M601_R2_AD2_MECHANICAL_EQUIPMENT_SCHEDULES.pdf

PDF 253 KB Posted

Attached to
RFP for Ridgeland High School Renovations
Solicitation number
PE-55462-NONST-2026-000000017
Issued by
Wilcox County, Georgia

About this file

This is a mechanical equipment schedules document prepared by Southern A&E, LLC for renovations to Ridgeland High School in Walker County Schools, located in Lafayette and Rossville, Georgia. The document outlines detailed specifications for HVAC equipment required for the project, including rooftop air conditioning units (RTUs), indoor heat pumps (IHPs), air handling units (AHUs), air handling heat pumps (IHPs), gas furnaces, condensing units, heat pump units, and exhaust fans. The schedules specify equipment manufacturers, model numbers, performance specifications including cooling and heating capacities, efficiency ratings (SEER, EER, IEER), airflow rates, and motor horsepower. Key equipment includes one RTU unit, 44 indoor heat pump units, 12 air handling units, 4 air handling heat pump units, 59 gas furnace units, 60 condensing units, 4 heat pump outdoor units, and 53 exhaust fans. The document is dated for construction issuance as of October 31, 2025, and has been revised as of November 21, 2025 (Addendum 2).

All specified equipment must meet or exceed performance standards outlined in referenced specification sections, including ASHRAE 62.1 indoor air quality requirements. Each major HVAC unit requires an air treatment system fully enclosed within the equipment and powered by a 24-volt circuit to control contaminants of concern. All units above 4.5 tons must include economizers; units above 5 tons require minimum two-stage fan control; and units above 6 tons must have minimum two stages of cooling. Equipment is predominantly manufactured by Carrier and Bard, with selected Greenheck exhaust fans. The document references related electrical drawings, control specifications (Section 230900 and M700 series sheets), and specific feature specifications for each equipment category. The schedules also establish performance data parameters based on manufacturer nominal values and require coordination of ductwork sizing with unit openings to accommodate one-inch duct liner.

View the file

Other files

File Type Posted
P203_R1_AD2___PLUMBING_ENLARGED_PLANS.pdf PDF
E003_R2_AD2___MECHANICAL_EQUIPMENT_CONNECTION.pdf PDF
M113_R2_AD2_MECHANICAL_DEMOLITION_PLAN__WING_.pdf PDF
M126_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
E123_R2_AD2___WING_G__ELECTRICAL_DEMOLITION_P.pdf PDF
Advertisement _ RHS Renovations.pdf PDF
E135_R2_AD2___WING_F_G_K__ROOF__POWER_PLAN.pdf PDF
P106_R1_AD2___PLUMBING_ROOF_PLAN__ALTERNATE.pdf PDF
E117_R1_AD2___WING_E__POWER_PLAN.pdf PDF
ADDENDUM_2__COMPLETE.pdf PDF
E103_R2_AD2___WING_A__POWER_PLAN.pdf PDF
M128_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
M112_R2_AD2_MECHANICAL_DEMOLITION_PLAN__WING_.pdf PDF
M130_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
P102_R1_AD2___PLUMBING_RENOVATION_PLAN__PHASE.pdf PDF
P201_R1_AD2___PLUMBING_ENLARGED_PLANS.pdf PDF
M115_R2_AD2_MECHANICAL_DEMOLITION_PLAN__WING_.pdf PDF
M127_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
M125_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
E129_R2_AD2___MEZZ_LEVEL__WING_G__POWER_PLAN.pdf PDF
M129_R2_AD2_MECHANICAL_RENOVATION_PLAN__WING_.pdf PDF
M602_R2_AD2_MECHANICAL_EQUIPMENT_SCHEDULES.pdf PDF
M110_R2_AD2_MECHANICAL_DEMOLITION_PLAN__WING_.pdf PDF
E125_R2_AD2___WING_G__POWER_PLAN.pdf PDF
P202_R1_AD2___PLUMBING_ENLARGED_PLANS.pdf PDF
P103_R1_AD2___PLUMBING_RENOVATION_FLOOR_PLAN_.pdf PDF
M503_R2_AD2_MECHANICAL_EQUIPMENT_DETAILS.pdf PDF
Project Award Recommendation _ RHS HVAC.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DRAWING NUMBER

REVISIONS

COPYRIGHT 2025 BY SOUTHERN A&E, LLC. ALL RIGHTS RESERVED.

