S02 - ATT 26 - 581-22-700 - 100 Drawings Part-24 of 24.pdf

PDF 17 MB Posted

Attached to
EHRM Huntington VAMC 581-22-700 Construct Infrastructure Upgrades
Solicitation number
36C77626R0025
Issued by

About this file

This document is a comprehensive set of telecommunications design and installation plans for the EHRM Infrastructure Upgrades project at the VA Huntington facility in Huntington, West Virginia. The plans are 100% construction documents prepared by SPEES Design Build and cover Building 01S Level 01 through various other buildings and structures across the campus.

The telecommunications systems include the installation and upgrade of category 6A cabling infrastructure, data racks, fiber optic backbone cabling with diverse A-side and B-side routing, telecommunications rooms (TRs), telecommunications enclosures, work area outlets (WAOs), cable tray systems, and physical access control systems. Key requirements include: removal and replacement of existing category 6 and below cabling with CAT6A; provision of fire-rated plywood backboards in all telecommunications rooms; installation of wire basket cable trays; provision of pull boxes at 100-foot intervals per ANSI/TIA-569; fire-stop sleeves with A-side and B-side separation of minimum 10 feet; and complete labeling and certification per ANSI/TIA-606C standards. The design specifies multiple data rack configurations with fiber distribution panels, CAT6A patch panels, network switches, cable managers, and UPS systems. Fire alarm systems, card access control panels, and wireless access points are integrated throughout. Installation details address fiber-optic pathways, backbone cabling routing from the Main Distribution Area to individual telecommunications rooms, building entry procedures through conduit systems, and microduct tube cable installations. All work requires coordination with architectural drawings, compliance with existing fire ratings, and field verification of existing conditions before demolition.

View the file

Other files

File Type Posted
S06 - 36C77626R0025 0008.pdf PDF
S06 - Amendment 0008 - ATT 7 - 02EP100B - ELECTRICAL 20260413.pdf PDF
S06 - Amendment 0008 - ATT 11 - Burn Permit.pdf PDF
S06 - Amendment 0008 - ATT 10 - 260508 - Sheet AD103-1B Data Center Phase 1B Demo Roof update.pdf PDF
S06 - Amendment 0008 - ATT 9 - 260508 - Sheet AD101-1B Data Center Phase 1B Demo Floor Plan update.pdf PDF
S06 - Amendment 0008 - ATT 1 - TechQuestionsVAresponses Final Set - Huntington EHRM IU.pdf PDF
S06 - Amendment 0008 - ATT 14 - Energized Electrical Work Permit.pdf PDF
S06 - Amendment 0008 - ATT 5 - ELECTRICAL 2026.04.13.pdf PDF
S06 - Amendment 0008 - ATT 6 - 01WEP100G - ELECTRICAL 20260413.pdf PDF
S06 - Amendment 0008 - ATT 3 - Civil OSP Redesign-signed.pdf PDF
S06 - Amendment 0008 - ATT 12 - Environmental Report Huntington WV.pdf PDF
S06 - Amendment 0008 - ATT 8 - 260508 - Sheet 01S-AE452 TR Tower 4 Wall sections update.pdf PDF
S06 - Amendment 0008 - ATT 13 - Hot Tapping Permit.pdf PDF
S06 - Amendment 0008 - ATT 2 - UPDATED SHEETS.pdf PDF
S06 - Amendment 0008 - ATT 4 - Structural Set 04-21-2026.pdf PDF
S06 - 36C77626R0025 0007.pdf PDF
S06 - Amendment 0007 - ATT 1 - TechQuestionsVAresponses Partial 4 - Huntington EHRM IU.pdf PDF
S06 - Amendment 0007 - ATT 3 - Lift Planning.pdf PDF
S06 - Amendment 0007 - ATT 2 - Geotechnical Report.pdf PDF
S06 - Amendment 0007 - ATT 5 - Appendix A - PFC FPT.pdf PDF
S06 - Amendment 0007 - ATT 4 - 01 00 00 - GENERAL REQUIREMENTS_A1.pdf PDF
S06 - Amendment 0007 - ATT 6 - Crane lift Info.pdf PDF
S06 - 36C77626R0025 0006.pdf PDF
S06 - Amendment 0006 - ATT 1 - TechQuestionsVAresponses Partial 3 - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0005.pdf PDF
S06 - Amendment 0004 - ATT 2 - FAR 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS - APR 2026.pdf PDF
S06 - Amendment 0004 - ATT 1 - TechQuestionsVAresponses Partial 2 - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0004.pdf PDF
S06 - Amendment 0003 - ATT 2 - TechQuestionsVAresponses Partial - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0003.pdf PDF
S06 - 36C77626R0025 0002.pdf PDF
S06 - Amendment 0001 - ATT 1 - Site Visit In-Sheet - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0001.pdf PDF
S02 - ATT 28 - 581-22-700 - FLS Compliance Letter.pdf PDF
S02 - ATT 3 - 581-22-700 - 100 Drawings Part-1 of 24.pdf PDF
S02 - ATT 15 - 581-22-700 - 100 Drawings Part-13 of 24.pdf PDF
S02 - ATT 30 - 581-22-700 - 100 Commissioning Plan.pdf PDF
S02 - ATT 20 - 581-22-700 - 100 Drawings Part-18 of 24.pdf PDF
S02 - ATT 24 - 581-22-700 - 100 Drawings Part-22 of 24.pdf PDF
S02 - ATT 1 - 581-22-700 - 100 Specifications Part-1 of 2.pdf PDF
S02 - ATT 10 - 581-22-700 - 100 Drawings Part-8 of 24.pdf PDF
S02 - ATT 12 - 581-22-700 - 100 Drawings Part-10 of 24.pdf PDF
S02 - ATT 23 - 581-22-700 - 100 Drawings Part-21 of 24.pdf PDF
S02 - ATT 31 - 581-22-700 - Topographic Survey TR Tower 3.pdf PDF
S02 - ATT 25 - 581-22-700 - 100 Drawings Part-23 of 24.pdf PDF
S02 - ATT 16 - 581-22-700 - 100 Drawings Part-14 of 24.pdf PDF
S02 - ATT 21 - 581-22-700 - 100 Drawings Part-19 of 24.pdf PDF
S02 - ATT 34 - HEFP SEP Design Alerts 1-9 and 11-16.pdf PDF
S02 - ATT 29 - 581-22-700 - Geotechnical Report - W24044 - VA Duct Bank 11.21.24.pdf PDF
S02 - ATT 14 - 581-22-700 - 100 Drawings Part-12 of 24.pdf PDF
Show 40 more

