M503_R2_AD2_MECHANICAL_EQUIPMENT_DETAILS.pdf
PDF 252 KB Posted
- Attached to
- RFP for Ridgeland High School Renovations
- Solicitation number
- PE-55462-NONST-2026-000000017
- Issued by
- Wilcox County, Georgia
About this file
This document is a mechanical equipment details specification sheet prepared by Southern A&E, LLC for Ridgeland High School Renovations, a project involving Walker County Schools located at 301 N Cherokee Street, Lafayette, Georgia 30728. The specifications detail installation requirements for multiple HVAC systems including rooftop units (RTU), air handling units (AHU), mini-split systems (both outdoor and indoor cassette/hi-wall units), energy recovery units (ERU), and duct furnaces. Key installation requirements include insulated roof curbs with minimum 12-inch height, Schedule 40 black steel pipe sleeves with silicone caulk backfill, refrigerant line routing through exterior walls with aluminum jacketing weather protection, condensate drain lines routed as shown on floor plans without trapping until maximum lift is reached, and all piping supports following specification section 230529. The specifications reference architectural, structural, and plumbing documents and require coordination with Division 23 and Division 26 contractors for support channel frames, bracing, and electrical disconnects.
Delegated design requirements mandate that support stands (Big Foot or approved equivalent) undergo lateral stability calculations for wind loads per the 2012 International Building Code, with calculations to be performed by a professional engineer registered in Georgia and submitted with shop drawings. Additional components specified include Plenums Inc. roof curbs, Sigrist pipe chase housing or approved equivalents, Diversitech equipment rails, and Alta Products, LLC manufactured roof curb assemblies. Condensate drainage systems require full-line-size maintenance, insulation per specification section 230719, and union connections between unit and trap. The document was issued for construction on November 21, 2025 (Addendum 2) with original issuance on November 13, 2025 (Addendum 1), as part of Bid Package BP-1 under project number 01-920-045.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ECONOMIZER O.A. INTAKE HOOD
EXTEND FULL SIZE TRAPPED CONDENSATE
LINE FROM UNIT TO NEAREST GUTTER.
PROVIDE UNION BETWEEN UNIT CONNECTION
AND TRAP. PROVIDE LINE SUPPORTS..
ROOF ASSEMBLY - RE: ARCH. & STRUCT.
DOCUMENTS.
RTU
INSULATED ROOF CURB WITH DUCT OPENINGS
ONLY BY PLENUMS INC. TO CORRESPOND W/
SPECIFIC RTU SUPPLIED. MINIMUM 12" HEIGHT.
LINED S.A. & R.A. DUCT - TRANSITION FROM EACH
UNIT CONNECTION SHOWN ON FLOOR PLANS.
IF ROOF OPENING IS LARGER THAN
DUCT PERMETER, SEAL GAPS WITH
2"-6" FIBER GLASS INSULATION ON
TOP OF (2) 5/8: GYP BOARD
(STAGGER JOINTS, NO GAPS)
SCHED. 40 BLACK STEEL PIPE SLEEVE.
BACKFILL WITH SILICONE CAULK.
REFRIGERANT LINES. ROUTE THRU EXTERIOR
WALL TO AHP UNIT INSIDE. ROUTE THROUGH WALL
SLEEVE.
AIR FLOW
4" CONCRETE PAD RE:
ARCH. DOCUMENTS
REFRIGERANT PIPE SUPPORT - RE:
PART 3 SECTION 230529. INSULATE PIPE
PRIOR TO INSTALLATION OF SUPPORTS.
WEATHER PROTECT REFRIGERANT
LINES WITH ALUMINUM JACKETING.
EXISTING FENCING
SUPPORT PIPING AT ELBOWS AND PER
SPECIFICATION SECTIONS 230529. SEE
PIPING SUPPORT DETAIL.
ROOF ASSEMBLY
SUPPORT CHANNEL FRAME AND BRACING BY DIV.
