This solicitation is for a construction contract to build a 36,139 square foot National Guard Readiness Center in Barrigada, Guam. Functional areas include administrative spaces for the 1224th Engineer Support Company and 1-244th Aviation Regiment, as well as arms vaults, classrooms, and unit locker rooms. The estimated price range for construction is $25-100 million. Offerors must submit technical and past performance proposals as well as a price proposal by the response date. A pre-proposal conference and site visit will be held in May 2022 to address any questions. The Naval Facilities Engineering Command is the contracting agency. The North American Industry Classification System code is 236220 and the annual revenue standard is $39.5 million.
View the file
Other files
Show all 50
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FY22 National Guard Readiness Center WON 1674991 Barrigada, Guam Part 3 Chapter 5 Room Requirements
Final DB-RFP Submittal
5.0 ROOM REQUIREMENTS
RC02 – Lobby Space Characteristics Function/adjacencies: Main Entry Lobby/Transition area from exterior to admin/support spaces, classrooms of Aviation and ESC.
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access: Covered Main Entrance
Number of Occupants:
Other/Special Requirements:
Uniformat Section
Description Qty Size Specific Requirements
B202002 Storefronts As Required As Required Provide anodized aluminum storefront window and door system and typhoon shutters as required
B203008 Exterior Door Hardware Provide non-removable hinges and high-security mechanical or electronic locks on exterior door
B202004 Exterior Glazing Provide laminated glazing system in compliance with the latest IBC
C103004 Identifying Devices Provide interior signage at each interior door and interior directional signage for way finding.
C3010 Wall Finishes Provide painted concrete wall and paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
D4010 Fire Alarm As Required As Required
FAMNS control panel, LED Sign, smoke detector, pull station at exit door, key box at exterior wall, audible and visual notification.
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
Final DB-RFP Submittal
RC02 – Lobby Space Characteristics Function/adjacencies: Main Entry Lobby/Transition area from exterior to admin/support spaces, classrooms of Aviation and ESC.
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access: Covered Main Entrance
Description Qty Size Specific Requirements
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503004 CATV As Required As Required Provide CATV outlet
D503002 Public address As Required As Required Speaker with volume control
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted
FF&E.
Final DB-RFP Submittal
RC02a – Copier Space Characteristics Function/adjacencies: Central copier/printer station
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C103008 Counters Provide solid polymer countertops and backsplash.
C103009 Cabinets Provide veneer- core plywood cabinets
C3010 Wall Finishes Provide painted paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide quad/duplex general-purpose receptacles
Provide dedicated outlet for copier machine
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad data outlets
D503004 CATV As Required As Required Provide CATV outlet
E10 Equipment As Required As Required Refer to CID – FF&E Summary / Budget List for
Government Furnished item; Coordinate with
Final DB-RFP Submittal
RC02a – Copier Space Characteristics Function/adjacencies: Central copier/printer station
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
Electrical/Telecom to provide infrastructure.
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E
Final DB-RFP Submittal
RC03 – Hallway 1 Space Characteristics Function/adjacencies: Transition area from exterior to admin/support spaces, classrooms, cages of Aviation and ESC.
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
B202002 Storefronts Provide anodized aluminum storefront window and door system and typhoon shutters as required
B2030 Exterior Door As Required As Required Provide anodized aluminum door and door system and typhoon shutters as required
B203008 Exterior Door Hardware As Required As Required Provide non-removable hinges and high-security mechanical or electronic locks on exterior door
B202004 Exterior Glazing Provide laminated glazing system in compliance with the latest IBC
C1020 Interior Doors Provide interior flush door with louvers or electrical closet
C103004 Identifying Devices Provide interior directional signage for facility way finding.
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control
D4010 Fire Alarm As Required As Required LED sign, pull station at exit door, audible and visual notification
Final DB-RFP Submittal
RC03 – Hallway 1 Space Characteristics Function/adjacencies: Transition area from exterior to admin/support spaces, classrooms, cages of Aviation and ESC.
