E103_R2_AD2___WING_A__POWER_PLAN.pdf
PDF 2 MB Posted
- Attached to
- RFP for Ridgeland High School Renovations
- Solicitation number
- PE-55462-NONST-2026-000000017
- Issued by
- Wilcox County, Georgia
About this file
This is an electrical power plan drawing for Ridgeland High School Renovations, prepared by Southern A&E, LLC for Walker County Schools located in Rossville, Georgia. The drawing depicts Wing A of the school facility at a scale of 1/8" = 1'-0" and details electrical power distribution, circuit connections, and equipment modifications across multiple rooms and spaces including classrooms, mechanical rooms, storage areas, offices, and common areas. The plan includes keynoted instructions for electrical work such as connecting mechanical equipment to maintained circuits, extending branch circuit conductors, installing new disconnect switches, replacing receptacles with GFCI-type units, and reworking electrical raceways to accommodate new mechanical installations. A mandatory pre-proposal meeting is scheduled for Thursday, November 20, 2025 at 9:00 AM at the project site, with sealed proposals from general contractors due by 2:00 PM on Thursday, December 11, 2025 to the Walker County Board of Education's Facilities and Operations Department. Failure to attend the mandatory pre-proposal meeting will result in rejection of any submitted proposal without review.
The electrical power plan document serves as a construction specification sheet issued for the renovation project. The drawing was originally issued at full size of 30" x 42" (Arch E1 format) and includes revision tracking with the current revision (AD2) dated November 21, 2025. The plan designates multiple electrical circuits, panel connections, and equipment specifications using standardized keynote descriptions (E3, E4, E8, E10, E11, E21, E30, E36, E37, E42) that provide detailed installation requirements and coordination notes for electrical contractors. The document is the property of Southern A&E, LLC (Engineer Firm License No. PEF003374, expiration date June 30, 2026) and is protected under copyright, with explicit restrictions against reproduction without written consent.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M M M M
M
M M
M M
M M gf
M
J J
J
J
MECH.
STORAGE
OFFICE
STORAGE
401A
ROBOTICS
RADIO
407C
WORKROOM
407B
WORKROOM
407A PUBLIC SAFETY
MATERIALS LAB
ART
OFFICE
TOOLS
OFFICE
421 VEST.
CONSTRUCTION
CLASSROOM
CORRIDOR
JAN.
BOYS
GIRLS
BUSINESS 1
CORRIDOR
300B
PRINT SHOP
BUSINESS 2
SPED
STOR.
OFFICE
HEALTH
DISPLAY
EXAM
GRAPHIC DESIGN
414MECH.
STORAGE
OFFICE
VEST.
AG. MECH. CLASSROOM
VEST.
STUDIO
A/V ROOM
STORAGE
STOR.
255 MECH.
STOR.
259 MECH.
CORRIDOR
300C
CORRIDOR
300A
FOR CONTINUATION REFER TO: 1/ E107
LPE4
LPE3
LPE8LPE2
LPE1
LF2A
AH
AH
ELEC.
306STOR.
MECH.
MECH.
STOR.
STOR.
243MECH.
AH
AH
HP
AH
AH
AH
AH
AH
HP
54B
HP
54A
HP
HP
E21
POSSIBLE RTU CKT
HPE2-2 (35A)
AHU
E4
E3
E4
E4
E4
E4
E3
E3
E3
E3
E3 E3E3
AH
AH
E21
E3
F
E11
LPF2- 14
LPF2- 24
LPF2- 22
E8
E8
E8
E30
LPE6
LPE7
LPE5
E36
E10
E10 E37
E36
E8
TOILET
233.2
E42
E42
VEST.
TOILET
TOILET
C.B.V.I
SCALE: = 1'-0"
DRAWING NUMBER
REVISIONS
COPYRIGHT 2025 BY SOUTHERN A&E, LLC. ALL RIGHTS RESERVED.
THIS DOCUMENT IS THE PROPERTY OF SOUTHERN A&E, LLC AND SHALL
NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT
EXPRESSED WRITTEN CONSENT FROM SOUTHERN A&E, LLC.