Latest 50 of 68 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W

C

360°

X

S

X

W

G H

DATA RACK,

TYP.

TYP.

G

H

DATA RACKTN502

TR

135 SF

06-6113B

06-6113A

C

TN503

ACCESS CONTROL

PANEL "06-ACP-6113"

SECONDARY BONDING BUSBAR

G H

TYP.

G H

TYP.

TN501

DATA RACK

TYP.

TN501

TR

135 SF

G H

132 SF

IRM

132 SF

IRM

AREA SHOWN

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:3

:0 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

.r v t

06TN401

BLDG 06 - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1/2" = 1'-0"06TN101

1 RM 6113 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"06TN101

2 RM 6113 - TELECOMMUNICATIONS PLAN1'0 2' 4' 1'0 2' 4'

PROJECT

NORTH

PROJECT

NORTH

1/2" = 1'-0"06TN101

3 RM 6113 - DEMOLITION OVERHEAD PLAN 1'0 2' 4'

PROJECT

NORTH

1/2" = 1'-0"06TN101

4 RM 6113 - OVERHEAD PLAN 1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

KEY NOTES

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING CABLE TRAY SHALL BE DEMOLISHED.

PROVIDE FIRE STOP SLEEVES AS REQUIRED. SIDE 'A' AND SIDE 'B' SLEEVES SHALL

BE SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

PROVIDE (1) CAT6A CABLE FOR ADDED SECURITY CAMERA.

PROVIDE (2)-CARD ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY

EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,

PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE

AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL

ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.

Revisions: Date: 661 OF 693

W

C

W

XX

S

A B

ELECTRICAL

108 SF

ELECTRICAL

108 SF

EXISTING

GROUNDING

BUSBAR

DATA RACK,

TYP.FIRE

ALARM

PANEL

TELECOM

ENCLOSURE

PANEL 'H-P7-G'

PANEL 'L-P7-GA'

PANEL 'L-P7-GB'

ATS-07

ATS 7 DISC.

