E125_R2_AD2___WING_G__POWER_PLAN.pdf
PDF 2 MB Posted
- Attached to
- RFP for Ridgeland High School Renovations
- Solicitation number
- PE-55462-NONST-2026-000000017
- Issued by
- Wilcox County, Georgia
About this file
This is an electrical power plan drawing for the Ridgeland High School Renovations project prepared by Southern A&E, LLC for Walker County Schools located at 301 N Cherokee Street, Lafayette, Georgia 30728. The drawing, designated as E125 Wing G - Power Plan, is part of Bid Package BP-1 and was issued for construction on January 920-045. The document details electrical modifications and connections for mechanical equipment throughout Wing G of the facility, including power routing for HVAC units, electric hand dryers, drink fountains, and receptacles across multiple spaces such as the gymnasium, locker rooms, restrooms, offices, and storage areas. The drawing includes a comprehensive keynote schedule defining specific electrical work requirements, including connection procedures for mechanical equipment to maintained circuits, protective measures for existing equipment, new disconnect switch installations, motor-rated switch provisions, and GFCI breaker installations. The plan specifies conductor sizing, raceway routing preferences, and coordination requirements to maintain National Electrical Code (NEC) working clearances.
The document was prepared by Southern A&E, LLC, an engineering firm licensed by the State Board of Registration for Professional Engineers and Land Surveyors under License No. PEF003374, with an expiration date of June 30, 2026. The drawing was originally issued on October 31, 2025, for construction purposes, with revisions documented as Addendum 2 dated November 21, 2025. The sheet size is specified as ARCH E1 (30" x 42") at a scale of 1/8" = 1'-0", and includes detailed grid references and a key plan to orient specific electrical work locations within Wing G. No pricing information, set-aside provisions, funding sources, or contract award dates are included in this technical drawing document.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M M
J
J
JJ
J
J
JJ
J
J
JJ J J
J
M
M
MSB
XELPA
XLPA
LPA1
PRINCIPAL
TOILET
LOBBY
CONCESSIONS
STOR.
STAIR
STAIR
STOR.
WOMENS
MENS
MENS
WOMEN
CORRIDOR
R.O.T.C.
A.F.J.R.O.T.C.
C.B.V.I.
ART
STOR.
DARK ROOM
OFFICE
LIB.
OFFICE
OFFICE
MECH.
STOR.
JAN.
SUP.S
BOILER
ELEC.
COLONNADE
MECH.
LOCKERS
SHOWERS
SHOWERS
617 LOCKERS
514 LOCKERS
SHOWERS
SHOWERS
608 LOCKERS
TOILET
GIRLS P.E.
GIRLS VARSITY
TOILET
TOILET
BOYS P.E.
BOYS VARSITY
TOILET
STAIR
EQUIP. STOR.
STOR.
OFFICE
VEST.
PASS.
WEIGHT ROOM
STOR.
EQUIP. STOR.
VEST.
PASS.
OFFICE
LAUNDRY
MECH.
GYMNASIUM
STOR.
VEST.
500F
STAIR
F O
R C
O N
T
IN
U A
T
IO
N
R E
F E
R T
O
E
FOR CONTINUATION REFER TO: 1/ E121
ATS EHPA
LPA
HPA1
HPA
ELPA
LPA2
E2
AHU
GDF
GDF
AHU
E1
E3
E3
E1
EH
E11
EH
E11
E21 E21
E21
E10
E10 E10
E10
E10 E10 E10 E10
To LPA1
E38
EUH
To HPA1
E40
MAHU
MAHU
EUH-10 REMOVED
IHP-4 REMOVED
E6
IHP-3 REMOVED
E6
E42
E42 E42
E42
SCALE: = 1'-0"
DRAWING NUMBER
REVISIONS
COPYRIGHT 2025 BY SOUTHERN A&E, LLC. ALL RIGHTS RESERVED.
THIS DOCUMENT IS THE PROPERTY OF SOUTHERN A&E, LLC AND SHALL
NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT
EXPRESSED WRITTEN CONSENT FROM SOUTHERN A&E, LLC.