THIS DOCUMENT IS THE PROPERTY OF SOUTHERN A&E, LLC AND SHALL

NOT BE COPIED OR REPRODUCED IN WHOLE OR IN PART WITHOUT

EXPRESSED WRITTEN CONSENT FROM SOUTHERN A&E, LLC.

10-31-2025

BID PACKAGE BP-1

SA&E PROJECT NUMBER

ORIGINAL SHEET SIZE: ARCH E1 (30" X 42")

A

12" GRIDS 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19

B

C

D

E

F

G

H

I

J

K

L

M

N

RIDGELAND HIGH SCHOOL

RENOVATIONS TO:

WALKER COUNTY SCHOOLS

301 N CHEROKEE ST, LAFAYETTE, GA 30728

2478 HAPPY VALLEY RD, ROSSVILLE, GA 30741

746-0190

01-920-045

ISSUED FOR CONSTRUCTION

STATE BOARD OF REGISTRATION

FOR PROFESSIONAL ENGINEERS AND

LAND SURVEYORS

SOUTHERN A & E, LLC

ENGINEER FIRM

LICENSE NO: PEF003374

EXP. DATE - 06/30/2026

M601

MECHANICAL EQUIPMENT SCHEDULES

6. ALL UNITS ABOVE 6 TONS SHALL HAVE A MIN. OF 2 STAGES OF COOLING. ALL UNITS ABOVE 5 TONS SHALL HAVE A MIN. OF 2 STAGE FAN CONTROL. ALL UNITS 4.5 TONS AND ABOVE SHALL HAVE A ECONOMIZER.

5. PROVIDE THIRD PARTY ECONOMIZER IF REQUIRED TO ALLOW FOR DUCT CONFIGURATION ON THE FLOOR PLAN AND RELIEF.

FOR REDUCTION OF OUTSIDE AIR AS WELL AS SUBMIT ALL SUPPORTING DOCUMENTS AND CALCULATIONS.

SUPPLIER SHALL PROVIDE A LETTER STATING THAT THEIR AIR TREATMENT SYSTEM MEETS ALL REQUIREMENTS OF ASHRAE 62.1

AIR TREATMENT SYSTEM MUST BE FULLY ENCLOSED IN THE EQUIPMENT AND POWERED BY 24 VOLT CIRCUIT THROUGHT THE UNIT.

4. PROVIDE EACH RTU WITH AN AIR TREATMENT SYSTEM CONTOLLING CONTAMINANTS OF CONCERN AND MEETING THE REQUIREMENTS OF THE INDOOR AIR QUALITY PROCEDURE OF ASHRAE 62.1.

3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.

2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.

1. REFER TO SPECIFICATION SECTION 237413 FOR FEATURES.

NOTES:

ROOFTOP AIR CONDITIONING UNIT SCHEDULE

NUMBER

SUPPLY AIRFLOW FAN

MOTOR

H.P.

COOLING HEATING

FUEL

TYPE

SEER EER IEER

WEIGHT

(LBS.)

MANUFACTURERSUPPLY AIR

(CFM)

OUTSIDE AIR

(CFM)

E.S.P.

(IN. W.C.)

TOTAL CAP.

(BTU/HR)

SENSIBLE CAP.

(BTU/HR)

EAT D.B.

(°F)

EAT W.B.

(°F)

LAT D.B.

(°F)

LAT W.B.

(°F)

OD AMB

(°F)

STAGES

INPUT CAP.

(BTU/HR)

OUTPUT CAP.

(BTU/HR)

LAT D.B.

