08_Roybal_room_requirements_Pg_117-138.pdf

PDF 101 KB Posted

Attached to
Edward R. Roybal Repair and Alteration Tenant Improvement Prospectus Project
Solicitation number
GS-09P-15-KT-C-0014
Issued by

About this file

Volume 2B Roybal Program Development Study (PDS) 8th Floor Room Requirements (missing pages 8-117 to 8-138)

View the file

Other files

File Type Posted
Roybal_DB_RFP_Amendment_06.pdf PDF
Roybal_DB_RFP_Amendment_05.pdf PDF
Roybal_DB_RFP_Amendment_04.pdf PDF
Roybal_DB_RFP_Amendment_04_14th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_6th_FL_room_reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_revised_bid_sheet.pdf PDF
Roybal_DB_RFP_Amendment_04_9th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_scope_reductions.pdf PDF
Roybal_DB_RFP_Amendment_04_16th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_8th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_15th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_10th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Amendment_04_7th_Fl_Room_Reqs.pdf PDF
Roybal_DB_RFP_Certificate_of_Current_Cost_or_Pricing_Data_(1).pdf PDF
Roybal_DB_RFP_Amendment_03_SF30.pdf PDF
Roybal_DB_bid_sheet_Amendment_03.pdf PDF
Roybal_DB_RFP_PPQ_Amendment_02.docx DOCX document
Roybal_DB_bid_sheet_Amendment_02.pdf PDF
Roybal_DB_RFP_Offeror_Representations_and_Certifications.doc DOC document
Roybal_DB_RFP_Amendment_02_SF30.pdf PDF
Roybal_DB_RFP_Amendment_01.pdf PDF
Roybal_Pre_proposal_Conference_Final_05_28_2015_(1).pdf PDF
Appendix_C_Roybal_Swing_Space_Requirements_and_Move_Matrix_04_06_2015.pdf PDF
Roybal_Fed_Bldg_BER_Final_Submittal.pdf PDF
Roybal_Fed_Bldg_BER_Final_Submittal_Appendices.pdf PDF
AmendmenttoAppendixCSwingSpaceandMovesSOWFinal.doc.pdf PDF
Roybal_DB_RFP_preproposal_attendees.pdf PDF
Volume_3_-_References.pdf PDF
Past_Performance_Questionnaire.docx DOCX document
Volume_2B_Roybal_PDS_and_Appendix.pdf PDF
VOLUME_2A_SCOPE_OF_WORK.pdf PDF
Roybal_DB_1442.pdf PDF
Roybal_DB_RFP_Agreement.pdf PDF
Roybal_DB_Division_1.pdf PDF
Roybal_DB_Solicitation.pdf PDF
Show all 35

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

United States General Service Administration

PROGRAM DEVELOPMENT STUDY – FINAL SUBMITTAL

Edward R. Roybal Federal Building and U.S. Courthouse 8.0 IMPLEMENTATION PLAN

Joseph Chow & Associates, Inc. 8.0 - 117 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY Do not remove this notice. Properly destroy documents when no longer required

ROOM REQUIREMENTS

The Room Requirements tables below represent preliminary information from the User describing general requirements. During the design process, the Design/Build Contractor shall work with the Users to confirm the room requirements and effectively utilize the maximum allowable space.

8.1 EIGHTH FLOOR – USDC GRAND JURY HEARING ROOM

8.1.1 USDC Grand Jury Hearing Room

ROOM: 840, 850

Space Characteristics

Function/adjacencies: USDC: Grand Jury Hearing Room.

Special Dimensions: Existing.

Access: Existing.

Courts’ POR Reference: 4.2.1

Special Requirements: An existing and repurposed USDC courtroom will be used for this space.

Verify specific infrastructure requirements with the court (i.e. electrical, telecom, floor boxes, etc.)

Uniformat Section

Description Qty Size Specific Requirements

C101001 Fixed Partitions SF N/A. Existing courtroom.

C1020 Interior Doors EA N/A. Existing to remain.

C102007 Interior Door Hardware

As Req’d

Existing entry door hardware to remain. Provide mechanical lockset. Coordinate door hardware type and function with the Users. For additional door hardware, see USMS security drawings in Appendix A.

C3010 Wall Finishes SF Keep existing wall paneling. Patch walls as required to accommodate new work. Re-upholster the East wall in Room 840 and the West wall in Room 850.

C3020 Floor Finishes SY 26-28 oz. broadloom carpet over carpet pad.

Joseph Chow & Associates, Inc. 8.0 - 118 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Uniformat Section

Description Qty Size Specific Requirements

C3020 Floor Finishes LF N/A. Existing wood base to remain. Provide new wood base as needed to accommodate new construction.

C3030 Ceiling Finishes SF To remain. Patch and repair as needed to accommodate new work. Fabric on soffits to be replaced with fabric to match existing.

D304007 Exhaust Systems MBH N/A. Existing to remain.

D4010 Fire Alarm and Detection System

LF N/A. Existing to remain.

D4040 Sprinkler Systems

EA N/A. Existing to remain.

D502001 Branch Wiring As Req’d

Distributed convenience outlets, including provisions for cleaning equipment/motor loads.

Coordinate electrical requirements with the AV designer, USMS, ALS system, and court staff.

Multiple isolated ground outlets (as required) for sound, ALS, data, telecommunication and video recording and presentation equipment as per court direction. Conduit and boxes for a loudspeaker sound system allowing audio inputs from video or other projection equipment. One MATV outlet. Provide conduit and outlet boxes for video conferencing system. Provide conduit pathway to A/V closet.

Floor boxes shall be flush mounted with carpet covered or metal inserts. Provide connections for voice, data, and power within the floor box below the surface of the floor. Provide power for wall mounted flat screen presentation monitor.

Electrical outlets or junction boxes will be required at the U.S. Attorney station, grand jury forepersons and secretary stations, court report station, jury and witness boxes judge’s bench, jury box, and witness stand.

D502002 Lighting Equipment

As Req’d

N/A. Existing to remain.

Joseph Chow & Associates, Inc. 8.0 - 119 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Uniformat Section

Description Qty Size Specific Requirements

D503001 Telecom. System EA Provide infrastructure to support court-hired telecommunications vendor. Infrastructure includes but is not limited to, conduit boxes, pull strings, cable trays, j-hooks, etc.

Provide conduit from Jury Assembly Room 740 to Room 790 to provide connectivity of audio and video between the two rooms.

D503005 Security System EA Refer to locations of USMS required security equipment in Appendix A. Design/Build Contractor shall provide infrastructure to support USMS security equipment. The existing security equipment room is located in Room 809.

Connect security infrastructure to this room as required.

E1010 Commercial Equipment

EA Video projector, media equipment, and retractable overhead screen and ceiling projector unit(s) will be provided by the Courts – FF & E.

Contractor to provide infrastructure only.

E202003 Freestanding Furniture

EA Freestanding furniture. FF & E.

F2010 Building Demolition

EA Remove existing spectator seating, spectator railing, and jury box. Salvage and store spectator seating for future re-use. Judge’s bench to remain.

Joseph Chow & Associates, Inc. 8.0 - 120 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

- Page Left Intentionally Blank -

Joseph Chow & Associates, Inc. 8.0 - 121 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

8.1.2 USDC Security

ROOMS: 850-01

Function/adjacencies: USDC: Security.

Special Dimensions: N/A.

Access: Access from existing corridor.

Courts’ POR Reference: N/A.

Special Requirements:

Uniformat Section

Description Qty Size Specific Requirements

C101002 Fixed Partitions SF N/A. Existing to remain.

C1020 Interior Doors EA N/A. Existing to remain.

C102007 Interior Door Hardware

As Req’d

N/A. Existing to remain.

C3010 Wall Finishes SF N/A. Existing to remain.

C3020 Floor Finishes SF N/A. Existing to remain.

C3020 Floor Finishes LF N/A. Existing to remain.

C3030 Ceiling Finishes SF N/A. Existing to remain.

D304007 Exhaust Systems MBH N/A. Existing to remain.

D4010 Fire Alarm and Detection System

LF N/A. Existing to remain.

D4040 Sprinkler Systems

EA N/A. Existing to remain.

D502001 Branch Wiring As Req’d

Distributed convenience outlets, including provisions for cleaning equipment/motor loads.

Min. one quadriplex receptacle (general use).

Duplex outlet(s), isolated ground- two minimum.

D502002 Lighting Equipment

As

N/A. Existing to remain.

Joseph Chow & Associates, Inc. 8.0 - 122 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Uniformat Section

Description Qty Size Specific Requirements

D503001 Telecom. System Provide infrastructure to support court-hired telecommunications vendor. Infrastructure includes but is not limited to, conduit boxes, pull strings, cable trays, j-hooks, etc.

D503005 Security System EA Refer to locations of USMS required security equipment in Appendix A. Design/Build Contractor shall provide infrastructure to support USMS security equipment. The existing security equipment room is located in Room 809.

Connect security infrastructure to this room as required.

E202003 Freestanding

EA Freestanding office furniture. FF & E.

Joseph Chow & Associates, Inc. 8.0 - 123 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

8.1.3 USDC Vestibule – Base Scope of Work and Option D

Room: 857

Function/adjacencies: USDC: Vestibule.

Special Dimensions: Provide 9’-0” min. ceiling height.

Access: Access from the Sallyport.

Courts’ POR Reference: N/A.

Special Requirements: A portion of work in this room shall be completed as part of the BASE

SCOPE OF WORK.

Uniformat Section

Description Qty Size Specific Requirements

C101001 Fixed Partitions SF N/A. Existing to remain.

C1020 Interior Doors EA Building standard. Provide a new door from the Sallyport to the Vestibule and from the Vestibule into the Jury Lounge.

Existing door leading to the secure corridor shall be locked in place – COMPLETED UNDER

BASE SCOPE OF WORK

C102007 Interior Door Hardware

As Req’d

Provide mechanical lockset. Coordinate door hardware type and function with the Users.

C3010 Wall Finishes SF Paint.

C3020 Floor Finishes SF N/A. Existing to remain.

C3020 Floor Finishes LF N/A. Existing to remain.

C3030 Ceiling Finishes SF N/A. Existing to remain.

D304007 Exhaust Systems MBH N/A. Existing to remain.

D4010 Fire Alarm and Detection System

LF N/A. Existing to remain.

D4040 Sprinkler Systems

EA N/A. Existing to remain.

Joseph Chow & Associates, Inc. 8.0 - 124 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Uniformat Section

Description Qty Size Specific Requirements

D502001 Branch Wiring As Req’d

N/A. Existing to remain.

D502002 Lighting Equipment

As Req’d

N/A. Existing to remain.

D503001 Telecom. System EA N/A. Existing to remain.

E202003 Freestanding

Joseph Chow & Associates, Inc. 8.0 - 125 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

8.1.4 USDC Conference Room – Option D

ROOMS: 844

Function/adjacencies: USDC: Conference room.

Special Dimensions: N/A.

Access: Access from the existing corridor.

Courts’ POR Reference: N/A.

Special Requirements:

Uniformat Section

Description Qty Size Specific Requirements

C101002 Fixed Partitions SF N/A. Existing to remain.

C1020 Interior Doors EA N/A. Existing to remain. The existing door leading to the secured corridor shall be locked in place.

C102007 Interior Door Hardware

As Req’d

N/A. Existing to remain.

C3010 Wall Finishes SF Remove existing wall covering and paint.

C3020 Floor Finishes SF 24” x 24” Carpet Tile

C3020 Floor Finishes LF 4” min. Vinyl wall base.

C3030 Ceiling Finishes SF N/A. Existing to remain.

D304007 Exhaust Systems MBH N/A. Existing to remain.

D4010 Fire Alarm and Detection System

LF N/A. Existing to remain.

D4040 Sprinkler Systems

EA N/A. Existing to remain.

D502001 Branch Wiring As Req’d

N/A. Existing to remain.

D502002 Lighting Equipment

As Req’d

D503001 Telecom. System N/A. Existing to remain.

Joseph Chow & Associates, Inc. 8.0 - 126 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Uniformat Section

Description Qty Size Specific Requirements

D503005 Security System EA Refer to locations of USMS required security equipment in Appendix A. Design/Build Contractor shall provide infrastructure to support USMS security equipment. The existing security equipment room is located in Room 809.

Connect security infrastructure to this room as required.

E202003 Freestanding

Joseph Chow & Associates, Inc. 8.0 - 127 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

8.1.5 USDC Jury Lounge – Option D

Room: 841

Function/adjacencies: USDC: Jury Lounge.

Special Dimensions: N/A.

Access: Access from the Vestibule.

Courts’ POR Reference: N/A.

Special Requirements: Existing counter and sink to remain.

Uniformat Section

Description Qty Size Specific Requirements

C101001 Fixed Partitions SF N/A. Existing to remain.

C1020 Interior Doors EA N/A. Existing to remain.

C102007 Interior Door Hardware

As

C3010 Wall Finishes SF Remove existing wall covering and paint.

C3020 Floor Finishes SF 24” x 24” Carpet Tile

C3020 Floor Finishes LF 4” min. Vinyl wall base.

C3030 Ceiling Finishes SF N/A. Existing to remain.

D304007 Exhaust Systems MBH N/A. Existing to remain.

D4010 Fire Alarm and Detection System

LF N/A. Existing to remain.

D4040 Sprinkler Systems

EA N/A. Existing to remain.

D502001 Branch Wiring As Req’d

N/A. Existing to remain.

D502002 Lighting Equipment

As Req’d

N/A. Existing to remain.

D503001 Telecom. System EA N/A. Existing to remain.

E202003 Freestanding

Joseph Chow & Associates, Inc. 8.0 - 128 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

‐ Page Left Intentionally Blank ‐

Joseph Chow & Associates, Inc. 8.0 - 129 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

8.1.6 USDC Witness Room – Option D

ROOMS: 851, 852

Function/adjacencies: USDC: Witness room.

Special Dimensions: Provide 9’-0” min. ceiling height.

Access: Access from existing corridor.

Courts’ POR Reference: N/A.

Special Requirements:

Uniformat Section

Description Qty Size Specific Requirements

C101002 Fixed Partitions SF N/A. Existing to remain.

In Room 851 – Modify the wall to accommodate the relocation of the existing door to meet ABAAS requirements.

C1020 Interior Doors EA N/A. Existing to remain.

In Room 851 – Relocate the existing door to provide the required maneuvering clearances per

ABAAS.

C102007 Interior Door Hardware

As Req’d

N/A. Existing to remain.

C3010 Wall Finishes SF Remove existing wall covering and paint.

In Room 851 – In the wall modified to accommodate the door relocation, remove any wall covering and paint.

C3020 Floor Finishes SF N/A. Existing to remain.

C3020 Floor Finishes LF 24” x 24” Carpet Tile

C3030 Ceiling Finishes SF 4” min. Vinyl wall base.

D304007 Exhaust Systems MBH N/A. Existing to remain.

D4010 Fire Alarm and Detection System

LF N/A. Existing to remain.

Joseph Chow & Associates, Inc. 8.0 - 130 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Uniformat Section

Description Qty Size Specific Requirements

D4040 Sprinkler Systems

EA N/A. Existing to remain.

D502001 Branch Wiring As Req’d

N/A. Existing to remain.

D502002 Lighting Equipment

As Req’d

N/A. Existing to remain.

D503001 Telecom. System N/A. Existing to remain.

E202003 Freestanding

Joseph Chow & Associates, Inc. 8.0 - 131 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

8.1.7 USDC Jury Lounge – Base Scope of Work and Option D

Room: 864

Function/adjacencies: USDC: Jury Lounge.

Special Dimensions: N/A.

Access: Access from the Vestibule.

Courts’ POR Reference: N/A.

Special Requirements: Existing counter and sink to remain. A portion of work in this room shall be completed as part of the BASE SCOPE OF WORK.

Uniformat Section

Description Qty Size Specific Requirements

C101001 Fixed Partitions SF N/A. Existing to remain.

C1020 Interior Doors EA Existing to remain.

Existing door leading to the secure corridor shall be locked in place – COMPLETED UNDER

BASE SCOPE OF WORK

C102007 Interior Door Hardware

As Req’d

N/A. Existing to remain.

C3010 Wall Finishes SF Remove existing wall covering and paint.

C3020 Floor Finishes SF 24” x 24” Carpet Tile

C3020 Floor Finishes LF 4” min. Vinyl wall base.

C3030 Ceiling Finishes SF N/A. Existing to remain.

D304007 Exhaust Systems MBH N/A. Existing to remain.

D4010 Fire Alarm and Detection System

LF N/A. Existing to remain.

D4040 Sprinkler Systems

EA N/A. Existing to remain.

D502001 Branch Wiring As

Joseph Chow & Associates, Inc. 8.0 - 132 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

Uniformat Section

Description Qty Size Specific Requirements

D502002 Lighting Equipment

As Req’d

N/A. Existing to remain.

D503001 Telecom. System EA N/A. Existing to remain.

E202003 Freestanding

Joseph Chow & Associates, Inc. 8.0 - 133 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

8.1.8 USDC Jury Toilet Rooms – Option D

ROOMS: 864-01, 861-02

Function/adjacencies: USDC: Jury Restrooms (Men’s and Women’s)

Special Dimensions: N/A.

Access: Access from the Jury Lounge.

Courts’ POR Reference: N/A.

Special Requirements:

Uniformat Section

Description Qty Size Specific Requirements

C101002 Fixed Partitions SF N/A. Existing to remain.

C1020 Interior Doors EA N/A. Existing to remain.

C102007 Interior Door Hardware

As Req’d

N/A. Existing to remain.

C103002 Toilet Accessories

EA N/A. Existing to remain.

C3010 Wall Finishes SF Paint.

C3020 Floor Finishes SF N/A. Existing to remain. Clean.

C3030 Ceiling Finishes SF N/A. Existing to remain. Clean.

D2010 Plumbing Fixtures

EA N/A. Existing to remain.

D304007 Exhaust Systems MBH N/A. Existing to remain.

D4010 Fire Alarm and Detection System

LF N/A. Existing to remain.

D4040 Sprinkler Systems

EA N/A. Existing to remain.

D502001 Branch Wiring As Req’d

N/A. Existing to remain.

D502002 Lighting Equipment

As

Joseph Chow & Associates, Inc. 8.0 - 134 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

‐ Page Left Intentionally Blank –

Joseph Chow & Associates, Inc. 8.0 - 135 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

8.1.9 USDC Jury Lounge Closet – Option D

ROOM: 864-03

Function/adjacencies: USDC: Closet

Special Dimensions: N/A.

Access: Access from the Jury Lounge.

Courts’ POR Reference: N/A.

Special Requirements:

Uniformat Section

Description Qty Size Specific Requirements

C101002 Fixed Partitions SF N/A. Existing to remain.

C1020 Interior Doors EA N/A. Existing to remain.

C102007 Interior Door Hardware

As Req’d

N/A. Existing to remain.

C3010 Wall Finishes SF N/A. Existing to remain.

C3020 Floor Finishes SF 24” x 24” Carpet tile.

C3020 Floor Finishes LF 4” Vinyl wall base.

C3030 Ceiling Finishes SF N/A. Existing to remain.

D502001 Branch Wiring As Req’d

N/A. Existing to remain.

D502002 Lighting Equipment

As

Joseph Chow & Associates, Inc. 8.0 - 136 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

‐ Page Left Intentionally Blank ‐

Joseph Chow & Associates, Inc. 8.0 - 137 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

8.1.10 USDC Conference Room – Option D

ROOM: 848

Function/adjacencies: USDC: Conference room.

Special Dimensions: N/A.

Access: Access from the Grand Jury Hearing Room Vestibule.

Courts’ POR Reference: N/A.

Special Requirements:

Uniformat Section

Description Qty Size Specific Requirements

C101002 Fixed Partitions SF N/A. Existing to remain.

C1020 Interior Doors EA N/A. Existing to remain.

C102007 Interior Door Hardware

As Req’d

N/A. Existing to remain.

C3010 Wall Finishes SF N/A. Paint.

C3020 Floor Finishes SF 24” x 24” Carpet tile.

C3020 Floor Finishes LF 4” Vinyl wall base.

C3030 Ceiling Finishes SF N/A. Existing to remain.

D502001 Branch Wiring As Req’d

N/A. Existing to remain.

D502002 Lighting Equipment

As Req’d

N/A. Existing to remain.

D503005 Security System EA Refer to locations of USMS required security equipment in Appendix A. Design/Build Contractor shall provide infrastructure to support USMS security equipment. The existing security equipment room is located in Room 809.

Connect security infrastructure to this room as required.

E202003 Freestanding

EA Freestanding furniture. FF & E.

Joseph Chow & Associates, Inc. 8.0 - 138 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY

‐ Page Left Intentionally Blank ‐

File details come from the government source that posted it. Updated .