P106_R1_AD2___PLUMBING_ROOF_PLAN__ALTERNATE.pdf

PDF 263 KB Posted

Attached to
RFP for Ridgeland High School Renovations
Solicitation number
PE-55462-NONST-2026-000000017
Issued by
Wilcox County, Georgia

About this file

This is a plumbing and roofing plan document prepared by Southern A&E, LLC for Ridgeland High School Renovations commissioned by Walker County Schools in Lafayette, Georgia. The document comprises architectural drawings and specifications for plumbing and gas system work to be performed only if the alternate is selected as part of Bid Package BP-1. The scope includes removal and replacement of roof drains, modification of gas piping systems at varying pressures (7" water column and 5 PSI medium pressure), removal of gas pressure regulators, connection of new sanitary vents, and connection of new drainage components to existing infrastructure. The work is designated as Phase 2 and requires field verification of exact sizes and locations of existing systems prior to installation. The drawings are presented at a scale of 1/16" = 1'-0" on standard architectural E1 sheet size and include a detailed keynote schedule identifying specific alternate tasks and their corresponding locations on the roof plan. The document was issued for construction on January 20, 2025, with revisions documented on November 13, 2025 (AD1) and November 21, 2025 (AD2).

The document provides technical specifications and visual reference materials for contractors bidding on the alternate plumbing scope rather than pricing or financial terms. The project is registered with the State Board of Registration for Professional Engineers and Land Surveyors under engineer firm license number PEF003374, with an expiration date of June 30, 2026. All intellectual property rights are retained by Southern A&E, LLC, and reproduction of the document without express written consent is prohibited. The drawings serve as construction documents to guide contractors in executing the specified alternates for gas piping, drainage, and vent modifications at Ridgeland High School.

View the file

Other files

File Type Posted
P203_R1_AD2___PLUMBING_ENLARGED_PLANS.pdf PDF
E003_R2_AD2___MECHANICAL_EQUIPMENT_CONNECTION.pdf PDF
M113_R2_AD2_MECHANICAL_DEMOLITION_PLAN__WING_.pdf PDF
M126_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
E123_R2_AD2___WING_G__ELECTRICAL_DEMOLITION_P.pdf PDF
Advertisement _ RHS Renovations.pdf PDF
E135_R2_AD2___WING_F_G_K__ROOF__POWER_PLAN.pdf PDF
E117_R1_AD2___WING_E__POWER_PLAN.pdf PDF
ADDENDUM_2__COMPLETE.pdf PDF
E103_R2_AD2___WING_A__POWER_PLAN.pdf PDF
M128_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
M112_R2_AD2_MECHANICAL_DEMOLITION_PLAN__WING_.pdf PDF
M130_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
P102_R1_AD2___PLUMBING_RENOVATION_PLAN__PHASE.pdf PDF
P201_R1_AD2___PLUMBING_ENLARGED_PLANS.pdf PDF
M115_R2_AD2_MECHANICAL_DEMOLITION_PLAN__WING_.pdf PDF
M127_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
M125_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
E129_R2_AD2___MEZZ_LEVEL__WING_G__POWER_PLAN.pdf PDF
M129_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
M602_R2_AD2_MECHANICAL_EQUIPMENT_SCHEDULES.pdf PDF
M110_R2_AD2_MECHANICAL_DEMOLITION_PLAN__WING_.pdf PDF
M601_R2_AD2_MECHANICAL_EQUIPMENT_SCHEDULES.pdf PDF
E125_R2_AD2___WING_G__POWER_PLAN.pdf PDF
P202_R1_AD2___PLUMBING_ENLARGED_PLANS.pdf PDF
P103_R1_AD2___PLUMBING_RENOVATION_FLOOR_PLAN_.pdf PDF
M503_R2_AD2_MECHANICAL_EQUIPMENT_DETAILS.pdf PDF
Project Award Recommendation _ RHS HVAC.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

M G

P

S I

G - 7" W.C.G - 7" W.C.

G5

G5

G5 G7

G7

G6

G8

D32

D33 D33

D32

D32

D32

D32 D32

D32

D32

NOTE: SCOPE OF WORK WILL ONLY BE PERFORMED IF ALTERNATE IS TAKEN.

