S02 - ATT 22 - 581-22-700 - 100 Drawings Part-20 of 24.pdf
PDF 18 MB Posted
- Solicitation number
- 36C77626R0025
About this file
This document set contains construction drawings for electrical and telecommunications infrastructure upgrades at the VA medical facility in Huntington, West Virginia, as part of the EHRM (Electronic Health Record Management) Infrastructure 581-22-700 project. The drawings are 100% Construction Documents issued September 3, 2025, prepared by SPEES Design Build with architect/engineer of record services.
The electrical scope includes panel schedules for Buildings 28, 34, and transformer rooms (TR1, TR3) showing existing equipment in gray text and new/revised circuits in black text. Key electrical requirements specify that contractors must update all panel circuit directories for changes with typewritten directories, reference associated equipment load schedules for overall panel loads, ensure all digital power meters and surge protective devices are integral to distribution equipment unless noted, and coordinate with existing conditions. The telecommunications scope establishes a physically secure, scalable, redundant backbone infrastructure with two independent indoor and outdoor conduit pathways (A/B routes) providing support for separate fiber optic network backbones extending from the Main Communications Room to each telecommunications room and equipment space. The outside plant design includes underground ductbanks with 4-inch Schedule 40 PVC conduits, in-ground handhole enclosures at 400-foot maximum intervals, metallic marker tape, and proper backfill procedures. Indoor pathways require wall-mounted lockable enclosures, 2-inch EMT conduits between building entry points and telecommunications rooms, and indoor tube distribution units in telecommunications/equipment rooms. Microduct tube cable installation uses HDPE 8.5/6mm microducts coupled with factory-authorized devices in sealed, air-tight enclosures. Fiber termination occurs via fusion splicing of factory-terminated LC style cassettes in telecommunications rooms with testing and as-built documentation required before project completion. Design standards reference ANSI/TIA Standards 568, 569, 606, 607, and 758, with all cabling installation following current editions of these standards and NEC requirements.
View the file
Other files
Show 40 more
Latest 50 of 68 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:1
:5
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
28EP701
BLDG 28 - ELECTRICAL SCHEDULES
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
Revisions: Date:
GENERAL NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT
DIRECTORIES TO INDICATE IN ANY AND ALL CHANGES; ALL
REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE
ASSOCIATED EQUIPMENT LOAD SCHEDULE FOR OVERALL
PANEL LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET
ARE SHOWN FOR ADDED BRANCH CIRCUIT SIZING ONLY.
3. ALL DIGITAL POWER METERS (DPM) AND SURGE
PROTECTIVE DEVICES (SPD) ARE INTEGRAL TO ELECTRICAL
DISTRIBUTION EQUIPMENT, UNLESS OTHERWISE NOTED.
4. SCHEDULES WITH GREY TEXT INDICATE EXISTING
PANELBOARD RATINGS, CIRCUITS, AND LOADS. BLACK TEXT
INDICATES REVISED CIRCUITS, PROVIDED EQUIPMENT, AND
ADDITIONAL LOAD.
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:1
:5
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
34EP701
BLDG 34 - ELECTRICAL SCHEDULES
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
Revisions: Date:
GENERAL NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT
DIRECTORIES TO INDICATE IN ANY AND ALL CHANGES; ALL
REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE
ASSOCIATED EQUIPMENT LOAD SCHEDULE FOR OVERALL
PANEL LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET
ARE SHOWN FOR ADDED BRANCH CIRCUIT SIZING ONLY.
3. ALL DIGITAL POWER METERS (DPM) AND SURGE
PROTECTIVE DEVICES (SPD) ARE INTEGRAL TO ELECTRICAL
DISTRIBUTION EQUIPMENT, UNLESS OTHERWISE NOTED.
4. SCHEDULES WITH GREY TEXT INDICATE EXISTING
PANELBOARD RATINGS, CIRCUITS, AND LOADS. BLACK TEXT
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:1
:0
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
TR1EP701
BLDG TR1 - ELECTRICAL SCHEDULES
TR1
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
Revisions: Date:
GENERAL NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT
DIRECTORIES TO INDICATE IN ANY AND ALL CHANGES; ALL
REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE
ASSOCIATED EQUIPMENT LOAD SCHEDULE FOR OVERALL
PANEL LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET
ARE SHOWN FOR ADDED BRANCH CIRCUIT SIZING ONLY.
3. ALL DIGITAL POWER METERS (DPM) AND SURGE
PROTECTIVE DEVICES (SPD) ARE INTEGRAL TO ELECTRICAL
DISTRIBUTION EQUIPMENT, UNLESS OTHERWISE NOTED.
4. SCHEDULES WITH GREY TEXT INDICATE EXISTING
PANELBOARD RATINGS, CIRCUITS, AND LOADS. BLACK TEXT
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:1
:0
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
TR3EP701
BLDG TR3 - ELECTRICAL SCHEDULES
TR3
DCW/NVP RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
Revisions: Date:
GENERAL NOTES
1. CONTRACTOR SHALL UPDATE ALL PANEL CIRCUIT
DIRECTORIES TO INDICATE IN ANY AND ALL CHANGES; ALL
REVISED CIRCUIT DIRECTORIES SHALL BE TYPEWRITTEN.
2. FOR ALL "REVISED" PANEL SCHEDULES REFERENCE
ASSOCIATED EQUIPMENT LOAD SCHEDULE FOR OVERALL
PANEL LOAD. "REVISED" PANEL SCHEDULES ON THIS SHEET
ARE SHOWN FOR ADDED BRANCH CIRCUIT SIZING ONLY.
3. ALL DIGITAL POWER METERS (DPM) AND SURGE
PROTECTIVE DEVICES (SPD) ARE INTEGRAL TO ELECTRICAL
DISTRIBUTION EQUIPMENT, UNLESS OTHERWISE NOTED.