(°F)

OD AMB

(°F)

STAGES

RTU - N04 3,000 300 0.8 2.08 84,730 61,880 76.3 64.2 57.2 54.8 95 2 180,000 148,000 105.7 17 2 NG 15 1,046 CARRIER 48FEEN08A2M5

8. CONTRACTOR TO TURN 6 INDOOR HEAT PUMPS OVER TO OWNER.

7. ALL UNITS 4.5 TONS AND ABOVE SHALL HAVE A ECONOMIZER.

6. PERFORMANCE DATA PROVIDED ON SCHEDULE IS BASED ON MANUFACTURER'S NOMINAL VALUES.

COORDINATE SUPPLY AND RETURN AIR SIZE WITH UNIT OPENINGS AND TO ACCOMODATE A 1 INCH LINER.

RETURN GRILLE SHALL BE HORIZONTAL FIXED BLADE 1/2" SPACING, 30° DEFLECTION GRILLE - BARD "RG/W" SERIES RETURN AIR GRILLE (OR APPROVED EQUIVALENT).

5. PROVIDE EACH UNIT WITH A SUPPLY AND RETURN AIR GRILLE. SUPPY GRILLE SHALL BE DOUBLE DEFLECTIN - BARD "SG/W" SERIES SUPPLY AIR GRILLES (OR APPROVED EQUIVALENT).

FOR REDUCTION OF OUTSIDE AIR AS WELL AS SUBMIT ALL SUPPORTING DOCUMENTS AND CALCULATIONS.

SUPPLIER SHALL PROVIDE A LETTER STATING THAT THEIR AIR TREATMENT SYSTEM MEETS ALL REQUIREMENTS OF ASHRAE 62.1

AIR TREATMENT SYSTEM MUST BE FULLY ENCLOSED IN THE EQUIPMENT AND POWERED BY 24 VOLT CIRCUIT THROUGHT THE UNIT.

4. PROVIDE EACH IHP WITH AN AIR TREATMENT SYSTEM CONTOLLING CONTAMINANTS OF CONCERN AND MEETING THE REQUIREMENTS OF THE INDOOR AIR QUALITY PROCEDURE OF ASHRAE 62.1.

3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.

2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.

1. REFER TO SPECIFICATION SECTIONS 238119 FOR FEATURES.

NOTES:

INDOOR HEAT PUMP UNIT W/ ELECTRIC HEATING SCHEDULE

NUMBER

SUPPLY AIRFLOW FAN

MOTOR

H.P.

COOLING HEATING

ADD. HTG.

(kW)

EFF.

(EER)

MANUFACTURERSUPPLY AIR

(CFM)

OUTSIDE AIR

(CFM)

E.S.P.

(IN. W.C.)

TOTAL CAP.

(BTU/HR)

SENSIBLE CAP.

(BTU/HR)

EAT D.B.

(°F)

EAT W.B.

(°F)

OD AMB

(°F)

OUTPUT CAP.

(BTU/HR)

OD AMB

(°F)

HP - 27 1,500 300 0.45 0.75 47,114 34,934 78.3 65.3 95 23,560 17 15 11 BARD Q48HFDC15

HP - 28 1,500 300 0.45 0.75 47,114 34,934 78.3 65.3 95 23,560 17 15 11 BARD Q48HFDC15

HP - 29 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 30A 1,125 200 0.45 0.33 33,200 25,220 77.9 65.1 95 19,460 17 15 11 BARD Q36HFDC15

HP - 30B 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 32 1,500 300 0.45 0.75 47,114 34,934 78.3 65.3 95 23,560 17 15 11 BARD Q48HFDC15

HP - 33 1,500 300 0.45 0.75 47,114 34,934 78.3 65.3 95 23,560 17 15 11 BARD Q48HFDC15

HP - 39 1,300 250 0.45 0.5 40,410 30,586 78.1 65.2 95 23,680 17 15 11.3 BARD Q43HFDC15

HP - 53 1,700 400 0.45 0.75 53,916 40,812 79 65.8 95 35,800 17 15 11.2 BARD I60HF-C15

HP - 54A 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 54B 1,125 200 0.45 0.33 33,200 25,220 77.9 65.1 95 19,460 17 15 11 BARD Q36HFDC15

