M602_R2_AD2_MECHANICAL_EQUIPMENT_SCHEDULES.pdf
PDF 241 KB Posted
- Attached to
- RFP for Ridgeland High School Renovations
- Solicitation number
- PE-55462-NONST-2026-000000017
- Issued by
- Wilcox County, Georgia
About this file
This is a Mechanical Equipment Schedules document for the Ridgeland High School Renovations project, prepared by Southern A&E, LLC for Walker County Schools in Georgia. The document provides detailed specifications for HVAC and mechanical equipment required for the renovation project, issued for construction as part of Bid Package BP-1. The schedules include 16 duct furnaces (Modine models ranging from DFS150 to DFS400), multiple air distribution components including transfer grilles, exhaust/return grilles, and supply diffusers, five electric heaters (Markel models), 11 mini-split indoor units (Carrier models), 11 mini-split outdoor units (Carrier models), three rooftop heat pumps (Carrier models), one dedicated outside air unit with energy recovery (Greenheck model), two make-air units (Carrier models), two pipe chase housings (Alta Products models), and two electric unit heaters (Markel models). All duct furnaces operate on natural gas with 81% AFUE efficiency and are sized between 150,000 and 400,000 BTU/hr input capacity. Mini-split systems include cooling capacities ranging from 12,000 to 36,000 BTU/hr and heating capacities from 12,000 to 37,000 BTU/hr, with efficiency ratings of SEER2 24-25.2 and HSPF2 9.5-9.8.
The document specifies that all equipment performance data is based on manufacturer's nominal values and references additional specification sections (235513, 238216.14, 238126, 236200, 237433, 237423, 237200, and 238239.16) for complete features and installation requirements. Key installation requirements include factory-insulated diffusers, wired 7-day programmable thermostats on all mini-split units, air treatment systems meeting ASHRAE 62.1 standards for units exceeding certain capacities, rotary-style condensate lift pumps, low ambient kits for cooling to 0°F on mini-split outdoor units, hot gas reheat on dedicated outside air units, and field verification of wall-mounted replacement grille dimensions prior to ordering. All electrical characteristics and control specifications are referenced in separate electrical drawings and control specification sheets. The document revision date of November 21, 2025 (AD2) reflects the second addendum issued for the project.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DRAWING NUMBER
REVISIONS
COPYRIGHT 2025 BY SOUTHERN A&E, LLC. ALL RIGHTS RESERVED.
THIS DOCUMENT IS THE PROPERTY OF SOUTHERN A&E, LLC AND SHALL
NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT
EXPRESSED WRITTEN CONSENT FROM SOUTHERN A&E, LLC.
10-31-2025
BID PACKAGE BP-1
SA&E PROJECT NUMBER
ORIGINAL SHEET SIZE: ARCH E1 (30" X 42")
A
12" GRIDS 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
B
C
D
E
F
G
H
I
J
K
L
M
N
RIDGELAND HIGH SCHOOL
RENOVATIONS TO:
WALKER COUNTY SCHOOLS
301 N CHEROKEE ST, LAFAYETTE, GA 30728
2478 HAPPY VALLEY RD, ROSSVILLE, GA 30741
746-0190
01-920-045
ISSUED FOR CONSTRUCTION
STATE BOARD OF REGISTRATION
FOR PROFESSIONAL ENGINEERS AND
LAND SURVEYORS
SOUTHERN A & E, LLC
ENGINEER FIRM
LICENSE NO: PEF003374
EXP. DATE - 06/30/2026
M602
MECHANICAL EQUIPMENT SCHEDULES
5. PERFORMANCE DATA PROVIDED ON SCHEDULE IS BASED ON MANUFACTURER'S NOMINAL VALUES.
4. INSTALL DUCT FURNACES WITHOUT FINGER-BAFFLES.
3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.
2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.
1. REFER TO SPECIFICATION SECTION 235513 FOR FEATURES.
NOTES:
DUCT FURNACE SCHEDULE
NUMBER CFM
HEATING
FUEL
TYPE
VENTILATION
EFF.
