S02 - ATT 22 - 581-22-700 - 100 Drawings Part-20 of 24.pdf

PDF 18 MB Posted

Attached to
EHRM Huntington VAMC 581-22-700 Construct Infrastructure Upgrades
Solicitation number
36C77626R0025
Issued by

About this file

This document set contains construction drawings for electrical and telecommunications infrastructure upgrades at the VA medical facility in Huntington, West Virginia, as part of the EHRM (Electronic Health Record Management) Infrastructure 581-22-700 project. The drawings are 100% Construction Documents issued September 3, 2025, prepared by SPEES Design Build with architect/engineer of record services.

The electrical scope includes panel schedules for Buildings 28, 34, and transformer rooms (TR1, TR3) showing existing equipment in gray text and new/revised circuits in black text. Key electrical requirements specify that contractors must update all panel circuit directories for changes with typewritten directories, reference associated equipment load schedules for overall panel loads, ensure all digital power meters and surge protective devices are integral to distribution equipment unless noted, and coordinate with existing conditions. The telecommunications scope establishes a physically secure, scalable, redundant backbone infrastructure with two independent indoor and outdoor conduit pathways (A/B routes) providing support for separate fiber optic network backbones extending from the Main Communications Room to each telecommunications room and equipment space. The outside plant design includes underground ductbanks with 4-inch Schedule 40 PVC conduits, in-ground handhole enclosures at 400-foot maximum intervals, metallic marker tape, and proper backfill procedures. Indoor pathways require wall-mounted lockable enclosures, 2-inch EMT conduits between building entry points and telecommunications rooms, and indoor tube distribution units in telecommunications/equipment rooms. Microduct tube cable installation uses HDPE 8.5/6mm microducts coupled with factory-authorized devices in sealed, air-tight enclosures. Fiber termination occurs via fusion splicing of factory-terminated LC style cassettes in telecommunications rooms with testing and as-built documentation required before project completion. Design standards reference ANSI/TIA Standards 568, 569, 606, 607, and 758, with all cabling installation following current editions of these standards and NEC requirements.

View the file

Other files

File Type Posted
S06 - 36C77626R0025 0008.pdf PDF
S06 - Amendment 0008 - ATT 7 - 02EP100B - ELECTRICAL 20260413.pdf PDF
S06 - Amendment 0008 - ATT 11 - Burn Permit.pdf PDF
S06 - Amendment 0008 - ATT 10 - 260508 - Sheet AD103-1B Data Center Phase 1B Demo Roof update.pdf PDF
S06 - Amendment 0008 - ATT 9 - 260508 - Sheet AD101-1B Data Center Phase 1B Demo Floor Plan update.pdf PDF
S06 - Amendment 0008 - ATT 1 - TechQuestionsVAresponses Final Set - Huntington EHRM IU.pdf PDF
S06 - Amendment 0008 - ATT 14 - Energized Electrical Work Permit.pdf PDF
S06 - Amendment 0008 - ATT 5 - ELECTRICAL 2026.04.13.pdf PDF
S06 - Amendment 0008 - ATT 6 - 01WEP100G - ELECTRICAL 20260413.pdf PDF
S06 - Amendment 0008 - ATT 3 - Civil OSP Redesign-signed.pdf PDF
S06 - Amendment 0008 - ATT 12 - Environmental Report Huntington WV.pdf PDF
S06 - Amendment 0008 - ATT 8 - 260508 - Sheet 01S-AE452 TR Tower 4 Wall sections update.pdf PDF
S06 - Amendment 0008 - ATT 13 - Hot Tapping Permit.pdf PDF
S06 - Amendment 0008 - ATT 2 - UPDATED SHEETS.pdf PDF
S06 - Amendment 0008 - ATT 4 - Structural Set 04-21-2026.pdf PDF
S06 - 36C77626R0025 0007.pdf PDF
S06 - Amendment 0007 - ATT 1 - TechQuestionsVAresponses Partial 4 - Huntington EHRM IU.pdf PDF
S06 - Amendment 0007 - ATT 3 - Lift Planning.pdf PDF
S06 - Amendment 0007 - ATT 2 - Geotechnical Report.pdf PDF
S06 - Amendment 0007 - ATT 5 - Appendix A - PFC FPT.pdf PDF
S06 - Amendment 0007 - ATT 4 - 01 00 00 - GENERAL REQUIREMENTS_A1.pdf PDF
S06 - Amendment 0007 - ATT 6 - Crane lift Info.pdf PDF
S06 - 36C77626R0025 0006.pdf PDF
S06 - Amendment 0006 - ATT 1 - TechQuestionsVAresponses Partial 3 - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0005.pdf PDF
S06 - Amendment 0004 - ATT 2 - FAR 52.222-90 ADDRESSING DEI DISCRIMINATION BY FEDERAL CONTRACTORS - APR 2026.pdf PDF
S06 - Amendment 0004 - ATT 1 - TechQuestionsVAresponses Partial 2 - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0004.pdf PDF
S06 - Amendment 0003 - ATT 2 - TechQuestionsVAresponses Partial - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0003.pdf PDF
S06 - 36C77626R0025 0002.pdf PDF
S06 - Amendment 0001 - ATT 1 - Site Visit In-Sheet - Huntington EHRM IU.pdf PDF
S06 - 36C77626R0025 0001.pdf PDF
S02 - ATT 28 - 581-22-700 - FLS Compliance Letter.pdf PDF
S02 - ATT 3 - 581-22-700 - 100 Drawings Part-1 of 24.pdf PDF
S02 - ATT 15 - 581-22-700 - 100 Drawings Part-13 of 24.pdf PDF
S02 - ATT 30 - 581-22-700 - 100 Commissioning Plan.pdf PDF
S02 - ATT 20 - 581-22-700 - 100 Drawings Part-18 of 24.pdf PDF
S02 - ATT 24 - 581-22-700 - 100 Drawings Part-22 of 24.pdf PDF
S02 - ATT 1 - 581-22-700 - 100 Specifications Part-1 of 2.pdf PDF
S02 - ATT 10 - 581-22-700 - 100 Drawings Part-8 of 24.pdf PDF
S02 - ATT 12 - 581-22-700 - 100 Drawings Part-10 of 24.pdf PDF
S02 - ATT 23 - 581-22-700 - 100 Drawings Part-21 of 24.pdf PDF
S02 - ATT 31 - 581-22-700 - Topographic Survey TR Tower 3.pdf PDF
S02 - ATT 25 - 581-22-700 - 100 Drawings Part-23 of 24.pdf PDF
S02 - ATT 16 - 581-22-700 - 100 Drawings Part-14 of 24.pdf PDF
S02 - ATT 21 - 581-22-700 - 100 Drawings Part-19 of 24.pdf PDF
S02 - ATT 34 - HEFP SEP Design Alerts 1-9 and 11-16.pdf PDF
S02 - ATT 29 - 581-22-700 - Geotechnical Report - W24044 - VA Duct Bank 11.21.24.pdf PDF
S02 - ATT 14 - 581-22-700 - 100 Drawings Part-12 of 24.pdf PDF
Show 40 more

Latest 50 of 68 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/3

/2

:1

:5

A M

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /V

A H

U N

T

IN

G T

O N

L e g e n d

G e n e ra l N o te s D ia g ra m s a n d

D e ta ils

.r v t

28EP701

BLDG 28 - ELECTRICAL SCHEDULES

DCW/NVP RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

Revisions: Date:

GENERAL NOTES

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT

DIRECTORIES TO INDICATE IN ANY AND ALL CHANGES; ALL

REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE

ASSOCIATED EQUIPMENT LOAD SCHEDULE FOR OVERALL

PANEL LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET

ARE SHOWN FOR ADDED BRANCH CIRCUIT SIZING ONLY.

3. ALL DIGITAL POWER METERS (DPM) AND SURGE

PROTECTIVE DEVICES (SPD) ARE INTEGRAL TO ELECTRICAL

DISTRIBUTION EQUIPMENT, UNLESS OTHERWISE NOTED.

4. SCHEDULES WITH GREY TEXT INDICATE EXISTING

PANELBOARD RATINGS, CIRCUITS, AND LOADS. BLACK TEXT

INDICATES REVISED CIRCUITS, PROVIDED EQUIPMENT, AND

ADDITIONAL LOAD.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/3

/2

:1

:5

A M

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /V

A H

U N

T

IN

G T

O N

L e g e n d

G e n e ra l N o te s D ia g ra m s a n d

D e ta ils

.r v t

34EP701

BLDG 34 - ELECTRICAL SCHEDULES

DCW/NVP RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

Revisions: Date:

GENERAL NOTES

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT

DIRECTORIES TO INDICATE IN ANY AND ALL CHANGES; ALL

REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE

ASSOCIATED EQUIPMENT LOAD SCHEDULE FOR OVERALL

PANEL LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET

ARE SHOWN FOR ADDED BRANCH CIRCUIT SIZING ONLY.

3. ALL DIGITAL POWER METERS (DPM) AND SURGE

PROTECTIVE DEVICES (SPD) ARE INTEGRAL TO ELECTRICAL

DISTRIBUTION EQUIPMENT, UNLESS OTHERWISE NOTED.