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503002 Public address As Required As Required Speaker with volume control
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E
Final DB-RFP Submittal
RC03a – Hallway 2 Space Characteristics Function/adjacencies: Transition area to admin/support spaces of ESC, classrooms, common use areas.
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
B2030 Exterior Door As Required As Required Provide anodized aluminum door and door system and typhoon shutters as required
B203008 Exterior Door Hardware Provide non-removable hinges and high-security mechanical or electronic locks on exterior door
C1020 Interior Doors Provide interior flush door with louvers or electrical closet
C103004 Identifying Devices Provide interior directional signage for facility way finding.
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control
D4010 Fire Alarm As Required As Required LED sign, pull station at exit door, audible and visual notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
Final DB-RFP Submittal
RC03a – Hallway 2 Space Characteristics Function/adjacencies: Transition area to admin/support spaces of ESC, classrooms, common use areas.
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503002 Public address As Required As Required Speaker with volume control
Final DB-RFP Submittal
RC03b – Hallway 3 Space Characteristics Function/adjacencies: Transition area to admin/support spaces of ESC, unit lockers, common use areas.
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
B2030 Exterior Door Provide anodized aluminum door and door system and typhoon shutters as required
B203008 Exterior Door Hardware Provide non-removable hinges and high-security mechanical or electronic locks on exterior door
C103004 Identifying Devices Provide interior directional signage for facility way finding.
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D201006 Drinking Fountain 2 As Required
Provide wall mounted drinking fountain with built-in filtration system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control
D4010 Fire Alarm As Required As Required LOC, LED sign, pull station at exit door, audible and visual notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As
Final DB-RFP Submittal
RC03b – Hallway 3 Space Characteristics Function/adjacencies: Transition area to admin/support spaces of ESC, unit lockers, common use areas.
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503002 Public address As Required As Required Speaker with volume control
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E
Final DB-RFP Submittal
RC03c – Hallway 4 Space Characteristics Function/adjacencies: Transition area to classrooms, unit lockers, common use and facility support areas.
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C1030 Identifying Devices Provide interior directional signage for facility way finding.
C301004 Wall Finishes As Required As Required Provide painted paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control
D4010 Fire Alarm As Required As Required Audible and visual notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503002 Public address As Required As Required Speaker with volume control
Final DB-RFP Submittal
RC04 – ESC/Admin Open Office Space Characteristics Function/adjacencies: Admin open space to support the mission of ESC
Special Dimensions:
Ideal Plan Dimensions: 1900 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access: Lobby and Hallway 2
Number of Occupants: 9
Description Qty Size Specific Requirements
C1020 Interior Doors As Required As Required Provide interior flush doors with vision panel
C103004 Identifying Devices Provide interior signage at each interior door, and workstations.
C3010 Wall Finishes Provide painted paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
D4010 Fire Alarm As Required As Required Audible and visual notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
Final DB-RFP Submittal
RC04 – ESC/Admin Open Office Space Characteristics Function/adjacencies: Admin open space to support the mission of ESC
Special Dimensions:
Ideal Plan Dimensions: 1900 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access: Lobby and Hallway 2
Number of Occupants: 9
Description Qty Size Specific Requirements
D503001 Data As Required As Required Provide quad/duplex data outlets
D503002 Public address As Required As Required Speaker with volume control
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted FF&E. Coordinate with Electrical/Telecom to provide infrastructure.