(AFUE%)
MANUFACTURERINPUT CAP.
(BTU/HR)
OUTPUT CAP.
(BTU/HR)
COIL EAT
D.B. (°F)
INLET DUCT
(IN.)
OUTLET DUCT
(IN.)
GDF - 1 9,600 400,000 324,000 60 NG 6" 6" 81 MODINE DFS400
GDF - 2 9,600 400,000 324,000 60 NG 6" 6" 81 MODINE DFS400
GDF - 3 3,500 175,000 141,750 60 NG 4" 4" 81 MODINE DFS175
GDF - 4 3,200 150,000 121,500 60 NG 4" 4" 81 MODINE DFS150
GDF - 6 6,915 350,000 283,500 60 NG 6" 6" 81 MODINE DFS350
GDF - 7 6,915 350,000 283,500 60 NG 6" 6" 81 MODINE DFS350
GDF - 8 9,600 400,000 324,000 60 NG 6" 6" 81 MODINE DFS400
GDF - 9 4,000 200,000 162,000 60 NG 6" 6" 81 MODINE DFS200
GDF - 10 4,000 200,000 162,000 60 NG 6" 6" 81 MODINE DFS200
GDF - 11 4,000 200,000 162,000 60 NG 6" 6" 81 MODINE DFS200
GDF - 12 3,200 150,000 121,500 60 NG 4" 4" 81 MODINE DFS150
GDF - 13 4,200 200,000 162,000 60 NG 6" 6" 81 MODINE DFS200
GDF - 14 3,000 150,000 121,500 60 NG 4" 4" 81 MODINE DFS150
GDF - 15 2,670 250,000 202,500 17 NG 6" 6" 81 MODINE DFS250
GDF - 16 2,670 250,000 202,500 17 NG 6" 6" 81 MODINE DFS250
6. FIELD VERIFY DIMENSIONS OF ALL WALL MOUNTED REPLACEMENT GRILLES PRIOR TO ORDERING.
5. PROVIDE SQUARE TO ROUND ADAPTERS FOR EXHAUST/RETURN GRILLES AS REQUIRED.
4. PROVIDE SURFACE MOUNT FRAME FOR ALL DIFFUSERS / GRILLES THAT ARE LOCATED WITH GYPSUM BOARD CEILING. REFER TO ARCHITECTURAL CEILING PLAN.
3. ALL SIDEWALL MOUNTED DEVICES SHALL BE FACTORY PRIMED FOR FIELD PAINTING TO MATCH THE WALL PER SPECIFICATION SECTION 099123.