4. SCHEDULES WITH GREY TEXT INDICATE EXISTING

PANELBOARD RATINGS, CIRCUITS, AND LOADS. BLACK TEXT

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/3

/2

:1

:0

A M

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /V

A H

U N

T

IN

G T

O N

L e g e n d

G e n e ra l N o te s D ia g ra m s a n d

D e ta ils

.r v t

TR1EP701

BLDG TR1 - ELECTRICAL SCHEDULES

TR1

DCW/NVP RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

Revisions: Date:

GENERAL NOTES

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT

DIRECTORIES TO INDICATE IN ANY AND ALL CHANGES; ALL

REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE

ASSOCIATED EQUIPMENT LOAD SCHEDULE FOR OVERALL

PANEL LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET

ARE SHOWN FOR ADDED BRANCH CIRCUIT SIZING ONLY.

3. ALL DIGITAL POWER METERS (DPM) AND SURGE

PROTECTIVE DEVICES (SPD) ARE INTEGRAL TO ELECTRICAL

DISTRIBUTION EQUIPMENT, UNLESS OTHERWISE NOTED.

4. SCHEDULES WITH GREY TEXT INDICATE EXISTING

PANELBOARD RATINGS, CIRCUITS, AND LOADS. BLACK TEXT

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/3

/2

:1

:0

A M

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /V

A H

U N

T

IN

G T

O N

L e g e n d

G e n e ra l N o te s D ia g ra m s a n d

D e ta ils

.r v t

TR3EP701

BLDG TR3 - ELECTRICAL SCHEDULES

TR3

DCW/NVP RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

Revisions: Date:

GENERAL NOTES

1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT

DIRECTORIES TO INDICATE IN ANY AND ALL CHANGES; ALL

REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.

2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE

ASSOCIATED EQUIPMENT LOAD SCHEDULE FOR OVERALL

PANEL LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET

ARE SHOWN FOR ADDED BRANCH CIRCUIT SIZING ONLY.

3. ALL DIGITAL POWER METERS (DPM) AND SURGE

PROTECTIVE DEVICES (SPD) ARE INTEGRAL TO ELECTRICAL

DISTRIBUTION EQUIPMENT, UNLESS OTHERWISE NOTED.