Final DB-RFP Submittal
RC05 – Office Space Characteristics Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Number of Occupants: 1
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors As Required As Required Provide interior flush door with vision panel
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide carpet tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
D4010 Fire Alarm As Required As Required Audible notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
Required As Required Provide duplex general-purpose receptacles
Final DB-RFP Submittal
RC05 – Office Space Characteristics Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad/duplex data outlets
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted
Final DB-RFP Submittal
RC06 – Office Space Characteristics Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors As Required As Required Provide interior flush door with vision panel
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide carpet tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
D4010 Fire Alarm As Required As Required Audible notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As
Final DB-RFP Submittal
RC06 – Office Space Characteristics Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad/duplex data outlets
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted
RC07 – Office
Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors As Required As Required Provide interior flush door with vision panel
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide carpet tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
D4010 Fire Alarm As Required As Required Audible notification
Final DB-RFP Submittal
RC07 – Office Space Characteristics Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad/duplex data outlets
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted
RC08 – Office
Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors Provide interior flush door with vision panel
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide carpet tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
D4010 Fire Alarm As Required As Required Audible notification
Final DB-RFP Submittal
RC08 – Office Space Characteristics Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad/duplex data outlets
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted
RC09 – Office
Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors As Required As Required Provide interior flush door with vision panel
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide carpet tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
Final DB-RFP Submittal
RC09 – Office Space Characteristics Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D4010 Fire Alarm As Required As Required Audible notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad/duplex data outlets
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted
RC10 – Office
Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors Provide interior flush door with vision panel
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide carpet tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
Final DB-RFP Submittal
RC10 – Office Space Characteristics Function/adjacencies: Private office for ESC officer
Special Dimensions:
Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
D4010 Fire Alarm As Required As Required Audible notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad/duplex data outlets
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted
RC11 – Surveyor Storage
Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 375 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C1020 Interior Doors As Required As Required Provide interior flush door with vision panel
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
Final DB-RFP Submittal
RC11 – Surveyor Storage Space Characteristics Function/adjacencies:
Special Dimensions:
Ideal Plan Dimensions: 375 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
D4010 Fire Alarm As Required As Required Audible notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad data outlets
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E
RC12 – Medical Storage
Function/adjacencies: Medical supply storage
Special Dimensions:
Ideal Plan Dimensions: 355 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C1020 Interior Doors Provide interior flush door with vision panel
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
Final DB-RFP Submittal
RC12 – Medical Storage Space Characteristics Function/adjacencies: Medical supply storage
Special Dimensions:
Ideal Plan Dimensions: 355 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
D4010 Fire Alarm As Required As Required Audible notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad/duplex data outlets
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E
RC13 – Unit Lockers
Function/adjacencies: TA 50 Unit locker for equipment/personal storage
Special Dimensions:
Ideal Plan Dimensions: 3242 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Number of Occupants: 169
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors Provide interior flush doors with vision panels
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
C103005 Lockers 169 Provide TA 50 Lockers
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3030 Air-cooled chiller As As Required Provide air-cooled chiller system, with ducted type
Final DB-RFP Submittal
RC13 – Unit Lockers Space Characteristics Function/adjacencies: TA 50 Unit locker for equipment/personal storage
Special Dimensions:
Ideal Plan Dimensions: 3242 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Number of Occupants: 169
Description Qty Size Specific Requirements system Required variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
D4010 Fire Alarm As Required As Required Audible and visual notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles and GFCI outlets
E201003 Fixed Seating and Tables 23 Provide fixed locker room benches of non-corrosive material
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E
RC14 – Men’s Restroom
Function/adjacencies: Enclosed Men’s Toilet with individual cubicles, urinals and washing area
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Other/Special Requirements: ADA Accessible
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors Provide interior flush door
C103004 Identifying Devices Provide interior signage at each interior door
C103001 Toilet Partitions Provide HDPE toilet partitions and urinal screens
C103002 Toilet and Bath Accessories Provide stainless steel grab bars, robe hooks, soap, paper towel, tissue and toilet dispensers and mirrors.
C3010 Wall Finishes Provide ceramic tiles wainscot on painted paperless gypsum wallboard
C3020 Floor Finishes Provide ceramic floor tiles
Final DB-RFP Submittal
RC14 – Men’s Restroom Space Characteristics Function/adjacencies: Enclosed Men’s Toilet with individual cubicles, urinals and washing area
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C3030 Ceiling Finishes Provide painted gypsum board ceiling
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D201001 Water Closet As Required
As Required Plumbing fixtures will be low flow, and Water Sense certified (where available).
