N4019222R2012_Amend0002_Attach(5)_5_Room_Requirements_Rev1.pdf

PDF 1 MB Posted

Attached to
FY22 MILCON P-052 National Guard Readiness Center, Barrigada, Guam
Solicitation number
N4019222R2012
Issued by

About this file

This solicitation is for the design and construction of a 36,139 square foot National Guard Readiness Center in Barrigada, Guam to support the 1224th Engineer Support Company and 1-244th Aviation Regiment. Key requirements include administrative areas, arms vaults, classrooms, and unit lockers. The estimated price range is $25-100 million. Offerors must submit technical and past performance proposals as well as pricing by the response date. A pre-proposal conference and one-time site visit will be held. The Naval Facilities Engineering Command is the contracting agency. Offerors should monitor the sam.gov website for solicitation documents and amendments.

View the file

Other files

File Type Posted
N4019222R2012_Amend0007_Encl(1)_RFI_Notice_7.pdf PDF
N4019222R2012_Amend0007_Attach(1)_Civil_C2toC4_Rev_ 20220727.pdf PDF
N4019222R2012_Amendment_0007.pdf PDF
N4019222R2012_Amend0006_Attach(1)_6_ESR_C10._Rev4.pdf PDF
N4019222R2012_Amend0006_Encl(1)_RFI_Notice_6.pdf PDF
N4019222R2012_Amendment_0006.pdf PDF
N4019222R2012_Amend0006_Attach(2)_6_ESR_G20_Rev2.pdf PDF
N4019222R2012_Amendment_0005.pdf PDF
N4019222R2012_Amend0005_Attach(1)_6_ESR_C10._Rev3.pdf PDF
N4019222R2012_Amend0005_Encl(1)_RFI_Notice_5.pdf PDF
N4019222R2012_Amend0004_Attach(1)_6_ESR_C10._Rev3.pdf PDF
N4019222R2012_Amend0004_Encl_(1)_RFI_Notice_4.pdf PDF
N4019222R2012_Amend0004_Attach(2)_5_Room_Requirements_Rev3.pdf PDF
N4019222R2012_Amendment_0004.pdf PDF
N4019222R2012_Amendment_0003.pdf PDF
N4019222R2012_Amend0003_Attach(8)_6_ESR_D30_Rev1.pdf PDF
N4019222R2012_Amend0003_Attach(6)_5_Room_Requirements_Rev2.pdf PDF
N4019222R2012_Amend0003_Attach(7)_6_ESR_C10._Rev2.pdf PDF
N4019222R2012_Amend0003_Encl (1)_RFI_Notice_3.pdf PDF
N4019222R2012_Amend0003_Attach(3)_6_ESR_G20_Rev1.pdf PDF
N4019222R2012_Amend0003_Attach(10)_6_ESR_G20_Rev1.pdf PDF
N4019222R2012_Amend0003_Attach(1)_NGRC_C2 Site Layout Plan_Rev1.pdf PDF
N4019222R2012_Amend0003_Attach(5)_4_Figure 1_Space Tabulation_Rev1.pdf PDF
N4019222R2012_Amend0003_Attach(9)_6_ESR_E20_Rev2.pdf PDF
N4019222R2012_Amend0003_Attach(2)_6_ESR_C10_doneF._Rev1.pdf PDF
N4019222R2012_Amend0003_Attach(4)_01 50 00.05 20_Rev1.pdf PDF
N4019222R2012_Amend0002_Attach(7)_6_ESR_D40_20220614_Rev1.pdf PDF
N4019222R2012_Amend0002_Attach(3)_E1_NGRC_Elect_Site_Plan_20220614_Rev1.pdf PDF
N4019222R2012_Amend0002_Encl(3)_RFI_Notice_2.pdf PDF
N4019222R2012_Amend0002_Attach(9)_6_ESR_E20_Rev1.pdf PDF
N4019222R2012_Amend0002_Attach(2)__AS1_Architectural_Site_Plan_20220614_Rev1.pdf PDF
N4019222R2012_Amend0002_Attach(4)_P1_NGRC_Enlarged_Plumbing_Plan_Rev1.pdf PDF
N4019222R2012_Amend0002_Encl(2)_NGRC_CID_20211228_Final.pdf PDF
N4019222R2012_Amend0002_Attach(6)_6_ESR_C30_20220614_Rev1.pdf PDF
N4019222R2012_Amend0002_Attach(10)_PTS_SECTION_G20_Rev1.pdf PDF
N4019222R2012_Amend0002_Attach(1)_A4_NGRC_Building_Elevations_20220614_Rev1.pdf PDF
N4019222R2012_Amend0002_Encl(1)_Price Proposal Schedule_REV1.pdf PDF
N4019222R2012_Amend0002_Attach(8)_6_ESR_D50_20220614_Rev1.pdf PDF
N4019222R2012_Amend0002_Encl(4)_1224th_laydown_sketch.pdf PDF
N4019222R2012_Amendment_0002.pdf PDF
Amendment_0001_N4019222R2012.pdf PDF
N4019222R2012_Amendment0001_Encl (1)_RFI_Notice_1.pdf PDF
N4019222R2012_Pre-proposal_Conference_Slides.pdf PDF
N4019222R2012_Site_Visit_Attendance_Sheet.pdf PDF
N4019222R2012_RFP_Part_A_Proposal_Forms_and_Documents.pdf PDF
N4019222R2012_RFP_Part_A_Attachment _1_Request_for_Information_(RFI)_Form.pdf PDF
N4019222R2012_RFP_Part_B_Part_3_Project_Program.pdf PDF
N4019222R2012_RFP_Part_C_Drawings.pdf PDF
N4019222R2012_RFP_Part_B_Part_2_Specification_01_57_19_03_20_SUPP_TEMP_ENVI_CON_JRM_ESS.pdf PDF
N4019222R2012_RFP_Part_B_Prelim-Draft Munitions_Response_ESS_Guam_Construction_AMD7.pdf PDF
Show all 50