2. ALL SUPPLY-AIR DIFFUSERS SHALL BE FACTORY INSULATED, FOIL -BACKED TYPE.
1. REFER TO SPECIFICATION SECTION 233713 FOR FEATURES.
NOTES:
AIR DISTRIBUTION SCHEDULE
knkn MAX AIRFLOW (CFM) FACE SIZE
NOMINAL
NECK SIZE
THROW FUNCTION MANUFACTURER
MAX NC
RATING
DESCRIPTION
DG1 --- 24"x24" 22"x22" --- TRANSFER AJ INDUSTRIES 1900 20 OPERABLE DOOR GRILL U.L LISTED FIRE RATED
DG2 --- 24"x24" 22"x22" --- TRANSFER PRICE ATGH 20 HEAVY DUTY ALUMINUM TRANSFER GRILLE, SIGHT PROOF
DG3 --- 18"x12" 16"x10" --- TRANSFER AJ INDUSTRIES 1900 20 OPERABLE DOOR GRILL U.L LISTED FIRE RATED
DG4 --- 24"x12" 22"x10" --- TRANSFER AJ INDUSTRIES 1900 20 OPERABLE DOOR GRILL U.L LISTED FIRE RATED
DG5 --- 12"x12" 10"x10" --- TRANSFER AJ INDUSTRIES 1900 20 OPERABLE DOOR GRILL U.L LISTED FIRE RATED
E1 750 24"x12" 22"x10" --- EXHAUST / RETURN PRICE 80 20 W/ SHEET METAL PLENUM, FULL SIZE OF GRILLE FACE
E2 1,600 24"x24" 22"x22" --- EXHAUST / RETURN PRICE 80 20 W/ SHEET METAL PLENUM, FULL SIZE OF GRILLE FACE
E4 325 8"x8" 6"x6" --- EXHAUST / RETURN PRICE 80 20 W/ SHEET METAL PLENUM, FULL SIZE OF GRILLE FACE
G1 540 12"x12" 10"x10" 4-WAY SUPPLY PRICE 520 20 DOUBLE DEFLECTION, 3/4" SPACING , W/DAMPER
G2 145 6"x6" 4"x4" 4-WAY SUPPLY PRICE 520 20 DOUBLE DEFLECTION, 3/4" SPACING , W/DAMPER
G3 710 24"x8" 22"x6" --- SUPPLY PRICE 520 20 DOUBLE DEFLECTION, 3/4" SPACING , W/DAMPER
G4 710 20"x10" 18"x8" --- SUPPLY PRICE 520 20 DOUBLE DEFLECTION, 3/4" SPACING , W/DAMPER
G5 1390 34"x12" 32"x10" --- SUPPLY PRICE 520 20 DOUBLE DEFLECTION, 3/4" SPACING , W/DAMPER
G6 640 20"x8" 18"x6" --- SUPPLY PRICE 520 20 DOUBLE DEFLECTION, 3/4" SPACING , W/DAMPER
G7 415 12"X10" 10"X8" --- SUPPLY PRICE 520 20 DOUBLE DEFLECTION, 3/4" SPACING , W/DAMPER
S1 100 24"x24" 6"Ø 4-WAY SUPPLY PRICE SCD 20 w/ FACTORY INSULATED METAL BACK PAN
S2 230 24"x24" 8"Ø 4-WAY SUPPLY PRICE SCD 20 w/ FACTORY INSULATED METAL BACK PAN
S3 380 24"x24" 10"Ø 4-WAY SUPPLY PRICE SCD 20 w/ FACTORY INSULATED METAL BACK PAN
S4 550 24"x24" 12"Ø 4-WAY SUPPLY PRICE SCD 20 w/ FACTORY INSULATED METAL BACK PAN
S6 100 12"x12" 6"Ø 4-WAY SUPPLY PRICE SCD 20 w/ FACTORY INSULATED METAL BACK PAN
SR1 14000 72"x64" 70"x62" --- RETURN GRILLE PRICE 96 20 HEAVY DUTY GYM GRILLE. 45 DEG. DEFLECTION. 3/4" SPACING
SR2 4500 72"x24" 70"x22" --- RETURN GRILLE PRICE 96 20 HEAVY DUTY GYM GRILLE. 45 DEG. DEFLECTION. 3/4" SPACING
SR3 11000 74"x62" 72"x60" --- RETURN GRILLE PRICE 96 20 HEAVY DUTY GYM GRILLE. 45 DEG. DEFLECTION. 3/4" SPACING
SR4 3750 62"x26" 60"x24" --- RETURN GRILLE PRICE 96 20 HEAVY DUTY GYM GRILLE. 45 DEG. DEFLECTION. 3/4" SPACING
SR5 3750 26"x58" 24"x56" --- RETURN GRILLE PRICE 96 20 HEAVY DUTY GYM GRILLE. 45 DEG. DEFLECTION. 3/4" SPACING
SR6 3500 38"x38" 36"x36" --- RETURN GRILLE PRICE 96 20 HEAVY DUTY GYM GRILLE. 45 DEG. DEFLECTION. 3/4" SPACING
4. PROVIDE ALL WALL MOUNTED HEATERS WITH SURFACE MOUNTING FRAME.
3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.
2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.