4. SCHEDULES WITH GREY TEXT INDICATE EXISTING

PANELBOARD RATINGS, CIRCUITS, AND LOADS. BLACK TEXT

TNG000 - SHEET INDEX

TNG001 - ABBREVIATIONS AND GENERAL NOTES

TNG002 - TELECOMMUNICATIONS LEGENDS

TNG003 - TELECOMMUNICATIONS FIBER GENERAL NOTES

01TN100G - BLDG 01 - LEVEL 00G - TELECOMMUNICATIONS PLAN

01TN101 - BLDG 01 - LEVEL 01 - TELECOMMUNICATIONS PLAN

01TN102 - BLDG 01 - LEVEL 02 - TELECOMMUNICATIONS PLAN

01TN103 - BLDG 01 - LEVEL 03 - TELECOMMUNICATIONS PLAN

01TN104 - BLDG 01 - LEVEL 04 - TELECOMMUNICATIONS PLAN

01ATN100G - BLDG 01A - LEVEL 00G - TELECOMMUNICATIONS PLAN

01ATN101 - BLDG 01A - LEVEL 01 - TELECOMMUNICATIONS PLAN

01ATN102 - BLDG 01A - LEVEL 02 - TELECOMMUNICATIONS PLAN

01ATN103 - BLDG 01A - LEVEL 03 - TELECOMMUNICATIONS PLAN

01ATN104 - BLDG 01A - LEVEL 04 - TELECOMMUNICATIONS PLAN

01STN100B - BLDG 01S - LEVEL 00B - TELECOMMUNICATIONS PLAN

01STN100G - BLDG 01S - LEVEL 00G - TELECOMMUNICATIONS PLAN

01STN101 - BLDG 01S - LEVEL 01 - TELECOMMUNICATIONS PLAN

01STN102 - BLDG 01S - LEVEL 02 - TELECOMMUNICATIONS PLAN

01STN103 - BLDG 01S - LEVEL 03 - TELECOMMUNICATIONS PLAN

01STN104 - BLDG 01S - LEVEL 04 - TELECOMMUNICATIONS PLAN

01STN105 - BLDG 01S - LEVEL 05 - TELECOMMUNICATIONS PLAN

01STN106 - BLDG 01S - LEVEL 06 - TELECOMMUNICATIONS PLAN

01WTN100B - BLDG 01W - LEVEL 00B - TELECOMMUNICATIONS PLAN

01WTN100G - BLDG 01W - LEVEL 00G - TELECOMMUNICATIONS PLAN

01WTN101 - BLDG 01W - LEVEL 01 - TELECOMMUNICATIONS PLAN

01WTN102 - BLDG 01W - LEVEL 02 - TELECOMMUNICATIONS PLAN

01WTN103 - BLDG 01W - LEVEL 03 - TELECOMMUNICATIONS PLAN

01WTN104 - BLDG 01W - LEVEL 04 - TELECOMMUNICATIONS PLAN

02TN100B - BLDG 02 - LEVEL 00B - TELECOMMUNICATIONS PLAN

02TN100G - BLDG 02 - LEVEL 00G - TELECOMMUNICATIONS PLAN

02TN101 - BLDG 02 - LEVEL 01 - TELECOMMUNICATIONS PLAN

02TN102 - BLDG 02 - LEVEL 02 - TELECOMMUNICATIONS PLAN

03TN101 - BLDG 03 - LEVEL 01 - TELECOMMUNICATIONS PLAN

03TN102 - BLDG 03 - LEVEL 02 - TELECOMMUNICATIONS PLAN

04TN100 - BLDG 04 - LEVEL 00 - TELECOMMUNICATIONS PLAN

04TN101 - BLDG 04 - LEVEL 01 - TELECOMMUNICATIONS PLAN

04TN102 - BLDG 04 - LEVEL 02 - TELECOMMUNICATIONS PLAN

05TN100 - BLDG 05 - LEVEL 00 - TELECOMMUNICATIONS PLAN

05TN101 - BLDG 05 - LEVEL 01 - TELECOMMUNICATIONS PLAN

05TN102 - BLDG 05 - LEVEL 02 - TELECOMMUNICATIONS PLAN

06TN100 - BLDG 06 - LEVEL 00 - TELECOMMUNICATIONS PLAN

06TN101 - BLDG 06 - LEVEL 01 - TELECOMMUNICATIONS PLAN

06TN102 - BLDG 06 - LEVEL 02 - TELECOMMUNICATIONS PLAN

07TN100 - BLDG 07 - LEVEL 00 - TELECOMMUNICATIONS PLAN

07TN101 - BLDG 07 - LEVEL 01 - TELECOMMUNICATIONS PLAN

07TN102 - BLDG 07 - LEVEL 02 - TELECOMMUNICATIONS PLAN

07TN103 - BLDG 07 - LEVEL 03 - TELECOMMUNICATIONS PLAN

08TN100 - BLDG 08 - LEVEL 00 - TELECOMMUNICATIONS PLAN

08TN101 - BLDG 08 - LEVEL 01 - TELECOMMUNICATIONS PLAN

08TN102 - BLDG 08 - LEVEL 02 - TELECOMMUNICATIONS PLAN

08TN103 - BLDG 08 - LEVEL 03 - TELECOMMUNICATIONS PLAN

09TN100 - BLDG 09 - LEVEL 00 - TELECOMMUNICATIONS PLAN

09TN101 - BLDG 09 - LEVEL 01 - TELECOMMUNICATIONS PLAN

09TN102 - BLDG 09 - LEVEL 02 - TELECOMMUNICATIONS PLAN

12TN100G - BLDG 12 - LEVEL 00G - TELECOMMUNICATIONS PLAN

12TN101 - BLDG 12 - LEVEL 01 - TELECOMMUNICATIONS PLAN

12TN102 - BLDG 12 - LEVEL 02 - TELECOMMUNICATIONS PLAN

20TN101 - BLDG 20 - LEVEL 01 - TELECOMMUNICATIONS PLAN

20TN102 - BLDG 20 - LEVEL 02 - TELECOMMUNICATIONS PLAN

23RTN100B - BLDG 23R - LEVEL 00B - TELECOMMUNICATIONS PLAN

23RTN100G - BLDG 23R - LEVEL 00G - TELECOMMUNICATIONS PLAN

23RTN101 - BLDG 23R - LEVEL 01 - TELECOMMUNICATIONS PLAN

23RTN102 - BLDG 23R - LEVEL 02 - TELECOMMUNICATIONS PLAN

25TN101 - BLDG 25 - LEVEL 01 - TELECOMMUNICATIONS PLAN

25TN102 - BLDG 25 - LEVEL 02 - TELECOMMUNICATIONS PLAN

25TN103 - BLDG 25 - LEVEL 03 - TELECOMMUNICATIONS PLAN

25TN104 - BLDG 25 - LEVEL 04 - TELECOMMUNICATIONS PLAN

25TN105 - BLDG 25 - LEVEL 05 - TELECOMMUNICATIONS PLAN

28TN101 - BLDG 28 - LEVEL 01 - TELECOMMUNICATIONS PLAN

34TN100 - BLDG 34 - LEVEL 00 - TELECOMMUNICATIONS PLAN

34TN101 - BLDG 34 - LEVEL 01 - TELECOMMUNICATIONS PLAN

TR1TN101 - BLDG TR1 - LEVEL 01 - TELECOMMUNICATIONS PLAN

TR2TN101 - BLDG TR2 - LEVEL 01 - TELECOMMUNICATIONS PLAN

TR3TN101 - BLDG TR3 - LEVEL 01 - TELECOMMUNICATIONS PLAN

TR4TN101 - BLDG TR4 - LEVEL 01 - TELECOMMUNICATIONS PLAN

TR5TN101 - BLDG TR5 - LEVEL 01 - TELECOMMUNICATIONS PLAN

01TN400Ga - BLDG 01 - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01TN400Gb - DATA CENTER - DEMOLITION FLOOR PLAN - PHASE 1B 01TN400Gc - DATA CENTER - DEMOLITION OVERHEAD PLAN - PHASE 1B 01TN400Gd - DATA CENTER - TELECOMMUNICATIONS PLAN - PHASE 1B 01TN400Ge - DATA CENTER - OVERHEAD PLAN - PHASE 1B 01TN400Gf - DATA CENTER - DEMOLITION FLOOR PLAN - PHASE 2A 01TN400Gg - DATA CENTER - DEMOLITION OVERHEAD PLAN - PHASE 2A 01TN400Gh - DATA CENTER - TELECOMMUNICATIONS PLAN - PHASE 2A 01TN400Gi - DATA CENTER - OVERHEAD PLAN - PHASE 2A 01TN400Gj - DATA CENTER - DEMOLITION FLOOR PLAN - PHASE 2B 01TN400Gk - DATA CENTER - DEMOLITION OVERHEAD PLAN - PHASE 2B 01TN400Gl - DATA CENTER - TELECOMMUNICATIONS PLAN - PHASE 2B 01TN400Gm - DATA CENTER - OVERHEAD PLAN - PHASE 2B

01TN401 - BLDG 01 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

01TN402 - BLDG 01 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS

01TN403 - BLDG 01 - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS

01ATN400G - BLDG 01A - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS

01ATN402 - BLDG 01A - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS

01ATN403 - BLDG 01A - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS

01STN400Ba - BLDG 01S - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS 01STN400Bb - BLDG 01S - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS 01STN400Ga - BLDG 01S - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01STN400Gb - BLDG 01S - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01STN401a - BLDG 01S - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01STN401b - BLDG 01S - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01STN401c - BLDG 01S - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01STN401d - BLDG 01S - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01STN402a - BLDG 01S - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01STN402b - BLDG 01S - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01STN403a - BLDG 01S - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS 01STN403b - BLDG 01S - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS 01STN404a - BLDG 01S - LEVEL 04 - ENLARGED TELECOMMUNICATIONS PLANS 01STN404b - BLDG 01S - LEVEL 04 - ENLARGED TELECOMMUNICATIONS PLANS 01STN405a - BLDG 01S - LEVEL 05 - ENLARGED TELECOMMUNICATIONS PLANS 01STN405b - BLDG 01S - LEVEL 05 - ENLARGED TELECOMMUNICATIONS PLANS

01STN406 - BLDG 01S - LEVEL 06 - ENLARGED TELECOMMUNICATIONS PLANS

01WTN400Ga - BLDG 01W - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01WTN400Gb - BLDG 01W - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01WTN401a - BLDG 01W - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01WTN401b - BLDG 01W - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01WTN402a - BLDG 01W - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01WTN402b - BLDG 01W - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01WTN403a - BLDG 01W - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS 01WTN403b - BLDG 01W - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/3

/2

:3

:4

A M

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /V

A H

U N

T

IN

G T

O N

L e g e n d

G e n e ra l N o te s D ia g ra m s a n d

D e ta ils

.r v t

TNG000

SHEET INDEX

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

S H E E T I N D E X

02TN400B - BLDG 02 - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS

02TN400G - BLDG 02 - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS

03TN401 - BLDG 03 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

04TN400a - BLDG 04 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS 04TN400b - BLDG 04 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS

05TN400 - BLDG 05 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS

06TN401- BLDG 06 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

07TN400 - BLDG 07 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS

08TN400 - BLDG 08 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS

09TN402 - BLDG 09 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS

12TN401 - BLDG 12 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

12TN402 - BLDG 12 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS

20TN401a - BLDG 20 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 20TN401b - BLDG 20 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 20TN402a - BLDG 20 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 20TN402b - BLDG 20 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS

23RTN400B - BLDG 23R - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS

23RTN401 - BLDG 23R - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

25TN401 - BLDG 25 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

28TN401 - BLDG 28 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

34TN400 - BLDG 34 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS

TR1TN401a - BLDG TR1 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS TR1TN401b - BLDG TR1 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