HP - 61 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 63 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 65 1,125 200 0.45 0.33 33,200 25,220 77.9 65.1 95 19,460 17 15 11 BARD Q36HFDC15

HP - 67 1,300 250 0.45 0.5 40,410 30,586 78.1 65.2 95 23,680 17 15 11.3 BARD Q43HFDC15

HP - 70 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 72 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 74 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 76 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 78 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 80 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 82 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 84 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 86 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 88 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 90 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 92 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 94 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 96 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 99 1,300 250 0.45 0.5 40,410 30,586 78.1 65.2 95 23,680 17 15 11.3 BARD Q43HFDC15

HP - 100 1,300 250 0.45 0.5 40,410 30,586 78.1 65.2 95 23,680 17 15 11.3 BARD Q43HFDC15

HP - 101 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 102 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 103 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 104 900 200 0.45 0.33 27,542 20,832 78.7 65.6 95 16,400 17 9 11.5 BARD Q30HFDC09

HP - 105 1,300 250 0.45 0.5 40,410 30,586 78.1 65.2 95 23,680 17 15 11.3 BARD Q43HFDC15

HP - 106 1,300 250 0.45 0.5 40,410 30,586 78.1 65.2 95 23,680 17 15 11.3 BARD Q43HFDC15

3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.

2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.

1. REFER TO SPECIFICATION SECTION 236200 FOR FEATURES.

NOTES:

CONDENSING UNIT SCHEDULE

NUMBER

COOLING

STAGES EFF. (SEER) EFF. (EER) EFF. (IEER) MANUFACTURER

ASSOCIATED

INDOOR UNITTOTAL CAP.

(BTU/HR)

SENSIBLE CAP.

(BTU/HR)

OD AMB

(°F)