1. REFER TO SPECIFICATION SECTION 238216.14 FOR FEATURES.
NOTES:
ELECTRIC HEATER SCHEDULE
NUMBER MOUNTING TYPE kW MANUFACTURER CONTROLLED BY
EH - 1 WALL 2 MARKEL 3320HD THERMOSTAT
EH - 2 WALL 2 MARKEL 3320HD THERMOSTAT
EH - 3 CEILING 3 MARKEL 3480 THERMOSTAT
EH - 4 CEILING 3 MARKEL 3480 THERMOSTAT
EH - 5 CEILING 3 MARKEL 3480 THERMOSTAT
AND REFRIGERANT LINE SETS.
RESERVOIRS FOR ALL WALL MOUNTED MINI-SPLITS. PROVIDE LINESET COVER TO CONCEAL PUMP, CONDENSATE,
8. PROVIDE ROTARY STYLE CONDENSATE LIFT PUMP (MAXI-BLUE OR APPROVED EQUIVALENT) AND ASSOCIATED...
7. PERFORMANCE DATA PROVIDED ON SCHEDULE IS BASED ON MANUFACTURER'S NOMINAL VALUES.
6. PROVIDE ALL UNITS WITH WIRED 7 DAY PROGRAMMABLE WALL-MOUNTED THERMOSTATS.
5. PROVIDE ALL UNITS WITH TWO (2) SETS OF WASHABLE FILTERS.
DOCUMENTATION AND CALCULATIONS.
REQUIREMENTS OF ASHRAE 62.1 FOR REDUCTION OF OUTSIDE AIR AS WELL AS SUBMIT ALL SUPPORTING
THROUGH THE UNIT. SUPPLIER SHALL PROVIDE A LETTER STATING THAT THEIR AIR TREATMENT SYSTEM MEETS ALL
AIR TREATMENT SYSTEM MUST BE FULLY ENCLOSED IN THE EQUIPMENT AND POWERED BY 208/230 VOLT CIRCUIT
AND MEETING THE REQUIREMENTS OF THE INDOOR AIR QUALITY PROCEDURE OF ASHRAE 62.1.
4. PROVIDE EACH MAHU WITH AN AIR TREATMENT SYSTEM CONTROLLING CONTAMINANTS OF CONCERN
3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.
2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.
1. REFER TO SPECIFICATION SECTION 238126 FOR FEATURES.
NOTES:
MINI-SPLIT INDOOR UNIT SCHEDULE
NUMBER
SUPPLY
AIRFLOW
COIL CONDITIONS
MANUFACTURER
PIPE LENGTH
(FT.)
ASSOCIATED
OUTDOOR UNITSUPPLY AIR
(CFM)
EAT D.B.
(°F)
EAT W.B.
(°F)
MAHU - 4 360 80 67 CARRIER 45MAHAQ18XA3 15 MHP-4
MAHU - 5A 415 80 67 CARRIER 45MBCAQ12XA3 85 MHP-5
MAHU - 5B 415 80 67 CARRIER 45MBCAQ12XA3 75 MHP-5
MAHU - 5C 415 80 67 CARRIER 45MBCAQ12XA3 65 MHP-5
MAHU - 6A 415 80 67 CARRIER 45MBCAQ12XA3 70 MHP-6
MAHU - 6B 415 80 67 CARRIER 45MBCAQ12XA3 55 MHP-6
MAHU - 7 415 80 67 CARRIER 45MBCAQ12XA3 30 MHP-7
MAHU - 8 415 80 67 CARRIER 45MBCAQ12XA3 20 MHP-8
MAHU - 9 415 80 67 CARRIER 45MBCAQ12XA3 20 MHP-9
MAHU - 10 325 80 67 CARRIER 45MAHAQ12XA3 45 MHP-10
MAHU - 11 325 80 67 CARRIER 45MAHAQ12XA3 45 MHP-11
5. PERFORMANCE DATA PROVIDED ON SCHEDULE IS BASED ON MANUFACTURER'S NOMINAL VALUES.
4. PROVIDE LOW AMBIENT KIT FOR COOLING DOWN TO 0°F.
3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.