4. SCHEDULES WITH GREY TEXT INDICATE EXISTING
PANELBOARD RATINGS, CIRCUITS, AND LOADS. BLACK TEXT
TNG000 - SHEET INDEX
TNG001 - ABBREVIATIONS AND GENERAL NOTES
TNG002 - TELECOMMUNICATIONS LEGENDS
TNG003 - TELECOMMUNICATIONS FIBER GENERAL NOTES
01TN100G - BLDG 01 - LEVEL 00G - TELECOMMUNICATIONS PLAN
01TN101 - BLDG 01 - LEVEL 01 - TELECOMMUNICATIONS PLAN
01TN102 - BLDG 01 - LEVEL 02 - TELECOMMUNICATIONS PLAN
01TN103 - BLDG 01 - LEVEL 03 - TELECOMMUNICATIONS PLAN
01TN104 - BLDG 01 - LEVEL 04 - TELECOMMUNICATIONS PLAN
01ATN100G - BLDG 01A - LEVEL 00G - TELECOMMUNICATIONS PLAN
01ATN101 - BLDG 01A - LEVEL 01 - TELECOMMUNICATIONS PLAN
01ATN102 - BLDG 01A - LEVEL 02 - TELECOMMUNICATIONS PLAN
01ATN103 - BLDG 01A - LEVEL 03 - TELECOMMUNICATIONS PLAN
01ATN104 - BLDG 01A - LEVEL 04 - TELECOMMUNICATIONS PLAN
01STN100B - BLDG 01S - LEVEL 00B - TELECOMMUNICATIONS PLAN
01STN100G - BLDG 01S - LEVEL 00G - TELECOMMUNICATIONS PLAN
01STN101 - BLDG 01S - LEVEL 01 - TELECOMMUNICATIONS PLAN
01STN102 - BLDG 01S - LEVEL 02 - TELECOMMUNICATIONS PLAN
01STN103 - BLDG 01S - LEVEL 03 - TELECOMMUNICATIONS PLAN
01STN104 - BLDG 01S - LEVEL 04 - TELECOMMUNICATIONS PLAN
01STN105 - BLDG 01S - LEVEL 05 - TELECOMMUNICATIONS PLAN
01STN106 - BLDG 01S - LEVEL 06 - TELECOMMUNICATIONS PLAN
01WTN100B - BLDG 01W - LEVEL 00B - TELECOMMUNICATIONS PLAN
01WTN100G - BLDG 01W - LEVEL 00G - TELECOMMUNICATIONS PLAN
01WTN101 - BLDG 01W - LEVEL 01 - TELECOMMUNICATIONS PLAN
01WTN102 - BLDG 01W - LEVEL 02 - TELECOMMUNICATIONS PLAN
01WTN103 - BLDG 01W - LEVEL 03 - TELECOMMUNICATIONS PLAN
01WTN104 - BLDG 01W - LEVEL 04 - TELECOMMUNICATIONS PLAN
02TN100B - BLDG 02 - LEVEL 00B - TELECOMMUNICATIONS PLAN
02TN100G - BLDG 02 - LEVEL 00G - TELECOMMUNICATIONS PLAN
02TN101 - BLDG 02 - LEVEL 01 - TELECOMMUNICATIONS PLAN
02TN102 - BLDG 02 - LEVEL 02 - TELECOMMUNICATIONS PLAN
03TN101 - BLDG 03 - LEVEL 01 - TELECOMMUNICATIONS PLAN
03TN102 - BLDG 03 - LEVEL 02 - TELECOMMUNICATIONS PLAN
04TN100 - BLDG 04 - LEVEL 00 - TELECOMMUNICATIONS PLAN
04TN101 - BLDG 04 - LEVEL 01 - TELECOMMUNICATIONS PLAN
04TN102 - BLDG 04 - LEVEL 02 - TELECOMMUNICATIONS PLAN
05TN100 - BLDG 05 - LEVEL 00 - TELECOMMUNICATIONS PLAN
05TN101 - BLDG 05 - LEVEL 01 - TELECOMMUNICATIONS PLAN
05TN102 - BLDG 05 - LEVEL 02 - TELECOMMUNICATIONS PLAN
06TN100 - BLDG 06 - LEVEL 00 - TELECOMMUNICATIONS PLAN
06TN101 - BLDG 06 - LEVEL 01 - TELECOMMUNICATIONS PLAN
06TN102 - BLDG 06 - LEVEL 02 - TELECOMMUNICATIONS PLAN
07TN100 - BLDG 07 - LEVEL 00 - TELECOMMUNICATIONS PLAN
07TN101 - BLDG 07 - LEVEL 01 - TELECOMMUNICATIONS PLAN
07TN102 - BLDG 07 - LEVEL 02 - TELECOMMUNICATIONS PLAN
07TN103 - BLDG 07 - LEVEL 03 - TELECOMMUNICATIONS PLAN
08TN100 - BLDG 08 - LEVEL 00 - TELECOMMUNICATIONS PLAN
08TN101 - BLDG 08 - LEVEL 01 - TELECOMMUNICATIONS PLAN
08TN102 - BLDG 08 - LEVEL 02 - TELECOMMUNICATIONS PLAN
08TN103 - BLDG 08 - LEVEL 03 - TELECOMMUNICATIONS PLAN
09TN100 - BLDG 09 - LEVEL 00 - TELECOMMUNICATIONS PLAN
09TN101 - BLDG 09 - LEVEL 01 - TELECOMMUNICATIONS PLAN
09TN102 - BLDG 09 - LEVEL 02 - TELECOMMUNICATIONS PLAN
12TN100G - BLDG 12 - LEVEL 00G - TELECOMMUNICATIONS PLAN
12TN101 - BLDG 12 - LEVEL 01 - TELECOMMUNICATIONS PLAN
12TN102 - BLDG 12 - LEVEL 02 - TELECOMMUNICATIONS PLAN
20TN101 - BLDG 20 - LEVEL 01 - TELECOMMUNICATIONS PLAN
20TN102 - BLDG 20 - LEVEL 02 - TELECOMMUNICATIONS PLAN
23RTN100B - BLDG 23R - LEVEL 00B - TELECOMMUNICATIONS PLAN
23RTN100G - BLDG 23R - LEVEL 00G - TELECOMMUNICATIONS PLAN
23RTN101 - BLDG 23R - LEVEL 01 - TELECOMMUNICATIONS PLAN
23RTN102 - BLDG 23R - LEVEL 02 - TELECOMMUNICATIONS PLAN
25TN101 - BLDG 25 - LEVEL 01 - TELECOMMUNICATIONS PLAN
25TN102 - BLDG 25 - LEVEL 02 - TELECOMMUNICATIONS PLAN
25TN103 - BLDG 25 - LEVEL 03 - TELECOMMUNICATIONS PLAN
25TN104 - BLDG 25 - LEVEL 04 - TELECOMMUNICATIONS PLAN
25TN105 - BLDG 25 - LEVEL 05 - TELECOMMUNICATIONS PLAN
28TN101 - BLDG 28 - LEVEL 01 - TELECOMMUNICATIONS PLAN
34TN100 - BLDG 34 - LEVEL 00 - TELECOMMUNICATIONS PLAN
34TN101 - BLDG 34 - LEVEL 01 - TELECOMMUNICATIONS PLAN
TR1TN101 - BLDG TR1 - LEVEL 01 - TELECOMMUNICATIONS PLAN
TR2TN101 - BLDG TR2 - LEVEL 01 - TELECOMMUNICATIONS PLAN
TR3TN101 - BLDG TR3 - LEVEL 01 - TELECOMMUNICATIONS PLAN
TR4TN101 - BLDG TR4 - LEVEL 01 - TELECOMMUNICATIONS PLAN
TR5TN101 - BLDG TR5 - LEVEL 01 - TELECOMMUNICATIONS PLAN
01TN400Ga - BLDG 01 - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01TN400Gb - DATA CENTER - DEMOLITION FLOOR PLAN - PHASE 1B 01TN400Gc - DATA CENTER - DEMOLITION OVERHEAD PLAN - PHASE 1B 01TN400Gd - DATA CENTER - TELECOMMUNICATIONS PLAN - PHASE 1B 01TN400Ge - DATA CENTER - OVERHEAD PLAN - PHASE 1B 01TN400Gf - DATA CENTER - DEMOLITION FLOOR PLAN - PHASE 2A 01TN400Gg - DATA CENTER - DEMOLITION OVERHEAD PLAN - PHASE 2A 01TN400Gh - DATA CENTER - TELECOMMUNICATIONS PLAN - PHASE 2A 01TN400Gi - DATA CENTER - OVERHEAD PLAN - PHASE 2A 01TN400Gj - DATA CENTER - DEMOLITION FLOOR PLAN - PHASE 2B 01TN400Gk - DATA CENTER - DEMOLITION OVERHEAD PLAN - PHASE 2B 01TN400Gl - DATA CENTER - TELECOMMUNICATIONS PLAN - PHASE 2B 01TN400Gm - DATA CENTER - OVERHEAD PLAN - PHASE 2B
01TN401 - BLDG 01 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
01TN402 - BLDG 01 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS
01TN403 - BLDG 01 - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS
01ATN400G - BLDG 01A - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS
01ATN402 - BLDG 01A - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS
01ATN403 - BLDG 01A - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS
01STN400Ba - BLDG 01S - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS 01STN400Bb - BLDG 01S - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS 01STN400Ga - BLDG 01S - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01STN400Gb - BLDG 01S - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01STN401a - BLDG 01S - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01STN401b - BLDG 01S - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01STN401c - BLDG 01S - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01STN401d - BLDG 01S - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01STN402a - BLDG 01S - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01STN402b - BLDG 01S - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01STN403a - BLDG 01S - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS 01STN403b - BLDG 01S - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS 01STN404a - BLDG 01S - LEVEL 04 - ENLARGED TELECOMMUNICATIONS PLANS 01STN404b - BLDG 01S - LEVEL 04 - ENLARGED TELECOMMUNICATIONS PLANS 01STN405a - BLDG 01S - LEVEL 05 - ENLARGED TELECOMMUNICATIONS PLANS 01STN405b - BLDG 01S - LEVEL 05 - ENLARGED TELECOMMUNICATIONS PLANS
01STN406 - BLDG 01S - LEVEL 06 - ENLARGED TELECOMMUNICATIONS PLANS
01WTN400Ga - BLDG 01W - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01WTN400Gb - BLDG 01W - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS 01WTN401a - BLDG 01W - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01WTN401b - BLDG 01W - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 01WTN402a - BLDG 01W - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01WTN402b - BLDG 01W - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 01WTN403a - BLDG 01W - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS 01WTN403b - BLDG 01W - LEVEL 03 - ENLARGED TELECOMMUNICATIONS PLANS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:3