10-31-2025
BID PACKAGE BP-1
SA&E PROJECT NUMBER
ORIGINAL SHEET SIZE: ARCH E1 (30" X 42")
A
TRUE
NORTH
0 8 168
1/8"
2" GRIDS 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
I
J
K
L
M
N
KEYPLAN
RIDGELAND HIGH SCHOOL
RENOVATIONS TO:
WALKER COUNTY SCHOOLS
301 N CHEROKEE ST, LAFAYETTE, GA 30728
2478 HAPPY VALLEY RD, ROSSVILLE, GA 30741
746-0190
01-920-045
ISSUED FOR CONSTRUCTION
STATE BOARD OF REGISTRATION
FOR PROFESSIONAL ENGINEERS AND
LAND SURVEYORS
SOUTHERN A & E, LLC
ENGINEER FIRM
LICENSE NO: PEF003374
EXP. DATE - 06/30/2026
B
A
C
D E
F
G
H
J
K
E103
WING A - POWER PLAN
KEYNOTE SCHEDULE - THIS SHEET
# KEYNOTE DESCRIPTION
E3 CONNECT MECHANICAL EQUIPMENT TO CIRCUIT MAINTAINED FROM DEMOLITION
PHASE. EXTEND ASSOCIATED BRANCH CIRCUIT CONDUCTORS/RACEWAY AS
REQUIRED, SIZED TO MATCH EXISTING BRANCH CIRCUIT. PROVIDE NEW MOTOR
RATED SWITCH. COORDINATE SWITCH LOCATION TO MAINTAIN NEC WORKING
CLEARANCES. PROVIDE NEW LOAD SIDE CONDUCTORS/RACEWAY TO EQUIPMENT
CONNECTION POINT. WHERE POSSIBLE, ROUTE OVERHEAD AND ONLY TRANSITION TO
FLEXIBLE RACEWAY WITHIN 18" OF UNIT CONNECTION POINT.
E4 CONNECT MECHANICAL EQUIPMENT TO CIRCUIT MAINTAINED FROM DEMOLITION
PHASE. EXTEND ASSOCIATED BRANCH CIRCUIT CONDUCTORS/RACEWAY AS
REQUIRED, SIZED TO MATCH EXISTING BRANCH CIRCUIT. PROVIDE NEW DISCONNECT
SWITCH LOCATED ABOVE CEILING, SIZE PER SCHEDULE. COORDINATE SWITCH
LOCATION TO MAINTAIN NEC WORKING CLEARANCES. PROVIDE NEW LOAD SIDE
CONDUCTORS/RACEWAY TO EQUIPMENT CONNECTION POINT. REFER TO INDOOR
HEAT PUMP DETAIL.
E8 ROUTE TO PANEL/POSITION INDICATED AND TERMINATE ON NEW 20A/1P BREAKER.
NEW BRANCH CIRCUIT SHALL BE 3#12 CU IN 1/2"C.
E10 ELECTRIC HAND DRYER TO BE REPLACED AT THIS LOCATION. EXTEND\/TRIM
CONDUCTORS/RACEWAY AS REQUIRED FOR CONNECTION TO NEW EQUIPMENT.
COORDINATE W/ ARCH DRAWINGS.
E11 CONNECT MECHANICAL EQUIPMENT TO CIRCUIT MAINTAINED FROM DEMOLITION
PHASE. EXTEND ASSOCIATED BRANCH CIRCUIT CONDUCTORS/RACEWAY AS
REQUIRED FOR CONNECTION TO NEW EQUIPMENT. SIZE CONDUCTORS TO MATCH
EXISTING BRANCH CIRCUIT.
E21 MODIFIY RECEPTACLE LOCATION AS REQUIRED FOR RECEPTACLE TO BE CONCEALED
WITHIN NEW DRINK FOUNTAIN SHROUD. RECEPTACLE SHALL BE PROTECTED VIA A
NEW 20A/1P GFCI BREAKER. FIELD VERIFY ASSOCIATED PANEL AND CIRCUIT.
E30 ROUTE TO PANEL AND BREAKER POSITION INDICATED. TERMINATE ON NEW 20/1P
BREAKER W/ GFCI OPTION. NEW BRANCH CIRCUIT SHALL BE 3#12 CU THWN IN A 1/2"C.
E36 REPLACE ALL RECEPTACLE IN THIS SPACE WITH NEW GFCI TYPE RECEPTACLE.
E37 REWORK ELECTRICAL RACEWAYS/CONDUCTORS ROUTED THROUGH THIS AREA AS
REQUIRED FOR INSTALLATION OF NEW FRESH AIR DUCTWORK. COORDINATE
LOCATION WITH MECHANICAL CONTRACTOR.
E42 WHERE PRESENT, REMOVE 120V POWER & JUNCTION BOX LOCATED BENEATH SINKS.
MAINTAIN CIRCUIT INTEGRITY TO DOWNSTREAM DEVICES.
1/8" = 1'-0"E103
1 LEVEL 01 - WING A - POWER PLAN
# Doc # Date
1 AD1 11/13/25
2 AD2 11/21/25
File details come from the government source that posted it. Updated .