M G

P

S I

MG - 5 PSI

MG - 5 PSI

GPR-2A

GPR-2B

G9

3/4"

1 1/2"

2" G - 7" W.C.

1 1/4"

1 1/4"

1 1/4"

G10

G10

G - 7" W.C.

1 1/2"

RD-1

RD-1

RD-1

RD-1 RD-1

RD-1

RD-1

RD-1

P46 P46

P45 P45

P45

P45

P45P45

P45

P45

NOTE: SCOPE OF WORK WILL ONLY BE PERFORMED IF ALTERNATE IS TAKEN.

G15

DRAWING NUMBER

REVISIONS

COPYRIGHT 2025 BY SOUTHERN A&E, LLC. ALL RIGHTS RESERVED.

THIS DOCUMENT IS THE PROPERTY OF SOUTHERN A&E, LLC AND SHALL

NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT

EXPRESSED WRITTEN CONSENT FROM SOUTHERN A&E, LLC.

10-31-2025

BID PACKAGE BP-1

SA&E PROJECT NUMBER

ORIGINAL SHEET SIZE: ARCH E1 (30" X 42")

A

TRUE

NORTH

2" GRIDS 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

B

C

D

E

F

G

H

I

J

K

L

M

N

RIDGELAND HIGH SCHOOL

RENOVATIONS TO:

WALKER COUNTY SCHOOLS

301 N CHEROKEE ST, LAFAYETTE, GA 30728

2478 HAPPY VALLEY RD, ROSSVILLE, GA 30741

746-0190

01-920-045

ISSUED FOR CONSTRUCTION

STATE BOARD OF REGISTRATION

FOR PROFESSIONAL ENGINEERS AND

LAND SURVEYORS

SOUTHERN A & E, LLC

ENGINEER FIRM

LICENSE NO: PEF003374

EXP. DATE - 06/30/2026

P106

PLUMBING ROOF PLAN - ALTERNATE

1/16" = 1'-0"P106

1 ALTERNATE: PLUMBING DEMOLITION ROOF PLAN - PHASE 2

1/16" = 1'-0"P106

2 ALTERNATE: PLUMBING ROOF PLAN - PHASE 2

SCALE: = 1'-0"

0 16 3216

1/16"

KEYNOTE SCHEDULE

# KEYNOTE DESCRIPTION

D32 ALTERNATE: REMOVE ROOF DRAIN AND REPLACE WITH NEW RD-1. FIELD VERIFY EXACT SIZE

AND LOCATION OF EXISTING.

D33 ALTERNATE: EXISTING SANITARY VENT TO REMAIN.

G5 ALTERNATE: REMOVE GAS PIPE - RE: RENOVATION PLANS FOR NEW GAS PIPING.

G6 ALTERNATE: REMOVE GAS PIPE BACK TO APPROX 1 FT BELOW ROOF LINE.

G7 ALTERNATE: EXISTING LOW PRESSURE (7" WC) GAS PIPE THROUGH ROOF TO REMAIN.

G8 ALTERNATE: REMOVE GAS PRESSURE REGULATOR.

G9 ALTERNATE: CONNECT NEW 1-1/4" MEDIUM PRESSURE (5 PSI) GAS PIPE TO EXISTING. FIELD

VERIFY EXACT SIZE OF EXISTING.

G10 ALTERNATE: NEW LOW PRESSURE (7" WC) DOWN THROUGH ROOF AND GAS PIPE CONNECT

TO EXISTING. FIELD VERIFY EXACT SIZE AND LOCATION OF EXISTING.

G15 GAS PIPE SUPPORT - RE: DETAIL 3/P601. TYPICAL.

P45 ALTERNATE: CONNECT NEW RD-1 TO EXISTING 6" RAIN LEADER. FIELD VERIFY EXACT SIZE

AND LOCATION OF EXISTING.

P46 ALTERNATE: CONNECT NEW 4" SANITARY VENT TO EXISTING. EXTEND SANITARY VENT UP

THROUGH NEW ROOF APPROX 18" ABOVE ROOF. FIELD VERIFY EXACT SIZE AND LOCATION OF

EXISTING.

# Doc # Date

AD1 11-13-2025

1 AD2 11-21-2025

File details come from the government source that posted it. Updated .