CU - 1 112,000 79,900 95 3 11.2 14.9 CARRIER 38AXDU12A0A5 AHU-1

CU - 2 109,000 76,000 95 3 11.2 14.9 CARRIER 38AXDU12A0A5 AHU-2

CU - 6 235,400 164,300 95 3 10.6 13.5 CARRIER 38AXDU25A0A5 AHU-6

CU - 7 235,400 164,300 95 3 10.6 13.5 CARRIER 38AXDU25A0A5 AHU-7

CU - 8 296,900 208,700 95 3 10.2 13.2 CARRIER 38AXDU28A0A5 AHU-8

CU - 9 115,900 86,900 95 3 11.2 14.9 CARRIER 38AXDU12A0A5 AHU-9

CU - 10 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-10

CU - 11 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-11

CU - 12 120,000 93,200 95 3 11.2 14.9 CARRIER 38AXDU12A0A5 AHU-12

CU - 13 120,000 93,200 95 3 11.2 14.9 CARRIER 38AXDU12A0A5 AHU-13

CU - 14 112,000 77,400 95 3 11.2 14.9 CARRIER 38AXDU12A0A5 AHU-14

CU - 15 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-15

CU - 16 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-16

CU - 17 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-17

CU - 18 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-18

CU - 19 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-19

CU - 20 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-20

CU - 21 120,000 93,200 95 3 11.2 14.9 CARRIER 38AXDU12A0A5 AHU-21

CU - 22 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-22

CU - 23 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-23

CU - 24 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-24

CU - 25 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-25

CU - 26 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-26

CU - 31 55,740 41,130 95 1 14 11.5 CARRIER 26SCA460N003 AH-31

CU - 34 89,100 64,700 95 2 11.2 15.5 CARRIER 38AXZN08A0A5 AHU-34

CU - 35 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-35

CU - 36 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-36

CU - 37 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-37

CU - 38 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-38

CU - 40 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-40

CU - 41 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-41

CU - 42 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-42

CU - 43 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-43

CU - 44 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-44

CU - 45 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-45

CU - 46 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-46

CU - 47 55,740 41,130 95 1 14 11.5 CARRIER 26SCA460N003 AH-47

CU - 48 32,900 24,210 95 1 14.5 12 CARRIER 26SCA436N003 AH-48

CU - 49 55,740 41,130 95 1 14 11.5 CARRIER 26SCA460N003 AH-49

CU - 50 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-50

CU - 51 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-51

CU - 52 55,740 41,130 95 1 14 11.5 CARRIER 26SCA460N003 AH-52

CU - 56 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-56

CU - 59 44,450 32,240 95 1 14 11.5 CARRIER 26SCA448N003 AH-59

CU - 107 405,560 333,240 95 2 10.8 14.8 CARRIER 38APD030 AHU-107

CU - 108 405,560 333,240 95 2 10.8 14.8 CARRIER 38APD030 AHU-108

FOR REDUCTION OF OUTSIDE AIR AS WELL AS SUBMIT ALL SUPPORTING DOCUMENTATION AND CALCULATIONS.

SUPPLIER SHALL PROVIDE A LETTER STATING THAT THEIR AIR TREATMENT SYSTEM MEETS ALL REQUIREMENTS OF ASHRAE 62.1

QUALITY PROCEDURE OF ASHRAE 62.1. AIR TREATMENT SYSTEM MUST BE FULLY ENCLOSED IN THE EQUIPMENT AND POWERED BY 24 VOLT CIRCUIT THROUGH THE UNIT.

4. PROVIDE EACH AHU WITH AN AIR TREATMENT SYSTEM CONTROLLING CONTAMINANTS OF CONCERN AND MEETING THE REQUIREMENTS OF THE INDOOR AIR

3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.

2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.

1. REFER TO SPECIFICATION SECTION 237313 FOR FEATURES.

NOTES:

AIR HANDLING UNIT SCHEDULE

NUMBER

SUPPLY AIRFLOW FAN

MOTOR

H.P.

COOLING

FAN DISCHARGE

ARRANGEMENT

MANUFACTURER

PIPE LENGTH

(FT.)

ASSOCIATED

OUTDOOR UNITSUPPLY AIR

(CFM)

OUTSIDE AIR

(CFM)

E.S.P.

(IN. W.C.)

EAT D.B.

(°F)

EAT W.B.

(°F)

LAT D.B.

(°F)

LAT W.B.

(°F)

AHU - 1 3,500 350 0.8 2.4 76.3 64.2 55.2 53.4 UBR VERTICAL CARRIER 40RLAA12A3A5 20 CU-1

AHU - 2 3,200 350 0.8 2.4 76.5 64.3 54.5 52.6 UBR VERTICAL CARRIER 40RLAA12A3A5 30 CU-2

AHU - 6 6,915 745 0.8 5 76.5 64.3 54.5 52.7 UBR VERTICAL CARRIER 40RLAA25T1A5 75 CU-6

AHU - 7 6,915 745 0.8 5 76.5 64.3 54.5 52.7 UBR VERTICAL CARRIER 40RLAA25T1A5 75 CU-7

AHU - 8 9,600 2,000 0.8 7.5 78.5 65.4 58.4 55.3 UBF VERTICAL CARRIER 40RLAA28T1A5 70 CU-8

AHU - 9 4,000 500 0.8 2.4 76.9 64.5 56.8 54.9 UBR VERTICAL CARRIER 40RLAA12A3A5 60 CU-9

AHU - 12 4,000 500 0.8 2.5 76.9 64.5 56.8 54.9 UBR VERTICAL CARRIER 40RLAA12A3A5 70 CU-12

AHU - 13 4,000 500 0.8 2.5 76.9 64.5 56.8 54.9 UBR VERTICAL CARRIER 40RLAA12A3A5 55 CU-13

AHU - 14 3,200 500 0.8 2.4 77.5 64.9 55.1 53.3 UBF VERTICAL CARRIER 40RLAA12A3A5 55 CU-14

AHU - 21 3,600 1,050 0.8 3 79.2 65.9 58.6 56.7 UBR VERTICAL CARRIER 40RLAA12A3A5 45 CU-21

AHU - 34 3,000 300 0.8 2.4 76.3 64.2 56.3 54.3 UBR VERTICAL CARRIER 40RLAA08A2A5 35 CU-34

AHU - 107 14,250 1,900 0.8 7.4 76.9 64.2 55.5 54.7 VERTICAL CARRIER 39MN3003HPEE 65 CU-107

AHU - 108 14,250 1,900 0.8 7.4 76.9 64.2 55.5 54.7 VERTICAL CARRIER 39MN3003HPEE 65 CU-108

3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.