TR2TN401 - BLDG TR2 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

TR3TN401 - BLDG TR3 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

TR4TN401 - BLDG TR4 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

TR5TN401 - BLDG TR5 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS

TN501 - TELECOMMUNICATIONS DETAILS

TN502 - TELECOMMUNICATIONS DETAILS

TN503 - TELECOMMUNICATIONS DETAILS

TN504 - TELECOMMUNICATIONS DETAILS

TN505 - TELECOMMUNICATIONS DETAILS

TN506 - TELECOMMUNICATIONS DETAILS

TN507 - TELECOMMUNICATIONS DETAILS

TN508 - TELECOMMUNICATIONS DETAILS

TN509 - TELECOMMUNICATIONS DETAILS

TN510 - TELECOMMUNICATIONS DETAILS

TN601 - FIBER RISER DIAGRAM

TN701 - TELECOMMUNICATIONS SCHEDULES

Revisions: Date: 535 OF 693

A B B R E V I A T I O N S

1PH SINGLE-PHASE

1P SINGLE POLE

2/C TWO-CONDUCTOR

3/C THREE-CONDUCTOR

3PH THREE-PHASE

4/C FOUR-CONDUCTOR

4W FOUR-WIRE

A/C AIR CONDITIONING UNIT

A/E ARCHITECT/ENGINEER

AAP ALARM ANNUNCIATOR PANEL

AC ALTERNATING CURRENT OR ARMORED CABLE

ACC ACCESSIBLE

ADDL ADDITIONAL

ADJ ADJACENT, ADJOINING

AF AMPERE FRAME OR AMP FUSE

AFC ABOVE FINISHED COUNTER, AUTOMATIC

FREQUENCY CONTROL, OR AVAILABLE

FAULT CURRENT

AFCI ARC-FAULT CURRENT INTERRUPTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AMPERE HOUR

AHJ AUTHORITY HAVING JURISDICTION

AIC AMPERE INTERRUPTING CAPACITY

ALT ALTERNATE

AMB AMBIENT

AMP AMPERE

ARCH ARCHITECT

ASC AMPS SHORT CIRCUIT

AT AMPERE TRIP

ATS AUTOMATIC TRANSFER SWITCH

AUTO AUTOMATIC

AV AUDIO VISUAL

BAT BATTERY

BD BOARD

BFF BELOW FINISH FLOOR

BLDG BUILDING

BRKR BREAKER

BYP BY PASS

C CONDUIT

CAB CABINET

CALC CALCULATE

CAP CAPACITY

CAT CATALOG

CATV COMMUNITY ANTENNA TELEVISION

CCR CONTROL CONTACTOR

CCTV CLOSED CIRCUIT TELEVISION

CD CANDELA

CD CONSTRUCTION DOCUMENTS

CF CONTRACTOR FURNISHED

CF/CI CONTRACTOR FURNISHED/

CONTRACTOR INSTALLED

CF/OI CONTRACTOR FURNISHED/

OWNER INSTALLED

CFE CONTRACTOR FURNISHED EQUIPMENT

CHW CHILLED WATER

CHWP CHILLED WATER PUMP

CKT CIRCUIT

C/B CIRCUIT BREAKER

CL CONNECTOR LIGHTING

CLF CURRENT LIMITING FUSE

CLG CEILING

CO CONDUIT ONLY

COAX COAX CABLE

COMM COMMUNICATION

COMPT COMPARTMENT

CONC CONCRETE

CONT CONTINUE

CONTR CONTRACTOR

COORD COORDINATE

CPT CONTROL POWER TRANSFORMER

CRI COLOR RENDERING INDEX

CT CURRENT TRANSFORMER

CTV CABLE TELEVISION

CU COPPER

CUR CURRENT

DB DECIBEL

DC DIRECT CURRENT

DCP DIMMER CONTROL PANEL

DDC DIRECT DIGITAL CONTROLS

DEG C DEGREES CELSIUS

DEG F DEGREES FAHRENHEIT

DEMO DEMOLITION

DIAG DIAGRAM

DISC DISCONNECT

DP DISTRIBUTION PANEL

DMR SW DIMMER SWITCH

DPDT DOUBLE POLE, DOUBLE THROW

DPST DOUBLE POLE, SINGLE THROW

DRSW DOOR SWITCH

DS DISCONNECT SWITCH

DWG DRAWING

EC ELECTRICAL CONTRACTOR

EL ELEVATION OR EXISTING TO BE RELOCATED

ELEC ELECTRIC OR ELECTRICAL

ELEV ELEVATOR

EMER/EM EMERGENCY

EMI ELECTROMAGNETIC INTERFERENCE

EMT ELECTRICAL METALLIC TUBING

EN EXISTING IN NEW LOCATION

ENCL ENCLOSURE

EPO EMERGENCY POWER OFF

EPRF EXPLOSION PROOF

ER EXISTING TO REMAIN

ESMT EASEMENT

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EXIST(E) EXISTING

FA FIRE ALARM

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

FC FOOTCANDLE

FCIO FURNISHED BY CONTRACTOR,

INSTALLED BY OWNER

FOIC FURNISHED BY OWNER,

INSTALLED BY CONTRACTOR

FIXT FIXTURE

FLA FULL LOAD AMPS

FLUOR FLUORESCENT

FP FIRE PROTECTION

FT FEET OR FOOT

FU SW FUSED SWITCH

FVNR FULL VOLTAGE NON-REVERSING

FVR FULL VOLTAGE REVERSING

G ELECTRICAL GROUND

GEN GENERATOR

GFCI GROUND FAULT

CIRCUIT INTERRUPTER

GFP GROUND FAULT PROTECTION

GND GROUND

HID HIGH INTENSITY DISCHARGE

HOA HAND-OFF-AUTOMATIC

HP HORSEPOWER

HT HEIGHT

HZ HERTZ

IG ISOLATED GROUND

IESNA ILLUMINATION ENGINEERING

SOCIETY OF NORTH AMERICA

IMC INTERMEDIATE METAL CONDUIT

INCAND INCANDESCENT

IR INFRARED

IWH INSTANTANEOUS WATER HEATER

J-BOX JUNCTION BOX

KV KILOVOLT

KVA KILOVOLT AMPERE

KVAH KILOVOLT AMPERE PER HOUR

KVAR KILOVOLT AMPERE REACTIVE

KW KILOWATT

KWH KILOWATT HOUR

KWHM KILOWATT HOUR METER

LCP LIGHTING CONTROL PANEL

LED LIGHT EMITTING DIODE

LF LINEAR FEET (FOOT)

LP LIGHT POLE

LPS LOW PRESSURE SODIUM

LRA LOCKED ROTOR AMPS

LT LIGHT

LTG LIGHTING

LTG PNL LIGHTING PANEL

LTNG LIGHTNING

LV LOW VOLTAGE

MAX MAXIMUM

MC METAL-CLAD

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MCC MOTOR CONTROL CENTER

MDP MAIN DISTRIBUTION PANEL

MECH MECHANICAL

MH MANHOLE

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MLO MAIN LUGS ONLY

MS MOTOR STARTER

MT MOUNT

MTD MOUNTED

MTG MOUNTING

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

MVA MEGAVOLT-AMPERE

MW MEGAWATT

NA NOT APPLICABLE

NAC NOTIFICATION APPLIANCE CABINET

NC NORMALLY CLOSED

NEC NATIONAL ELECTRICAL CODE

NEMA NATIONAL ELECTRICAL

MANUFACTURERS ASSOCIATION

NEUT, N NEUTRAL

NFC NOT FOR CONSTRUCTION

NFPA NATIONAL FIRE PROTECTION ASSOCIATION

NIC NOT IN CONTRACT

NL NIGHT LIGHT

NO NORMALLY OPEN

NTS NOT TO SCALE

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD

OL OVERLOAD

OS OCCUPANCY SENSOR

P POLE

PB PULL BOX

PEC PHOTOELECTRIC CELL

PED PEDESTAL

PEND PENDANT

PIV POST INDICATOR VALVE

PF POWER FACTOR

PH PHASE

PNL PANEL

PS POWER SUPPLY

PT POTENTIAL TRANSFORMER

PVC POLYVINYL CHLORIDE (PLASTIC)

PWR POWER

R EXISTING TO BE REMOVED

RCP REFLECTED CEILING PLAN

REC RECESSED

RECPT RECEPTACLE

RM ROOM

RMC RIGID METAL CONDUIT

RMS ROOT MEAN SQUARE

REQD REQUIRED

SAC SMALL APPLIANCE CIRCUIT

SCC SHORT CIRCUIT CAPACITY

SD SMOKE DETECTOR

SF SQUARE FOOT (FEET)

SHT SHEET

SI INTERNATIONAL SYSTEM OF UNITS

SM SMART METER

SPD SURGE PROTECTIVE DEVICE

SPEC SPECIFICATION

SPST SINGLE POLE, SINGLE THROW

SURF SURFACE

SW SWITCH

SWBD OR SB SWITCHBOARD

SWGR OR SG SWITCHGEAR

TEL TELEPHONE

TR TAMPER RESISTANT

TV TELEVISION

TYP TYPICAL

UFD UNDERFLOOR DUCT

UGND UNDERGROUND

UL UNDERWRITERS LABORATORY

UON UNLESS OTHERWISE NOTED

UPS UNINTERRUPTIBLE POWER

POWER SUPPLY

UTIL UTILITY

V VOLT

VA VOLT AMPERE

VAR VOLT AMPERE REACTIVE

VFD VARIABLE FREQUENCY DRIVE

VOLT VOLTAGE

W WATT/WEATHERPROOF

(WHILE IN USE)

WAO WORK AREA OUTLET

WH WATER HEATER

WP/W WEATHERPROOF

XFER TRANSFER

XFMR TRANSFORMER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/3

/2

:1

:5

A M

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /V

A H

U N

T

IN

G T

O N

L e g e n d

G e n e ra l N o te s D ia g ra m s a n d

D e ta ils

.r v t

TNG001

ABBREVIATIONS AND GENERAL NOTES

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

G E N E R A L N O T E S

1. THESE "GENERAL NOTES" SHALL APPLY TO ALL DRAWINGS WITHIN THIS DRAWING SET.

2. IF THE SPECIFICATIONS OR DRAWINGS CONFLICT WITH EACH OTHER THE MORE STRINGENT CRITERIA/SCOPE OF WORK SHALL BE REQUIRED.

3. BLACKENED OR BOLDED EQUIPMENT INDICATES THE EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR. ITEMS NOT DIRECTLY FURNISHED BY THE CONTRACTOR SHALL HAVE A DESIGNATION SUCH AS OFCI (OWNER FURNISHED CONTRACTOR INSTALLED), OFOI (OWNER FURNISHED OWNER INSTALLED), OR NIC (NOT IN CONTRACT). GRAY OR GRAY-SCALED EQUIPMENT SHALL BE ASSUMED TO BE EXISTING OR SHOWN FOR EQUIPMENT LOCATION COORDINATION.

4. ALL TELECOMMUNICATIONS SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE BICSI TDMM LATEST EDITION. ALL CONTRACTOR PERSONNEL WORKING ON THIS PROJECT SHALL BE TRAINED AND CERTIFIED BY THE MANUFACTURER OF THOSE PRODUCTS AND SHALL SUPPLY AS PART OF THE SUBMITTAL PROCESS THOSE CERTIFICATIONS PRIOR TO THE START OF ANY WORK.

5. ALL CONDUIT, SLEEVES, AND PATHWAYS SHALL BE FREE OF DEBRIS OR BLOCKAGES. ALL FIELD CUT RAW EDGES SHALL BE DEBURRED BY THE INSTALLING CONTRACTOR. ALL CONDUITS THAT FEED CATEGORY 6A CABLE TO A WORK AREA OUTLET (WAO) BOX

SHALL HAVE A PLASTIC BUSHING PLACED ON THE END OF THE CONDUIT.

6. THE INSTALLATION OF ALL COMMUNICATIONS PATHWAYS, SLEEVES, AND CABLE TRAYS SHALL BE LAID OUT BY THE CONTRACTOR AND SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO ANY WORK. DRAWINGS SHALL SHOW PROPOSED ROUTES THAT

WILL NOT CONFLICT WITH OTHER TRADES SUCH AS HVAC, ELECTRICAL, AND ARCHITECTURAL.

7. PRIOR TO INSTALLING CABLING, ALL EXISTING CABLES SHALL BE SEGREGATED INTO DIFFERENT GROUP TYPES; ONCE SEPARATED, CONTRACTOR SHALL DETERMINE WHICH CABLES SHALL BE REMOVED AND WHICH SHALL REMAIN. DEMOLISH ALL CABLES TO BE

REMOVED BACK TO SOURCE IN ITS ENTIRETY, UNLESS OTHERWISE NOTED.

8. MINIMUM CONDUIT SIZE SHALL BE 4” IN DIAMETER FOR EXTERIOR AND UNDERGROUND CONDUIT. MINIMUM CONDUIT SIZE SHALL BE ¾” IN DIAMETER FOR INTERIOR CONDUIT. ALL CONDUIT SHALL BE CONCEALED. THE ABOVE COMMENTS SHALL BE ADHERED TO

UNLESS OTHERWISE NOTED ON THE DRAWINGS.

9. LOW VOLTAGE VOICE AND DATA CABLING SHALL NOT BE INSTALLED IN THE SAME CONDUIT AS 120 VAC POWER CABLES.

10. ALL EQUIPMENT AND DEVICES INCLUDING, BUT NOT LIMITED TO LOW VOLTAGE EQUIPMENT, DATA OUTLETS, FIBER OPTIC CABLE, AND SPECIAL SYSTEM DEVICES, SHALL HAVE THEIR EXACT LOCATION COORDINATED WITH ARCHITECTURAL DRAWINGS AND ALL

TRADES PRIOR TO COMMENCING WORK.

11. ALL CONDUIT/SLEEVE FLOOR AND WALL PENETRATIONS SHALL BE SEALED WITH FIRE RATED ASSEMBLIES, CAULKING, AND APPURTENANCES. ELECTRICAL BOXES LOCATED IN FIRE RATED WALLS SHALL BE RATED FOR USE IN FIRE RATED WALLS.