:4
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
TNG000
SHEET INDEX
KG RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
S H E E T I N D E X
02TN400B - BLDG 02 - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS
02TN400G - BLDG 02 - LEVEL 00G - ENLARGED TELECOMMUNICATIONS PLANS
03TN401 - BLDG 03 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
04TN400a - BLDG 04 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS 04TN400b - BLDG 04 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS
05TN400 - BLDG 05 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS
06TN401- BLDG 06 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
07TN400 - BLDG 07 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS
08TN400 - BLDG 08 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS
09TN402 - BLDG 09 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS
12TN401 - BLDG 12 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
12TN402 - BLDG 12 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS
20TN401a - BLDG 20 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 20TN401b - BLDG 20 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS 20TN402a - BLDG 20 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS 20TN402b - BLDG 20 - LEVEL 02 - ENLARGED TELECOMMUNICATIONS PLANS
23RTN400B - BLDG 23R - LEVEL 00B - ENLARGED TELECOMMUNICATIONS PLANS
23RTN401 - BLDG 23R - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
25TN401 - BLDG 25 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
28TN401 - BLDG 28 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
34TN400 - BLDG 34 - LEVEL 00 - ENLARGED TELECOMMUNICATIONS PLANS
TR1TN401a - BLDG TR1 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS TR1TN401b - BLDG TR1 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
TR2TN401 - BLDG TR2 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
TR3TN401 - BLDG TR3 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
TR4TN401 - BLDG TR4 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
TR5TN401 - BLDG TR5 - LEVEL 01 - ENLARGED TELECOMMUNICATIONS PLANS
TN501 - TELECOMMUNICATIONS DETAILS
TN502 - TELECOMMUNICATIONS DETAILS
TN503 - TELECOMMUNICATIONS DETAILS
TN504 - TELECOMMUNICATIONS DETAILS
TN505 - TELECOMMUNICATIONS DETAILS
TN506 - TELECOMMUNICATIONS DETAILS
TN507 - TELECOMMUNICATIONS DETAILS
TN508 - TELECOMMUNICATIONS DETAILS
TN509 - TELECOMMUNICATIONS DETAILS
TN510 - TELECOMMUNICATIONS DETAILS
TN601 - FIBER RISER DIAGRAM
TN701 - TELECOMMUNICATIONS SCHEDULES
Revisions: Date: 535 OF 693
A B B R E V I A T I O N S
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
AFCI ARC-FAULT CURRENT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AH AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BD BOARD
BFF BELOW FINISH FLOOR
BLDG BUILDING
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
CD CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/
OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
C/B CIRCUIT BREAKER
CL CONNECTOR LIGHTING
CLF CURRENT LIMITING FUSE
CLG CEILING
CO CONDUIT ONLY
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CUR CURRENT
DB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DDC DIRECT DIGITAL CONTROLS
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DP DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EL ELEVATION OR EXISTING TO BE RELOCATED
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER/EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
EN EXISTING IN NEW LOCATION
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ER EXISTING TO REMAIN
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST(E) EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCIO FURNISHED BY CONTRACTOR,
INSTALLED BY OWNER
FOIC FURNISHED BY OWNER,
INSTALLED BY CONTRACTOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G ELECTRICAL GROUND
GEN GENERATOR
GFCI GROUND FAULT
CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IG ISOLATED GROUND
IESNA ILLUMINATION ENGINEERING
SOCIETY OF NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERE
KVAH KILOVOLT AMPERE PER HOUR
KVAR KILOVOLT AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
KWHM KILOWATT HOUR METER
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MS MOTOR STARTER
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
NA NOT APPLICABLE
NAC NOTIFICATION APPLIANCE CABINET
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NEUT, N NEUTRAL
NFC NOT FOR CONSTRUCTION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
OS OCCUPANCY SENSOR
P POLE
PB PULL BOX
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PIV POST INDICATOR VALVE
PF POWER FACTOR
PH PHASE
PNL PANEL
PS POWER SUPPLY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
R EXISTING TO BE REMOVED
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RM ROOM
RMC RIGID METAL CONDUIT
RMS ROOT MEAN SQUARE
REQD REQUIRED
SAC SMALL APPLIANCE CIRCUIT
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SM SMART METER
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD OR SB SWITCHBOARD
SWGR OR SG SWITCHGEAR
TEL TELEPHONE
TR TAMPER RESISTANT
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER
POWER SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT/WEATHERPROOF
(WHILE IN USE)
WAO WORK AREA OUTLET
WH WATER HEATER
WP/W WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:1
:5
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
TNG001
ABBREVIATIONS AND GENERAL NOTES
KG RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
G E N E R A L N O T E S
1. THESE "GENERAL NOTES" SHALL APPLY TO ALL DRAWINGS WITHIN THIS DRAWING SET.
2. IF THE SPECIFICATIONS OR DRAWINGS CONFLICT WITH EACH OTHER THE MORE STRINGENT CRITERIA/SCOPE OF WORK SHALL BE REQUIRED.
3. BLACKENED OR BOLDED EQUIPMENT INDICATES THE EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR. ITEMS NOT DIRECTLY FURNISHED BY THE CONTRACTOR SHALL HAVE A DESIGNATION SUCH AS OFCI (OWNER FURNISHED CONTRACTOR INSTALLED), OFOI (OWNER FURNISHED OWNER INSTALLED), OR NIC (NOT IN CONTRACT). GRAY OR GRAY-SCALED EQUIPMENT SHALL BE ASSUMED TO BE EXISTING OR SHOWN FOR EQUIPMENT LOCATION COORDINATION.
4. ALL TELECOMMUNICATIONS SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE BICSI TDMM LATEST EDITION. ALL CONTRACTOR PERSONNEL WORKING ON THIS PROJECT SHALL BE TRAINED AND CERTIFIED BY THE MANUFACTURER OF THOSE PRODUCTS AND SHALL SUPPLY AS PART OF THE SUBMITTAL PROCESS THOSE CERTIFICATIONS PRIOR TO THE START OF ANY WORK.
5. ALL CONDUIT, SLEEVES, AND PATHWAYS SHALL BE FREE OF DEBRIS OR BLOCKAGES. ALL FIELD CUT RAW EDGES SHALL BE DEBURRED BY THE INSTALLING CONTRACTOR. ALL CONDUITS THAT FEED CATEGORY 6A CABLE TO A WORK AREA OUTLET (WAO) BOX
SHALL HAVE A PLASTIC BUSHING PLACED ON THE END OF THE CONDUIT.
6. THE INSTALLATION OF ALL COMMUNICATIONS PATHWAYS, SLEEVES, AND CABLE TRAYS SHALL BE LAID OUT BY THE CONTRACTOR AND SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO ANY WORK. DRAWINGS SHALL SHOW PROPOSED ROUTES THAT
WILL NOT CONFLICT WITH OTHER TRADES SUCH AS HVAC, ELECTRICAL, AND ARCHITECTURAL.
7. PRIOR TO INSTALLING CABLING, ALL EXISTING CABLES SHALL BE SEGREGATED INTO DIFFERENT GROUP TYPES; ONCE SEPARATED, CONTRACTOR SHALL DETERMINE WHICH CABLES SHALL BE REMOVED AND WHICH SHALL REMAIN. DEMOLISH ALL CABLES TO BE
REMOVED BACK TO SOURCE IN ITS ENTIRETY, UNLESS OTHERWISE NOTED.