LIGHTING CONTACTOR

FIRE ALARM

SYSTEM 'L-P7-GA'

UNKNOWN PANEL

CONTROL ACCESS PANEL

SECURITY PANEL

'L-P7-GA'

UNKNOWN EXISTING

EQUIPMENT

XFMR 'T-7'

EXISTING

HOUSEKEEPING PAD

A B

SECONDARY

BONDING BUSBAR

C

TR

73 SF

ACCESS

CONTROL

PANEL

"07-ACP7004"

DATA

RACK

TN503

TN502

07-7004B

07-7004A

FIRE

ALARM

PANEL

108 SF

ELECTRICAL

TELECOM

ENCLOSURE

PANEL 'H-P7-G'

PANEL 'L-P7-GA'

PANEL 'L-P7-GB'

ATS-07

ATS 7 DISC.

LIGHTING CONTACTOR

FIRE ALARM

SYSTEM 'L-P7-GA'

UNKNOWN PANEL

CONTROL ACCESS PANEL

SECURITY PANEL

'L-P7-GA'

UNKNOWN EXISTING

EQUIPMENT

XFMR 'T-7'

EXISTING

HOUSEKEEPING PAD

A B

TYP.

ELECTRICAL

108 SF

A B

TR

73 SF

DATA RACK

TYP.

TN501

TYP.

TN501

108 SF

ELECTRICAL

TELECOM

ENCLOSURE

73 SF

IT

73 SF

IT

AREA SHOWN

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:5

:0 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

.r v t

07TN400

BLDG 07 - LEVEL 00 - ENLARGED

TELECOMMUNICATIONS PLANS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY NOTES

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1/2" = 1'-0"07TN100

1 RM 7004 & 7005 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"07TN100

2 RM 7004 - TELECOMMUNICATIONS PLAN1'0 2' 4'

PROJECT

NORTH

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

PROVIDE FIRE STOP SLEEVES AS REQUIRED. SIDE 'A' AND SIDE 'B' SLEEVES SHALL

BE SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

EXISTING CABLE TRAY TO BE DEMOLISHED.

PROVIDE (1) CAT6A CABLE FOR ADDED SECURITY CAMERA.

PROVIDE (2)-CARD ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY

EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,

PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE

AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL

ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.

EXISTING EQUIPMENT SHALL BE RELOCATED AS SHOWN IN DETAIL '2' ON THIS

SHEET. ALL CABLING AND CONDUIT SHALL BE DEMOLISEHD BACK TO SOURCE.

RELOCATED EQUIPMENT. COORDINATE WITH EXISTING CONDITIONS AND PROVIDE

ALL APPURTENANCES TO RESTORE FUNCTIONALITY TO EQUIPMENT AS REQUIRED.

1/2" = 1'-0"07TN100

3 RM 7004 & 7005 - DEMOLITION OVERHEAD PLAN

1/2" = 1'-0"07TN100

4 RM 7004 - OVERHEAD PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND TO

ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date:

C360°

S

X X

W

D

DATA RACK,

TYP.

D

TR

51 SF

08-8009A08-8009B

DATA

RACK

SECONDARY BONDING

BUSBAR

C

ACCESS CONTROL

PANEL "08-ACP-8009"

TN502

TN503

D

TYP.

D

TR

51 SF

DATA

RACK

TYP.

TN501

TYP.

TN501

IT

51 SF

IT

51 SF

AREA SHOWN

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:1 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

.r v t

08TN400

BLDG 08 - LEVEL 00 - ENLARGED

TELECOMMUNICATIONS PLANS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY NOTES

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1/2" = 1'-0"08TN100

1 RM 8009 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"08TN100

2 RM 8009 - TELECOMMUNICATIONS PLAN

PROJECT

NORTH

PROJECT

NORTH

1'0 2' 4' 1'0 2' 4'

1/2" = 1'-0"08TN100

3 RM 8009 - DEMOLITION OVERHEAD PLAN

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

PROVIDE FIRE STOP SLEEVES AS REQUIRED. SIDE 'A' AND SIDE 'B' SLEEVES SHALL

BE SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

EXISTING CABLE TRAY SHALL BE DEMOLISHED.

PROVIDE (1) CAT6A CABLE FOR ADDED SECURITY CAMERA.

PROVIDE (2)-CARD ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY

EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,

PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE

AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 -

PHYSICAL ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.

PROVIDE CONDUIT (4", MINIMUM) WITH APPROPRIATE FIRE-PROOFING AND

CAULKING AS REQUIRED TO EXTEND FROM LEVEL 00 ACCESSIBLE CEILING TO

LEVEL 01 ACCESSIBLE CEILING. CONDUIT PROVIDED TO SERVE HORIZONTAL

CABLING SERVING WAOs FROM TR AS INDICATED ON PLANS.