12. ALL EQUIPMENT AND INSTALLATION METHODS SHALL BE LISTED AND LABELED PER NEC, UL LISTED, OR REVIEWED EQUAL.

13. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR NOTCHED WITHOUT PRIOR WRITTEN CONSENT FROM THE STRUCTURAL ENGINEER OR ARCHITECT.

14. IN AREAS WITH HARD LID CEILINGS, RE-USE EXISTING PATHWAYS TO RE-CABLE WAO (WORK AREA OUTLET) WITH CAT6A.

15. FOR EXISTING EQUIPMENT, SUCH AS LOW VOLTAGE DEVICES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.

16. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.

17. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT6A CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR, UNLESS OTHERWISE NOTED.

18. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER

OBSTRUCTIONS PRIOR TO INSTALLATION.

19. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180 DEGREES.

20. ALL SLOW SCAN TELEVISION AND ACCESS CONTROL SYSTEMS WILL BE INSTALLED AND MAINTAINED BY A CERTIFIED INSTALLER FOR EACH SPECIFIC SYSTEM.

21. THE DATA CENTER SHALL HAVE AN ALPHA-NUMERIC GRID ANNOTATED ON THE WALLS IN ACCORDANCE WITH ANSI/TIA 606-D. STARTING IN THE NORTHWEST CORNER WORKING THE ALPHABET LEFT TO RIGHT AND NUMBERS TOP TO BOTTOM IN 24-INCH INCREMENTS USING BLACK LETTERS AND NUMBERS FOUR INCHES MINIMUN IN HEIGHT NOT PLACED MORE THAN SIX INCHES BELOW THE CEILING.

22. ALL CEILING TILES WILL BE REINSTALLED AT THE END OF EACH WORK SHIFT.

23. ALL FIRE RATED PENETRATIONS WILL HAVE PROPER TEMPORARY FIRESTOP INSTALLED AT THE END OF EACH SHIFT AND UNTIL PERMANENT FIRESTOPPING IS COMPLETE.

24. GROUNDING & BONDING: AN ANTIOXIDANT SHALL BE USED ON ALL MECHANICAL CONNECTIONS AND TERMINATIONS.

25. THE CONTRACTOR SHALL PROVIDE ALL COPPER CATEGORY 6A PATCH CORDS FOR ALL TRs IN SCOPE. TR CATEGORY 6A PATCH CORDS SHALL BE 50% 3 FEET IN LENGTH AND 50% 5 FEET IN LENGTH. 28 AWG STRANDED PATCH CORDS ARE NOT ALLOWED.

CONTRACTOR SHALL PROVIDE 48 CATEGORY 6A PATCH CORDS FOR EACH 48-PORT SWITCH. JACKET COLORS SHALL BE BLUE OR WHITE. CONTRACTOR SHALL ALSO PROVIDE FIBER OPTIC PATCH CABLES (JUMPERS) FOR ALL FIBER OPTIC CABLES TERMINATED IN THE TRs. THESE CABLES MUST MATCH THE FIBER TYPE, OM4, OS1 AND OS2. FIBER OPTIC PATCH CABLES SHALL BE JACKETED WITH TWO (2) STRANDS EACH AND BE FACTORY TERMINATED WITH LC STYLE CONNECTORS. THE QUANTITY OF FIBER OPTIC PATCH CORDS SHALL MATCH THE NUMBER OF STRANDS TO EACH TR. FOR EXAMPLE, A TR HAVING 24 STRANDS OF OM4 FIBER OPTIC CABLE SHALL HAVE 12 OM4 FIBER OPTIC PATCH CABLES. IN THE TRS THE FIBER OPTIC PATCH CORDS WILL BE 5 FEET IN LENGTH AND BE JACKETED AS FOLLOWS: OM4 AQUA, OS1 AND OS2 YELLOW. CONTRACTOR SHALL BID AN ADDITIONAL 20% OF THE TOTAL PATCH COUNTS (FIBER AND COPPER).

26. THE CONTRACTOR SHALL PROVIDE ALL FACTORY TERMINATED CATEGORY 6A CABLES IN QUANTITIES LISTED IN THE DRAWINGS WITHIN THE MCR. 28 AWG STRANDED PATCH CORDS ARE NOT ACCEPTABLE. CABLE LENGTHS SHALL BE DETERMINED BY THE CONTRACTOR AFTER ALL CABINETS AND WIRE MANAGEMENT HAVE BEEN INSTALLED. CABLES SHALL HAVE AS LITTLE SLACK AS POSSIBLE, AND THAT SLACK SHALL BE CONTAINED WITHIN THE VERTICAL WIRE MANAGERS. CABLE JACKET COLORS SHALL BE BLUE OR WHITE. CONTRACTOR SHALL PROVIDE ALL FACTORY TERMINATED FIBER OPTIC PATCH CABLES REQUIRED AS LISTED IN THE DRAWINGS FOR THE MCR. THESE FIBER OPTIC CABLES, SHALL MATCH THE FIBER OPTIC CABLE TYPE. THESE CABLE TYPES ARE OM4, OS1 AND OS2. EACH PATCH CORD SHALL BE JACKETED TO MATCH THE FIBER TYPE, OM4 AQUA, OS1 AND OS2 YELLOW. EACH FIBER OPTIC PATCH CORD SHALL CONSIST OF TWO STRANDS OF THE CORRECT FIBER TYPE TERMINATED ON LC STYLE CONNECTORS.

FIBER OPTIC PATCH CORD LENGTHS SHALL NOT HAVE IN EXCESS OF 1 FOOT OF SLACK ON EACH END. CONTRACTOR SHALL BID AN ADDITIONAL 20% OF THE TOTAL PATCH COUNTS (FIBER AND COPPER).

27. ALL LOW-VOLTAGE SYSTEM CABLING NOT INSTALLED IN CONDUIT TO WALL MOUNTED DEVICE SHALL HAVE A MINIMUM 1"C ROUTED FROM DEVICE THROUGH WALL INTO THE ACCESSIBLE CEILING SPACE; CABLING SHALL NOT BE ROUTED IN WALLS OR IN AN

INACCESSIBLE LOCATION WITHOUT CONDUIT.

28. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, AND FINISHES SHALL BE REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE OWNER.

29. FOR ALL EQUIPMENT, COORDINATE WITH ALL TRADES (ARCHITECTURAL, MECHANICAL, PLUMBING, ETC) FOR ELECTRICAL AND LOW VOLTAGE REQUIREMENTS AND INSTALLATION LOCATIONS PRIOR TO INSTALLATION.

30. DEMOLISHED TELECOMMUNICATION RACKS SUPPORTING EXISTING/REMAINING SYSTEMS.

-COPPER & FIBER PHASING

• COPPER: CONTRACTOR TO PULL (12) CAT6A CABLES FROM DEMOLISHED TELECOMMUNICATION RACK TO NEW TELECOMMUNICATION RACK. TERMINATE, TEST AND COIL UP ON BOTH ENDS.

• FIBER: CONTRACTOR TO PULL 12-STRAND OPTICAL-MULTIMODE-4 FIBER AND 12-STRAND SINGLE-MODE FIBER FROM DEMOLISHED TELECOMMUNICATION RACK TO NEW TELECOMMUNICATION RACK. TERMINATE WITH LUCENT CONNECTORS ON NEW TELECOMMUNICATION RACK END, MATCH CONNECTOR TYPE WITH EXISTING EQUIPMENT ON DEMOLISHED TELECOMMUNICATION RACK END. TEST AND COIL UP ON BOTH ENDS.

31. FOR DEMOLISHED WAO'S (WORK AREA OUTLETS) THAT WON’T BE REPLACED: CABLE WILL BE REMOVED BACK TO THE SOURCE, A BLANK FACEPLATE WILL BE INSTALLED OVER THE DEMOLISHED BOX. CONDUIT WILL REMAIN.

32. CONTRACTOR SHALL FIELD VERIFY QUANTITY OF TELECOMMUNICATIONS EQUIPMENT REQUIRED PRIOR TO PURCHASE INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING: CABLE TRAY, WAO'S (WORK AREA OUTLETS), CAT6A CABLING, J-HOOKS, AND PATCH PANELS: VA SHALL NOT BE RESPONSIBLE FOR ANY SURPLUS OR OVERSTOCKING FEES FOR SAID EQUIPMENT.

33. ALL TERMINATIONS, CONNECTING BLOCKS, PATCH PANELS, RACKS, GROUND BARS, AND ASSOCIATED COMMUNICATIONS EQUIPMENT SHALL BE LABELED AND RECORDED BY THE CONTRACTOR. AS BUILT DOCUMENTS SHALL BE COMPILED BY THE CONTRACTOR AND FURNISHED TO THE ENGINEER AT THE END OF THE PROJECT INDICATING THE LOCATION OF ALL INSTALLED COMPONENTS AND THE LABELING OF THOSE COMPONENTS.

34. EQUIPMENT CIRCUITS SHALL BE ROUTED INDEPENDENT FROM OTHER CIRCUIT TYPES; ENSURE NEC 700.10 REQUIREMENTS ARE MET.

35. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.

36. THE CONTRACTOR SHALL USE EXISTING CABLE PATHWAY SUPPORTS FOR HORIZONTAL CAT6A CABLE RUNS. ADDITIONAL J-HOOKS WILL BE ADDED IF NEEDED TO MEET THE 3 - 5 FT SPACING STANDARD. IF EXISTING CABLE TRAY AND J-HOOKS ARE FULL, REMOVE EXISTING CABLE FROM CABLE TRAY AND J-HOOKS, SUPPORT THAT CABLE TO THE OUTSIDE OF THE TRAY AND J-HOOKS SO NEW CABLE CAN BE PLACED IN CABLE TRAY AND J-HOOKS. CABLE THAT HAS BEEN REPLACED WILL BE DEMOLISHED BACK TO THE

SOURCE.

