United States General Service Administration
PROGRAM DEVELOPMENT STUDY – FINAL SUBMITTAL
Edward R. Roybal Federal Building and U.S. Courthouse 8.0 IMPLEMENTATION PLAN
Joseph Chow & Associates, Inc. 8.0 - 117 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY Do not remove this notice. Properly destroy documents when no longer required
ROOM REQUIREMENTS
The Room Requirements tables below represent preliminary information from the User describing general requirements. During the design process, the Design/Build Contractor shall work with the Users to confirm the room requirements and effectively utilize the maximum allowable space.
8.1 EIGHTH FLOOR – USDC GRAND JURY HEARING ROOM
8.1.1 USDC Grand Jury Hearing Room
ROOM: 840, 850
Space Characteristics
Function/adjacencies: USDC: Grand Jury Hearing Room.
Special Dimensions: Existing.
Access: Existing.
Courts’ POR Reference: 4.2.1
Special Requirements: An existing and repurposed USDC courtroom will be used for this space.
Verify specific infrastructure requirements with the court (i.e. electrical, telecom, floor boxes, etc.)
Uniformat Section
Description Qty Size Specific Requirements
C101001 Fixed Partitions SF N/A. Existing courtroom.
C1020 Interior Doors EA N/A. Existing to remain.
C102007 Interior Door Hardware
As Req’d
Existing entry door hardware to remain. Provide mechanical lockset. Coordinate door hardware type and function with the Users. For additional door hardware, see USMS security drawings in Appendix A.
C3010 Wall Finishes SF Keep existing wall paneling. Patch walls as required to accommodate new work. Re-upholster the East wall in Room 840 and the West wall in Room 850.
C3020 Floor Finishes SY 26-28 oz. broadloom carpet over carpet pad.
Joseph Chow & Associates, Inc. 8.0 - 118 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
Uniformat Section
Description Qty Size Specific Requirements
C3020 Floor Finishes LF N/A. Existing wood base to remain. Provide new wood base as needed to accommodate new construction.
C3030 Ceiling Finishes SF To remain. Patch and repair as needed to accommodate new work. Fabric on soffits to be replaced with fabric to match existing.
D304007 Exhaust Systems MBH N/A. Existing to remain.
D4010 Fire Alarm and Detection System
LF N/A. Existing to remain.
D4040 Sprinkler Systems
EA N/A. Existing to remain.
D502001 Branch Wiring As Req’d
Distributed convenience outlets, including provisions for cleaning equipment/motor loads.
Coordinate electrical requirements with the AV designer, USMS, ALS system, and court staff.
Multiple isolated ground outlets (as required) for sound, ALS, data, telecommunication and video recording and presentation equipment as per court direction. Conduit and boxes for a loudspeaker sound system allowing audio inputs from video or other projection equipment. One MATV outlet. Provide conduit and outlet boxes for video conferencing system. Provide conduit pathway to A/V closet.
Floor boxes shall be flush mounted with carpet covered or metal inserts. Provide connections for voice, data, and power within the floor box below the surface of the floor. Provide power for wall mounted flat screen presentation monitor.
Electrical outlets or junction boxes will be required at the U.S. Attorney station, grand jury forepersons and secretary stations, court report station, jury and witness boxes judge’s bench, jury box, and witness stand.
D502002 Lighting Equipment
As Req’d
N/A. Existing to remain.
Joseph Chow & Associates, Inc. 8.0 - 119 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
Uniformat Section
Description Qty Size Specific Requirements
D503001 Telecom. System EA Provide infrastructure to support court-hired telecommunications vendor. Infrastructure includes but is not limited to, conduit boxes, pull strings, cable trays, j-hooks, etc.
Provide conduit from Jury Assembly Room 740 to Room 790 to provide connectivity of audio and video between the two rooms.
D503005 Security System EA Refer to locations of USMS required security equipment in Appendix A. Design/Build Contractor shall provide infrastructure to support USMS security equipment. The existing security equipment room is located in Room 809.
Connect security infrastructure to this room as required.
E1010 Commercial Equipment
EA Video projector, media equipment, and retractable overhead screen and ceiling projector unit(s) will be provided by the Courts – FF & E.
Contractor to provide infrastructure only.
E202003 Freestanding Furniture
EA Freestanding furniture. FF & E.
F2010 Building Demolition
EA Remove existing spectator seating, spectator railing, and jury box. Salvage and store spectator seating for future re-use. Judge’s bench to remain.
Joseph Chow & Associates, Inc. 8.0 - 120 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
- Page Left Intentionally Blank -
Joseph Chow & Associates, Inc. 8.0 - 121 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
8.1.2 USDC Security
ROOMS: 850-01
Function/adjacencies: USDC: Security.