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FY22 National Guard Readiness Center WON 1674991 Barrigada, Guam Part 3 Chapter 5 Room Requirements

Final DB-RFP Submittal

5.0 ROOM REQUIREMENTS

RC02 – Lobby

Space Characteristics

Function/adjacencies: Main Entry Lobby/Transition area from exterior to admin/support spaces, classrooms of Aviation and ESC.

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access: Covered Main Entrance

Number of Occupants:

Other/Special Requirements:

Uniformat Section

Description Qty Size Specific Requirements

B202002 Storefronts As Required

As Required Provide anodized aluminum storefront window and door system and typhoon shutters as required

B203008 Exterior Door Hardware Provide non-removable hinges and high-security mechanical or electronic locks on exterior door

B202004 Exterior Glazing Provide laminated glazing system in compliance with the latest IBC

C103004 Identifying Devices Provide interior signage at each interior door and interior directional signage for way finding.

C3010 Wall Finishes Provide painted concrete wall and paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required FAMNS control panel, LED Sign, smoke detector, pull station at exit door, key box at exterior wall, audible and visual notification.

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

Final DB-RFP Submittal

RC02 – Lobby

Space Characteristics

Function/adjacencies: Main Entry Lobby/Transition area from exterior to admin/support spaces, classrooms of Aviation and ESC.

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access: Covered Main Entrance

Description Qty Size Specific Requirements

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As Required

As Required Provide duplex telephone outlets

D503004 CATV

As Required

As Required Provide CATV outlet

D503002 Public address As Required

As Required Speaker with volume control

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted

FF&E.

Final DB-RFP Submittal

RC02a – Copier

Space Characteristics

Function/adjacencies: Central copier/printer station

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C103008 Counters Provide solid polymer countertops and backsplash.

C103009 Cabinets Provide veneer- core plywood cabinets

C3010 Wall Finishes Provide painted paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide quad/duplex general-purpose receptacles Provide dedicated outlet for copier machine

D503001 Telephone As Required

As Required Provide duplex telephone outlets

D503001 Data As Required

As Required Provide quad data outlets

D503004 CATV

As Required

As Required Provide CATV outlet

E10 Equipment As Required

As Required Refer to CID – FF&E Summary / Budget List for Government Furnished item; Coordinate with

Final DB-RFP Submittal

RC02a – Copier

Space Characteristics

Function/adjacencies: Central copier/printer station

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

Electrical/Telecom to provide infrastructure.

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E

Final DB-RFP Submittal

RC03 – Hallway 1

Space Characteristics

Function/adjacencies: Transition area from exterior to admin/support spaces, classrooms, cages of Aviation and ESC.

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

B202002 Storefronts Provide anodized aluminum storefront window and door system and typhoon shutters as required

B2030 Exterior Door As Required

As Required Provide anodized aluminum door and door system and typhoon shutters as required

B203008 Exterior Door Hardware As Required

As Required Provide non-removable hinges and high-security mechanical or electronic locks on exterior door

B202004 Exterior Glazing Provide laminated glazing system in compliance with the latest IBC

C1020 Interior Doors Provide interior flush door with louvers or electrical closet

C103004 Identifying Devices Provide interior directional signage for facility way finding.

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control

D4010 Fire Alarm As Required

As Required LED sign, pull station at exit door, audible and visual notification

Final DB-RFP Submittal

RC03 – Hallway 1

Space Characteristics

Function/adjacencies: Transition area from exterior to admin/support spaces, classrooms, cages of Aviation and ESC.

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503002 Public address As Required

As Required Speaker with volume control

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E

Final DB-RFP Submittal

RC03a – Hallway 2

Space Characteristics

Function/adjacencies: Transition area to admin/support spaces of ESC, classrooms, common use areas.

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

B2030 Exterior Door As Required

As Required Provide anodized aluminum door and door system and typhoon shutters as required

B203008 Exterior Door Hardware Provide non-removable hinges and high-security mechanical or electronic locks on exterior door

C1020 Interior Doors Provide interior flush door with louvers or electrical closet

C103004 Identifying Devices Provide interior directional signage for facility way finding.

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control

D4010 Fire Alarm As Required

As Required LED sign, pull station at exit door, audible and visual notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

Final DB-RFP Submittal

RC03a – Hallway 2

Space Characteristics

Function/adjacencies: Transition area to admin/support spaces of ESC, classrooms, common use areas.

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503002 Public address As

As Required Speaker with volume control

Final DB-RFP Submittal

RC03b – Hallway 3

Space Characteristics

Function/adjacencies: Transition area to admin/support spaces of ESC, unit lockers, common use areas.

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

B2030 Exterior Door Provide anodized aluminum door and door system and typhoon shutters as required

B203008 Exterior Door Hardware Provide non-removable hinges and high-security mechanical or electronic locks on exterior door

C103004 Identifying Devices Provide interior directional signage for facility way finding.

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D201006 Drinking Fountain 2 As Required

Provide wall mounted drinking fountain with built-in filtration system

D209001 Radon Mitigation As Required

See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control

D4010 Fire Alarm As Required

As Required LOC, LED sign, pull station at exit door, audible and visual notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required

Final DB-RFP Submittal

RC03b – Hallway 3

Space Characteristics

Function/adjacencies: Transition area to admin/support spaces of ESC, unit lockers, common use areas.

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503002 Public address As Required

As Required Speaker with volume control

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E

Final DB-RFP Submittal

RC03c – Hallway 4

Space Characteristics

Function/adjacencies: Transition area to classrooms, unit lockers, common use and facility support areas.

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1030 Identifying Devices Provide interior directional signage for facility way finding.

C301004 Wall Finishes As Required

As Required Provide painted paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control

D4010 Fire Alarm As Required

As Required Audible and visual notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503002 Public address As

As Required Speaker with volume control

Final DB-RFP Submittal

RC04 – ESC/Admin Open Office

Space Characteristics

Function/adjacencies: Admin open space to support the mission of ESC

Special Dimensions:

Ideal Plan Dimensions: 1900 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access: Lobby and Hallway 2

Number of Occupants: 9

Description Qty Size Specific Requirements

C1020 Interior Doors As Required

As Required Provide interior flush doors with vision panel

C103004 Identifying Devices Provide interior signage at each interior door, and workstations.