2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.

1. REFER TO SPECIFICATION SECTION 237313 FOR FEATURES.

NOTES:

AIR HANDLING HEAT PUMP SCHEDULE

NUMBER

SUPPLY AIRFLOW FAN

MOTOR

H.P.

COOLING

FAN DISCHARGE

ARRANGEMENT

HEATING EFF.

(SEER2

EFF.

(EER2)

PIPE

LENGTH

(FT.)

MANUFACTURER

ASSOCIATED

OUTDOOR UNITSUPPLY AIR

(CFM)

OUTSIDE AIR

(CFM)

E.S.P.

(IN. W.C.)

EAT D.B.

(°F)

EAT W.B.

(°F)

LAT D.B.

(°F)

LAT W.B.

(°F)

ADD. HTG.

(kW)

STAGES

IHP - 1 4,000 500 0.45 1.2 76.9 64.5 58.8 55.7 VERTICAL 25 2 11 20' CARRIER 40RLQA12A2A5 OHP-1

IHP - 2 1,600 160 0.45 0.75 76.3 64.2 56.2 54.9 VERTICAL 10 1 15 12 15' CARRIER FJ5ANXC48L00 OHP-2

IHP - 5 800 150 0.4 0.33 78.1 65.2 57.5 56.1 HORIZONTAL 7.5 1 15.2 12 38' CARRIER FJ5ANXB24L00 OHP-5

IHP - 6 800 150 0.4 0.33 78.1 65.2 57.4 56.1 HORIZONTAL 7.5 1 15.2 12 38' CARRIER FJ5ANXB24L00 OHP-6

FOR REDUCTION OF OUTSIDE AIR AS WELL AS SUBMIT ALL SUPPORTING DOCUMENTS AND CALCULATIONS.

FULLY ENCLOSED IN THE EQUIPMENT AND POWERED BY 24 VOLT CIRCUIT THROUGHT THE UNIT. SUPPLIER SHALL PROVIDE A LETTER STATING THAT THEIR AIR TREATMENT SYSTEM MEETS ALL REQUIREMENTS OF ASHRAE 62.1

4. PROVIDE EACH GF WITH AN AIR TREATMENT SYSTEM CONTOLLING CONTAMINANTS OF CONCERN AND MEETING THE REQUIREMENTS OF THE INDOOR AIR QUALITY PROCEDURE OF ASHRAE 62.1. AIR TREATMENT SYSTEM MUST BE

3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.

2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.

1. REFER TO SPECIFICATION SECTION 237313 FOR FEATURES.

NOTES:

GAS FURNACE SCHEDULE

NUMBER

SUPPLY AIRFLOW COOLING COIL HEATING

EFF. AFUE

MANUFACTURER

ASSOCIATED

OUTDOOR UNITSUPPLY AIR

(CFM)

OUTSIDE AIR

(CFM)

E.S.P.

(IN. W.C.)

FAN

MOTOR

H.P.

EAT (DB/WB) LAT (DB/WB) OD AMB

EAT D.B.

(°F)

LAT D.B.

(°F)

INPUT CAP.

(BTU/HR)

OUTPUT CAP.