PROJECT

NORTH

1'0 2' 4'

1/2" = 1'-0"08TN100

4 RM 8009 - OVERHEAD PLAN

PROJECT

NORTH

1'0 2' 4'

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND TO

ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date:

51 SF

C

S

X

X

W

E F

DATA RACK,

TYP.

TYP.

EXISTING VERTICAL

SLEEVES

EXISTING

VERTICAL SLEEVES

CARD READER

WITHOUT KEYPAD

E F

TR

71 SF

DATA RACK

09-9202A

09-9202B

SECONDARY

BONDING BUSBAR

EXISTING

VERTICAL SLEEVES

C

ACCESS CONTROL

PANEL "09-ACP-9202"

TN502

TN503

EXISTING

VERTICAL SLEEVES

A

B

E F

TYP.

EXISTING

HORIZONTAL

SLEEVE

E F

DATA RACK

TR

71 SF

TYP.

TN501

TYP.

TN501

AREA SHOWN

71 SF

IT

71 SF

IT

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:5

:3 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

.r v t

09TN402

BLDG 09 - LEVEL 02 - ENLARGED

TELECOMMUNICATION PLANS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY PLAN

GENERAL NOTES

1/2" = 1'-0"09TN102

1 RM 9202 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"09TN102

2 RM 9202 - TELECOMMUNICATIONS PLAN

1/2" = 1'-0"09TN102

3 RM 9202 - DEMOLITION OVERHEAD PLAN

1'0 2' 4' 1'0 2' 4'

1'0 2' 4'

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1/2" = 1'-0"09TN102

4 RM 9202 - OVERHEAD PLAN

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

KEY NOTES

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING CABLE TRAY SHALL BE DEMOLISHED.

WIRE BASKET CABLE TRAY.

PROVIDE FIRE STOP SLEEVES AS REQUIRED. SIDE 'A' AND SIDE 'B' SLEEVES SHALL

BE SEPARATED BY AT LEAST 10-FT.

PROVIDE (1) CAT6A CABLE FOR ADDED SECURITY CAMERA.

PROVIDE (2)-CARD ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY

EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,

PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE

AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL

ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.

Revisions: Date: 664 OF 693

AREA SHOWN

N

IRM

1A111

45 SF

TELEPHONE TERMINAL

BOARDS

FIBER OPTIC

PANEL (BELOW) TELEPHONE TERMINAL

BOARD (ABOVE)

DATA RACK

N

IRM

1A111

45 SF

TELEPHONE TERMINAL

BOARDS

FIBER OPTIC

PANEL (BELOW) TELEPHONE TERMINAL

BOARD (ABOVE)

1A111

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:5

:3 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

12TN401

BLDG 12 - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

KEY PLAN

KEY NOTES

1/2" = 1'-0"12TN101

1 RM 1A111 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"12TN101

2 RM 1A111 - TELECOMMUNICATIONS PLAN1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND TO

ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date:

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

PROJECT

NORTH

O

23 SF

2A125

DATA RACK

TELEPHONE

TERMINAL BOARD

O

23 SF

2A125

TELEPHONE

TERMINAL BOARD

2A125

O

23 SF

2A125

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:2

:0 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

L E

V E

L

.r v t

12TN402

BLDG 12 - LEVEL 02 - ENLARGED

TELECOMMUNICATIONS PLANS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY NOTES

KEY PLAN

GENERAL NOTES

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING. PROVIDE RACEWAYS TO EXTEND TO ASSOCIATED TR.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS

CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY,

CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO

SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

PROJECT

NORTH

1/2" = 1'-0"12TN102

1 RM 2A125 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"12TN102

2 RM 2A125 - TELECOMMUNICATIONS PLAN1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1/2" = 1'-0"12TN102

3 RM 2A125 - DEMOLITION OVERHEAD PLAN

PROJECT

NORTH

1'0 2' 4'

Revisions: Date:

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING VERTICAL CABLING SLEEVES SHALL BE PRESERVED. EXISTING CABLING

SHALL BE DEMOLISHED AND REMOVED.

360°

X

S

W

X

AREA SHOWN

TYP.

C

DV1

DD2

DV1

DD2

TR

20121

98 SF

TN502

C

C

20-20121A

20-20121B

TN503

ACCESS CONTROL

PANEL"20-ACP-20121"

DATA RACK,

TYP.

SECONDARY BONDING

BUSBAR

C

TR

20121

98 SF

TYP.

TN501

TYP.

TN501

C

DATA RACK,TYP.

20121

98 SF

20121

98 SF

20121

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0 /2

:0

:0 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

.r v t

20TN401a

BLDG 20 - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

KEY PLAN

KEY NOTES

PROJECT

NORTH

EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

PROVIDE FIRE STOP SLEEVES AS REQUIRED. SIDE 'A' AND SIDE 'B' SLEEVES SHALL BE

SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

PROVIDE (1) CAT6A CABLE FOR ADDED SECURITY CAMERA.

PROVIDE (2)-CARD ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY

EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,

PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE

AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL

ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.

11/2" = 1'-0"20TN101

1 RM 20121 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"20TN101

2 RM 20121 - TELECOMMUNICATIONS PLAN

1/2" = 1'-0"20TN101

3 RM 20121 - DEMOLITION OVERHEAD PLAN

1/2" = 1'-0"20TN101

4 RM 20121 - OVERHEAD PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND

TO ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date: 667 OF 693

WW

F

WW

F

AREA SHOWN

IT CLOSET

20120

64 SF

FIRE ALARM

STROBE LIGHT

CARD READER

TYP.

C

DATA RACK

IT CLOSET

20120

64 SF

FIRE ALARM

STROBE LIGHT

CARD READER

C

TYP.

20120

IT CLOSET

20120

64 SF 3

TYP.

C C

IT CLOSET

20120

64 SF

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:0

:1 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

.r v t

20TN401b

BLDG 20 - LEVEL 01 - ENLARGED

TELECOMMUNICATIONS PLANS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

KEY PLAN

KEY NOTES

PROJECT

NORTH

1/2" = 1'-0"20TN101

1 RM 20120 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"20TN101

2 RM 20120 - TELECOMMUNICATIONS PLAN

1/2" = 1'-0"20TN101

3 RM 20120 - DEMOLITION OVERHEAD PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING CABLE TRAY SHALL BE DEMOLISHED.

PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO

REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT

SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL "1" ON

SHEET TN501 AND GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION,

COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.

20TN101

4 RM 20120 - OVERHEAD PLAN 1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND

TO ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date:

360°

W

X

S

X

AREA SHOWN

TYP.

A

TR

20211A

113 SF

TN502

C

A

20-20211AB

20-20211AA

TN502

ACCESS CONTROL

PANEL "20-ACP-20211A"

DATA RACK,

TYP.

SECONDARY BONDING

BUSBAR

A

TR

20211A

113 SF

TYP.

TN501

TYP.

TN501

A

DATA

RACK,

TYP.

20211A

200 SF

20211

200 SF

20211

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:0

:2 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

.r v t

20TN402a

BLDG 20 - LEVEL 02 - ENLARGED

TELECOMMUNICATIONS PLANS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

KEY PLAN

KEY NOTES

PROJECT

NORTH

1/2" = 1'-0"20TN102

1 RM 20211 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"20TN102

2 RM 20211A - TELECOMMUNICATIONS PLAN

1/2" = 1'-0"20TN102

3 RM 20211 - DEMOLITION OVERHEAD PLAN

1/2" = 1'-0"20TN102

4 RM 20211A - OVERHEAD PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND

TO ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

PROVIDE FIRE STOP SLEEVES AS REQUIRED. SIDE 'A' AND SIDE 'B' SLEEVES SHALL BE

SEPARATED BY AT LEAST 10-FT.

WIRE BASKET CABLE TRAY.

PROVIDE (1) CAT6A CABLE FOR ADDED SECURITY CAMERA.

PROVIDE (2)-CARD ACCESS CONTROL PANEL TO SERVE ALL PACS DOOR SECURITY

EQUIPMENT FOR THIS TR ROOM. PROVIDE ALL REQUIRED CONNECTIONS,

PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A COMPLETE

AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 - PHYSICAL

ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION.

Revisions: Date: 669 OF 693

F

F

W

AREA SHOWN

CARD READER

WITH KEYPAD

FIRE ALARM

STROBE LIGHT

SECONDARY

BONDING

BUSBAR

TYP.

20218

60 SF

B

DATA RACK

CARD READER

WITH KEYPAD

SECONDARY

BONDING

BUSBAR

20218

60 SF

B

FIRE ALARM

STROBE LIGHT

TYP.