2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.
1. REFER TO SPECIFICATION SECTION 238126 FOR FEATURES.
NOTES:
MINI-SPLIT OUTDOOR UNIT SCHEDULE
NUMBER
COOLING HEATING
EFF.
(SEER2)
EFF.
(HSPF2)
MANUFACTURER
ASSOCIATED
INDOOR UNITTOTAL CAP.
(BTU/HR)
OD AMB
(°F)
TOTAL CAP.
(BTU/HR)
OD AMB
(°F)
MHP - 4 18,000 95 19,200 17 25.2 9.8 CARRIER 37MAHAQ18AA3 MAHU-4
MHP - 5 36,000 95 37,000 17 24 9.5 CARRIER 37MGRAQ36EA3 MAHU-5A,5B,5C
MHP - 6 24,000 95 25,000 17 25 9.5 CARRIER 37MGRAQ24DA3 MAHU-6A,6B
MHP - 7 12,000 95 12,800 17 25.5 9.8 CARRIER 37MAHAQ12AA3 MAHU-7
MHP - 8 12,000 95 12,800 17 25.5 9.8 CARRIER 37MAHAQ12AA3 MAHU-8
MHP - 9 12,000 95 12,800 17 25.5 9.8 CARRIER 37MAHAQ12AA3 MAHU-9
MHP - 10 12,000 27.8 12,800 17 25.5 9.8 CARRIER 37MAHAQ12AA3 MAHU-10
MHP - 11 12,000 27.8 12,800 17 25.5 9.8 CARRIER 37MAHAQ12AA3 MAHU-11
3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.
2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.
1. REFER TO SPECIFICATION SECTION 236200 FOR FEATURES.
NOTES:
ROOFTOP HEAT PUMP SCHEDULE
NUMBER
SUPPLY AIRFLOW COOLING HEATING
WEIGHT
(LBS.)
MANUFACTURERSUPPLY AIR
(CFM)
OUTSIDE AIR
(CFM) E.S.P (IN-WG)
FAN MOTOR
H.P.
TOTAL CAP.
(BTU/HR)
SENSIBLE CAP.
(BTU/HR)
EAT D.B.
(°F)
EAT W.B.
(°F)
LAT D.B. (°F) LAT W.B. (°F)
OD AMB
(°F)
STAGES
OUTPUT CAP.
(BTU/HR)
ELECTRIC
HEATER KW
LAT D.B. (°F)
OD AMB
(°F)
EFF. (HSPF2)
RTHP - K1 1950 250 0.8 1.1 60,340 47,060 76.9 64.5 55.1 54.4 95 1 58,230 19.7 118.1 °F 47 6.7 771 CARRIER 50FEQA06A2M5
RTHP - K2 1950 250 0.8 1.1 60,340 47,060 76.9 64.5 55.1 54.4 95 1 58,230 19.7 118.1 °F 47 6.7 771 CARRIER 50FEQA06A2M5
RTHP - K3 1200 200 0.8 0.53 35,340 27,060 77.7 65 56.8 55.3 95 1 34,770 8.8 108.2 °F 47 6.7 663 CARRIER 50FEQA04A2M6
# Doc # Date
1 AD1 11-13-2025
2 AD2 11-21-2025
6. PROVIDE HOT GAS REHEAT ON ALL UNITS.
5. ROOM RETURN AIR CONDITIONS: 75 °F DB @ 50 R.H.
4. ENERGY RECOVERY WHEEL MOTOR TO BE A MINIMUM 1/2 HP.
3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.
2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.
1. REFER TO SPECIFICATION SECTION 237433 FOR FEATURES.
NOTES:
DEDICATED OUTSIDE AIR UNIT W/ ELECTRIC HEATING & ENERGY RECOVERY
NUMBER
SUPPLY AIRFLOW EXHAUST AIRFLOW COOLING HEATING
WEIGHT
(LBS.)
MANUFACTURER
CFM
E.S.P.
(IN. W.C.)
FAN
MOTOR
H.P.