D201002 Urinal As Required
As Required Plumbing fixtures will be low flow, and Water Sense certified (where available).
D201003 Lavatory As Required
As Required Plumbing fixtures will be low flow, and Water Sense certified (where available).
D201003 Floor Drain As Required
As Required Provide floor drain with primer and stainless steel cover.
D2020 Domestic water Distribution
As Required
As Required Provide hot and cold-water service with isolation valves to each fixture. Design water system to minimize water hammer from fast closing valve.
D202003 Electric Water Heater As Required
As Required Provide high-efficiency electric water heater.
D2030 Sanitary Waste As Required
As Required Provide sewer, waste and vent piping from all fixtures.
D209001 Radon Mitigation As Required
As Required See Chapter 6 ESR
D3040 Distribution System As Required
As Required Provide make-up air to toilet through air-conditioning distribution system on Classroom Areas without any return air.
D304007 Exhaust System As Required
As Required Provide exhaust ventilation system interlocked via the light switch with an adjustable time delay up to 30 minutes when turned off
D4010 Fire Alarm As Required
As Required Audible and visual notification
Final DB-RFP Submittal
RC14 – Men’s Restroom Space Characteristics Function/adjacencies: Enclosed Men’s Toilet with individual cubicles, urinals and washing area
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D4040 Fire Sprinkler As Required
As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required
As Required Provide LED lighting fixtures Provide lighting controls
D5020 General Use Receptacle
As Required
As Required Provide GFCI receptacles
E20 Furnishings As Required
As Required Refer to CID – FF&E Summary / Budget List for FF&E and SID items
RC14a – Men’s Shower
Function/adjacencies: Shower area with individual shower stalls and benches
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Final DB-RFP Submittal
Uniformat Section
Description Qty Size Specific Requirements
C1020 Interior Doors Provide interior flush door
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide ceramic tiles wainscot on painted paperless gypsum wallboard
C3020 Floor Finishes Provide ceramic floor tiles
C3030 Ceiling Finishes Provide painted gypsum board ceiling
D201005 Shower As Required
As Required
Plumbing fixtures will be low flow, and Water Sense certified (where available).
D201003 Floor Drain As Required
As Required Provide floor drain with primer and stainless steel cover.
D2020 Domestic water Distribution
As Required
As Required Provide hot and cold-water service with isolation valves to each fixture. Design water system to minimize water hammer from fast closing valves such as shower and control valves.
D202003 Electric Water Heater As Required
As Required Provide high-efficiency electric water heater.
D2030 Sanitary Waste As Required
As Required Provide waste and vent piping from all fixtures.
D209001 Radon Mitigation
Required
As Required See Chapter 6 ESR
D4010 Fire Alarm As Required As Required Audible and visual notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted
FF&E.
E201003 Fixed Seating and Tables 6 Provide fixed bench of non-corrosive material
RC15 – Janitor Room
Function/adjacencies: Enclosed room for cleaning equipment storage
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C1020 Interior Doors Provide interior flush door
C103004 Identifying Devices Provide interior signage at each interior door
C103006 Shelving Provide veneer core plywood 2-layer built in shelves in paint finish
C3010 Wall Finishes Provide ceramic tiles wainscot on painted paperless gypsum wallboard
C3020 Floor Finishes Provide ceramic floor tiles
C3030 Ceiling Finishes Provide painted gypsum board ceiling
Final DB-RFP Submittal
RC15 – Janitor Room Space Characteristics Function/adjacencies: Enclosed room for cleaning equipment storage
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D201004 Mop Sinks As Required
As Required
Plumbing fixtures will be low flow, and Water Sense certified (where available).
D2020 Domestic Water Distribution
As Required
As Required Provide domestic cold and hot water service to mop sink with isolation valve on each branch.
D2030 Sanitary Waste As Required
As Required Provide waste and vent piping for floor drain and mop sink. Provide trap primer connection to floor drain.