(BTU/HR)

FUEL TYPE

AH - 10 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-10

AH - 11 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-11

AH - 15 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-15

AH - 16 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-16

AH - 17 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-17

AH - 18 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-18

AH - 19 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-19

AH - 20 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-20

AH - 22 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-22

AH - 23 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-23

AH - 24 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-24

AH - 25 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-25

AH - 26 800 120 0.4 0.5 77.7/65 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA2414XMA 59SC2E040M14--12 CU-26

AH - 31 1,800 200 0.4 0.75 76.5/64.3 55/54 95 60 95 100,000 93,000 NG 92 CARRIER CVAMA6021XMA 59SC2E100M21--20 CU-31

AH - 35 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-35

AH - 36 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-36

AH - 37 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-37

AH - 38 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-38

AH - 40 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-40

AH - 41 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-41

AH - 42 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-42

AH - 43 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-43

AH - 44 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-44

AH - 45 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-45

AH - 46 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-46

AH - 47 1,800 200 0.4 0.75 76.5/64.3 55/54 95 60 95 100,000 93,000 NG 92 CARRIER CVAMA6021XMA 59SC2E100M21--20 CU-47

AH - 48 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-48

AH - 49 1,800 200 0.4 0.75 76.5/64.3 55/54 95 60 95 100,000 93,000 NG 92 CARRIER CVAMA6021XMA 59SC2E100M21--20 CU-49

AH - 50 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-50

AH - 51 1,440 200 0.4 0.75 77.1/64.6 55/54 95 60 95 80,000 75,000 NG 92 CARRIER CVAMA4821XMA 59SC2E080M21--20 CU-51

AH - 52 1,800 200 0.4 0.75 76.5/64.3 55/54 95 60 95 100,000 93,000 NG 92 CARRIER CVAMA6021XMA 59SC2E100M21--20 CU-52

AH - 56 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-56

AH - 59 1,080 200 0.4 0.5 78.1/65.2 55/54 95 60 95 60,000 56,000 NG 92 CARRIER CVAMA3617XMA 59SC2E060M17--14 CU-59

3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.

2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.

1. REFER TO SPECIFICATION SECTION 236200 FOR FEATURES.

NOTES:

HEAT PUMP SCHEDULE

NUMBER

COOLING HEATING

EFF.

(EER)

EFF.

(IEER)

MANUFACTURER

ASSOCIATED

INDOOR UNITTOTAL CAP.

(BTU/HR)

SENSIBLE CAP.

(BTU/HR)

EAT D.B.

(°F)

EAT W.B.

(°F)

OD AMB

(°F)

OUTPUT CAP.

(BTU/HR)

OD AMB

(°F)

OHP - 1 107,100 78,000 76.9 64.5 95 115,220 17 11 15.3 CARRIER 38AXQM12A0A5 IHP-1

OHP - 2 44,820 34,690 76.3 64.2 95 47,810 17 12 CARRIER 27SPA648A003 IHP-2

OHP - 5 22,350 17,760 78.1 65.2 95 22,800 17 12 CARRIER 27SPA624A003 IHP-5

OHP - 6 22,350 17,760 78.1 65.2 95 22,800 17 12 CARRIER 27SPA624A003 IHP-6

5. CEILING MOUNTED EXHAUST FANS SHALL BE INSTALLED WITH MANUFACTURER'S ALUMINUM GRILLE.

ROUND DUCT AND EXTEND DOWN TO EXHAUST GRILLE, WHEN FAN SERVES A SINGLE GRILLE.

4. AT CONTRACTOR'S OPTION, PROVIDE TRANSITION FROM FAN BACKDRAFT DAMPER TO EQUIVALENT

3. REFER TO ELECTRICAL DRAWINGS FOR ELECTRICAL CHARACTERISTICS.

2. REFER TO SPECIFICATION SECTION 230900 AND M700 SERIES SHEETS FOR CONTROLS.

1. REFER TO SPECIFICATION SECTION 233423 FOR FEATURES.

NOTES:

EXHAUST FAN SCHEDULE

NUMBER CFM

E.S.P.

(IN. W.C.)

MAX. SOUND

LEVEL (SONES)

DRIVE TYPE

FAN

MOTOR H.P.