8. MINIMUM CONDUIT SIZE SHALL BE 4” IN DIAMETER FOR EXTERIOR AND UNDERGROUND CONDUIT. MINIMUM CONDUIT SIZE SHALL BE ¾” IN DIAMETER FOR INTERIOR CONDUIT. ALL CONDUIT SHALL BE CONCEALED. THE ABOVE COMMENTS SHALL BE ADHERED TO
UNLESS OTHERWISE NOTED ON THE DRAWINGS.
9. LOW VOLTAGE VOICE AND DATA CABLING SHALL NOT BE INSTALLED IN THE SAME CONDUIT AS 120 VAC POWER CABLES.
10. ALL EQUIPMENT AND DEVICES INCLUDING, BUT NOT LIMITED TO LOW VOLTAGE EQUIPMENT, DATA OUTLETS, FIBER OPTIC CABLE, AND SPECIAL SYSTEM DEVICES, SHALL HAVE THEIR EXACT LOCATION COORDINATED WITH ARCHITECTURAL DRAWINGS AND ALL
TRADES PRIOR TO COMMENCING WORK.
11. ALL CONDUIT/SLEEVE FLOOR AND WALL PENETRATIONS SHALL BE SEALED WITH FIRE RATED ASSEMBLIES, CAULKING, AND APPURTENANCES. ELECTRICAL BOXES LOCATED IN FIRE RATED WALLS SHALL BE RATED FOR USE IN FIRE RATED WALLS.
12. ALL EQUIPMENT AND INSTALLATION METHODS SHALL BE LISTED AND LABELED PER NEC, UL LISTED, OR REVIEWED EQUAL.
13. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR NOTCHED WITHOUT PRIOR WRITTEN CONSENT FROM THE STRUCTURAL ENGINEER OR ARCHITECT.
14. IN AREAS WITH HARD LID CEILINGS, RE-USE EXISTING PATHWAYS TO RE-CABLE WAO (WORK AREA OUTLET) WITH CAT6A.
15. FOR EXISTING EQUIPMENT, SUCH AS LOW VOLTAGE DEVICES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
16. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING UNDISTURBED AREAS.
17. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT6A CABLING FROM EACH WAO (WORK AREA OUTLET) TO ITS RESPECTIVE TR, UNLESS OTHERWISE NOTED.
18. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/ CABLE TRAY ARE DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS, ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY OTHER
OBSTRUCTIONS PRIOR TO INSTALLATION.
19. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180 DEGREES.
20. ALL SLOW SCAN TELEVISION AND ACCESS CONTROL SYSTEMS WILL BE INSTALLED AND MAINTAINED BY A CERTIFIED INSTALLER FOR EACH SPECIFIC SYSTEM.
21. THE DATA CENTER SHALL HAVE AN ALPHA-NUMERIC GRID ANNOTATED ON THE WALLS IN ACCORDANCE WITH ANSI/TIA 606-D. STARTING IN THE NORTHWEST CORNER WORKING THE ALPHABET LEFT TO RIGHT AND NUMBERS TOP TO BOTTOM IN 24-INCH INCREMENTS USING BLACK LETTERS AND NUMBERS FOUR INCHES MINIMUN IN HEIGHT NOT PLACED MORE THAN SIX INCHES BELOW THE CEILING.
22. ALL CEILING TILES WILL BE REINSTALLED AT THE END OF EACH WORK SHIFT.
23. ALL FIRE RATED PENETRATIONS WILL HAVE PROPER TEMPORARY FIRESTOP INSTALLED AT THE END OF EACH SHIFT AND UNTIL PERMANENT FIRESTOPPING IS COMPLETE.
24. GROUNDING & BONDING: AN ANTIOXIDANT SHALL BE USED ON ALL MECHANICAL CONNECTIONS AND TERMINATIONS.
25. THE CONTRACTOR SHALL PROVIDE ALL COPPER CATEGORY 6A PATCH CORDS FOR ALL TRs IN SCOPE. TR CATEGORY 6A PATCH CORDS SHALL BE 50% 3 FEET IN LENGTH AND 50% 5 FEET IN LENGTH. 28 AWG STRANDED PATCH CORDS ARE NOT ALLOWED.
CONTRACTOR SHALL PROVIDE 48 CATEGORY 6A PATCH CORDS FOR EACH 48-PORT SWITCH. JACKET COLORS SHALL BE BLUE OR WHITE. CONTRACTOR SHALL ALSO PROVIDE FIBER OPTIC PATCH CABLES (JUMPERS) FOR ALL FIBER OPTIC CABLES TERMINATED IN THE TRs. THESE CABLES MUST MATCH THE FIBER TYPE, OM4, OS1 AND OS2. FIBER OPTIC PATCH CABLES SHALL BE JACKETED WITH TWO (2) STRANDS EACH AND BE FACTORY TERMINATED WITH LC STYLE CONNECTORS. THE QUANTITY OF FIBER OPTIC PATCH CORDS SHALL MATCH THE NUMBER OF STRANDS TO EACH TR. FOR EXAMPLE, A TR HAVING 24 STRANDS OF OM4 FIBER OPTIC CABLE SHALL HAVE 12 OM4 FIBER OPTIC PATCH CABLES. IN THE TRS THE FIBER OPTIC PATCH CORDS WILL BE 5 FEET IN LENGTH AND BE JACKETED AS FOLLOWS: OM4 AQUA, OS1 AND OS2 YELLOW. CONTRACTOR SHALL BID AN ADDITIONAL 20% OF THE TOTAL PATCH COUNTS (FIBER AND COPPER).
26. THE CONTRACTOR SHALL PROVIDE ALL FACTORY TERMINATED CATEGORY 6A CABLES IN QUANTITIES LISTED IN THE DRAWINGS WITHIN THE MCR. 28 AWG STRANDED PATCH CORDS ARE NOT ACCEPTABLE. CABLE LENGTHS SHALL BE DETERMINED BY THE CONTRACTOR AFTER ALL CABINETS AND WIRE MANAGEMENT HAVE BEEN INSTALLED. CABLES SHALL HAVE AS LITTLE SLACK AS POSSIBLE, AND THAT SLACK SHALL BE CONTAINED WITHIN THE VERTICAL WIRE MANAGERS. CABLE JACKET COLORS SHALL BE BLUE OR WHITE. CONTRACTOR SHALL PROVIDE ALL FACTORY TERMINATED FIBER OPTIC PATCH CABLES REQUIRED AS LISTED IN THE DRAWINGS FOR THE MCR. THESE FIBER OPTIC CABLES, SHALL MATCH THE FIBER OPTIC CABLE TYPE. THESE CABLE TYPES ARE OM4, OS1 AND OS2. EACH PATCH CORD SHALL BE JACKETED TO MATCH THE FIBER TYPE, OM4 AQUA, OS1 AND OS2 YELLOW. EACH FIBER OPTIC PATCH CORD SHALL CONSIST OF TWO STRANDS OF THE CORRECT FIBER TYPE TERMINATED ON LC STYLE CONNECTORS.
FIBER OPTIC PATCH CORD LENGTHS SHALL NOT HAVE IN EXCESS OF 1 FOOT OF SLACK ON EACH END. CONTRACTOR SHALL BID AN ADDITIONAL 20% OF THE TOTAL PATCH COUNTS (FIBER AND COPPER).
27. ALL LOW-VOLTAGE SYSTEM CABLING NOT INSTALLED IN CONDUIT TO WALL MOUNTED DEVICE SHALL HAVE A MINIMUM 1"C ROUTED FROM DEVICE THROUGH WALL INTO THE ACCESSIBLE CEILING SPACE; CABLING SHALL NOT BE ROUTED IN WALLS OR IN AN
INACCESSIBLE LOCATION WITHOUT CONDUIT.
28. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY DAMAGED MATERIALS, SYSTEMS, COMPONENTS, AND FINISHES SHALL BE REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF THE OWNER.
29. FOR ALL EQUIPMENT, COORDINATE WITH ALL TRADES (ARCHITECTURAL, MECHANICAL, PLUMBING, ETC) FOR ELECTRICAL AND LOW VOLTAGE REQUIREMENTS AND INSTALLATION LOCATIONS PRIOR TO INSTALLATION.
30. DEMOLISHED TELECOMMUNICATION RACKS SUPPORTING EXISTING/REMAINING SYSTEMS.
-COPPER & FIBER PHASING
• COPPER: CONTRACTOR TO PULL (12) CAT6A CABLES FROM DEMOLISHED TELECOMMUNICATION RACK TO NEW TELECOMMUNICATION RACK. TERMINATE, TEST AND COIL UP ON BOTH ENDS.
• FIBER: CONTRACTOR TO PULL 12-STRAND OPTICAL-MULTIMODE-4 FIBER AND 12-STRAND SINGLE-MODE FIBER FROM DEMOLISHED TELECOMMUNICATION RACK TO NEW TELECOMMUNICATION RACK. TERMINATE WITH LUCENT CONNECTORS ON NEW TELECOMMUNICATION RACK END, MATCH CONNECTOR TYPE WITH EXISTING EQUIPMENT ON DEMOLISHED TELECOMMUNICATION RACK END. TEST AND COIL UP ON BOTH ENDS.
31. FOR DEMOLISHED WAO'S (WORK AREA OUTLETS) THAT WON’T BE REPLACED: CABLE WILL BE REMOVED BACK TO THE SOURCE, A BLANK FACEPLATE WILL BE INSTALLED OVER THE DEMOLISHED BOX. CONDUIT WILL REMAIN.
32. CONTRACTOR SHALL FIELD VERIFY QUANTITY OF TELECOMMUNICATIONS EQUIPMENT REQUIRED PRIOR TO PURCHASE INCLUDING, BUT NOT LIMITED TO, THE FOLLOWING: CABLE TRAY, WAO'S (WORK AREA OUTLETS), CAT6A CABLING, J-HOOKS, AND PATCH PANELS: VA SHALL NOT BE RESPONSIBLE FOR ANY SURPLUS OR OVERSTOCKING FEES FOR SAID EQUIPMENT.
33. ALL TERMINATIONS, CONNECTING BLOCKS, PATCH PANELS, RACKS, GROUND BARS, AND ASSOCIATED COMMUNICATIONS EQUIPMENT SHALL BE LABELED AND RECORDED BY THE CONTRACTOR. AS BUILT DOCUMENTS SHALL BE COMPILED BY THE CONTRACTOR AND FURNISHED TO THE ENGINEER AT THE END OF THE PROJECT INDICATING THE LOCATION OF ALL INSTALLED COMPONENTS AND THE LABELING OF THOSE COMPONENTS.
34. EQUIPMENT CIRCUITS SHALL BE ROUTED INDEPENDENT FROM OTHER CIRCUIT TYPES; ENSURE NEC 700.10 REQUIREMENTS ARE MET.
35. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS BETWEEN DEVICES.
36. THE CONTRACTOR SHALL USE EXISTING CABLE PATHWAY SUPPORTS FOR HORIZONTAL CAT6A CABLE RUNS. ADDITIONAL J-HOOKS WILL BE ADDED IF NEEDED TO MEET THE 3 - 5 FT SPACING STANDARD. IF EXISTING CABLE TRAY AND J-HOOKS ARE FULL, REMOVE EXISTING CABLE FROM CABLE TRAY AND J-HOOKS, SUPPORT THAT CABLE TO THE OUTSIDE OF THE TRAY AND J-HOOKS SO NEW CABLE CAN BE PLACED IN CABLE TRAY AND J-HOOKS. CABLE THAT HAS BEEN REPLACED WILL BE DEMOLISHED BACK TO THE
SOURCE.
37. CONTRACTOR TO COORDINATE WITH THE STATION TO IDENTIFY UNUSED CABLE. THESE IDENTIFIED UNUSED CABLES SHALL BE DEMOLISHED BACK TO THE SOURCE.
38. CONTRACTOR SHALL INCLUDE IN THEIR FINAL BID AN ADDITIONAL 10% WAO'S (WORK AREA OUTLETS) FOR THE ENTIRE PROJECT. CONTRACTOR SHALL RECEIVE DIRECTION FROM THE COR (CONTRACTING OFFICER'S REPRESENTATIVE) WHEN AND WHERE THESE ADDITIONAL WAO'S (WORK AREA OUTLETS) MAY BE USED. UPON THE INSTALLATION OF THESE ADDITIONAL WAO'S (WORK AREA OUTLETS), THE CONTRACTOR SHALL PROVIDE PAPERWORK TO THE COR (CONTRACTING OFFICER'S REPRESENTATIVE) SHOWING THE LOCATION, DATE OF INSTALLATION AND WAO'S (WORK AREA OUTLET) LABEL NUMBER WITH A RUNNING TOTAL OF WAO'S (WORK AREA OUTLETS) USED AND THE BALANCE LEFT. THESE WAO'S (WORK AREA OUTLETS) ARE TO BE INCLUDED IN THE AS BUILT
DOCUMENTS AT THE COMPLETION OF THE PROJECT.
Revisions: Date: 536 OF 693
SECTION
SHEET WHERE
SECTION IS
TAKEN FROM
SECTION LETTER
DETAIL NUMBER
SHEET ON WHICH
DETAIL APPEARS
DETAIL AREA
XXX CONDUIT & WIRE TAG
(REFER TO CONDUIT
AND WIRE SCHEDULE)
XX FAULT CURRENT TAG
(3 PH, SYM AMPS)
KEY NOTE
FIGURE OR PHOTO
DETAIL NUMBER
IF PHOTO, ARROW DENOTES
DIRECTION TAKEN
SHEET WHERE
DETAIL IS
TAKEN FROM
DETAIL/PLAN
DETAIL/PLAN NUMBER
SHEET WHERE
SECTION IS
TAKEN FROM
SCALE
SECTION LETTER
A
XXX
A
XXX
XXX
XXX
FIRE WALL (2 HOUR MIN.)
2 HR FIRE RATED WALL
1 HOUR FIRE BARRIER
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of
Construction and Facilities
Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 300
KENT, WA 98032
/3
/2
:2
:1
A M
B
IM
/5
-2
-7
V A
H u n t i n g to n E
H R
M /V
A H
U N
T
IN
G T
O N
L e g e n d
G e n e ra l N o te s D ia g ra m s a n d
D e ta ils
.r v t
TNG002
TELECOMMUNICATIONS LEGENDS
KG RTS/JNV
100% CONSTRUCTION
DOCUMENTS
09/03/2025
581-22-700EHRM INFRASTRUCTURE
UPGRADES - HUNTINGTON
VA HUNTINGTON
1540 SPRING VALLEY DRIVE, HUNTINGTON, WV 25704-9300
G E N E R A L S Y M B O L D I V 2 7 - L E G E N D D I V 2 8 - L E G E N D
AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL C-CHIME H-HORN K-KLAXON
L-LISTEN-IN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER
BI-STATIC BEAM SENSOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
I-INFRARED M-MICROWAVE
F=FUNCTION
RX-RECEIVE TX-TRANSMIT
BIOMETRICS ACCESS CONTROL DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS
R-EYE RETINA V-VOICE
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALL CALL
M-MAG STRIP P-PROXIMITY S-SMART CARD
T-TOKEN
CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CARD READER WITH TIME AND ATTENDANCE; LETTER INDICATES ASFOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CENTRAL PROCESSING UNIT
CONTROL PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BURGLAR D-DOOR F-FIRE P-PERIMETER
ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE
EXIT DEVICE; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYP E
D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY
FIBER OPTIC MODULE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
R-RECEIVERT-TRANSCEIVER TX-TRANSMITTER
FIELD PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-ALARM C-CARD READER
GLASS BREAKAGE SENSOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN
M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO S-SHOCK
INTERCOM; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
KEYBOARD
KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
MONITOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DATA G-GRAPHIC M-MULTISCREEN V-VIDEO
MOTION DETECTOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DUAL TECHNOLOGY IR-INFRARED M-MICROWAVE U-ULTRASONIC
X-REQUEST-FOR-EXIT
RECORDER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO D-DIGITAL V-VIDEO
SECURITY ACCESS, ANNUNCIATOR PANEL
SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF
UNLESS OTHERWISE NOTED
SECURITY ACCESS, CONTROL UNIT WITH
CLOSED CIRCUIT TELEVISION CAMERA
SECURITY ACCESS, GENERIC "X" INDICATES THE
TYPE, PROVIDE SCHEDULE OR LEGEND
SECURITY ACCESS, HORN OR SIREN
SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT
SECURITY ACCESS, PANIC ALARM
SECURITY ACCESS, VIDEO CAMERA WITH LENS
M = MOTION DETECTOR
PZ = MOTION DETECTOR WITH PAN AND ZOOM
PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM
SECURITY ACCESS, VOLUMETRIC SENSOR
SECURITY SCREEN WITH ALARM; LETTER INDICATES ASFOLLOWS:
T=TECHNOLOGY/TYPE
B-BLIND S-SHADE
SECURITY WINDOW SCREEN; LETTER INDICATES ASFOLLOWS:
T=TECHNOLOGY/TYPE
B-BLIND
VIDEO CONTROL KEYBOARD
VIDEO MOTION DETECTOR
SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE
C = CEILING MOUNTED.
SECURITY ACCESS, SENSOR, BURIED VEHICULAR
SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL
SECURITY ACCESS, TELEPHONE HANDSET
SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW
ALARM, CHECK VALVE
ALARM, FIRE, COMMUNICATOR
ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:
FACC = CENTRAL CONSOLE FACP = CONTROL PANEL
MFACP= MASTER CONTROL PANELFAAP = ANNUNCIATORPANEL
ALARM, FIRE, MANUAL PULL STATION
ALARM, GONG
ALARM, HORN/LIGHT, ONE ASSEMBLY WITH CHIME
ALARM, HORN/LIGHT, SEPARATE ASSEMBLY
ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE
ALARM, MANUAL CONTROL
ALARM, MINI HORN
ALARM, SPRINKLER SYSTEM WATER FLOW BELL
ALARM, TAMPER SWITCH
DETECTION, GAS
DETECTION, SMOKE CONTROL AND PRESSURE PANEL
DETECTION SWITCH, ABORT
DETECTION SWITCH, VALVE TAMPER
DETECTOR, FLAME FLICKER
DETECTOR, FLOW SWITCH
DETECTOR, HEAT
DETECTOR, HEAT; LETTER INDICATES AS FOLLOWS:
R/T = COMBINATION F = FIXED TEMPERATURERISE
R/C = RATE COMPENSATION R = RATE OF
DETECTOR; LETTER INDICATES AS FOLLOWS:
BLANK = SMOKE DETECTOR
H = HEAT SMOKE
I = IONIZATION SMOKE
P = PHOTOELECTRIC SMOKE
IH = IONIZATION AND HEAT SMOKE
IP = IONIZATION AND PHOTOELECTRIC SMOKE
PH = PHOTOELECTRIC AND HEAT SMOKE
IPH = IONIZATION, PHOTOELECTRIC, AND HEAT
DETECTOR, SMOKE, FOR DUCT
DETECTOR, SWITCH LEVEL
PUSH BUTTON; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL PUSH D-DURESS P-PANIC R-DOOR RELEASE
X-REQUEST-FOR-EXIT
CODE ONE CONTROL AND ALARM STATION. MTD 5'-0"
AFF UNLESS OTHERWISE NOTED.
CODE ONE TERMINAL CABINET.
CODE ONE ANNUNCIATOR PANEL.
CODE ONE BEDSIDE STATION.
CODE ONE DUTY STATION, MTD 5'-0" AFF UNLESS
OTHERWISE NOTED.
ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:
BATT =BATTERIESCHR = CHARGER FAR = RECORDER
ALARM, FIRE, VALVE SUPERVISORY SWITCH.
ALARM, FIRE, TERMINAL CABINET.
ALARM, FIRE, POST INDICATOR VALVE.
ALARM, TRANSPONDER OR TRANSMITTER
ALARM, VOICE COMMUNICATION PANEL
FIRE ALARM STATION, MANUAL PULL
FIRE ALARM LINE = FA
ELECTROMAGNETIC TYPE DOOR HOLDER OUTLET
CITY FIRE ALARM MASTER STATION MTD 5'-6" [1676mm] AFF UNLESS
NOTED.
FIRE ALARM TRANSMITTER (BASE LOOP) NUMERALS DENOTE CODE.
FIRE ALARM TROUBLE TRANSMITTER (BASE LOOP) NUMERALS
DENOTE CODE.
ALARM, HORN/LIGHT, ONE ASSEMBLY C = WITH CHIME
360°
40°
X
M PTZ
FAT
2-4-6
FAT
2-4-6
AP
NIP
NIT
NIA
NI
NID
FAC
FACP
P
C
BATT
OSY
FATC
PIV
M
TS
FTR
SCCP
HD
R/T
HD
H
FS
DH
WB
M
T
M
T
M
F
T
M
T
T
M
M
M
M
T
T
M
T
M
T
M
T
M
T
M
M
T
M
T
M
T
M
T
T
T
CP
EPO
FA
M-MULLION
THESE ARE GENERAL LEGENDS. NOT ALL SYMBOLS MAY BE SHOWN.
REFERENCE PLANS FOR ALL UTILIZED SYMBOLS.
OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1" [25mm] CONDUIT
FIBEROPTICS LINE = FO
OUTLET TELEPHONE; LETTER INDICATES AS FOLLOWS:
J = JACK TYPE W = WALL TYPE
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON LEGEND
SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE
ON LEGEND. MTD. 7'-6" [2286mm] AFF UNLESS OTHERWISE NOTED.
OUTLET DATA OR VOIP TELEPHONE, "X" INDICATES NUMBER OF OUTLET PORTS. BOX AROUND
SYMBOL INDICATES FLOOR MOUNTED. "Y" = INDICATES AS FOLLOWS:
BLANK=EXISTING CONDUIT WITH NEW CAT6A CABLE
P=POLE/ PEDESTAL MOUNTED
F=FURNITURE MOUNTED
C=OUTLET WITH NEW CONDUIT INSTALLED, 3/4" MINIMUM UNLESS OTHERWISE STATED
TELEPHONE LINE = T
INTERCOM LINE = I. MINIMUM 3/4" [19mm] CONDUIT.
SOUND LINE = S
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM
RADIO CONDUIT RUN, MINIMUM 3/4" [19mm] CONDUIT.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME
CONTROL MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.
OUTLET, TELEVISION
BLANK = 4 11/16" [119mm] MASTER ANTENNA OUTLET BOX W/BLANK
COVER, MTD. 18" [457mm] AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" [457mm] AFF
M = MONITOR (CTTV SYSTEM).
TELEPHONE TERMINAL CABINET
TELEPHONE BACKBOARD (WALL MOUNTED)
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6" 1372mm] AFF.
REMOTE DICTATING OUTLET MTD 1'-6" [457mm] AFF. UNLESS OTHERWISE NOTED.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED).
INTERCOM STAFF STATION.
TELECOMMUNICATIONS MANHOLE
DATA/COMMUNICATION
TTB
A
J
S X
S
X
M
R
M
C
R
R M
S
CATV
CCTV
FO
T
I
S
R
WIRELESS ACCESS POINT.
"S" = STAFF; "G" = GUEST. IF NOTED LIKE THIS "S,G", CONTRACTOR SHALL PROVIDE
(2) SEPARATE WAPs, (1) WAP FOR EACH SERVICE.
X X
XWAP
Y Y
P/D POWER/DATA POLE.
VERTICAL PENETRATION FOR FIBER-OPTIC CABLE. SEE
PLANS IF PENETRATION IS EXTENDING TO FLOOR
ABOVE OR BELOW. "X" INDICATES FIBER-OPTIC CABLE
REDUNDANCY.
"A" = A-SIDE FIBER
"B" = B-SIDE FIBER
"U" = UMBILICAL CORD FIBER
X
CONDUIT OR EQUIPMENT TO BE REMOVED
CONDUIT CONCEALED IN WALL, CEILING, UNDER FLOOR, IN
FLOOR SLAB, OR ROUTED UNDERGROUND
CONDUIT CONCEALED WHERE POSSIBLE, OTHERWISE EXPOSED
EXTRA-HARD USAGE FLEXIBLE CORD
FLEXIBLE CONDUIT
CONDUIT / CABLE TURNED UP OR TOWARD
CONDUIT / CABLE TURNED DOWN OR AWAY
CONDUIT CAPPED
H HANDHOLE A & B PATHWAYS COMBINED
JUNCTION BOX
PULL BOX
TUBE DISTRIBUTION UNIT
JB
PB
TDU
H HANDHOLE SINGLE PATHWAY
DD2
N2
"DD#" = THE NUMBER OF ETHERNET CABLES TO BE DEMOLISHED
"N#" = THE NUMBER OF NEW ETHERNET DROPS TO BE INSTALLED
CABLE TRAY
SIDE B - TELECOMMUNICATIONS PULL BOX , SIZE AS REQUIRED.
SIDE A FIBER OPTIC CONDUIT PATHWAY
SIDE A UNDERGROUND HANDHOLEH
SIDE B FIBER OPTIC CONDUIT PATHWAY
SIDE B UNDERGROUND HANDHOLEH
HORIZONTAL FIRE SLEEVE
Revisions: Date:
TUBE DISTRIBUTION UNIT SINGLE PATH - SIDE A
TUBE DISTRIBUTION UNIT SINGLE PATH - SIDE B
SIDE A - TELECOMMUNICATIONS PULL BOX, SIZE AS REQUIRED.
TDU
TDU
PROJECT SCOPE - VA EHRM OUTDOOR FIBER OPTIC BACKBONE INFRASTRUCTURE:
THIS PROJECT WILL ESTABLISH A PHYSICALLY SECURE, SCALABLE, AND REDUNDANT TELECOMMUNICATIONS BACKBONE INFRASTRUCTURE FOR THE VA EHRM CAMPUS WIDE NETWORK. THE INFRASTRUCTURE WILL PROVIDE SUPPORT FOR TWO INDEPENDENT INDOOR AND OUTDOOR CONDUIT PATHWAYS (A/B ROUTES) PROVIDING SUPPORT FOR TWO SEPARATE, INDEPENDENT, AND DIVERSE FIBER OPTIC NETWORK BACKBONES EXTENDING FROM THE MCR LOCATION TO EACH TR AND TE SPACE WITHIN THE
CAMPUS BUILDINGS. THE OUTSIDE PLANT (OSP) DESIGN SCOPE WILL INCLUDE:
OUTDOOR PATHWAYS - (A & B ROUTES):
UNDERGROUND DUCTBANKS WILL BE SIZED ACCORDING TO SITE REQUIREMENTS, 4” SCHEDULE 40 PVC CONDUITS (2 SPARE) ARE TO BE SET IN TRENCH ATOP A BED OF AGGREGATE FILL, WITH SPACERS AND TIE BARS, ALL OF WHICH IS TO BE ENCASED IN CONCRETE.
PLACE METALLIC MARKER TAPE 12” ABOVE THE COMPLETED CONCRETE DUCT BANK. BACKFILL, COMPACT, AND LEVEL ALL DISTURBED SURFACES. UNUSED BACKFILL AND DEBRIS IS TO BE REMOVED FROM SITE AND DISPOSED OF PROPERLY BEFORE PROJECT COMPLETION. A/B PATHWAY ROUTES ARE NOT TO BE LOCATED CLOSER THAN 50 FEET (15 M) TO EACH OTHER UNLESS PART OF BI- DIRECTIONAL LOOP; PATHWAYS MUST ENTER HEALTHCARE BUILDINGS AT DIFFERENT LOCATIONS.
TO FACILITATE CABLE INSTALLATION AND SERVICE, IN-GROUND “HANDHOLE” ENCLOSURES ARE TO BE PLACED PER 400' (MAX) PIPE SEGMENTS. NOTE, IF A PIPE SEGMENT CONTAINS MORE THAN (2) 90 DEGREE SWEEPING BENDS IT IS RECOMMENDED TO REDUCE THE SEGMENT LENGTH TO 200'. CERTAIN IN-GROUND ENCLOSURES WILL SERVE AS “SPLICE” POINTS OR “BUILDING SERVICE” POINTS IN WHICH CASE LARGER ENCLOSURES WILL BE USED TO FACILITATE THE STORAGE OF MICROTUBE COUPLING ENCLOSURES.
BOTTOMLESS ENCLOSURES ARE TO BE BACKFILLED WITH MINIMUM OF 4” AGGREGATE BASE WHICH IS NOT TO RISE ABOVE THE LOWEST POINT OF THE ENCLOSURE. ALL ENCLOSURES ARE TO BE SET TO SURFACE GRADE LEVEL. ALL IN-GROUND ENCLOSURES AND COVERS ARE TO MEET ANSI T15 LOAD RATINGS OR GREATER, COVERS ARE TO BE CLEARLY MARKED AS “TELECOMMUNICATIONS.”
CONDUITS SHOULD ALWAYS ENTER / EXIT THE IN-GROUND ENCLOSURES SHORTEST WALL TO ALLOW FOR PROPER CABLE MANAGEMENT. ALL CONDUIT ENTRY POINTS ARE TO BE SLEEVED WITH CONDUIT TERMINATION FITTINGS.
AT BUILDING ENTRY POINTS, 4” CONDUITS ARE TO BE SET FROM THE BUILDING SERVICE HANDHOLE TO THE BUILDING ENTRY POINT.
INDOOR PATHWAYS - (A & B ROUTES):
FROM THE BUILDING POINT OF ENTRY LOCATION, AN INDOOR WALL MOUNTED, LOCKABLE ENCLOSURE WILL BE PLACED TO HOUSE THE
2” INDOOR EMT CONDUITS (VIA THE TOP OF THE ENCLOSURE).
2” EMT CONDUITS ARE TO BE INSTALLED BETWEEN THE BUILDING ENTRY POINT INDOOR ENCLOSURE AND TR / TE ROOMS. PLEASE NOTE - THIS DOES NOT MEAN “HOME RUN” CONDUITS. THIS TOGETHER WITH THE CORRECT COUNT OF AAF MICROTUBES WILL ULTIMATELY PROVIDE THE DEDICATED PATHWAYS FOR THE INDIVIDUAL HOME RUNS FROM THE MCR TO EACH TR OR TE SPACE.
INDOOR TUBE DISTRIBUTION UNITS (TDU) ALSO NAMED “INDOOR TDU” LOCATIONS ARE TO BE LOCATED WITHIN THE TR OR TE ROOMS.
THIS TYPICAL WALL MOUNTED ENCLOSURE WILL STORE THE INDOOR MICROTUBE CABLE ENDS. THE FIBER CABLE WILL EXIT THIS ENCLOSURE PROTECTED VIA PLASTIC INNERDUCT OR FIBER DUCT (OR TRAY) TO THE FINAL TERMINATION POINT WITHIN THE TR / TE
EQUIPMENT RACK SPACE.