D209001 Radon Mitigation As Required
As Required See Chapter 6 ESR
D304007 Exhaust System As Required
As Required Provide continuous exhaust ventilation system.
Provide manual on/off switch.
D4010 Fire Alarm As Required
As Required Audible notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5020 General Use Receptacle
As Required As Required Provide GFCI receptacles
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E
RC16 – Women’s Restroom
Function/adjacencies: Enclosed Women’s Toilet with individual cubicles and washing area
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors Provide interior flush door
C103004 Identifying Devices Provide interior signage at each interior door
C103001 Toilet Partitions Provide HDPE toilet partitions and urinal screens
C103002 Toilet and Bath Accessories Provide stainless steel grab bars, robe hooks, soap, paper towel, tissue and toilet dispensers and mirrors.
C3010 Wall Finishes Provide ceramic tiles wainscot on painted paperless gypsum wallboard
Final DB-RFP Submittal
RC16 – Women’s Restroom Space Characteristics Function/adjacencies: Enclosed Women’s Toilet with individual cubicles and washing area
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C3020 Floor Finishes Provide ceramic floor tiles
C3030 Ceiling Finishes Provide painted gypsum board ceiling
D201001 Water Closet As Required
As Required
Plumbing fixtures will be low flow, and Water Sense certified (where available).
D201003 Lavatory As Required
As Required
Plumbing fixtures will be low flow, and Water Sense certified (where available).
D201003 Floor Drain As Required
As Required
Provide floor drain with primer and stainless steel cover.
D2020 Domestic water Distribution
As Required
As Required Provide hot and cold-water service with isolation valves to each fixture. Design water system to minimize water hammer from fast closing valve.
D202003 Electric Water Heater As Required
As Required Provide high-efficiency electric water heater.
D2030 Sanitary Waste As Required
As Required Provide sewer, waste and vent piping from all fixtures.
D209001 Radon Mitigation As Required
As Required See Chapter 6 ESR
D3040 Distribution System As Required
As Required Provide make-up air to toilet through air-conditioning distribution system on Classroom Areas without any return air.
D304007 Exhaust System As Required
As Required Provide exhaust ventilation system interlocked via the light switch with an adjustable time delay up to 30 minutes when turned off
D4010 Fire Alarm As Required
As Required Audible and visual notification
Final DB-RFP Submittal
RC16 – Women’s Restroom Space Characteristics Function/adjacencies: Enclosed Women’s Toilet with individual cubicles and washing area
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5020 General Use Receptacle
As Required As Required Provide GFCI receptacles
E20 Furnishings As Required As Required Refer to CID – FF&E Summary / Budget List for FF&E and SID items
RC16a – Women’s Shower
Final DB-RFP Submittal
Function/adjacencies: Shower area with individual shower stalls and benches
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C1020 Interior Doors Provide interior flush door
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide ceramic tiles wainscot on painted paperless gypsum wallboard
C3020 Floor Finishes Provide ceramic floor tiles
C3030 Ceiling Finishes Provide painted gypsum board ceiling
D201005 Shower As Required
As Required Plumbing fixtures will be low flow, and Water Sense certified (where available).
D201003 Floor Drain As Required
As Required Provide floor drain with primer and stainless steel cover.
D2020 Domestic water Distribution
As Required As Required
Provide hot and cold-water service with isolation valves to each fixture. Design water system to minimize water hammer from fast closing valves such as shower and control valves.
D202003 Electric Water Heater As Required As Required Provide high-efficiency electric water heater.
D2030 Sanitary Waste As Required As Required Provide waste and vent piping from all fixtures.