26 CONTRACTOR
DISCONNECT BY DIV. 26
PROTECT REFRIGERANT LINES WITH
ALUMINUM JACKET. SEE SPECIFICATION SECTION
230719.
ROUTE EACH REFRIGERANT PIPE, CONTROL CONDUIT,
AND ELECTRICAL CONDUIT INTO A SIGRIST PIPE CHASE
HOUSING.
DIVERSITECH EQUIPMENT RAIL (OR APPROVED EQUIVALENT) -
SEE STRUCTURAL AND ARCHITECTURAL DOCUMENTS.
ROOF
DECK
DELEGATED DESIGN: BIG FOOT (OR APPROVED
EQUIVALENT) SUPPORT STANDS SHALL BE
CHECKED FOR STABILITY (OVERTURNING AND
SLIDING) AGAINST WIND LOADS PER THE 2012 IBC.
BY A PROFESSIONAL ENGINEER REGISTERED IN
GEORGIA. LATERAL STABILITY CALCULATIONS
SHALL BE PROVIDED WITH SHOP DRAWINGS
SUBMITTALS. THE SIZE OF THE STAND SHALL BE
ADJUSTED AS REQUIRED FOR STABILITY OR
PROVIDE A FULLY DETAILED BALLASTED DESIGN TO
MEET STABILITY REQUIREMENTS.
SUPPORT CHANNEL FRAME AND BRACING BY
DIV. 26 CONTRACTOR
WEATHER PROTECT REFRIGERANT
LINES WITH ALUMINUM JACKETING.
ROUTE EACH REFRIGERANT PIPE THROUGH
PIPE CHASE HOUSING WITH SIGRIST EXIT SEAL
OR APPROVED EQUIVALENT.
SIGRIST PIPE CHASE HOUSING OR APPROVED
EQUIVALENT. FOR USE BY DIV. 23 AND DIV 26.
MANUFACTURED BY ALTA PRODUCTS, LLC. SEE
SPECIFICATION SECTION 077200 FOR ROOF CURB.
DISCONNECT BY
DIV.26
MHP
MAHU
FINISHED CEILING
RE: ARCH. DOCUMENTS
FINISHED FLOOR
SUSPEND UNIT FROM STRUCTURE
ACCORDING TO MANUFACTURER'S
RECOMMENDATIONS. FRONT PLATE: ADJUST
HANGER ROD TO ENSURE FLUSH FIT WITH
CEILING. COORDINATE WITH OTHER TRADES
AND REFLECTED CELING GRID LAYOUT.
NOTES:
ROUTE CONDENSATE DRAIN AS SHOWN ON FLOOR
PLANS. MAINTAIN FULL LINE SIZE (DO NOT TRAP) UP TO
MAX LIFT, THEN TO LOCATION SHOWN ON FLOOR
PLANS. INSULATE PER SPECIFICATION SECTION 230719.
NOTES:
ROUTE CONDENSATE DRAIN AS SHOWN ON FLOOR
PLANS. MAINTAIN FULL LINE SIZE (DO NOT TRAP) UP TO
MAX LIFT, THEN TO LOCATION SHOWN ON FLOOR
PLANS. INSULATE PER SPECIFICATION SECTION 230719.
FINISHED CEILING
BUILDING WALL
RE: ARCH. DOCUMENTS
FINISHED FLOOR
SCHED. 40 BLACK STEEL PIPE SLEEVE -
BACKFILL WITH SILICONE CAULK.
ROUTE REFRIGERANT LINES UP
EXTERIOR FACE OF WALL TO A
POINT ABOVE CEILING THEN THRU
WALL SLEEVE AND IN MOST DIRECT
MANNER TO INDOOR UNIT. ANCHOR
LINES TO WALL WITH UNISTRUT AND
PAINT UNISTRUT TO MATCH WALL.
MHP
MHP SECURED ON WALL-
MOUNTED BRACKET
"PAINT GRIP" METAL OR UV RESISTANT
PVC LINESET COVER. PAINT COVER TO
MATCH PER SPEC. SECTION 099113.