MICRODUCT TUBE CABLE INSTALLATION:
INSTALLATION OF HDPE 8.5/6MM MICRODUCTS WILL INCLUDE OUTDOOR MICRODUCT TUBE CABLES AND INDOOR MICRODUCT TUBE CABLES. THE OUTDOOR TUBE CABLES WILL BE SIZED PER SITE REQUIREMENTS AND WILL BE INSTALLED WITHIN THE CAMPUS WIDE OUTDOOR 4-INCH, CONCRETE ENCASED CONDUIT DUCTBANKS. THE OUTDOOR TUBE CABLES ARE TO BE COUPLED TOGETHER (WITHIN UNDERGROUND HANDHOLE ENCLOSURES) WITH FACTORY AUTHORIZED COUPLING DEVICES. ALL COUPLING JOINTS ARE TO BE SEALED AND PROTECTED AS AIR AND WATERTIGHT WITHIN RE-ENTERABLE COUPLING ENCLOSURES. THE INDOOR TUBE CABLES WILL BE SIZED PER SITE REQUIREMENTS AND WILL BE INSTALLED WITHIN THE INDOOR 2-INCH EMT CONDUIT INFRASTRUCTURE. THE INDOOR MICROTUBE CABLES ARE TO BE COUPLED TOGETHER WITH FACTORY AUTHORIZED COUPLING DEVICES. ALL COUPLING JOINTS ARE TO
BE SEALED AND PROTECTED AS AIR AND WATERTIGHT.
THE INDOOR AND OUTDOOR TUBE CABLES WILL BE “COUPLED” TOGETHER WITHIN THE ENCLOSURE TO ALLOW FOR THE 24 STRAND, OS2, SINGLE MODE FIBER OPTIC CABLE TO PASS THROUGH TO THE INDOOR TUBE DISTRIBUTION ENCLOSURE.
THE INDOOR TUBE ENCLOSURE WILL HOUSE ONLY INDOOR MICROTUBE CABLES. THIS ENCLOSURE WILL MARK THE DEMARCATION POINT FOR ALL AIR ASSISTED MICRODUCT TUBING. THE ENCLOSURE WILL BE WALL MOUNTED IN A LOCATION TO PROVIDE SECURE TRANSITION FOR THE ACTUAL SINGLE MODE FIBER CABLES FROM WITHIN THE ENCLOSURE TO THE RACK MOUNTED FIBER TERMINATION HARDWARE. INSTALLATION OF FIBER DUCT OR CHANNEL OR SIMILAR PROTECTIVE PATHWAY SYSTEM IS REQUIRED.
ALL MICRODUCT TUBE CABLES HOUSED WITHIN INDOOR OR OUTDOOR TDU ENCLOSURES ARE TO BE LABELED (PER SPEC), FURCATED, PROTECTED, & NEATLY COILED WITH STRAIN RELIEF PROTECTION TO ENSURE THE TUBE CABLE GROUPS ARE SECURED IN SUCH A WAY THAT THEY WILL NOT BE DAMAGED OR DISTURBED DURING ROUTINE MAINTENANCE OR FUTURE WORK PERFORMED.
AIR ASSISTED FIBER INSTALLATION:
WITH CONDUITS, ENCLOSURES, AND MICRODUCT TUBE CABLE PATHWAYS INSTALLED, ALL MICRODUCT TUBE CABLE PATHWAYS ARE TO BE PRESSURE TESTED TO MANUFACTURE'S REQUIREMENTS (BOTH A AND B ROUTES). INSTALLATION OF AIR ASSISTED FIBER OPTIC CABLES MAY NOW COMMENCE, THE INSTALLATION WILL INCLUDE “BLOWING” OR “JETTING” (1) 24 STRAND, OS2, SINGLE MODE FIBER, VIA INDIVIDUAL MICROTUBES FROM THE MCR TO EACH TR AND TE SPACE PER (A) AND (B) ROUTE.
FIBER TERMINATION AND TESTING:
FIBERS WILL TERMINATE IN THE TR/TE SPACE VIA FUSION SPLICING OF FACTORY TERMINATED LC STYLE CASSETTE OR MODULES WHICH WILL BE HOUSED WITHIN A SINGLE RACK UNIT FIBER ENCLOSURE. THE MCR FIBER ENDS WILL BE TERMINATED VIA FUSION SPLICING OF FACTORY TERMINATED MPO PIGTAILS (COORDINATE POLARITY BEFORE INSTALLATION) WHICH WILL BE CONNECTED TO REAR INTERFACE OF A 24 PORT LC FIBER CASSETTE OR MODULE. ALL FIBERS ARE TO BE LABELED AND TESTED TO COMPLIANCE, TEST
RESULTS AND AS-BUILT DRAWINGS TO BE DELIVERED BEFORE PROJECT COMPLETION.
FIRESTOPPING:
1. REFER TO SECTION 27 06 37 FOR ADDITIONAL INFORMATION.
2. CONTRACTOR SHALL INSTALL FIRESTOP WHERE TELECOMMUNICATIONS EQUIPMENT AND/OR CABLE PENETRATES A FIRE-RATED
CONSTRUCTION. THE NEW FIRESTOP SHALL MAINTAIN THE FIRE RATING OF THAT WALL OR FLOOR.
3. FIRE-RATED PENETRATIONS FOR DIVISION 27 CABLING SHALL BE RE-ENTERABLE AND LISTED BY A NTRL RECOGNIZED BY THE
AHJ.
4. FIRE-RATED PATHWAYS SHALL BE LISTED FOR USE FROM 0% TO 100% FILL WITHOUT THE USE OF ANY ANCILLARY MATERIALS
UNLESS NOTED OTHERWISE.
TESTING:
1. ALL FIBER OPTIC BACKBONE MEDIA SHALL PASS ALL VA REQUIREMENTS.
DESIGN STANDARDS:
ON-SITE TELECOMMUNICATIONS WORK DONE BY CONTRACTOR TO ACCOMMODATE FIELD CONDITIONS SHALL COMPLY WITH THE
CURRENT EDITION OF THE FOLLOWING DESIGN STANDARDS:
1. ANSI/TIA STANDARD 568 "COMMERCIAL BUILDING TELECOMMUNICATIONS CABLING STANDARD"
2. ANSI/TIA STANDARD 569 "TELECOMMUNICATIONS PATHWAYS AND SPACES"
3. ANSI/TIA STANDARD 606 "ADMINISTRATIVE STANDARD FOR COMMERCIAL TELECOMMUNICATIONS INFRASTRUCTURE"
4. ANSI/TIA STANDARD 607 "TELECOMMUNICATIONS BONDING AND GROUNDING (EARTHING) FOR CUSTOMER PREMISES"
5. ANSI/TIA STANDARD 758 "CUSTOMER-OWNED OUTSIDE PLANT TELECOMMUNICATIONS INFRASTRUCTURE STANDARD"
SPECIFICATIONS:
1. THE REFERENCED VA SPECIFICATIONS, IN ADDITION TO DIVISION 1 AND OTHER SECTIONS GOVERN THE WORK SHOWN ON THE
DRAWINGS. COMPLIANCE WITH DIVISION 27 IS MANDATORY.
2. IN CASES WHERE THE DRAWINGS AND SPECIFICATIONS CONFLICT WITH THEMSELVES OR WITH CODE, PROVIDE THE GREATER
QUANTITY, THE HIGHER QUALITY AND FOLLOW THE STRICTER REQUIREMENTS.
GENERAL NOTES:
1. THE GENERAL CONTRACTOR AND THEIR SUBS SHALL NOT REVISE, MODIFY, ALTER OR OTHERWISE DEVIATE FROM THESE DESIGN
DOCUMENTS WITHOUT WRITTEN AUTHORIZATION FROM THE CONSULTANT AND OWNER.
2. CONTRACTOR MUST REVIEW AND COMPLY WITH ALL REFERENCED SPECIFICATIONS.
3. CONTRACTOR TO COORDINATE AND OBTAIN WRITTEN AUTHORIZATION FROM VA…
This is the start of the file's text. The full file is on GovTribe.