Special Dimensions: N/A.
Access: Access from existing corridor.
Courts’ POR Reference: N/A.
Special Requirements:
Uniformat Section
Description Qty Size Specific Requirements
C101002 Fixed Partitions SF N/A. Existing to remain.
C1020 Interior Doors EA N/A. Existing to remain.
C102007 Interior Door Hardware
As Req’d
N/A. Existing to remain.
C3010 Wall Finishes SF N/A. Existing to remain.
C3020 Floor Finishes SF N/A. Existing to remain.
C3020 Floor Finishes LF N/A. Existing to remain.
C3030 Ceiling Finishes SF N/A. Existing to remain.
D304007 Exhaust Systems MBH N/A. Existing to remain.
D4010 Fire Alarm and Detection System
LF N/A. Existing to remain.
D4040 Sprinkler Systems
EA N/A. Existing to remain.
D502001 Branch Wiring As Req’d
Distributed convenience outlets, including provisions for cleaning equipment/motor loads.
Min. one quadriplex receptacle (general use).
Duplex outlet(s), isolated ground- two minimum.
D502002 Lighting Equipment
As
N/A. Existing to remain.
Joseph Chow & Associates, Inc. 8.0 - 122 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
Uniformat Section
Description Qty Size Specific Requirements
D503001 Telecom. System Provide infrastructure to support court-hired telecommunications vendor. Infrastructure includes but is not limited to, conduit boxes, pull strings, cable trays, j-hooks, etc.
D503005 Security System EA Refer to locations of USMS required security equipment in Appendix A. Design/Build Contractor shall provide infrastructure to support USMS security equipment. The existing security equipment room is located in Room 809.
Connect security infrastructure to this room as required.
E202003 Freestanding
EA Freestanding office furniture. FF & E.
Joseph Chow & Associates, Inc. 8.0 - 123 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
8.1.3 USDC Vestibule – Base Scope of Work and Option D
Room: 857
Function/adjacencies: USDC: Vestibule.
Special Dimensions: Provide 9’-0” min. ceiling height.
Access: Access from the Sallyport.
Courts’ POR Reference: N/A.
Special Requirements: A portion of work in this room shall be completed as part of the BASE
SCOPE OF WORK.
Uniformat Section
Description Qty Size Specific Requirements
C101001 Fixed Partitions SF N/A. Existing to remain.
C1020 Interior Doors EA Building standard. Provide a new door from the Sallyport to the Vestibule and from the Vestibule into the Jury Lounge.
Existing door leading to the secure corridor shall be locked in place – COMPLETED UNDER
BASE SCOPE OF WORK
C102007 Interior Door Hardware
As Req’d
Provide mechanical lockset. Coordinate door hardware type and function with the Users.
C3010 Wall Finishes SF Paint.
C3020 Floor Finishes SF N/A. Existing to remain.
C3020 Floor Finishes LF N/A. Existing to remain.
C3030 Ceiling Finishes SF N/A. Existing to remain.
D304007 Exhaust Systems MBH N/A. Existing to remain.
D4010 Fire Alarm and Detection System
LF N/A. Existing to remain.
D4040 Sprinkler Systems
EA N/A. Existing to remain.
Joseph Chow & Associates, Inc. 8.0 - 124 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
Uniformat Section
Description Qty Size Specific Requirements
D502001 Branch Wiring As Req’d
N/A. Existing to remain.
D502002 Lighting Equipment
As Req’d
N/A. Existing to remain.
D503001 Telecom. System EA N/A. Existing to remain.
E202003 Freestanding
Joseph Chow & Associates, Inc. 8.0 - 125 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
8.1.4 USDC Conference Room – Option D
ROOMS: 844
Function/adjacencies: USDC: Conference room.
Special Dimensions: N/A.
Access: Access from the existing corridor.
Courts’ POR Reference: N/A.
Special Requirements:
Uniformat Section
Description Qty Size Specific Requirements
C101002 Fixed Partitions SF N/A. Existing to remain.
C1020 Interior Doors EA N/A. Existing to remain. The existing door leading to the secured corridor shall be locked in place.
C102007 Interior Door Hardware
As Req’d
N/A. Existing to remain.
C3010 Wall Finishes SF Remove existing wall covering and paint.
C3020 Floor Finishes SF 24” x 24” Carpet Tile
C3020 Floor Finishes LF 4” min. Vinyl wall base.
C3030 Ceiling Finishes SF N/A. Existing to remain.
D304007 Exhaust Systems MBH N/A. Existing to remain.
D4010 Fire Alarm and Detection System
LF N/A. Existing to remain.
D4040 Sprinkler Systems
EA N/A. Existing to remain.
D502001 Branch Wiring As Req’d
N/A. Existing to remain.
D502002 Lighting Equipment
As Req’d
D503001 Telecom. System N/A. Existing to remain.
Joseph Chow & Associates, Inc. 8.0 - 126 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
Uniformat Section
Description Qty Size Specific Requirements
D503005 Security System EA Refer to locations of USMS required security equipment in Appendix A. Design/Build Contractor shall provide infrastructure to support USMS security equipment. The existing security equipment room is located in Room 809.
Connect security infrastructure to this room as required.
E202003 Freestanding
Joseph Chow & Associates, Inc. 8.0 - 127 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
8.1.5 USDC Jury Lounge – Option D
Room: 841
Function/adjacencies: USDC: Jury Lounge.
Special Dimensions: N/A.
Access: Access from the Vestibule.
Courts’ POR Reference: N/A.
Special Requirements: Existing counter and sink to remain.
Uniformat Section
Description Qty Size Specific Requirements
C101001 Fixed Partitions SF N/A. Existing to remain.
C1020 Interior Doors EA N/A. Existing to remain.
C102007 Interior Door Hardware
As
C3010 Wall Finishes SF Remove existing wall covering and paint.
C3020 Floor Finishes SF 24” x 24” Carpet Tile
C3020 Floor Finishes LF 4” min. Vinyl wall base.
C3030 Ceiling Finishes SF N/A. Existing to remain.
D304007 Exhaust Systems MBH N/A. Existing to remain.
D4010 Fire Alarm and Detection System
LF N/A. Existing to remain.
D4040 Sprinkler Systems
EA N/A. Existing to remain.
D502001 Branch Wiring As Req’d
N/A. Existing to remain.
D502002 Lighting Equipment
As Req’d
N/A. Existing to remain.
D503001 Telecom. System EA N/A. Existing to remain.
E202003 Freestanding
Joseph Chow & Associates, Inc. 8.0 - 128 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
‐ Page Left Intentionally Blank ‐
Joseph Chow & Associates, Inc. 8.0 - 129 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
8.1.6 USDC Witness Room – Option D
ROOMS: 851, 852
Function/adjacencies: USDC: Witness room.
Special Dimensions: Provide 9’-0” min. ceiling height.
Access: Access from existing corridor.
Courts’ POR Reference: N/A.
Special Requirements:
Uniformat Section
Description Qty Size Specific Requirements
C101002 Fixed Partitions SF N/A. Existing to remain.
In Room 851 – Modify the wall to accommodate the relocation of the existing door to meet ABAAS requirements.
C1020 Interior Doors EA N/A. Existing to remain.
In Room 851 – Relocate the existing door to provide the required maneuvering clearances per
ABAAS.
C102007 Interior Door Hardware
As Req’d
N/A. Existing to remain.
C3010 Wall Finishes SF Remove existing wall covering and paint.
In Room 851 – In the wall modified to accommodate the door relocation, remove any wall covering and paint.
C3020 Floor Finishes SF N/A. Existing to remain.
C3020 Floor Finishes LF 24” x 24” Carpet Tile
C3030 Ceiling Finishes SF 4” min. Vinyl wall base.
D304007 Exhaust Systems MBH N/A. Existing to remain.
D4010 Fire Alarm and Detection System
LF N/A. Existing to remain.
Joseph Chow & Associates, Inc. 8.0 - 130 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
Uniformat Section
Description Qty Size Specific Requirements
D4040 Sprinkler Systems
EA N/A. Existing to remain.
D502001 Branch Wiring As Req’d
N/A. Existing to remain.
D502002 Lighting Equipment
As Req’d
N/A. Existing to remain.
D503001 Telecom. System N/A. Existing to remain.
E202003 Freestanding
Joseph Chow & Associates, Inc. 8.0 - 131 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
8.1.7 USDC Jury Lounge – Base Scope of Work and Option D
Room: 864
Function/adjacencies: USDC: Jury Lounge.
Special Dimensions: N/A.
Access: Access from the Vestibule.
Courts’ POR Reference: N/A.
Special Requirements: Existing counter and sink to remain. A portion of work in this room shall be completed as part of the BASE SCOPE OF WORK.
Uniformat Section
Description Qty Size Specific Requirements
C101001 Fixed Partitions SF N/A. Existing to remain.
C1020 Interior Doors EA Existing to remain.
Existing door leading to the secure corridor shall be locked in place – COMPLETED UNDER
BASE SCOPE OF WORK
C102007 Interior Door Hardware
As Req’d
N/A. Existing to remain.
C3010 Wall Finishes SF Remove existing wall covering and paint.
C3020 Floor Finishes SF 24” x 24” Carpet Tile
C3020 Floor Finishes LF 4” min. Vinyl wall base.
C3030 Ceiling Finishes SF N/A. Existing to remain.
D304007 Exhaust Systems MBH N/A. Existing to remain.
D4010 Fire Alarm and Detection System
LF N/A. Existing to remain.
D4040 Sprinkler Systems
EA N/A. Existing to remain.
D502001 Branch Wiring As
Joseph Chow & Associates, Inc. 8.0 - 132 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
Uniformat Section
Description Qty Size Specific Requirements
D502002 Lighting Equipment
As Req’d
N/A. Existing to remain.
D503001 Telecom. System EA N/A. Existing to remain.
E202003 Freestanding
Joseph Chow & Associates, Inc. 8.0 - 133 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
8.1.8 USDC Jury Toilet Rooms – Option D
ROOMS: 864-01, 861-02
Function/adjacencies: USDC: Jury Restrooms (Men’s and Women’s)
Special Dimensions: N/A.
Access: Access from the Jury Lounge.
Courts’ POR Reference: N/A.
Special Requirements:
Uniformat Section
Description Qty Size Specific Requirements
C101002 Fixed Partitions SF N/A. Existing to remain.
C1020 Interior Doors EA N/A. Existing to remain.
C102007 Interior Door Hardware
As Req’d
N/A. Existing to remain.
C103002 Toilet Accessories
EA N/A. Existing to remain.
C3010 Wall Finishes SF Paint.
C3020 Floor Finishes SF N/A. Existing to remain. Clean.
C3030 Ceiling Finishes SF N/A. Existing to remain. Clean.
D2010 Plumbing Fixtures
EA N/A. Existing to remain.
D304007 Exhaust Systems MBH N/A. Existing to remain.
D4010 Fire Alarm and Detection System
LF N/A. Existing to remain.
D4040 Sprinkler Systems
EA N/A. Existing to remain.
D502001 Branch Wiring As Req’d
N/A. Existing to remain.
D502002 Lighting Equipment
As
Joseph Chow & Associates, Inc. 8.0 - 134 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
‐ Page Left Intentionally Blank –
Joseph Chow & Associates, Inc. 8.0 - 135 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
8.1.9 USDC Jury Lounge Closet – Option D
ROOM: 864-03
Function/adjacencies: USDC: Closet
Special Dimensions: N/A.
Access: Access from the Jury Lounge.
Courts’ POR Reference: N/A.
Special Requirements:
Uniformat Section
Description Qty Size Specific Requirements
C101002 Fixed Partitions SF N/A. Existing to remain.
C1020 Interior Doors EA N/A. Existing to remain.
C102007 Interior Door Hardware
As Req’d
N/A. Existing to remain.
C3010 Wall Finishes SF N/A. Existing to remain.
C3020 Floor Finishes SF 24” x 24” Carpet tile.
C3020 Floor Finishes LF 4” Vinyl wall base.
C3030 Ceiling Finishes SF N/A. Existing to remain.
D502001 Branch Wiring As Req’d
N/A. Existing to remain.
D502002 Lighting Equipment
As
Joseph Chow & Associates, Inc. 8.0 - 136 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
‐ Page Left Intentionally Blank ‐
Joseph Chow & Associates, Inc. 8.0 - 137 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
8.1.10 USDC Conference Room – Option D
ROOM: 848
Function/adjacencies: USDC: Conference room.
Special Dimensions: N/A.
Access: Access from the Grand Jury Hearing Room Vestibule.
Courts’ POR Reference: N/A.
Special Requirements:
Uniformat Section
Description Qty Size Specific Requirements
C101002 Fixed Partitions SF N/A. Existing to remain.
C1020 Interior Doors EA N/A. Existing to remain.
C102007 Interior Door Hardware
As Req’d
N/A. Existing to remain.
C3010 Wall Finishes SF N/A. Paint.
C3020 Floor Finishes SF 24” x 24” Carpet tile.
C3020 Floor Finishes LF 4” Vinyl wall base.
C3030 Ceiling Finishes SF N/A. Existing to remain.
D502001 Branch Wiring As Req’d
N/A. Existing to remain.
D502002 Lighting Equipment
As Req’d
N/A. Existing to remain.
D503005 Security System EA Refer to locations of USMS required security equipment in Appendix A. Design/Build Contractor shall provide infrastructure to support USMS security equipment. The existing security equipment room is located in Room 809.
Connect security infrastructure to this room as required.
E202003 Freestanding
EA Freestanding furniture. FF & E.
Joseph Chow & Associates, Inc. 8.0 - 138 PROPERTY OF THE UNITED STATES GOVERNMENT – FOR OFFICE USE ONLY
‐ Page Left Intentionally Blank ‐