4-293C_TO_16G3-232C_TVI_908634.pdf PDF
16H3-009C_TO_16H3-009CA_TVI_908425.pdf PDF
16H3-077CDN_TO_16G4-319CBN_TVI_908433.pdf PDF
16H3-008C_TO_16H3-009C_TVI_437266.pdf PDF
16H3-077CA_TO_16H3-077CC_TVI_908440.pdf PDF
16H2-031C_TO_16H2-030C_TVI_437018.pdf PDF
16G4-258C_TO_16G4-260C_TVI_908418.pdf PDF
16G4-289C_TO_16G4-280C_TVI_908420.pdf PDF
16H3-009CA_TO_16H3-076C_TVI_908424.pdf PDF
XP-SWMM_Modeling_Summary.pdf PDF
16G4-280C_TO_16G4-237C_TVI_908421.pdf PDF
16H3-077CDS_TO_16G4-319CBS_TVI_908435.pdf PDF
16H3-077C_TO_16H3-077CA_TVI_908422.pdf PDF
16G4-319C_TO_16G4-284CA_TVI_908438.pdf PDF
16G4-319CA_TO_16G4-319C_TVI_908437.pdf PDF
16H3-011C_TO_16H3-006C_TVI_908426.pdf PDF
16H3-077CBN_TO_16H3-077CDN_TVI_908432.pdf PDF
16H2-100C_TO_16H3-004C_TVI_437486.pdf PDF
16G4-250C_TO_16G4-258C_TVI_459472.pdf PDF
16H3-077CC_TO_16G4-319CA_TVI_908441.pdf PDF
16G4-284CA_TO_16G4-282CA_TVI_908439.pdf PDF
16H2-029C_TO_16H2-030C_TVI_437012.pdf PDF
16H2-030C_TO_16H2-100C_TVI_437014.pdf PDF
Harlem_Baden_PIV_Dry_Weather.xlsm XLSM spreadsheet
16G4-237C_TO_16G4-234C_TVI_436894.pdf PDF
16G4-282CA_TO_16G4-289C_TVI_908419.pdf PDF
16H3-006C_TO_16H3-007C_TVI_437264.pdf PDF
16H3-007C_TO_16H3-008C_TVI_437265.pdf PDF
16H3-077CBS_TO_16H3-077CDS_TVI_908434.pdf PDF
16H3-076C_TO_16H3-077C_TVI_437431.pdf PDF
16H3-004C_TO_16H3-011C_TVI_908427.pdf PDF
GIS_Map_Name_to_ADS_CCTV_Log.pdf PDF
A22_Amendment_1.pdf PDF
Pre-bid_Sign-in_Sheet.pdf PDF
Harlem_Baden_1-200_West_NoAerial.png PNG image
Harlem_Baden_1-200_East_NoAerial.png PNG image
GIS_Map_Name_to_ADS_CCTV_Log_(sorted_by_GIS).pdf PDF
Table_A-1_-_Reach_Recommendation_excerpt_from_TM.pdf PDF
Rehab_Map_West.pdf PDF
Rehab_Map_East.pdf PDF
A02_19R0023_Plans_Harlem_Baden.pdf PDF
A02_19R0023_SOW_Harlem_Baden.pdf PDF
A22_19R0023_Solicitation_Clean_Copy.pdf PDF
Show all 50

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

INTERNAL INSPECTION LOG

FLow Measurement

Date: 2/11/2010

Technician: ADS

ADS Environmental Services

16G4-234C 16G4-250C

Downstream Line Depth NA

Sewer Plug Locations

None

Dyed-Water Flood Sketch None

Upstream Line Depth NA

ADDITIONAL INFORMATION

Type Of Sewer Combined

Harlem Baden Hebert

LOCATION: Easement Clara Avenue

PROJECT:

Total Line Length 564

Type Of Pipe RCP

Joint Spacing 0

Pipe Diameter 78x92

Avg. Depth

Uncapped SC's

Comments:

TAPE NO. 14

Start Counter 05810

End Counter 12935 ft.

ft. in.

in.

l.f.

l.f.

in.

ft.TV Line Length 564 l.f.

TV against the direction of flow

Time: 10:30 AM

Precleaning N

Upstream Structure Downstream Structure

End Inspection Start Inspection

Capped SC's

Distance Defect Description Clock Ref.

GPM Photo No.