20218

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:0

:2 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

.r v t

20TN402b

BLDG 20 - LEVEL 02 - ENLARGED

TELECOMMUNICATIONS PLANS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

GENERAL NOTES

KEY PLAN

KEY NOTES

PROJECT

NORTH

1/2" = 1'-0"20TN102

1 RM 20218 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"20TN102

2 RM 20218 - TELECOMMUNICATIONS PLAN1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

EXISTING EQUIPMENT SHALL BE DEMOLISHED. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

EXISTING EQUIPMENT SHALL BE SALVAGED TO VA. ASSOCIATED RACEWAYS AND

CABLING SHALL BE DEMOLISHED BACK TO SOURCE.

PROVIDE TELECOMMUNICATIONS OUTLET WITH PORT QUANTITY SHOWN TO

REPLACE EXISTING TELECOMMUNICATIONS OUTLET; EXISTING OUTLET CONDUIT

SHALL REMAIN AND BE UTILIZED TO FEED NEW CABLING; REFERENCE DETAIL "1" ON

SHEET TN501 AND GENERAL NOTES ON THIS SHEET FOR ADDITIONAL INFORMATION,

COORDINATE WITH VA FOR EXACT OUTLET PLACEMENT.

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE RACEWAYS TO EXTEND

TO ASSOCIATED TR AS REQUIRED.

5. A TELECOMMUNICATIONS OUTLET UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING EXISTING DEVICES AND CABLES; PROVIDING ALL LABOR,

MATERIALS, TOOLS, TEST INSTRUMENTS, AND CONSUMABLES REQUIRED FOR THE

INSTALLATION, TERMINATION, TESTING, LABELING, AND CERTIFICATION OF A FULLY

FUNCTIONAL CATEGORY 6A OUTLET WITH THE PORT QUANTITY INDICATED.

6. WHERE DATA OUTLETS ARE PROVIDED AND EXISTING DATA OUTLET CURRENTLY

DOES NOT EXIST, PROVIDE (1) 1-1/4" CONDUIT FROM NEW BACKBOX TO ACCESSIBLE

CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET TO TR VIA CABLE

TRAY. IF CABLE TRAY IS NON-EXISTENT, EXTEND RACEWAY FROM OUTLET TO TR AS

REQUIRED.

7. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

8. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

9. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

10. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

11. ALL TELECOMMUNICATION ROOMS SHALL BE PROVIDED WITH FIRE-RATED PLYWOOD

BACKBOARDS. REFERENCE EXACT PLACEMENTS WITH ARCHITECTURE DRAWINGS AS

REQUIRED.

Revisions: Date:

C 360°

WS

X

X

W

WAP

AREA SHOWN

B

TYP.

B

TN502

C

TN503

23R-B09B

23R-B09A

DATA RACK

ACCESS CONTROL

PANEL "23R-ACP-B09"

TR

B09

102 SF

SECONDARY BONDING

BUSBAR

B

TYP.

TN501

DATA RACK

TYP.

TN501

TR

B09

102 SF

B09

STORAGE

B09

101 SF

A SIDE FIBER WORK

B SIDE FIBER WORK

FIBER-OPTIC BACKBONE CABLING

REFERENCE NOTES ON THIS SHEET REGARDING VERTICAL AND HORIZONTAL FIBER-OPTIC

CABLING ROUTING. CONTRACTOR SHALL ENSURE A-SIDE AND B-SIDE ROUTING IS AS

DIVERSE AS PRACTICAL. REFERENCE SHEET TN508, TN509, AND TN510 FOR ALL FIBER

PATHWAY DETAILS.

SHEET SHALL BE PRINTED IN COLOR TO INDICATE ALL REQUIRED INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/0

/2

:4

:4 a m

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /E

E

B L D

G

B A

S E

M E

N T

.r v t

23RTN400B

BLDG 23R - LEVEL 00B - ENLARGED

TELECOMMUNICATIONS PLANS

23R

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

1/2" = 1'-0"23RTN100B

1 RM B09 - DEMOLITION FLOOR PLAN

1/2" = 1'-0"23RTN100B

2 RM B09 - TELECOMMUNICATIONS PLAN

1/2" = 1'-0"23RTN100B

4 RM B09 - OVERHEAD PLAN

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1'0 2' 4'

PROJECT

NORTH

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER AND SIGNAL DEVICES AND ASSOCIATED CIRCUITRY AS

REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

2. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

3. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

4. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS.