The specification establishes comprehensive requirements for the design, manufacture, installation, and performance of roller window shade systems. Products must comply with multiple industry standards including ANSI/WCMA A100.1 for safety, NFPA 701 for flammability (small and large-scale vertical burn testing), ASTM G21 for anti-microbial resistance (no growth for fungi ATCC9642, ATCC 9644, ATCC9645), and UL 325 for electrical system safety. Indoor air quality certification is required via UL 2818 (Greenguard Gold), SCS Global Services Indoor Advantage Gold, or equivalent third-party validation. Manufacturers must have minimum twenty years of experience with at least three comparable projects. The specification requires various fiber components to contain a minimum 60 percent recycled content, and room darkening shades must use PVC polyester with minimum 78 percent recycled fiber content. Key deliverables include detailed shop drawings, location schedules, product data, samples (minimum 6 by 6 inches), mock-up installation for approval, and flammability test reports. Installation must be performed by manufacturer-trained and certified installers with minimum ten years of comparable experience. The contractor must provide a 10-year manufacturer's warranty covering defective materials and workmanship from the date of final acceptance. Manually operated shades feature #10 stainless steel bead chains (90 lb. minimum breaking strength) with chain-and-clutch mechanisms, while dual-roller configurations are also specified. All shade cloth must meet light-filtering or light-blocking requirements with steel or aluminum hem bars, and metal components require corrosion-resistant treatment or anodized finishes. Installation must be completed in accordance with approved drawings and manufacturer instructions, with all materials delivered in original packaging and stored in dry, controlled conditions above 50 degrees Fahrenheit.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
P-995 Composite Repair Facility 24 December 2025 MCAS Cherry Point, NC
SECTION 12 24 13
ROLLER WINDOW SHADES
08/20
PART 1 GENERAL
1.1 REFERENCES
The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.
AMERICAN NATIONAL STANDARDS INSTITUTE (ANSI)
ANSI/WCMA A100.1 (2018) American National Standard for Safety of Window Covering Products
ASTM INTERNATIONAL (ASTM)
ASTM G21 (2015; R 2021; E 2021) Standard Practice for Determining Resistance of Synthetic Polymeric Materials to Fungi
NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)
NFPA 701 (2023; ERTA 1 2023) Standard Methods of Fire Tests for Flame Propagation of Textiles and Films
SCIENTIFIC CERTIFICATION SYSTEMS (SCS)
SCS SCS Global Services (SCS) Indoor Advantage
UL SOLUTIONS (UL)
UL 325 (2017; Reprint Feb 2020) UL Standard for Safety Door, Drapery, Gate, Louver, and Window Operators and Systems
UL 2818 (2022) GREENGUARD Certification Program For Chemical Emissions For Building Materials, Finishes And Furnishings
1.2 SUBMITTALS
Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES
SD-02 Shop Drawings
Detailed Drawings ; G
Location Schedule ; G
SD-03 Product Data
SECTION 12 24 13 Page 1 REVISED Amendment 003 - 17 APR 2026
Window Shades ; G
Recycled Content for various fiber components ; S
SD-04 Samples
Window Shades ; G
SD-06 Test Reports
Flammability Requirements ; G
SD-07 Certificates
Indoor Air Quality for roller window shades ; S
Qualifications
SD-10 Operation and Maintenance Data
Window Shades , Data Package 1; G
SD-11 Closeout Submittals
Submit Data Package 1 for roller window shades, and Data Package 2 for electrical operators, in accordance with Section 01 78 23
OPERATIONS AND MAINTENANCE DATA.
1.3 CERTIFICATES
1.3.1 Indoor Air Quality Certifications
1.3.1.1 Roller Window Shades
Provide products certified to meet indoor air quality requirements by UL 2818 (Greenguard) Gold, SCS Global Services Indoor Advantage Gold or provide validation by other third-party program that products meet the requirements of this paragraph. Provide current product certification documentation from certification body.
1.4 QUALITY ASSURANCE
1.4.1 Qualifications
1.4.1.1 Installer's Qualifications
Installer trained and certified by the manufacturer with a minimum of ten years of experience in installing products comparable to those specified in this section.
1.4.2 Flammability Requirements
Passes in accordance with NFPA 701 small and large-scale vertical burn.
Materials tested are identical to products proposed for use.
1.4.3 Electrical Requirements
NFPA Article 100 listed and labeled in accordance with UL 325 or other
SECTION 12 24 13 Page 2 testing agency acceptable to authorities having jurisdiction, marked for intended use, and tested as a system. Individual testing of components is not acceptable in lieu of system testing.
1.4.4 Anti-Microbial Requirements
'No Growth' per ASTM G21 results for fungi ATCC9642, ATCC 9644, ATCC9645.
1.5 DELIVERY, STORAGE, AND HANDLING
Deliver components to the jobsite in the manufacturer's original packaging with the brand or company name, item identification, and project reference clearly marked. Store components in a dry location that is adequately ventilated and free from dust, water, or other contaminants and has easy access for inspection and handling. Store materials flat in a clean dry area with temperature maintained above 50 degrees F . Do not open containers until needed for installation unless verification inspection is required. Handle and store shades in accordance with manufacturer's recommendations.
1.6 WARRANTY
Provide manufacturer's warranty to repair or replace defective materials and workmanship for a period of 10years from date of final acceptance of the work.
PART 2 PRODUCTS
2.1 WINDOW SHADES
Submit drawings showing plans, elevations, sections, product details, installation details, operational clearances, wiring diagrams and relationship to work. Submit a location schedule showing location, size and quantity of shades. Include the use of same room designations as indicated on the drawings.
Provide product data composed of catalog cuts, brochures, and operating and maintenance instructions on each product to be used. Include styles, profiles and features.
Furnish samples of each type and color of roller shade fabric and roller shade channel. Provide shade material minimum 6 by 6 inches in size.
Mark face of material to indicate interior faces.
Mock up: Install shade in area designated by Contracting Officer. Do not proceed with remaining work until the Contracting Officer approves workmanship and operation. Rework mock up as required to produce acceptable work. The approved shade can be used in the installation.
Submit fire resistance data, flame spread and smoke contribution data.
Provide roller tube that operates smoothly and of sufficient diameter and thickness to prevent excessive deflection. Provide brackets that are appropriate for outside mount. Provide shade cloth meeting the performance described in NFPA 701 , small scale test. Treat steel features for corrosion resistance.
Provide Various Fiber Components with a minimum of 60 percent recycled content. Provide data identifying percentage of recycled content for
SECTION 12 24 13 Page 3 various fiber components .
Provide certification of indoor air quality for roller window shades .
2.1.1 Manufacturer's Qualifications
Obtain motor-controlled roller shades through one source from a single manufacturer with a minimum of twenty years of experience and minimum of three projects of similar scope and size in manufacturing products comparable to those specified in this section. Furnish manual and motorized shades produced by the same manufacturer to provide matching appearance.
2.1.2 Manually Operated Shades with Single Rollers
2.1.2.1 Chain-and-Clutch Operating Mechanisms
Provide continuous-loop bead chain and clutch that stops shade movement when bead chain is released; shade to be permanently adjusted and lubricated.
2.1.2.2 Bead Chains
Provide bead chain from #10 stainless steel rated to 90 lb. minimum breaking strength with pull chain tensioning device complying with
ANSI/WCMA A100.1
a. Loop Length: Full length of roller shade.
b. Limit Stops: Allows shade to stop when chain is released. Provide limit stops to prevent shade from being raised or lowered too far.
c. Chain-Retainer Type: Chain tensioner, jamb mounted.
2.1.2.3 Rollers
Provide corrosion-resistant steel or extruded-aluminum tubes of diameters and wall thicknesses required to accommodate operating mechanisms and weights and widths of shade bands indicated without deflection. Provide with permanently lubricated drive-end assemblies and idle-end assemblies designed to facilitate removal of shade cloth for service.
a. Roller Drive-End Location: Right side of interior face of shade.
b. Direction of Shade cloth Roll: Regular, from back (exterior face) of roller.
c. Shade cloth-to-Roller Attachment: Manufacturer's standard method.
Adhesive attachment is not acceptable.
2.1.2.4 Mounting Hardware
Provide corrosion resistant brackets or endcaps compatible with roller assembly, operating mechanism, installation accessories, and mounting location and conditions indicated. Provide hardware that allows for field adjustment or removal of shade roller tube and other operable hardware component without removal of brackets and end or center supports.
SECTION 12 24 13 Page 4
2.1.2.5 Shade Cloth
a. Shade Material: Light-filtering fabric: Openness 3 percent.
b. Shade Cloth Bottom (Hem) Bar: Steel or extruded aluminum. Provide shade bar enclosed in sealed pocket of shade band material.
2.1.2.6 Installation Accessories
a. Front Fascia: L-shaped aluminum extrusion to conceal shade roller and hardware that snaps onto end caps without requiring exposed fasteners of any kind. Fascia can be mounted continuously across two or more shade bands. Provide manufacturers standard height fascia as required to conceal roller and shade band assembly when shade is fully open.
b. Exposed Headbox: Rectangular, extruded-aluminum enclosure including front fascia, top and back covers, endcaps, and removable bottom closure. Provide manufacturers standard height fascia as required to conceal roller and shade band assembly when shade is fully open.
c. Endcaps: Extruded aluminum with universal design suitable for mounting to window mullions. Provide size compatible with roller size. Provide end cap covers matching fascia/headbox finish.
d. Recessed Shade Pocket: Rectangular, extruded-aluminum enclosure designed for recessed ceiling installation; with front, top, and back formed as one piece, end plates, and removable bottom closure panel. Provide manufacturers standard height fascia as required to conceal roller and shade band assembly when shade is fully open. Provide pocket with lip at lower edge to support acoustical ceiling panel.
e. Closure Panel and Wall Clip: Removable aluminum panel designed for installation at bottom of site-constructed ceiling recess or pocket and for snap-in attachment to wall clip without fasteners.
2.1.3 Manually Operated Shades with Dual Rollers
2.1.3.1 Chain-and-Clutch Operating Mechanisms
Provide continuous-loop bead chain and clutch that stops shade movement when bead chain is released; shade to be permanently adjusted and lubricated.
2.1.3.2 Bead Chains
Provide bead chain from #10 stainless steel rated to 90 lb. minimum breaking strength with pull chain tensioning device complying with ANSI/WCMA A100.1 . Provide positive mechanical engagement of drive mechanism to shade roller tube. Center bead chain placement for right or left- hand operation.
a. Loop Length: Full length of roller shade.
b. Limit Stops: Allows shade to stop when chain is released. Provide limit stops to prevent shade from being raised or lowered too far.
SECTION 12 24 13 Page 5
c. Chain-Retainer Type: Chain tensioner, jamb mounted.
2.1.3.3 Rollers
Provide corrosion-resistant steel or extruded-aluminum tubes of diameters and wall thicknesses required to accommodate operating mechanisms and weights and widths of shade bands indicated without deflection. Provide with permanently lubricated drive-end assemblies and idle-end assemblies designed to facilitate removal of shade bands for service.
a. Dual Shade-Roller Mounting Configuration: Side by Side.
b. Inside Roller: Drive-End Location: Right side of interior face of shade. Direction of Shade cloth Roll: Regular, from back (exterior face) of roller.
c. Outside Roller: Drive-End Location: Right side of interior face of shade. Direction of Shade cloth Roll: Regular, from back (exterior face) of roller .
d. Shade cloth-to-Roller Attachment: Manufacturer's standard method.
Adhesive attachment is not acceptable.
2.1.3.4 Mounting Hardware
Provide corrosion resistant brackets or endcaps compatible with roller assembly, operating mechanism, installation accessories, and mounting location and conditions indicated. Provide hardware that allows for field adjustment or removal of shade roller tube and other operable hardware component without removal of brackets and end or center supports.
2.1.3.5 Inside Shade Cloth
a. Shade Material: Light-filtering fabric: Openness 3 percent and Light-blocking fabric.
b. Shade Cloth Bottom (Hem) Bar: Steel or extruded aluminum. Provide shade bar enclosed in sealed pocket of shade cloth material.
2.1.3.6 Installation Accessories
a. Front Fascia: L-shaped aluminum extrusion to conceal shade roller and hardware that snaps onto end caps without requiring exposed fasteners of any kind. Fascia can be mounted continuously across two or more shade bands. Provide manufacturers standard height fascia as required to conceal roller and shade band assembly when shade is fully open.
b. Exposed Headbox: Rectangular, extruded-aluminum enclosure including front fascia, top and back covers, endcaps, and removable bottom closure. Provide manufacturers standard height fascia as required to conceal roller and shade band assembly when shade is fully open.
c. Endcaps: Extruded aluminum with universal design suitable for mounting to window mullions. Provide size compatible with roller size. Provide end cap covers matching fascia/headbox finish.
d. Recessed Shade Pocket: Rectangular, extruded-aluminum enclosure designed for recessed ceiling installation; with front, top, and back formed as one piece, end plates, and removable bottom closure panel.
SECTION 12 24 13 Page 6
Provide manufacturers standard height fascia as required to conceal roller and shade band assembly when shade is fully open. Provide pocket with lip at lower edge to support acoustical ceiling panel.
e. Closure Panel and Wall Clip: Removable aluminum panel designed for installation at bottom of site-constructed ceiling recess or pocket and for snap-in attachment to wall clip without fasteners.
2.1.3.7 Room Darkening Shades
Provide room darkening (black-out) window shades designed to eliminate all visible light gaps when shades are fully closed, and conform with the following:
a. Provide roller tube made of aluminum. Provide shop fabricated light traps, consisting of a head box to house the shade roller, and U-shaped channels to serve as guides for the shade along the sides and to receive the bottom edge of the shade along the sill.
b. Provide light trap made of sheet steel having a minimum thickness of 22 gauge or anodized, extruded, aluminum. Provide legs of the channels not less than 1-3/4 inches long and separated by the minimum distance that permits free operation of the shade. Edges of light trap coming into contact with the shade cloth are smooth pile light seal. The exposed face of the head box is hinged or removable for access to the shade roller. The interior or unexposed surfaces of the light trap have a finish coat of flat black enamel. The exposed portions of the light trap have a factory-applied priming coat of gray paint.
c. Provide type of cloth for blackout purposes. Provide shade from a single piece of PVC polyester that contains a minimuum of 78 percent fibers made from recycled content .
d. Fit the bottom edge of the shade with a steel operating bar. Shades to engage positively with bottom rail through operating bar. Paint bars with flat black enamel.
2.2 COLOR
Provide color, pattern and texture for metal trim and shade fabric as indicated on the drawings. Fascia/headbox finish must be brushed satin metal finish ; colors listed are not intended to limit the selection of equal colors from other manufacturers.
PART 3 EXECUTION
3.1 FIELD MEASUREMENTS
After becoming familiar with details of the work, verify all dimensions in the field, and advise the Contracting Officer of any discrepancy before performing the work.
3.2 INSTALLATION
Do not install building construction materials that show visual evidence of biological growth.
Provide roller window shades, complete with necessary brackets, fittings, SECTION 12 24 13 Page 7 and hardware as indicated.
Perform installation in accordance with the approved detailed drawings and manufacturer's installation instructions. Install units level, plumb, secure, and at proper height and location relative to window units.
Provide and install supplementary or miscellaneous items in total, including clips, brackets, or anchorages incidental to or necessary for a sound, secure, and complete installation. Do not start installation until completion of room painting and finishing operations.
3.3 CLEAN-UP
Upon completion of the installation, clean window treatments and exposed components as recommended by manufacturer. Adjust window treatment for form and appearance and proper operating condition. Repair or replace damaged units as directed by the Contracting Officer. Isolate metal parts from direct contact with concrete, mortar, or dissimilar metals. Ensure shades installed in recessed pockets can be removed without disturbing the pocket. The entire shade, when retracted, is contained inside the pocket. For shades installed outside the jambs and mullions, overlap each jamb and mullion 0.75 inch or more when the jamb and mullion sizes permit. Include all hardware, brackets, anchors, fasteners, and accessories necessary for a complete, finished installation.
-- End of Section --
SECTION 12 24 13 Page 8
| 12 24 13 - ROLLER WINDOW SHADES |
| PART 1 GENERAL |
| 1.1 REFERENCES |
| 1.2 SUBMITTALS |
| 1.3 CERTIFICATES |
| 1.3.1 Indoor Air Quality Certifications |
| 1.3.1.1 Roller Window Shades |
| 1.4 QUALITY ASSURANCE |
| 1.4.1 Qualifications |
| 1.4.1.1 Installer's Qualifications |
| 1.4.2 Flammability Requirements |
| 1.4.3 Electrical Requirements |
| 1.4.4 Anti-Microbial Requirements |
| 1.5 DELIVERY, STORAGE, AND HANDLING |
| 1.6 WARRANTY |
| PART 2 PRODUCTS |
| 2.1 WINDOW SHADES |
| 2.1.1 Manufacturer's Qualifications |
| 2.1.2 Manually Operated Shades with Single Rollers |
| 2.1.2.1 Chain-and-Clutch Operating Mechanisms |
| 2.1.2.2 Bead Chains |
| 2.1.2.3 Rollers |
| 2.1.2.4 Mounting Hardware |
| 2.1.2.5 Shade Cloth |
| 2.1.2.6 Installation Accessories |
| 2.1.3 Manually Operated Shades with Dual Rollers |
| 2.1.3.1 Chain-and-Clutch Operating Mechanisms |
| 2.1.3.2 Bead Chains |
| 2.1.3.3 Rollers |
| 2.1.3.4 Mounting Hardware |
| 2.1.3.5 Inside Shade Cloth |
| 2.1.3.6 Installation Accessories |
| 2.1.3.7 Room Darkening Shades |
2.2 COLOR
| PART 3 EXECUTION |
| 3.1 FIELD MEASUREMENTS |
| 3.2 INSTALLATION |
| 3.3 CLEAN-UP |