10-31-2025
BID PACKAGE BP-1
SA&E PROJECT NUMBER
ORIGINAL SHEET SIZE: ARCH E1 (30" X 42")
A
TRUE
NORTH
0 8 168
1/8"
2" GRIDS 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
I
J
K
L
M
N
KEYPLAN
RIDGELAND HIGH SCHOOL
RENOVATIONS TO:
WALKER COUNTY SCHOOLS
301 N CHEROKEE ST, LAFAYETTE, GA 30728
2478 HAPPY VALLEY RD, ROSSVILLE, GA 30741
746-0190
01-920-045
ISSUED FOR CONSTRUCTION
STATE BOARD OF REGISTRATION
FOR PROFESSIONAL ENGINEERS AND
LAND SURVEYORS
SOUTHERN A & E, LLC
ENGINEER FIRM
LICENSE NO: PEF003374
EXP. DATE - 06/30/2026
B
A
C
D E
F
G
H
J
K
E125
WING G - POWER PLAN
KEYNOTE SCHEDULE - THIS SHEET
# KEYNOTE DESCRIPTION
E1 CONNECT MECHANICAL EQUIPMENT TO CIRCUIT MAINTAINED FROM DEMOLITION
PHASE. EXTEND ASSOCIATED BRANCH CIRCUIT CONDUCTORS/RACEWAY AS
REQUIRED, SIZED TO MATCH EXISTING BRANCH CIRCUIT. PROVIDE NEW DISCONNECT
SWITCH, SIZE PER SCHEDULE. COORDINATE SWITCH LOCATION TO MAINTAIN NEC
WORKING CLEARANCES. PROVIDE NEW LOAD SIDE CONDUCTORS/RACEWAY TO
EQUIPMENT CONNECTION POINT. WHERE POSSIBLE, ROUTE OVERHEAD AND ONLY
TRANSITION TO FLEXIBLE RACEWAY WITHIN 18" OF UNIT CONNECTION POINT.
E2 EXISTING MECHANICAL EQUIPMENT TO REMAIN, PROTECT ELECTRICAL CONNECTIONS
AND/OR EQUIPMENT FROM DAMAGE THROUGH ALL PHASES OF CONSTRUCTION.
E3 CONNECT MECHANICAL EQUIPMENT TO CIRCUIT MAINTAINED FROM DEMOLITION
PHASE. EXTEND ASSOCIATED BRANCH CIRCUIT CONDUCTORS/RACEWAY AS
REQUIRED, SIZED TO MATCH EXISTING BRANCH CIRCUIT. PROVIDE NEW MOTOR
RATED SWITCH. COORDINATE SWITCH LOCATION TO MAINTAIN NEC WORKING
CLEARANCES. PROVIDE NEW LOAD SIDE CONDUCTORS/RACEWAY TO EQUIPMENT
CONNECTION POINT. WHERE POSSIBLE, ROUTE OVERHEAD AND ONLY TRANSITION TO
FLEXIBLE RACEWAY WITHIN 18" OF UNIT CONNECTION POINT.
E6 PROVIDE CONNECTION FROM OUTDOOR UNIT TO INDOOR UNIT FOR POWER AND
CONTROL. REFER TO MINI-SPLIT DETAILS AND MANUFACTURERS INSTALLATION
INSTRUCTIONS.
E10 ELECTRIC HAND DRYER TO BE REPLACED AT THIS LOCATION. EXTEND\/TRIM
CONDUCTORS/RACEWAY AS REQUIRED FOR CONNECTION TO NEW EQUIPMENT.
COORDINATE W/ ARCH DRAWINGS.
E11 CONNECT MECHANICAL EQUIPMENT TO CIRCUIT MAINTAINED FROM DEMOLITION
PHASE. EXTEND ASSOCIATED BRANCH CIRCUIT CONDUCTORS/RACEWAY AS
REQUIRED FOR CONNECTION TO NEW EQUIPMENT. SIZE CONDUCTORS TO MATCH
EXISTING BRANCH CIRCUIT.
E21 MODIFIY RECEPTACLE LOCATION AS REQUIRED FOR RECEPTACLE TO BE CONCEALED
WITHIN NEW DRINK FOUNTAIN SHROUD. RECEPTACLE SHALL BE PROTECTED VIA A
NEW 20A/1P GFCI BREAKER. FIELD VERIFY ASSOCIATED PANEL AND CIRCUIT.
E38 ROUTE TO PANEL AND LOCATE BREAKER IN NEXT AVAILABLE POLE . TERMINATE ON
NEW 20/1P BREAKER. NEW BRANCH CIRCUIT SHALL BE 3#12 CU THWN IN A 1/2"C.
E40 ROUTE TO PANEL AND LOCATE BREAKER IN NEXT AVAILABLE POLE . TERMINATE ON
NEW 30/1P BREAKER. NEW BRANCH CIRCUIT SHALL BE 3#10 CU THWN IN A 1/2"C.
E42 WHERE PRESENT, REMOVE 120V POWER & JUNCTION BOX LOCATED BENEATH SINKS.
MAINTAIN CIRCUIT INTEGRITY TO DOWNSTREAM DEVICES.
1/8" = 1'-0"E125
1 LEVEL 01 - WING G - POWER PLAN
# Doc # Date
1 AD1 11/13/25
2 AD2 11/21/25
File details come from the government source that posted it. Updated .