MANUFACTURER FAN CONTROLLED BY

F - 1 340 0.25 1.9 DIRECT 1/6 GREENHECK G-095-VG I'LOCK WITH AH-1

F - 2 90 0.25 0.7 DIRECT 1/15 GREENHECK G-060-VG I'LOCK WITH AH-1

F - 3 195 0.25 3.2 DIRECT 1/6 GREENHECK G-070-VG I'LOCK WITH AH-2

F - 4 900 0.25 9.3 DIRECT 1/6 GREENHECK G-095-VG BMS SCHEDULE

F - 6 600 0.25 6.1 DIRECT 1/6 GREENHECK G-095-VG THERMOSTAT

F - 7 700 0.25 7 DIRECT 1/6 GREENHECK G-095-VG WALL SWITCH

F - 8 900 0.25 5.9 DIRECT 1/4 GREENHECK G-120-VG BMS SCHEDULE

F - 10 3,020 0.25 9.8 DIRECT 3/4 GREENHECK G-180-VG I'LOCK WITH MAH-1

F - 11 2,840 0.25 8.9 DIRECT 3/4 GREENHECK G-180-VG I'LOCK WITH MAH-2

F - 14 150 0.25 2.6 DIRECT 1/6 GREENHECK G-070-VG BMS SCHEDULE

F - 16 670 0.25 6.7 DIRECT 1/6 GREENHECK G-095-VG BMS SCHEDULE

F - 17 90 0.15 0.3 DIRECT 1/100 GREENHECK SP-A90 I'LOCK W/LIGHTS

F - 18 90 0.15 0.3 DIRECT 1/100 GREENHECK SP-A90 I'LOCK W/LIGHTS

F - 19 680 0.25 6.8 DIRECT 1/6 GREENHECK G-095-VG BMS SCHEDULE

F - 20 1,250 0.25 6.6 DIRECT 1/4 GREENHECK G-140-VG BMS SCHEDULE

F - 21 280 0.25 0.7 DIRECT 1/15 GREENHECK G-070-VG BMS SCHEDULE

F - 22 280 0.25 5 DIRECT 1/6 GREENHECK G-070-VG BMS SCHEDULE

F - 23 600 0.25 6.1 DIRECT 1/6 GREENHECK G-095-VG WALL SWITCH

F - 24 1,310 0.25 6.8 DIRECT 1/4 GREENHECK G-140-VG BMS SCHEDULE

F - 25 915 0.25 6 DIRECT 1/4 GREENHECK G-120-VG INTERVAL TIMER

F - 26 915 0.25 6 DIRECT 1/4 GREENHECK G-120-VG INTERVAL TIMER

F - 27 915 0.25 6 DIRECT 1/4 GREENHECK G-120-VG INTERVAL TIMER

F - 29 120 0.25 2.4 DIRECT 1/6 GREENHECK G-070-VG BMS SCHEDULE

F - 30 1,310 0.15 6.6 DIRECT 1/4 GREENHECK G-140-VG BMS SCHEDULE

F - 31 170 0.25 2.9 DIRECT 1/6 GREENHECK G-070-VG WALL SWITCH

F - 32 170 0.25 6.1 DIRECT 1/6 GREENHECK SE1-8-440-VG WALL SWITCH

F - 33 250 0.25 4.2 DIRECT 1/6 GREENHECK G-070-VG I'LOCK W/LIGHTS

F - 34 90 0.25 3.1 DIRECT 1/6 GREENHECK G-060-VG WALL SWITCH

F - 46 350 0.25 4.5 DIRECT 1/6 GREENHECK G-090-VG THERMOSTAT

F - 47 350 0.25 4.5 DIRECT 1/6 GREENHECK G-090-VG THERMOSTAT

F - 48 1,000 0.25 6.7 DIRECT 1/4 GREENHECK G-120-VG WALL SWITCH

F - 51 90 0.15 0.3 DIRECT 1/100 GREENHECK SP-A90 I'LOCK W/LIGHTS

F - 52 350 0.25 4.5 DIRECT 1/6 GREENHECK G-090-VG THERMOSTAT

F - 53 120 0.25 2.4 DIRECT 1/6 GREENHECK G-070-VG I'LOCK W/LIGHTS

# Doc # Date

1 AD1 11-13-2025

2 AD2 11-21-2025

Sheets
M601 - MECHANICAL EQUIPMENT SCHEDULES

File details come from the government source that posted it. Updated .