C3010 Wall Finishes Provide painted paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible and visual notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As

As Required Provide duplex telephone outlets

Final DB-RFP Submittal

RC04 – ESC/Admin Open Office

Space Characteristics

Function/adjacencies: Admin open space to support the mission of ESC

Special Dimensions:

Ideal Plan Dimensions: 1900 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access: Lobby and Hallway 2

Number of Occupants: 9

Description Qty Size Specific Requirements

D503001 Data As Required

As Required Provide quad/duplex data outlets

D503002 Public address As Required

As Required Speaker with volume control

E20 Furnishings As Required

As Required

Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted FF&E. Coordinate with Electrical/Telecom to provide infrastructure.

Final DB-RFP Submittal

RC05 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Number of Occupants: 1

Description Qty Size Specific Requirements

C1020 Interior Doors As Required

As Required Provide interior flush door with vision panel

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide carpet tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As

Final DB-RFP Submittal

RC05 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D503001 Data As Required

As Required Provide quad/duplex data outlets

E20 Furnishings As Required

As Required

Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted

Final DB-RFP Submittal

RC06 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors As Required

As Required Provide interior flush door with vision panel

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide carpet tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As

Final DB-RFP Submittal

RC06 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D503001 Data As Required

As Required Provide quad/duplex data outlets

E20 Furnishings As Required

As Required

Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted

Final DB-RFP Submittal

RC07 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors As Required

As Required Provide interior flush door with vision panel

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide carpet tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As

Final DB-RFP Submittal

RC07 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D503001 Data As Required

As Required Provide quad/duplex data outlets

E20 Furnishings As Required

As Required

Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted

Final DB-RFP Submittal

RC08 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush door with vision panel

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide carpet tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As

Final DB-RFP Submittal

RC08 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D503001 Data As Required

As Required Provide quad/duplex data outlets

E20 Furnishings As Required

As Required

Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted

Final DB-RFP Submittal

RC09 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors As Required

As Required Provide interior flush door with vision panel

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide carpet tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As

Final DB-RFP Submittal

RC09 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D503001 Data As Required

As Required Provide quad/duplex data outlets

E20 Furnishings As Required

As Required

Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted

Final DB-RFP Submittal

RC10 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush door with vision panel

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide carpet tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As

Final DB-RFP Submittal

RC10 – Office

Space Characteristics

Function/adjacencies: Private office for ESC officer

Special Dimensions:

Ideal Plan Dimensions: 133 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D503001 Data As Required

As Required Provide quad/duplex data outlets

E20 Furnishings As Required

As Required

Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted

Final DB-RFP Submittal

RC11 – Surveyor Storage

Space Characteristics

Function/adjacencies:

Special Dimensions:

Ideal Plan Dimensions: 375 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors As Required

As Required Provide interior flush door with vision panel

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As

Final DB-RFP Submittal

RC11 – Surveyor Storage

Space Characteristics

Function/adjacencies:

Special Dimensions:

Ideal Plan Dimensions: 375 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D503001 Data As Required

As Required Provide quad data outlets

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E

Final DB-RFP Submittal

RC12 – Medical Storage

Space Characteristics

Function/adjacencies: Medical supply storage

Special Dimensions:

Ideal Plan Dimensions: 355 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush door with vision panel

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As

Final DB-RFP Submittal

RC12 – Medical Storage

Space Characteristics

Function/adjacencies: Medical supply storage

Special Dimensions:

Ideal Plan Dimensions: 355 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D503001 Data As Required

As Required Provide quad/duplex data outlets

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E

Final DB-RFP Submittal

RC13 – Unit Lockers

Space Characteristics

Function/adjacencies: TA 50 Unit locker for equipment/personal storage

Special Dimensions:

Ideal Plan Dimensions: 3242 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Number of Occupants: 169

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush doors with vision panels

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide painted concrete walls and paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tile with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

C103005 Lockers 169 Provide TA 50 Lockers

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible and visual notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles and GFCI outlets

Final DB-RFP Submittal

RC13 – Unit Lockers

Space Characteristics

Function/adjacencies: TA 50 Unit locker for equipment/personal storage

Special Dimensions:

Ideal Plan Dimensions: 3242 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Number of Occupants: 169

Description Qty Size Specific Requirements

E201003 Fixed Seating and Tables

Provide fixed locker room benches of non-corrosive material

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E

Final DB-RFP Submittal

RC14 – Men’s Restroom

Space Characteristics

Function/adjacencies: Enclosed Men’s Toilet with individual cubicles, urinals and washing area

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 8’-0”

Acoustics:

Access:

Other/Special Requirements: ADA Accessible

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush door

C103004 Identifying Devices Provide interior signage at each interior door

C103001 Toilet Partitions Provide HDPE toilet partitions and urinal screens

C103002 Toilet and Bath Accessories

Provide stainless steel grab bars, robe hooks, soap, paper towel, tissue and toilet dispensers and mirrors.

C3010 Wall Finishes Provide ceramic tiles wainscot on painted paperless gypsum wallboard

C3020 Floor Finishes Provide ceramic floor tiles

C3030 Ceiling Finishes Provide painted gypsum board ceiling

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D201001 Water Closet As Required

As Required Plumbing fixtures will be low flow, and Water Sense certified (where available).

D201002 Urinal As Required

As Required Plumbing fixtures will be low flow, and Water Sense certified (where available).

D201003 Lavatory As Required

As Required Plumbing fixtures will be low flow, and Water Sense certified (where available).

D201003 Floor Drain As Required

As Required Provide floor drain with primer and stainless steel cover.

D2020 Domestic water Distribution

As Required

As Required Provide hot and cold-water service with isolation valves to each fixture. Design water system to minimize water hammer from fast closing valve.

D202003 Electric Water Heater As Required

Provide high-efficiency electric water heater.

Final DB-RFP Submittal

RC14 – Men’s Restroom

Space Characteristics

Function/adjacencies: Enclosed Men’s Toilet with individual cubicles, urinals and washing area

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 8’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D2030 Sanitary Waste As Required

As Required Provide sewer, waste and vent piping from all fixtures.

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3040 Distribution System As Required

As Required Provide make-up air to toilet through air-conditioning distribution system on Classroom Areas without any return air.

D304007 Exhaust System As Required

As Required Provide exhaust ventilation system interlocked via the light switch with an adjustable time delay up to 30 minutes when turned off

D4010 Fire Alarm As Required

As Required Audible and visual notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5020 General Use Receptacle

As Required

As Required Provide GFCI receptacles

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E and SID items

Final DB-RFP Submittal

RC14a – Men’s Shower

Space Characteristics

Function/adjacencies: Shower area with individual shower stalls and benches

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 8’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush door

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide ceramic tiles wainscot on painted paperless gypsum wallboard

C3020 Floor Finishes Provide ceramic floor tiles

C3030 Ceiling Finishes Provide painted gypsum board ceiling

D201005 Shower As Required

As Required

Plumbing fixtures will be low flow, and Water Sense certified (where available).

D201003 Floor Drain As Required

As Required Provide floor drain with primer and stainless steel cover.

D2020 Domestic water Distribution

As Required

As Required Provide hot and cold-water service with isolation valves to each fixture. Design water system to minimize water hammer from fast closing valves such as shower and control valves.

D202003 Electric Water Heater As Required

As Required Provide high-efficiency electric water heater.

D2030 Sanitary Waste As Required

As Required Provide waste and vent piping from all fixtures.

D209001 Radon Mitigation

As

As Required See Chapter 6 ESR

D4010 Fire Alarm As Required

As Required Audible and visual notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required

Final DB-RFP Submittal

RC14a – Men’s Shower

Space Characteristics

Function/adjacencies: Shower area with individual shower stalls and benches

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 8’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted

FF&E.

E201003 Fixed Seating and Tables

6 Provide fixed bench of non-corrosive material

Final DB-RFP Submittal

RC15 – Janitor Room

Space Characteristics

Function/adjacencies: Enclosed room for cleaning equipment storage

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 8’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush door

C103004 Identifying Devices Provide interior signage at each interior door

C103006 Shelving Provide veneer core plywood 2-layer built in shelves in paint finish

C3010 Wall Finishes Provide ceramic tiles wainscot on painted paperless gypsum wallboard

C3020 Floor Finishes Provide ceramic floor tiles

C3030 Ceiling Finishes Provide painted gypsum board ceiling

D201004 Mop Sinks As Required

As Required

Plumbing fixtures will be low flow, and Water Sense certified (where available).

D2020 Domestic Water Distribution

As Required

As Required Provide domestic cold and hot water service to mop sink with isolation valve on each branch.

D2030 Sanitary Waste As Required

As Required Provide waste and vent piping for floor drain and mop sink. Provide trap primer connection to floor drain.

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D304007 Exhaust System As Required

As Required Provide continuous exhaust ventilation system.

Provide manual on/off switch.

D4010 Fire Alarm As Required

As Required Audible notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures

D5020 General Use As As Required Provide GFCI receptacles

Final DB-RFP Submittal

RC15 – Janitor Room

Space Characteristics

Function/adjacencies: Enclosed room for cleaning equipment storage

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 8’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

Receptacle Required

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E

Final DB-RFP Submittal

RC16 – Women’s Restroom

Space Characteristics

Function/adjacencies: Enclosed Women’s Toilet with individual cubicles and washing area

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 8’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush door

C103004 Identifying Devices Provide interior signage at each interior door

C103001 Toilet Partitions Provide HDPE toilet partitions and urinal screens

C103002 Toilet and Bath Accessories

Provide stainless steel grab bars, robe hooks, soap, paper towel, tissue and toilet dispensers and mirrors.

C3010 Wall Finishes Provide ceramic tiles wainscot on painted paperless gypsum wallboard

C3020 Floor Finishes Provide ceramic floor tiles

C3030 Ceiling Finishes Provide painted gypsum board ceiling

D201001 Water Closet As Required

As Required

Plumbing fixtures will be low flow, and Water Sense certified (where available).

D201003 Lavatory As Required

As Required

Plumbing fixtures will be low flow, and Water Sense certified (where available).

D201003 Floor Drain As Required

As Required

Provide floor drain with primer and stainless steel cover.

D2020 Domestic water Distribution

As Required

As Required Provide hot and cold-water service with isolation valves to each fixture. Design water system to minimize water hammer from fast closing valve.

D202003 Electric Water Heater As Required

As Required Provide high-efficiency electric water heater.

D2030 Sanitary Waste As Required

As Required Provide sewer, waste and vent piping from all fixtures.

D209001 Radon Mitigation As Required

See Chapter 6 ESR

Final DB-RFP Submittal

RC16 – Women’s Restroom

Space Characteristics

Function/adjacencies: Enclosed Women’s Toilet with individual cubicles and washing area

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 8’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

D3040 Distribution System As Required

As Required Provide make-up air to toilet through air-conditioning distribution system on Classroom Areas without any return air.

D304007 Exhaust System As Required

As Required Provide exhaust ventilation system interlocked via the light switch with an adjustable time delay up to 30 minutes when turned off

D4010 Fire Alarm As Required

As Required Audible and visual notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5020 General Use Receptacle

As Required

As Required Provide GFCI receptacles

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E and SID items

Final DB-RFP Submittal

RC16a – Women’s Shower

Space Characteristics

Function/adjacencies: Shower area with individual shower stalls and benches

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 8’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush door

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide ceramic tiles wainscot on painted paperless gypsum wallboard

C3020 Floor Finishes Provide ceramic floor tiles

C3030 Ceiling Finishes Provide painted gypsum board ceiling

D201005 Shower As Required

As Required Plumbing fixtures will be low flow, and Water Sense certified (where available).

D201003 Floor Drain As Required

As Required Provide floor drain with primer and stainless steel cover.

D2020 Domestic water Distribution

As Required

As Required

Provide hot and cold-water service with isolation valves to each fixture. Design water system to minimize water hammer from fast closing valves such as shower and control valves.

D202003 Electric Water Heater As Required

As Required Provide high-efficiency electric water heater.

D2030 Sanitary Waste As Required

As Required Provide waste and vent piping from all fixtures.

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D4010 Fire Alarm As Required

As Required Audible and visual notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required

Final DB-RFP Submittal

RC16a – Women’s Shower

Space Characteristics

Function/adjacencies: Shower area with individual shower stalls and benches

Special Dimensions:

Ideal Plan Dimensions:

Minimum Ceiling Height: 8’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E and SID items; Provide blocking for wall mounted

FF&E.

E201003 Fixed Seating and Tables

4 Provide fixed bench of non-corrosive material

Final DB-RFP Submittal

RC17 – Lactation(Lac) Room

Space Characteristics

Function/adjacencies: Enclosed room for nursing/lactating

Special Dimensions:

Ideal Plan Dimensions: 80 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush door

C103004 Identifying Devices Provide interior signage at each interior door

C103008 Counters Provide solid polymer countertops and backsplash.

C103009 Cabinets Provide veneer- core plywood cabinets

C3010 Wall Finishes Provide painted paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tiles with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D201004 Sinks As Required

As Required Provide hand sink

D2020 Domestic Water Distribution

As Required

As Required Provide domestic cold and hot water service to hand sink with isolation valve on each branch.

D2030 Sanitary Waste As

As Required Provide waste and vent piping for hand sink.

system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As As Required Audible and visual notification

Final DB-RFP Submittal

RC17 – Lactation(Lac) Room

Space Characteristics

Function/adjacencies: Enclosed room for nursing/lactating

Special Dimensions:

Ideal Plan Dimensions: 80 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

Required

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As Required

As Required Provide duplex telephone outlets

D503001 Data As Required

As Required Provide quad/duplex data outlets

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E

Final DB-RFP Submittal

RC18 – Break Room

Space Characteristics

Function/adjacencies: Enclosed room for personnel lounge and kitchenette

Special Dimensions:

Ideal Plan Dimensions: 300 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1020 Interior Doors Provide interior flush door with vision panel

C103004 Identifying Devices Provide interior signage at each interior door

C103008 Counters Provide solid polymer countertops and backsplash.

C103009 Cabinets Provide veneer- core plywood cabinets

C3010 Wall Finishes Provide painted paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tiles with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D201004 Sinks As Required

As Required Provide kitchen sink.

D2020 Domestic Water Distribution

As Required

As Required Provide domestic cold and hot water service to 1-compartment sink with isolation valve on each branch.

D2030 Sanitary Waste As Required

Provide waste and vent piping for 1-compartment sink.

system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As As Required Audible and visual notification

Final DB-RFP Submittal

RC18 – Break Room

Space Characteristics

Function/adjacencies: Enclosed room for personnel lounge and kitchenette

Special Dimensions:

Ideal Plan Dimensions: 300 NSF Minimum Ceiling Height: 9’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

Required

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles

D503001 Telephone As Required

As Required Provide duplex telephone outlets

D503001 Data As Required

As Required Provide quad/duplex data outlets

D503004 CATV

As Required

As Required Provide CATV outlet

D503002 Public address As Required

As Required Speaker with volume control

E20 Furnishings As Required

As Required Refer to CID – FF&E Summary / Budget List for FF&E

Final DB-RFP Submittal

RC19 – Classroom 1

Space Characteristics

Function/adjacencies: Classroom and Learning Center for small and large training, gathering and briefing area; Area can be enlarged or partitioned with retractable/operable panel partitions

Special Dimensions:

Ideal Plan Dimensions: 740 NSF Minimum Ceiling Height: 14’-0”

Acoustics:

Access:

Description Qty Size Specific Requirements

C1010 Retractable Partitions Provide retractable operable panel partitions with a minimum STC 42 rating

C1020 Interior Doors Provide interior flush door

C103004 Identifying Devices Provide interior signage at each interior door

C3010 Wall Finishes Provide painted paperless gypsum wallboard

C3020 Floor Finishes Provide vinyl composition tiles with 4” rubber cove base

C3030 Ceiling Finishes Provide acoustical tile ceiling on aluminum grid system

D209001 Radon Mitigation As Required

As Required See Chapter 6 ESR

D3030 Air-cooled chiller system

As Required

As Required Provide air-cooled chiller system, with ducted type variable speed air handling unit with vav boxes, and high-efficiency dedicated outdoor air system unit.

D3040 Distribution System As Required

As Required Provide variable air volume air distribution system.

D3060 HVAC Controls As Required

As Required DDC Control with wall mounted thermostat located in the room.

D4010 Fire Alarm As Required

As Required Audible and visual notification

D4040 Fire Sprinkler As Required

As Required Automatic wet-pipe sprinkler

D502002 Interior Lighting As Required

As Required Provide LED lighting fixtures Provide lighting controls

D5090 General Use Receptacle

As Required

As Required Provide duplex general-purpose receptacles;

Provide floor…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .