Roybal_DB_RFP_Amendment_04_16th_Fl_Room_Reqs.pdf

PDF 499 KB Posted

Attached to
Edward R. Roybal Repair and Alteration Tenant Improvement Prospectus Project
Solicitation number
GS-09P-15-KT-C-0014
Issued by

About this file

16th Fl Room Requirements

View the file

Other files

File Type Posted
Roybal_DB_RFP_Amendment_06.pdf PDF
Roybal_DB_RFP_Amendment_05.pdf PDF
Roybal_DB_RFP_Amendment_04.pdf PDF
Roybal_DB_RFP_Amendment_04_14th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_6th_FL_room_reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_revised_bid_sheet.pdf PDF
Roybal_DB_RFP_Amendment_04_9th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_scope_reductions.pdf PDF
Roybal_DB_RFP_Amendment_04_8th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_15th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_10th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_7th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Certificate_of_Current_Cost_or_Pricing_Data_(1).pdf PDF
Roybal_DB_RFP_Amendment_03_SF30.pdf PDF
Roybal_DB_bid_sheet_Amendment_03.pdf PDF
Roybal_DB_RFP_PPQ_Amendment_02.docx DOCX document
Roybal_DB_bid_sheet_Amendment_02.pdf PDF
Roybal_DB_RFP_Offeror_Representations_and_Certifications.doc DOC document
Roybal_DB_RFP_Amendment_02_SF30.pdf PDF
Roybal_DB_RFP_Amendment_01.pdf PDF
08_Roybal_room_requirements_Pg_117-138.pdf PDF
Roybal_Pre_proposal_Conference_Final_05_28_2015_(1).pdf PDF
Appendix_C_Roybal_Swing_Space_Requirements_and_Move_Matrix_04_06_2015.pdf PDF
Roybal_Fed_Bldg_BER_Final_Submittal.pdf PDF
Roybal_Fed_Bldg_BER_Final_Submittal_Appendices.pdf PDF
AmendmenttoAppendixCSwingSpaceandMovesSOWFinal.doc.pdf PDF
Roybal_DB_RFP_preproposal_attendees.pdf PDF
Volume_3_-_References.pdf PDF
Past_Performance_Questionnaire.docx DOCX document
Volume_2B_Roybal_PDS_and_Appendix.pdf PDF
VOLUME_2A_SCOPE_OF_WORK.pdf PDF
Roybal_DB_1442.pdf PDF
Roybal_DB_RFP_Agreement.pdf PDF
Roybal_DB_Division_1.pdf PDF
Roybal_DB_Solicitation.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

United States General Service Administration

PROGRAM DEVELOPMENT STUDY – FINAL SUBMITTAL

Edward R. Roybal Federal Building and U.S. Courthouse 8.0 IMPLEMENTATION PLAN

Joseph Chow & Associates, Inc. 8.0 - 397 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Do not remove this notice. Properly destroy documents when no longer required

ROOM REQUIREMENTS

The Room Requirements tables below represent preliminary information from the User describing general requirements. During the design process, the Design/Build Contractor shall work with the Users to confirm the room requirements and effectively utilize the maximum allowable space.

16.1 SIXTEENTH FLOOR – US BANKRUPTCY COURTS –

DELETED WORK SCOPE OPTION I

16.1.1 Board of Judges (BOJ) Conference Room - Option I

ROOM: 1645

Space Characteristics

Function/adjacencies: USBC: Conference Room.

Special Dimensions: Existing. 11’-6” ceiling height.

Access: Access from the building corridor.

Courts’ POR Reference: 5.6.9

Special Requirements: This room is otherwise known as the USBC Judicial Conference room. An existing, decommissioned USBC courtroom will be used for this space.

Verify specific infrastructure requirements with the court (i.e. electrical, telecom, floor boxes, etc…)

Uniformat

Section Description Qty Size Specific Requirements

C101001 Fixed Partitions SF N/A. Existing courtroom.

C1020 Interior Doors EA N/A. Existing.

C102007 Interior Door

Hardware

As

Req’d

Existing entry door hardware to remain. Provide mechanical lockset. Coordinate door hardware type and function with the Users. For additional door hardware, see USMS security drawings in

Appendix A.

C3010 Wall Finishes SF Keep existing wall paneling. Patch walls as required to accommodate new work.

C3020 Floor Finishes SF Carpet Tile with attached cushion backing over existing metal subfloor.

Joseph Chow & Associates, Inc. 8.0 - 398 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Uniformat

Section Description Qty Size Specific Requirements

C3020 Floor Finishes LF Clean base. Patch and repair base damaged by construction.

C3030 Ceiling Finishes SF N/A. Existing.

D304007 Exhaust Systems MBH KW N/A. Existing.

C103004 Identifying

Devices

EA N/A. Existing.

D4010 Fire Alarm and

Detection System

LF N/A. Existing.

D4040 Sprinkler

Systems

EA As

Required

N/A. Existing.

D502001 Branch Wiring As

Req’d

Keep existing power. Add Multiple isolated ground outlets (as required) for sound, ALS, data, telecommunication and video recording and presentation equipment as per court direction, if required.

D502002 Lighting

Equipment

As

Req’d

Keep existing lighting.

D503001 Telecom. System EA Provide infrastructure to support the telecommunications vendor hired by the Courts.

Infrastructure includes but is not limited to, conduit boxes, pull strings, cable trays, j-hooks, etc.

D503005 Security System EA Refer to locations of USMS required security equipment in Appendix A. Design/Build

Contractor shall provide infrastructure to support

USMS security equipment. The existing security equipment room is located in Room 1609.

Connect security infrastructure to this room as required.

E1010 Commercial

Equipment

EA Video projector, media equipment, and retractable overhead screen and ceiling projector unit(s) will be provided by the Courts – FF & E.

Contractor to provide infrastructure only.

E202003 Freestanding

Furniture

EA Freestanding court furniture. FF & E.

Joseph Chow & Associates, Inc. 8.0 - 399 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Notes: The designer of record shall include in accommodations to display Court selected portraits. The portrait layout shall accommodate additional portraits in the future. The left side of the room is for active judges, right side for retried judges, and the back if for Clerks and Group Judicial Portrait. Examples of the existing room are shown below.

Joseph Chow & Associates, Inc. 8.0 - 400 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

- Page Left Intentionally Blank -

Joseph Chow & Associates, Inc. 8.0 - 401 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

16.2 – SIXTEENTH FLOOR - COURT SHARED SUPPORT –

DELETED WORK SCOPE OPTION H

16.2.1 – Joint Use Operations Room - Option H

ROOM: 1639

Space Characteristics

Function/adjacencies: Joint use Operations room.

Special Dimensions: Existing. 11’-6” ceiling height.

Access: Access from the building corridor.

Courts’ POR Reference: 9.7.1

Special Requirements: Existing courtroom will be decommissioned and used for as a Joint

Use Operations Room.

Uniformat

Section Description Qty Size Specific Requirements

C101001 Fixed Partitions SF N/A. Existing courtroom.

C1020 Interior Doors EA N/A. Existing.

C102007 Interior Door

Hardware

As

Req’d

Existing entry door hardware to remain. Provide mechanical lockset. Coordinate door hardware type and function with the Users. For additional door hardware, see USMS security drawings in

Appendix A.

C3010 Wall Finishes SF Keep existing wall paneling. Patch walls as required to accommodate new work.

C3020 Floor Finishes SF Carpet Tile with attached cushion backing over existing metal subfloor.

Floor Finishes LF Clean base. Patch and repair base damaged by construction.

C3030 Ceiling Finishes SF N/A. Existing.

D304007 Exhaust Systems MBH KW N/A. Existing.

D4010 Identifying

Devices

EA N/A. Existing.

Joseph Chow & Associates, Inc. 8.0 - 402 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Uniformat

Section Description Qty Size Specific Requirements

D4040 Fire Alarm and

Detection System

LF N/A. Existing.

D502001 Sprinkler

Systems

EA As

Required

N/A. Existing.

D502002 Branch Wiring As

Req’d

Keep existing power. Add Multiple isolated ground outlets (as required) for sound, ALS, data, telecommunication and video recording and presentation equipment as per court direction, if required.

D503001 Lighting

Equipment

As

Req’d

Keep existing lighting.

D503005 Security System EA Refer to locations of USMS required security equipment in Appendix A. Design/Build

Contractor shall provide infrastructure to support

USMS security equipment. The existing security equipment room is located in Room 1609.

Connect security infrastructure to this room as required.

E1010 Telecom. System EA Provide infrastructure to support the telecommunications vendor hired by the Courts.

Infrastructure includes but is not limited to, conduit boxes, pull strings, cable trays, j-hooks, etc.

E202003 Freestanding

Furniture

EA Freestanding court furniture. FF & E.