LINESET SHALL COVER UNISTRUT.
HI-WALL
MAHU
SPLASH BLOCK
CONDENSATE DRAINAGE LINE
REFRIGERANT LINE
MOUNT BASE OF WALL MOUNT A
MINIMUM OF 6'-8" OFF A.F.F.
MECH. RM.
SMOKE/FIRE DAMPER
HVAC CONTROL PANEL
FIELD VERIFY LOCATION
SMOOTH RADIUSED OFFSETS
WHERE REQUIRED
FULL SIZE TRAPPED CONDENSATE DRAIN
LINE - FROM UNIT DRAIN CONNECTION TO
FLOOR. DRAIN - RE: PLBG. DOCUMENTS FOR
FLOOR DRAINS.
NEATLY RACK AND SECURE
REFRIGERANT PIPING TO WALL.
ROUTE THROUGH FOUR NIPPLE PIPE
PORTAL ON ROOF. PROVIDE RODS,
HANGERS AND SADDLES AS
REQUIRED TO FIRMLY SUPPORT THE
LINES. CONDENSING UNITS ARE
LOCATED ON ROOF.
AHU
O.A.
COIL
FAN
R.A.
S.A.
ECONOMIZER O.A. INTAKE HOOD
EXTEND FULL SIZE TRAPPED CONDENSATE
LINE FROM UNIT TO NEAREST GUTTER.
PROVIDE UNION BETWEEN UNIT CONNECTION
AND TRAP. PROVIDE LINE SUPPORTS..
ROOF ASSEMBLY - EXISTING
RTHP
INSULATED ROOF CURB WITH DUCT OPENINGS
ONLY BY PLENUMS INC. TO CORRESPOND W/
SPECIFIC RTU SUPPLIED. MINIMUM 12" HEIGHT.
S.A. & R.A. DUCT - EXISTING
NOTES:
ROUTE CONDENSATE DRAIN AS SHOWN ON FLOOR
PLANS. MAINTAIN FULL LINE SIZE (DO NOT TRAP) UP TO
MAX LIFT, THEN TO LOCATION SHOWN ON FLOOR
PLANS. INSULATE PER SPECIFICATION SECTION 230719.
MAHU
SUSPEND UNIT FROM STRUCTURE
ACCORDING TO MANUFACTURER'S
RECOMMENDATIONS. FRONT PLATE: ADJUST
HANGER ROD TO ENSURE FLUSH FIT WITH
CEILING. COORDINATE WITH OTHER TRADES
AND REFLECTED CELING GRID LAYOUT.
FINISHED CEILING
BUILDING WALL
RE: ARCH. DOCUMENTS
FINISHED FLOOR
SCHED. 40 BLACK STEEL PIPE SLEEVE -
BACKFILL WITH SILICONE CAULK.
INSULATED REFRIGERANT PIPING.
EXTERIOR FACE OF WALL TO A
POINT ABOVE CEILING THEN THRU
WALL SLEEVE AND IN MOST DIRECT
MANNER TO INDOOR UNIT. ANCHOR
LINES TO WALL WITH UNISTRUT AND
PAINT UNISTRUT TO MATCH WALL.
MHP
MHP SECURED ON WALL-
MOUNTED BRACKET
"PAINT GRIP" METAL SHROUD OR UV
RESISTANT PVC LINESET COVER. PAINT
COVER TO MATCH PER SPEC. SECTION
099113. LINESET SHALL COVER
UNISTRUT.
O.A. INTAKE HOOD
EXTEND FULL SIZED TRAPPED
CONDENSATE LINE FROM UNIT TO
NEAREST GUTTER OR ROOF DRAIN. REFER
TO P-TRAP DETAIL. PROVIDE UNION
BETWEEN UNIT CONNECTION AND TRAP.
PROVIDE ADJUSTABLE PIPE SUPORTS
(MICRO-8 BASE STRUT OR EQUAL) 10 FT.
MAX SPACING
ERU
INSULATED ROOF CURB WITH
DUCT OPENINGS.
LINED S.A. & R.A. DUCTS -
TRANSITION FROM UNIT
CONNECTIONS TO SIZES SHOWN
ON FLOOR PLANS.
ROOF DECK OPENINGS - SIZE TO
MATCH SUPPLY AIR AND RETURN
AIR DUCT.
STRUCTURAL & ROOF ASSEMBLY -
RE: ARCH & STRUCTURAL
DOCUMENTS.
SMOOTH RADIUSED
OFFSETS WHERE REQUIRED
MECH. RM.
EXISTING LOUVER
SEPARATED COMBUSTION PIPING
FROM DUCT FURNACE. SEE
FLOOR PLAN FOR ROUTING AND
EQUIPMENT SCHEDULE FOR SIZE
COPPER CONDENSATE LINE FROM DUCT
FURNACE. RACK TO WALL AND EXTEND TO
FLOOR DRAIN.
COMBINATION FILTER /
MIXING BOX
STEEL SUPPORT STAND
FAN
MAH
GDF
ALL THREAD RODS TO
STRUCTURE (TYP. OF 4)
ANGLE STEEL DUCT
SUPPORT STAND
EXISTING R.A. DUCT
EXISTING S.A. DUCTWORK
DRAWING NUMBER
REVISIONS
COPYRIGHT 2025 BY SOUTHERN A&E, LLC. ALL RIGHTS RESERVED.
THIS DOCUMENT IS THE PROPERTY OF SOUTHERN A&E, LLC AND SHALL
NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT
EXPRESSED WRITTEN CONSENT FROM SOUTHERN A&E, LLC.
10-31-2025
BID PACKAGE BP-1
SA&E PROJECT NUMBER
ORIGINAL SHEET SIZE: ARCH E1 (30" X 42")
A
12" GRIDS 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
I
J
K
L
M
N
RIDGELAND HIGH SCHOOL
RENOVATIONS TO:
WALKER COUNTY SCHOOLS
301 N CHEROKEE ST, LAFAYETTE, GA 30728
2478 HAPPY VALLEY RD, ROSSVILLE, GA 30741
746-0190
01-920-045
ISSUED FOR CONSTRUCTION
STATE BOARD OF REGISTRATION
FOR PROFESSIONAL ENGINEERS AND
LAND SURVEYORS
SOUTHERN A & E, LLC
ENGINEER FIRM
LICENSE NO: PEF003374
EXP. DATE - 06/30/2026
M503
MECHANICAL EQUIPMENT DETAILS
NOT TO SCALEM503
1 ROOFTOP UNIT WITH CURB DETAIL
NOT TO SCALEM503
2 CONDENSING UNIT DETAIL
NOT TO SCALEM503
3 ROOF MOUNTED CONDENSING UNIT DETAIL
NOT TO SCALEM503
4 MINI-SPLIT OUTDOOR UNIT DETAIL (BIG FOOT) NOT TO SCALEM503
5 MINI-SPLIT CASSETTE DETAIL
NOT TO SCALEM503
6 MINI-SPLIT HI-WALL W/ WALL BRACKET MHP DETAIL
NOT TO SCALEM503
8 AIR HANDLING UNIT IN MECH. RM. DETAIL
# Doc # Date
1 AD1 11-13-2025
2 AD2 11-21-2025
NOT TO SCALEM503
9 ROOFTOP UNIT WITH CURB DETAIL
NOT TO SCALEM503
7 MINI-SPLIT CASSETTE W/WALL BRACKET MHP DETAIL
NOT TO SCALEM503
10 ROOFTOP ENERGY RECOVERY UNIT DETAIL
NOT TO SCALEM503
11 AIR HANDLING UNIT IN MECH. RM. W/ DUCT FURNACE
File details come from the government source that posted it. Updated .