37. CONTRACTOR TO COORDINATE WITH THE STATION TO IDENTIFY UNUSED CABLE. THESE IDENTIFIED UNUSED CABLES SHALL BE DEMOLISHED BACK TO THE SOURCE.

38. CONTRACTOR SHALL INCLUDE IN THEIR FINAL BID AN ADDITIONAL 10% WAO'S (WORK AREA OUTLETS) FOR THE ENTIRE PROJECT. CONTRACTOR SHALL RECEIVE DIRECTION FROM THE COR (CONTRACTING OFFICER'S REPRESENTATIVE) WHEN AND WHERE THESE ADDITIONAL WAO'S (WORK AREA OUTLETS) MAY BE USED. UPON THE INSTALLATION OF THESE ADDITIONAL WAO'S (WORK AREA OUTLETS), THE CONTRACTOR SHALL PROVIDE PAPERWORK TO THE COR (CONTRACTING OFFICER'S REPRESENTATIVE) SHOWING THE LOCATION, DATE OF INSTALLATION AND WAO'S (WORK AREA OUTLET) LABEL NUMBER WITH A RUNNING TOTAL OF WAO'S (WORK AREA OUTLETS) USED AND THE BALANCE LEFT. THESE WAO'S (WORK AREA OUTLETS) ARE TO BE INCLUDED IN THE AS BUILT

DOCUMENTS AT THE COMPLETION OF THE PROJECT.

Revisions: Date: 536 OF 693

SECTION

SHEET WHERE

SECTION IS

TAKEN FROM

SECTION LETTER

DETAIL NUMBER

SHEET ON WHICH

DETAIL APPEARS

DETAIL AREA

XXX CONDUIT & WIRE TAG

(REFER TO CONDUIT

AND WIRE SCHEDULE)

XX FAULT CURRENT TAG

(3 PH, SYM AMPS)

KEY NOTE

FIGURE OR PHOTO

DETAIL NUMBER

IF PHOTO, ARROW DENOTES

DIRECTION TAKEN

SHEET WHERE

DETAIL IS

TAKEN FROM

DETAIL/PLAN

DETAIL/PLAN NUMBER

SHEET WHERE

SECTION IS

TAKEN FROM

SCALE

SECTION LETTER

A

XXX

A

XXX

XXX

XXX

FIRE WALL (2 HOUR MIN.)

2 HR FIRE RATED WALL

1 HOUR FIRE BARRIER

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of

Construction and Facilities

Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 300

KENT, WA 98032

/3

/2

:2

:1

A M

B

IM

/5

-2

-7

V A

H u n t i n g to n E

H R

M /V

A H

U N

T

IN

G T

O N

L e g e n d

G e n e ra l N o te s D ia g ra m s a n d

D e ta ils

.r v t

TNG002

TELECOMMUNICATIONS LEGENDS

KG RTS/JNV

100% CONSTRUCTION

DOCUMENTS

09/03/2025

581-22-700EHRM INFRASTRUCTURE

UPGRADES - HUNTINGTON

VA HUNTINGTON

1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300

G E N E R A L S Y M B O L D I V 2 7 - L E G E N D D I V 2 8 - L E G E N D

AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL C-CHIME H-HORN K-KLAXON

L-LISTEN-IN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER

BI-STATIC BEAM SENSOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

I-INFRARED M-MICROWAVE

F=FUNCTION

RX-RECEIVE TX-TRANSMIT

BIOMETRICS ACCESS CONTROL DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS

R-EYE RETINA V-VOICE

CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL

M-MAG STRIP P-PROXIMITY S-SMART CARD

T-TOKEN

CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

CARD READER WITH TIME AND ATTENDANCE; LETTER INDICATES ASFOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

CENTRAL PROCESSING UNIT

CONTROL PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BURGLAR D-DOOR F-FIRE P-PERIMETER

ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE

EXIT DEVICE; LETTER INDICATES AS FOLLOWS:

T=TECHNOLOGY/TYP E

D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY

FIBER OPTIC MODULE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

R-RECEIVERT-TRANSCEIVER TX-TRANSMITTER

FIELD PANEL; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-ALARM C-CARD READER

GLASS BREAKAGE SENSOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN

M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-AUDIO S-SHOCK

INTERCOM; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

M-MASTER S-SUBSTATION

KEYBOARD

KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

MONITOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO

MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC

X-REQUEST-FOR-EXIT

RECORDER; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

A-AUDIO D-DIGITAL V-VIDEO

SECURITY ACCESS, ANNUNCIATOR PANEL

SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF

UNLESS OTHERWISE NOTED

SECURITY ACCESS, CONTROL UNIT WITH

CLOSED CIRCUIT TELEVISION CAMERA

SECURITY ACCESS, GENERIC "X" INDICATES THE

TYPE, PROVIDE SCHEDULE OR LEGEND

SECURITY ACCESS, HORN OR SIREN

SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT

SECURITY ACCESS, PANIC ALARM

SECURITY ACCESS, VIDEO CAMERA WITH LENS

M = MOTION DETECTOR

PZ = MOTION DETECTOR WITH PAN AND ZOOM

PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM

SECURITY ACCESS, VOLUMETRIC SENSOR

SECURITY SCREEN WITH ALARM; LETTER INDICATES ASFOLLOWS:

T=TECHNOLOGY/TYPE

B-BLIND S-SHADE

SECURITY WINDOW SCREEN; LETTER INDICATES ASFOLLOWS:

T=TECHNOLOGY/TYPE

B-BLIND

VIDEO CONTROL KEYBOARD

VIDEO MOTION DETECTOR

SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE

C = CEILING MOUNTED.

SECURITY ACCESS, SENSOR, BURIED VEHICULAR

SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL

SECURITY ACCESS, TELEPHONE HANDSET

SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW

ALARM, CHECK VALVE

ALARM, FIRE, COMMUNICATOR

ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:

FACC = CENTRAL CONSOLE FACP = CONTROL PANEL

MFACP= MASTER CONTROL PANELFAAP = ANNUNCIATORPANEL

ALARM, FIRE, MANUAL PULL STATION

ALARM, GONG

ALARM, HORN/LIGHT, ONE ASSEMBLY WITH CHIME

ALARM, HORN/LIGHT, SEPARATE ASSEMBLY

ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE

ALARM, MANUAL CONTROL

ALARM, MINI HORN

ALARM, SPRINKLER SYSTEM WATER FLOW BELL

ALARM, TAMPER SWITCH

DETECTION, GAS

DETECTION, SMOKE CONTROL AND PRESSURE PANEL

DETECTION SWITCH, ABORT

DETECTION SWITCH, VALVE TAMPER

DETECTOR, FLAME FLICKER

DETECTOR, FLOW SWITCH

DETECTOR, HEAT

DETECTOR, HEAT; LETTER INDICATES AS FOLLOWS:

R/T = COMBINATION F = FIXED TEMPERATURERISE

R/C = RATE COMPENSATION R = RATE OF

DETECTOR; LETTER INDICATES AS FOLLOWS:

BLANK = SMOKE DETECTOR

H = HEAT SMOKE

I = IONIZATION SMOKE

P = PHOTOELECTRIC SMOKE

IH = IONIZATION AND HEAT SMOKE

IP = IONIZATION AND PHOTOELECTRIC SMOKE

PH = PHOTOELECTRIC AND HEAT SMOKE

IPH = IONIZATION, PHOTOELECTRIC, AND HEAT

DETECTOR, SMOKE, FOR DUCT

DETECTOR, SWITCH LEVEL

PUSH BUTTON; LETTER INDICATES AS FOLLOWS:

M=MOUNT

C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION

P-PEDESTAL R-RACK S-SURFACE W-WALL

T=TECHNOLOGY/TYPE

B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE

X-REQUEST-FOR-EXIT

CODE ONE CONTROL AND ALARM STATION. MTD 5'-0"

AFF UNLESS OTHERWISE NOTED.

CODE ONE TERMINAL CABINET.

CODE ONE ANNUNCIATOR PANEL.

CODE ONE BEDSIDE STATION.

CODE ONE DUTY STATION, MTD 5'-0" AFF UNLESS

OTHERWISE NOTED.

ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:

BATT =BATTERIESCHR = CHARGER FAR = RECORDER

ALARM, FIRE, VALVE SUPERVISORY SWITCH.

ALARM, FIRE, TERMINAL CABINET.

ALARM, FIRE, POST INDICATOR VALVE.

ALARM, TRANSPONDER OR TRANSMITTER

ALARM, VOICE COMMUNICATION PANEL

FIRE ALARM STATION, MANUAL PULL

FIRE ALARM LINE = FA

ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET

CITY FIRE ALARM MASTER STATION MTD 5'-6" [1676mm] AFF UNLESS

NOTED.

FIRE ALARM TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.

FIRE ALARM TROUBLE TRANSMITTER (BASE LOOP) NUMERALS

DENOTE CODE.