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D4010 Fire Alarm As Required As Required Audible and visual notification
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E
Final DB-RFP Submittal
RC16a – Women’s Shower Space Characteristics Function/adjacencies: Shower area with individual shower stalls and benches
Special Dimensions:
Ideal Plan Dimensions:
Minimum Ceiling Height: 8’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
E201003 Fixed Seating and Tables 4 Provide fixed bench of non-corrosive material
RC17 – Lactation(Lac) Room
Final DB-RFP Submittal
Function/adjacencies: Enclosed room for nursing/lactating
Special Dimensions:
Ideal Plan Dimensions: 80 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors Provide interior flush door
C103004 Identifying Devices Provide interior signage at each interior door
C103008 Counters Provide solid polymer countertops and backsplash.
C103009 Cabinets Provide veneer- core plywood cabinets
C3010 Wall Finishes Provide painted paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tiles with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D201004 Sinks As Required As Required Provide hand sink
D2020 Domestic Water Distribution
As Required As Required Provide domestic cold and hot water service to hand sink with isolation valve on each branch.
D2030 Sanitary Waste As Required As Required Provide waste and vent piping for hand sink.
Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
Required As Required Audible and visual notification
Final DB-RFP Submittal
RC17 – Lactation(Lac) Room Space Characteristics Function/adjacencies: Enclosed room for nursing/lactating
Special Dimensions:
Ideal Plan Dimensions: 80 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad/duplex data outlets
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E
RC18 – Break Room
Final DB-RFP Submittal
Function/adjacencies: Enclosed room for personnel lounge and kitchenette
Special Dimensions:
Ideal Plan Dimensions: 300 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors Provide interior flush door with vision panel
C103004 Identifying Devices Provide interior signage at each interior door
C103008 Counters Provide solid polymer countertops and backsplash.
C103009 Cabinets Provide veneer- core plywood cabinets
C3010 Wall Finishes Provide painted paperless gypsum wallboard
C3020 Floor Finishes Provide vinyl composition tiles with 4” rubber cove base
C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system
D201004 Sinks As Required
As Required Provide kitchen sink.
D2020 Domestic Water Distribution
As Required
As Required Provide domestic cold and hot water service to 1-compartment sink with isolation valve on each branch.
D2030 Sanitary Waste As Required
As Required Provide waste and vent piping for 1-compartment sink.
Air-cooled chiller system
As Required As Required
Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.
D209001 Radon Mitigation As Required As Required See Chapter 6 ESR
D3040 Distribution System As Required As Required Provide variable air volume air distribution system.
D3060 HVAC Controls As Required As Required DDC Control with wall mounted thermostat located in the room.
Final DB-RFP Submittal
RC18 – Break Room Space Characteristics Function/adjacencies: Enclosed room for personnel lounge and kitchenette
Special Dimensions:
Ideal Plan Dimensions: 300 NSF Minimum Ceiling Height: 9’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
D4040 Fire Sprinkler As Required As Required Automatic wet-pipe sprinkler
D502002 Interior Lighting As Required As Required Provide LED lighting fixtures
Provide lighting controls
D5090 General Use Receptacle
As Required As Required Provide duplex general-purpose receptacles
D503001 Telephone As Required As Required Provide duplex telephone outlets
D503001 Data As Required As Required Provide quad/duplex data outlets
D503004 CATV As Required As Required Provide CATV outlet
D503002 Public address As Required As Required Speaker with volume control
E20 Furnishings As Required As Required
Refer to CID – FF&E Summary / Budget List for FF&E
RC19 – Classroom 1
Final DB-RFP Submittal
Space Characteristics Function/adjacencies: Classroom and Learning Center for small and large training, gathering and briefing area; Area can be enlarged or partitioned with retractable/operable panel partitions
Special Dimensions:
Ideal Plan Dimensions: 740 NSF Minimum Ceiling Height: 14’-0”
Acoustics:
Access:
Description Qty Size Specific Requirements
C1010 Retractable Partitions Provide retractable operable panel partitions with a minimum STC 42 rating
C101001 Fixed Partitions As Required As Required minimum STC rated of 42
C1020 Interior Doors Provide interior flush door
C103004 Identifying Devices Provide interior signage at each interior door
C3010 Wall Finishes Provide painted…