Defect

0 MH 16G4-250C 1BDMH

2-562 Less Than 1/8-Pipe Water Depth W 1

ALIGN

2-562 Minimal to No Debris in Pipe

SGR

DEBRIS

2-562 Evidence of Leakage -- Slight

EL 1

LEAK

50 3Tap - Break-in - Fair Condition -- No protrusion -- 12-inch VCP 2

TB 2

LAT'L

50 General Condition Photo 3GCP

58 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 4

TC 2

LAT'L

87 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 5

TC 2

LAT'L

104-150 Bend to Right (slight -- <15 degrees)

BR 1

ALIGN

109 General Condition Photo 6GCP

148 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 7

TC 2

LAT'L

150 8Leak in Brickwork/Masonry (See I/I Severity Value) 8

LB

LEAK

Page 1 of 7 From MH 16G4-234C To 16G4-250C

Distance Defect Description Clock Ref.

GPM Photo No.

Defect

150 Leak - GW Infiltration (Moderate 1-5 gpm) 1

IGW 3

LEAK

169 General Condition Photo 9GCP

169 7Leak in Brickwork/Masonry (See I/I Severity Value) 10

LB

LEAK

169 Leak - GW Infiltration (Moderate 1-5 gpm) 1

IGW 3

LEAK

206 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 11

TC 2

LAT'L

235 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 12

TC 2

LAT'L

242 2Special Structure - Node Point/Junction 13STRJ

242 General Condition Photo 14GCP

262 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 15

TC 2

LAT'L

291 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP -- Deposits

TC 2

LAT'L

318 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP -- Deposits

TC 2

LAT'L

318 General Condition Photo 18GCP

346 11Tap - Capped - Fair-Poor Condition -- No protrusion -- 6-inch VCP -- Deposits

TC 3

LAT'L

355 3Tap - Break-in - Fair Condition -- No protrusion -- 8-inch VCP -- Deposits

TB 2

LAT'L

372 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP -- Deposits

TC 2

LAT'L

401 General Condition Photo 22GCP

401 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 23

TC 2

LAT'L

430 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP -- Deposits

TC 2

LAT'L

486 8Tap - Capped - Fair-Poor Condition -- No protrusion -- 21-inch VCP -- Deposits

TC 3

LAT'L

486 General Condition Photo 26GCP

501 11Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP 27

TC 2

LAT'L

564 MH 16G4-234C 28EUMH

Page 2 of 7 From MH 16G4-234C To 16G4-250C

LS 16G4-234C to 16G4-250C

Harlem Baden Hebert TV PHOTOS

FLow Measurement TV against the direction of flow

0 l.f.PHOTO 1 MH 16G4-250C 50 l.f.PHOTO 2 Tap - Break-in - Fair Condition -- No protrusion -- 12-inch VCP

50 l.f.PHOTO 3 General Condition Photo 58 l.f.PHOTO 4 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP

87 l.f.PHOTO 5 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP

109 l.f.PHOTO 6 General Condition Photo

Page 3 of 7 From MH 16G4-234C To 16G4-250C

148 l.f.PHOTO 7 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP

150 l.f.PHOTO 8 Leak in Brickwork/Masonry (See I/I Severity Value)

169 l.f.PHOTO 9 General Condition Photo 169 l.f.PHOTO 10 Leak in Brickwork/Masonry (See I/I Severity Value)

206 l.f.PHOTO 11 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP

235 l.f.PHOTO 12 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP

Page 4 of 7 From MH 16G4-234C To 16G4-250C

242 l.f.PHOTO 13 Special Structure - Node Point/Junction 242 l.f.PHOTO 14 General Condition Photo

262 l.f.PHOTO 15 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP

291 l.f.PHOTO 16 Tap - Capped - Fair Condition -- Deposits -- No protrusion -- 6-inch VCP

318 l.f.PHOTO 17 Tap - Capped - Fair Condition -- Deposits -- No protrusion -- 6-inch VCP

318 l.f.PHOTO 18 General Condition Photo

Page 5 of 7 From MH 16G4-234C To 16G4-250C

346 l.f.PHOTO 19 Tap - Capped - Fair-Poor Condition -- Deposits -- No protrusion -- 6-inch VCP

355 l.f.PHOTO 20 Tap - Break-in - Fair Condition -- Deposits -- No protrusion -- 8-inch VCP

372 l.f.PHOTO 21 Tap - Capped - Fair Condition -- Deposits -- No protrusion -- 6-inch VCP

401 l.f.PHOTO 22 General Condition Photo

401 l.f.PHOTO 23 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP

430 l.f.PHOTO 24 Tap - Capped - Fair Condition -- Deposits -- No protrusion -- 6-inch VCP

Page 6 of 7 From MH 16G4-234C To 16G4-250C

486 l.f.PHOTO 25 Tap - Capped - Fair-Poor Condition -- Deposits -- No protrusion -- 21-inch VCP

486 l.f.PHOTO 26 General Condition Photo

501 l.f.PHOTO 27 Tap - Capped - Fair Condition -- No protrusion -- 6-inch VCP

564 l.f.PHOTO 28 MH 16G4-234C

Page 7 of 7 From MH 16G4-234C To 16G4-250C

File details come from the government source that posted it.