ALARM, HORN/LIGHT, ONE ASSEMBLY C = WITH CHIME

360°

40°

X

M PTZ

FAT

2-4-6

FAT

2-4-6

AP

NIP

NIT

NIA

NI

NID

FAC

FACP

P

C

BATT

OSY

FATC

PIV

M

TS

FTR

SCCP

HD

R/T

HD

H

FS

DH

WB

M

T

M

T

M

F

T

M

T

T

M

M

M

M

T

T

M

T

M

T

M

T

M

T

M

M

T

M

T

M

T

M

T

T

T

CP

EPO

FA

M-MULLION

THESE ARE GENERAL LEGENDS. NOT ALL SYMBOLS MAY BE SHOWN.

REFERENCE PLANS FOR ALL UTILIZED SYMBOLS.

OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION

CABLE TELEVISION LINE = CATV

CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1" [25mm] CONDUIT

FIBEROPTICS LINE = FO

OUTLET TELEPHONE; LETTER INDICATES AS FOLLOWS:

J = JACK TYPE W = WALL TYPE

SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND

SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE

ON LEGEND. MTD. 7'-6" [2286mm] AFF UNLESS OTHERWISE NOTED.

OUTLET DATA OR VOIP TELEPHONE, "X" INDICATES NUMBER OF OUTLET PORTS. BOX AROUND

SYMBOL INDICATES FLOOR MOUNTED. "Y" = INDICATES AS FOLLOWS:

BLANK=EXISTING CONDUIT WITH NEW CAT6A CABLE

P=POLE/ PEDESTAL MOUNTED

F=FURNITURE MOUNTED

C=OUTLET WITH NEW CONDUIT INSTALLED, 3/4" MINIMUM UNLESS OTHERWISE STATED

TELEPHONE LINE = T

INTERCOM LINE = I. MINIMUM 3/4" [19mm] CONDUIT.

SOUND LINE = S

OUTLET; LETTER INDICATES AS FOLLOWS:

A = AUDIO V = VIDEO I = INTERCOM

RADIO CONDUIT RUN, MINIMUM 3/4" [19mm] CONDUIT.

RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.

SPEAKER PROGRAM SELECTOR SWITCH & VOLUME

CONTROL MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.

OUTLET, TELEVISION

BLANK = 4 11/16" [119mm] MASTER ANTENNA OUTLET BOX W/BLANK

COVER, MTD. 18" [457mm] AFF UNLESS OTHERWISE NOTED.

C = CAMERA (CCTV SYSTEM), MTD 18" [457mm] AFF

M = MONITOR (CTTV SYSTEM).

TELEPHONE TERMINAL CABINET

TELEPHONE BACKBOARD (WALL MOUNTED)

3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6" 1372mm] AFF.

REMOTE DICTATING OUTLET MTD 1'-6" [457mm] AFF. UNLESS OTHERWISE NOTED.

INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL

OPERATION OF INSTRUMENT & TYPE REQUIRED).

INTERCOM STAFF STATION.

TELECOMMUNICATIONS MANHOLE

DATA/COMMUNICATION

TTB

A

J

S X

S

X

M

R

M

C

R

R M

S

CATV

CCTV

FO

T

I

S

R

WIRELESS ACCESS POINT.

"S" = STAFF; "G" = GUEST. IF NOTED LIKE THIS "S,G", CONTRACTOR SHALL PROVIDE

(2) SEPARATE WAPs, (1) WAP FOR EACH SERVICE.

X X

XWAP

Y Y

P/D POWER/DATA POLE.

VERTICAL PENETRATION FOR FIBER-OPTIC CABLE. SEE

PLANS IF PENETRATION IS EXTENDING TO FLOOR

ABOVE OR BELOW. "X" INDICATES FIBER-OPTIC CABLE

REDUNDANCY.

"A" = A-SIDE FIBER

"B" = B-SIDE FIBER

"U" = UMBILICAL CORD FIBER

X

CONDUIT OR EQUIPMENT TO BE REMOVED

CONDUIT CONCEALED IN WALL, CEILING, UNDER FLOOR, IN

FLOOR SLAB, OR ROUTED UNDERGROUND

CONDUIT CONCEALED WHERE POSSIBLE, OTHERWISE EXPOSED

EXTRA-HARD USAGE FLEXIBLE CORD

FLEXIBLE CONDUIT

CONDUIT / CABLE TURNED UP OR TOWARD

CONDUIT / CABLE TURNED DOWN OR AWAY

CONDUIT CAPPED

H HANDHOLE A & B PATHWAYS COMBINED

JUNCTION BOX

PULL BOX

TUBE DISTRIBUTION UNIT

JB

PB

TDU

H HANDHOLE SINGLE PATHWAY

DD2

N2

"DD#" = THE NUMBER OF ETHERNET CABLES TO BE DEMOLISHED

"N#" = THE NUMBER OF NEW ETHERNET DROPS TO BE INSTALLED

CABLE TRAY

SIDE B - TELECOMMUNICATIONS PULL BOX , SIZE AS REQUIRED.

SIDE A FIBER OPTIC CONDUIT PATHWAY

SIDE A UNDERGROUND HANDHOLEH

SIDE B FIBER OPTIC CONDUIT PATHWAY

SIDE B UNDERGROUND HANDHOLEH

HORIZONTAL FIRE SLEEVE

Revisions: Date:

TUBE DISTRIBUTION UNIT SINGLE PATH - SIDE A

TUBE DISTRIBUTION UNIT SINGLE PATH - SIDE B

SIDE A - TELECOMMUNICATIONS PULL BOX, SIZE AS REQUIRED.

TDU

TDU

PROJECT SCOPE - VA EHRM OUTDOOR FIBER OPTIC BACKBONE INFRASTRUCTURE:

THIS PROJECT WILL ESTABLISH A PHYSICALLY SECURE, SCALABLE, AND REDUNDANT TELECOMMUNICATIONS BACKBONE INFRASTRUCTURE FOR THE VA EHRM CAMPUS WIDE NETWORK. THE INFRASTRUCTURE WILL PROVIDE SUPPORT FOR TWO INDEPENDENT INDOOR AND OUTDOOR CONDUIT PATHWAYS (A/B ROUTES) PROVIDING SUPPORT FOR TWO SEPARATE, INDEPENDENT, AND DIVERSE FIBER OPTIC NETWORK BACKBONES EXTENDING FROM THE MCR LOCATION TO EACH TR AND TE SPACE WITHIN THE

CAMPUS BUILDINGS. THE OUTSIDE PLANT (OSP) DESIGN SCOPE WILL INCLUDE:

OUTDOOR PATHWAYS - (A & B ROUTES):

UNDERGROUND DUCTBANKS WILL BE SIZED ACCORDING TO SITE REQUIREMENTS, 4” SCHEDULE 40 PVC CONDUITS (2 SPARE) ARE TO BE SET IN TRENCH ATOP A BED OF AGGREGATE FILL, WITH SPACERS AND TIE BARS, ALL OF WHICH IS TO BE ENCASED IN CONCRETE.

PLACE METALLIC MARKER TAPE 12” ABOVE THE COMPLETED CONCRETE DUCT BANK. BACKFILL, COMPACT, AND LEVEL ALL DISTURBED SURFACES. UNUSED BACKFILL AND DEBRIS IS TO BE REMOVED FROM SITE AND DISPOSED OF PROPERLY BEFORE PROJECT COMPLETION. A/B PATHWAY ROUTES ARE NOT TO BE LOCATED CLOSER THAN 50 FEET (15 M) TO EACH OTHER UNLESS PART OF BI- DIRECTIONAL LOOP; PATHWAYS MUST ENTER HEALTHCARE BUILDINGS AT DIFFERENT LOCATIONS.

TO FACILITATE CABLE INSTALLATION AND SERVICE, IN-GROUND “HANDHOLE” ENCLOSURES ARE TO BE PLACED PER 400' (MAX) PIPE SEGMENTS. NOTE, IF A PIPE SEGMENT CONTAINS MORE THAN (2) 90 DEGREE SWEEPING BENDS IT IS RECOMMENDED TO REDUCE THE SEGMENT LENGTH TO 200'. CERTAIN IN-GROUND ENCLOSURES WILL SERVE AS “SPLICE” POINTS OR “BUILDING SERVICE” POINTS IN WHICH CASE LARGER ENCLOSURES WILL BE USED TO FACILITATE THE STORAGE OF MICROTUBE COUPLING ENCLOSURES.

BOTTOMLESS ENCLOSURES ARE TO BE BACKFILLED WITH MINIMUM OF 4” AGGREGATE BASE WHICH IS NOT TO RISE ABOVE THE LOWEST POINT OF THE ENCLOSURE. ALL ENCLOSURES ARE TO BE SET TO SURFACE GRADE LEVEL. ALL IN-GROUND ENCLOSURES AND COVERS ARE TO MEET ANSI T15 LOAD RATINGS OR GREATER, COVERS ARE TO BE CLEARLY MARKED AS “TELECOMMUNICATIONS.”

CONDUITS SHOULD ALWAYS ENTER / EXIT THE IN-GROUND ENCLOSURES SHORTEST WALL TO ALLOW FOR PROPER CABLE MANAGEMENT. ALL CONDUIT ENTRY POINTS ARE TO BE SLEEVED WITH CONDUIT TERMINATION FITTINGS.

AT BUILDING ENTRY POINTS, 4” CONDUITS ARE TO BE SET FROM THE BUILDING SERVICE HANDHOLE TO THE BUILDING ENTRY POINT.

INDOOR PATHWAYS - (A & B ROUTES):

FROM THE BUILDING POINT OF ENTRY LOCATION, AN INDOOR WALL MOUNTED, LOCKABLE ENCLOSURE WILL BE PLACED TO HOUSE THE

2” INDOOR EMT CONDUITS (VIA THE TOP OF THE ENCLOSURE).

2” EMT CONDUITS ARE TO BE INSTALLED BETWEEN THE BUILDING ENTRY POINT INDOOR ENCLOSURE AND TR / TE ROOMS. PLEASE NOTE - THIS DOES NOT MEAN “HOME RUN” CONDUITS. THIS TOGETHER WITH THE CORRECT COUNT OF AAF MICROTUBES WILL ULTIMATELY PROVIDE THE DEDICATED PATHWAYS FOR THE INDIVIDUAL HOME RUNS FROM THE MCR TO EACH TR OR TE SPACE.

INDOOR TUBE DISTRIBUTION UNITS (TDU) ALSO NAMED “INDOOR TDU” LOCATIONS ARE TO BE LOCATED WITHIN THE TR OR TE ROOMS.

THIS TYPICAL WALL MOUNTED ENCLOSURE WILL STORE THE INDOOR MICROTUBE CABLE ENDS. THE FIBER CABLE WILL EXIT THIS ENCLOSURE PROTECTED VIA PLASTIC INNERDUCT OR FIBER DUCT (OR TRAY) TO THE FINAL TERMINATION POINT WITHIN THE TR / TE

EQUIPMENT RACK SPACE.

MICRODUCT TUBE CABLE INSTALLATION:

INSTALLATION OF HDPE 8.5/6MM MICRODUCTS WILL INCLUDE OUTDOOR MICRODUCT TUBE CABLES AND INDOOR MICRODUCT TUBE CABLES. THE OUTDOOR TUBE CABLES WILL BE SIZED PER SITE REQUIREMENTS AND WILL BE INSTALLED WITHIN THE CAMPUS WIDE OUTDOOR 4-INCH, CONCRETE ENCASED CONDUIT DUCTBANKS. THE OUTDOOR TUBE CABLES ARE TO BE COUPLED TOGETHER (WITHIN UNDERGROUND HANDHOLE ENCLOSURES) WITH FACTORY AUTHORIZED COUPLING DEVICES. ALL COUPLING JOINTS ARE TO BE SEALED AND PROTECTED AS AIR AND WATERTIGHT WITHIN RE-ENTERABLE COUPLING ENCLOSURES. THE INDOOR TUBE CABLES WILL BE SIZED PER SITE REQUIREMENTS AND WILL BE INSTALLED WITHIN THE INDOOR 2-INCH EMT CONDUIT INFRASTRUCTURE. THE INDOOR MICROTUBE CABLES ARE TO BE COUPLED TOGETHER WITH FACTORY AUTHORIZED COUPLING DEVICES. ALL COUPLING JOINTS ARE TO

BE SEALED AND PROTECTED AS AIR AND WATERTIGHT.

THE INDOOR AND OUTDOOR TUBE CABLES WILL BE “COUPLED” TOGETHER WITHIN THE ENCLOSURE TO ALLOW FOR THE 24 STRAND, OS2, SINGLE MODE FIBER OPTIC CABLE TO PASS THROUGH TO THE INDOOR TUBE DISTRIBUTION ENCLOSURE.

THE INDOOR TUBE ENCLOSURE WILL HOUSE ONLY INDOOR MICROTUBE CABLES. THIS ENCLOSURE WILL MARK THE DEMARCATION POINT FOR ALL AIR ASSISTED MICRODUCT TUBING. THE ENCLOSURE WILL BE WALL MOUNTED IN A LOCATION TO PROVIDE SECURE TRANSITION FOR THE ACTUAL SINGLE MODE FIBER CABLES FROM WITHIN THE ENCLOSURE TO THE RACK MOUNTED FIBER TERMINATION HARDWARE. INSTALLATION OF FIBER DUCT OR CHANNEL OR SIMILAR PROTECTIVE PATHWAY SYSTEM IS REQUIRED.

ALL MICRODUCT TUBE CABLES HOUSED WITHIN INDOOR OR OUTDOOR TDU ENCLOSURES ARE TO BE LABELED (PER SPEC), FURCATED, PROTECTED, & NEATLY COILED WITH STRAIN RELIEF PROTECTION TO ENSURE THE TUBE CABLE GROUPS ARE SECURED IN SUCH A WAY THAT THEY WILL NOT BE DAMAGED OR DISTURBED DURING ROUTINE MAINTENANCE OR FUTURE WORK PERFORMED.

AIR ASSISTED FIBER INSTALLATION:

WITH CONDUITS, ENCLOSURES, AND MICRODUCT TUBE CABLE PATHWAYS INSTALLED, ALL MICRODUCT TUBE CABLE PATHWAYS ARE TO BE PRESSURE TESTED TO MANUFACTURE'S REQUIREMENTS (BOTH A AND B ROUTES). INSTALLATION OF AIR ASSISTED FIBER OPTIC CABLES MAY NOW COMMENCE, THE INSTALLATION WILL INCLUDE “BLOWING” OR “JETTING” (1) 24 STRAND, OS2, SINGLE MODE FIBER, VIA INDIVIDUAL MICROTUBES FROM THE MCR TO EACH TR AND TE SPACE PER (A) AND (B) ROUTE.

FIBER TERMINATION AND TESTING:

FIBERS WILL TERMINATE IN THE TR/TE SPACE VIA FUSION SPLICING OF FACTORY TERMINATED LC STYLE CASSETTE OR MODULES WHICH WILL BE HOUSED WITHIN A SINGLE RACK UNIT FIBER ENCLOSURE. THE MCR FIBER ENDS WILL BE TERMINATED VIA FUSION SPLICING OF FACTORY TERMINATED MPO PIGTAILS (COORDINATE POLARITY BEFORE INSTALLATION) WHICH WILL BE CONNECTED TO REAR INTERFACE OF A 24 PORT LC FIBER CASSETTE OR MODULE. ALL FIBERS ARE TO BE LABELED AND TESTED TO COMPLIANCE, TEST

RESULTS AND AS-BUILT DRAWINGS TO BE DELIVERED BEFORE PROJECT COMPLETION.

FIRESTOPPING:

1. REFER TO SECTION 27 06 37 FOR ADDITIONAL INFORMATION.

2. CONTRACTOR SHALL INSTALL FIRESTOP WHERE TELECOMMUNICATIONS EQUIPMENT AND/OR CABLE PENETRATES A FIRE-RATED

CONSTRUCTION. THE NEW FIRESTOP SHALL MAINTAIN THE FIRE RATING OF THAT WALL OR FLOOR.

3. FIRE-RATED PENETRATIONS FOR DIVISION 27 CABLING SHALL BE RE-ENTERABLE AND LISTED BY A NTRL RECOGNIZED BY THE

AHJ.

4. FIRE-RATED PATHWAYS SHALL BE LISTED FOR USE FROM 0% TO 100% FILL WITHOUT THE USE OF ANY ANCILLARY MATERIALS

UNLESS NOTED OTHERWISE.

TESTING:

1. ALL FIBER OPTIC BACKBONE MEDIA SHALL PASS ALL VA REQUIREMENTS.

DESIGN STANDARDS:

ON-SITE TELECOMMUNICATIONS WORK DONE BY CONTRACTOR TO ACCOMMODATE FIELD CONDITIONS SHALL COMPLY WITH THE

CURRENT EDITION OF THE FOLLOWING DESIGN STANDARDS:

1. ANSI/TIA STANDARD 568 "COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD"

2. ANSI/TIA STANDARD 569 "TELECOMMUNICATIONS PATHWAYS AND SPACES"

3. ANSI/TIA STANDARD 606 "ADMINISTRATIVE STANDARD FOR COMMERCIAL TELECOMMUNICATIONS INFRASTRUCTURE"

4. ANSI/TIA STANDARD 607 "TELECOMMUNICATIONS BONDING AND GROUNDING (EARTHING) FOR CUSTOMER PREMISES"

5. ANSI/TIA STANDARD 758 "CUSTOMER-OWNED OUTSIDE PLANT TELECOMMUNICATIONS INFRASTRUCTURE STANDARD"

SPECIFICATIONS:

1. THE REFERENCED VA SPECIFICATIONS, IN ADDITION TO DIVISION 1 AND OTHER SECTIONS GOVERN THE WORK SHOWN ON THE

DRAWINGS. COMPLIANCE WITH DIVISION 27 IS MANDATORY.

2. IN CASES WHERE THE DRAWINGS AND SPECIFICATIONS CONFLICT WITH THEMSELVES OR WITH CODE, PROVIDE THE GREATER

QUANTITY, THE HIGHER QUALITY AND FOLLOW THE STRICTER REQUIREMENTS.

GENERAL NOTES:

1. THE GENERAL CONTRACTOR AND THEIR SUBS SHALL NOT REVISE, MODIFY, ALTER OR OTHERWISE DEVIATE FROM THESE DESIGN

DOCUMENTS WITHOUT WRITTEN AUTHORIZATION FROM THE CONSULTANT AND OWNER.

2. CONTRACTOR MUST REVIEW AND COMPLY WITH ALL REFERENCED SPECIFICATIONS.

3. CONTRACTOR TO COORDINATE AND OBTAIN WRITTEN AUTHORIZATION FROM VA…