CFM
E.S.P.
(IN. W.C.)
FAN
MOTOR
H.P.
O.A. EAT
D.B. (°F)
O.A. EAT
W.B. (°F)
WHEEL LAT
D.B. (°F)
WHEEL LAT
W.B. (°F)
WHEEL
EFF (%)
TOTAL CAP.
(BTU/HR)
SENSIBLE CAP.
(BTU/HR)
COMPRESSOR TYPE
COIL LAT
D.B. (°F)
COIL LAT
W.B. (°F)
HGR LAT
D.B. (°F)
O.A. EAT
D.B. (°F)
WHEEL LAT
D.B. (°F)
WHEEL
EFF (%)
CAP.
(kW)
COIL LAT
D.B. (°F)
STAGES
ERU - K1 3,880 1.5 5 4,130 1.5 5 94 74 81.9 66.9 62.8 183,900 123,300 INVERTER SCROLL 50.4 50.3 79.4 17 51.8 62.2 25 72.1 1 3,284 GREENHECK RVE-40-41D-15I-1-A2
OF OUTSIDE AIR AS WELL AS SUBMIT ALL SUPPORTING DOCUMENTS AND CALCULATIONS.
THEIR AIR TREATMENT SYSTEM MEETS ALL REQUIREMENTS OF ASHRAE 62.1 FOR THE REDUCTION
BY 24 VOLT CIRCUIT THROUGHT THE UNIT. SUPPLIER SHALL PROVIDE A LETTER STATING THAT
AIR TREATMENT SYSTEM MUST BE FULLY ENCLOSED IN THE EQUIPMENT AND POWERED
MEETING THE REQUIREMENTS OF THE INDOOR AIR QUALITY PROCEDURE OF ASHRAE 62.1.
4. PROVIDE EACH MAH WITH AN AIR TREATMENT SYSTEM CONTOLLING CONTAMINANTS OF CONCERN...
3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.
2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.
1. REFER TO SPECIFICATION SECTION 237423 FOR FEATURES.
NOTES:
MAKE-AIR UNITS SCHEDULE
NUMBER
SUPPLY AIRFLOW
MANUFACTURERSUPPLY AIR
(CFM)
E.S.P. (IN.
W.C.)
FAN MOTOR H.P.
MAH - 1 2,670 0.65 1 CARRIER 39LG06
MAH - 2 2,670 0.65 1 CARRIER 39LG06
4. REFER TO PLAN FOR PIPE ROUTING TO HOUSING. ONLY ONE SIDE OF PIPE CHASE HOUSING IS USED.
3. SIZE TO MATCH REQUIRED NUMBER OF PORTS FOR ELEC. & CONTROLS CONDUITS, AND PIPING.
2. PIPE CHASE HOUSING SHALL HAVE FACTORY OR FIELD INSTALLED INSULATION. INSULATE LID & ALL SIDES
1. REFER TO SPECIFICATION SECTION 237200 FOR FEATURES.
NOTES:
PIPE CHASE HOUSING
NUMBER NUMBER OF PORTS (EACH SIDE) MANUFACTURER
PCH - 1 7 ALTA PRODUCTS AL-161010 & AL-158
PCH - 2 4 ALTA PRODUCTS AL-161010 & AL-158
4. CONFIGURE ELECTRIC UNIT HEATERS FOR MAXIMUM HORIZONTAL THROW.
3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.
2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.
1. REFER TO SPECIFICATION SECTION 238239.16 FOR FEATURES.
NOTES:
ELECTRIC UNIT HEATER SCHEDULE
NUMBER kW
MOUNTING
HEIGHT
A.F.F.
FAN & MOTOR
MANUFACTURER CONTROLLED BY
CFM
MOTOR
POWER
EUH - 9 5 8' - 0" 400 1/125 MARKEL G1G5105N INTEGRAL THERMOSTAT
EUH - 11 5 8' - 0" 400 1/125 MARKEL G1G5105N INTEGRAL THERMOSTAT