FEGMC0~1.PDF

PDF 586 KB Posted

Attached to
Multiple Award Construction Contract (MACC) Italy Federal contract opportunity
Solicitation number
FA568219RA001
Issued by
Department of the Air Force United States Air Forces in Europe - Air Forces Africa

About this file

This is a draft request for proposal for an indefinite delivery, indefinite quantity multiple award construction contract for design-build construction services in Italy. The scope of work includes projects across multiple trades such as grading, utilities, painting, roofing, building construction, electrical work, HVAC, fire suppression, fuel systems, generators, communications, and abatement. The period of performance is one base year with four option years. The minimum guaranteed amount is 2,500 Euro and the maximum total value is estimated at 96 million dollars. Individual task order minimum is 2,500 dollars and maximum is 7 million dollars. Interested parties should submit comments on the draft attachments by April 19, 2019. The solicitation will be issued through FBO and awarded contracts will primarily perform work at Aviano Air Base in Italy but may include other locations in the country.

Attachment 10 ASHE 18-1025 Technical Specifications (Seed Project) Rev.1 Part 2

View the file

Other files for this federal contract opportunity

Other files attached to Multiple Award Construction Contract (MACC) Italy, newest first.
File Type Posted
Attachment 1 Section L REV 03.pdf PDF
Solicitation_Amendment_FA568219RA0010004_SF_30.pdf PDF
JA6P70~1.PDF PDF
ATTACH~3.PDF PDF
ATTACH~2.PDF PDF
Solicitation_Amendment_FA568219RA0010002_SF_30.pdf PDF
Attachment_1_Section_L_REV_02.pdf PDF
Attachment_9_Questions_and_Answers.docx DOCX document
ATTACH~3.DOC DOC document
ANNEX_S_-_STRUCTURAL_Part11.pdf PDF
ANNEX_E_-_ELECTRICAL_Part5.pdf PDF
ANNEX_E_-_ELECTRICAL_Part10.pdf PDF
ANNEX_S_-_STRUCTURAL_Part8.pdf PDF
ANNEX_E_-_ELECTRICAL_Part8.pdf PDF
ANNEX_S_-_STRUCTURAL_Part1.pdf PDF
ANNEX_E_-_ELECTRICAL_Part2.pdf PDF
ANNEX_E_-_ELECTRICAL_Part4.pdf PDF
Attachment_10_ASHE_18-1025_TS__Part6_Part5_Part2.pdf PDF
Attachment_10_ASHE_18-1025_TS__(Seed_project)_Part3.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part10_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part1_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part17.pdf PDF
Attachment_13_Physical_Data.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part6.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part7.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part2_Part5.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part7.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part4.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_Project)__Part1.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part5.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part15_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part13_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part15_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part1_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part2_Part2.pdf PDF
Attachment_10_ASHE_18-1025_TS__(Seed_project)_Part5.pdf PDF
Solicitation_-_FA568219RA001.pdf PDF
Attachment_3_CEN_-MACC_SOW_v3.pdf PDF
Attachment_2_Section_M.pdf PDF
Attachment_8_Client_Authorization_Letter.pdf PDF
Attachment_9_Questions_and_Answers.pdf PDF
Questions_and_Answers_draft_RFP_FA568219RA0001_May_03_2019.pdf PDF
Questions_and_Answers_draft_RFP_FA568219RA0001_May_02_2019.pdf PDF
(draft)_Attachment_6_Experience_Overview_Sheet.pdf PDF
(draft)_Attachment_9_Client_Authorization_Letter.pdf PDF
(draft)_Attachment_1_Section_L__20_March.pdf PDF
(draft)_Attachment_3_General_Requirements_and_Provisions.pdf PDF
(draft)_Attachment_10_Questions_and_Answers.pdf PDF
(draft)_Attachment_7_Experience_Information_Sheet.pdf PDF
Show all 50

Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

RENOVATE/EXPAND FAC. 939 ASHE18-1025

FINAL (100% design) SECTION 05500/R Page 77

Paragraph 1.2:

Delete “UNI 4634” and replace with “UNI EN ISO 15607 and any other regarding norm”.

Paragraph 1.3.1:

Delete:

a. Canopy

b. Panels for air handling unit casing

d. Fire extinguisher cabinet

e. Handrails

f. Steel louvers

Paragraph 1.3.2:

a. Canopy

b. Panels for air handling unit casing

d. Fire extinguisher cabinet

e. Handrails

f. Steel louvers

Paragraph 1.5:

Delete “UNI 4634” and replace with “UNI EN ISO 9606-1”.

Paragraph 2.1:

Delete “Law 1086” and replace with “D.M. 16 Feb 2007”.

Paragraph 2.1.8.2:

Add:

UNI EN ISO 4017 and UNI EN ISO 4018

2.1.8.3 Bolts and Studs

UNI EN ISO 898-1.

2.1.8.4 Screws

Provide hexagon head screws to conform to UNI EN ISO 4017. Slotted panhead tapping screws EN ISO 1481 slotted raised.

2.1.8.5 Washers

Provide plain washers to conform to UNI EN ISO 887 and UNI EN ISO 7089.

Provide comparable lock washers.

-- End of Section --

FINAL (100% design) SECTION 07112/R Page 78

SECTION 07112/R

BITUMINOUS DAMPPROOFING

Paragraph 1.0:

UNI 13108-6 (2006) Bituminous mixtures – Materials specifications - Part 6: Mastic Asphalt

UNI EN 13416 (2003) Flexible sheets for waterproofing -

Bitumen, plastic and rubber sheets for roof waterproofing - Rules for sampling

UNI EN 1849-1 (2002) Flexible sheets for waterproofing -

Determination of thickness and mass per unit area - Part 1: Bitumen sheets for roof waterproofing

D.M. 26 Jun 1984 Classification of Resistance to Fire and

Ratification of Materials for Fire

Prevention.

D.M. 15 Mar 2005 Classification of fire resistance of materials used in construction. Integrates

Italian requirements into the European classification system.

D.M. 16 Feb 2007 Classification of fire resistance of construction material and elements

D.M. 09 Mar 2007 Performance of resistance to fire in the activities subject to control by the

National Fire Department stabilizing criteria for determining the fire resistance performance.

UNI 8202-25 (1984) Building - Water proof sheets -

Determination of fire reaction

UNI 8490-3 (1984) Aqueous dispersions of polymers and copolymers - Test methods - Determination of viscosity by the Brookfield rotational viscometer

UNI 8898-3 (1987) Polimeric water proof sheets -

Elastomeric reinforced sheets -

Characteristics and acceptance limits

UNI EN 13707 (2013) Flexible sheets for waterproofing -

Reinforced bitumen sheets for roof waterproofing - Definitions and characteristics

-- End of Section –-

FINAL (100% design) SECTION 07220/R Page 79

Section 07220/R

ROOF INSULATION

Paragraph 1.1:

UNI 4157 (1987) Building. Bitumen for roofing.

Sampling and acceptance limits.

UNI 6541 (1969) Glass fiber materials for thermal and acoustical insulation. Resin bonded slabs. Determination of the Compressive

Requirements.

UNI 7891 (1978) Insulating materials. Determination of thermal conductivity by means of the heat flow meter method.

UNI EN 13165 (2003) Thermal insulation products for buildings - Factory made rigid polyurethane foam (PUR) products – Specification.

UNI EN 12086 (1999) Thermal insulating products for building applications - Determination of water vapor transmission properties.

UNI EN 1604 (1999) Thermal insulating products for dimensional stability under specified temperature and humidity conditions.

UNI EN 826 (1998) Thermal insulating products for compression behavior.

UNI EN ISO 845 (1997) Cellular plastics and rubbers.

Determination of apparent (bulk) density.

UNI EN ISO 844 (2014) Rigid cellular plastics -

Determination of compression properties

UNI EN ISO 845 (2009) Cellular plastics and rubbers -

Determination of apparent density

ISO 1209-1 (2007) Rigid cellular plastics -

Determination of flexural properties -

Basic bending test

ISO 1663 (2007) Rigid cellular plastics -

Determination of water vapour transmission properties

ISO 2796 (1986) Cellular Plastics, Rigid – Test for

Dimensional Stability

FINAL (100% design) SECTION 07220/R Page 80

ISO 2896 (2001) Rigid Cellular Plastics -

Determination of Water Absorption

ISO 4898 (2010) ( Rigid cellular plastics - Thermal insulation products for buildings -

Specifications

ISO 7616 (1986) Cellular plastics, rigid -

Determination of compressive creep under specified load and temperature conditions

ISO 8145 (1994) Thermal Insulation - Mineral Wool

Board for Over-Deck Insulation of Roofs -

Specification

ISO 8301 (1991) Thermal Insulation - Determination of Steady-State Thermal Resistance and

Related Properties – Heat Flow Meter

Apparatus

D.M. 26 Jun 1984 Classification of Resistance to Fire and

Ratification of Materials for Fire

Prevention classification system.

D.M. 09 Mar 2007 Performance of resistance to fire in the activities subject to control by the

National Fire Department stabilizing criteria for determining the fire resistance performance

D.Lgs. 09 Apr 2008, n.81 Unified Text, Safety Regulations;

realization of Article 1 of the Law 3 Aug

2007, n. 123, in the area of safeguarding the health and safety on the work place.

FINAL (100% design) SECTION 07231/R Page 81

Section 07231/R

WALL INSULATION

Paragraph 1.1:

Delete:

UNI 6547 (1985) Mineral Fiber Boards for Thermal and

Acoustical Insulation. Determination of

Flexibility Index.

UNI 6823 (1998) Mineral Wool Products for Thermal and Acoustical Insulation - Determination of Non-Fibrous Material Content -

Floatation Method.

Add

UNI EN 822 (2013) Thermal Insulating Products for

Building Applications - Determination of

Length and Width

UNI EN 823 (2013) Thermal Insulating Products for

Building Applications - Determination of

Thickness

UNI EN 824 (2013) Thermal Insulating Products for

Building Applications - Determination of

Squareness

UNI EN 825 (2013) Thermal Insulating Products for

Building Applications - Determination of

Flatness

UNI EN 826 (2013) Thermal Insulating Products for

Building Applications - Determination of

Compression Behavior

UNI EN ISO 6946 (2008) Building Components and Building

Elements - Thermal Resistance - Calculation

Method

UNI EN ISO 7345 (1999) Thermal Insulation – Physical

Quantities and Definitions

UNI EN ISO 9229 (2008) Thermal insulation – Vocabulary

UNI EN 13162 (2013) Thermal insulation for construction

- Mineral Wood (MW) product, factory produced - Specifications

D.Lgs. 09 Apr 2008, n.81 Unified Text, Safety Regulations;

realization of Article 1 of the Law 3 Aug

FINAL (100% design) SECTION 07231/R Page 82

D.M. 15 Mar 2005 Classification of fire resistance of materials used in construction. Integrates

Italian requirements

D.M. 16 Feb 2007 Classification of fire resistance of construction material and elements

D.M. 09 Mar 2007 Performance of resistance to fire in the activities subject to control by the

National Fire Department stabilizing criteria for determining the fire resistance performance.

D.M. 26 Jun 1984 (Classification of Resistance to Fire and

Ratification of Materials for Fire

Prevention.

FINAL (100% design) SECTION 07321/R Page 83

SECTION 07321/R

CLAY ROOFING TILE

Paragraph 1.1:

Add:

ITALIAN LAWS AND NORMS

D.Lgs. 09 Apr 2008, n.81 Unified Text, Safety Regulations;

realization of Article 1 of the Law 03 Aug

2007, n. 123, in the area of safeguarding the health and safety on the work place

Delete:

ITALIAN/EUROPEAN HARMONIZATION STANDARDS (UNI EN)(UNI ENV)(UNI EN ISO)

UNI 196.1-7 (1996) Test Method of Concrete.

UNI EN 413-1 (1996) Masonry Cement - Part 1 –

Specification.

UNI EN 413-2 (1996) Masonry Cement - Part 2 - Test

Methods.

UNI EN 538 (1997) Clay Roofing Tiles for Discontinuous

Laying - Flexural Strength Test.

UNI EN 539-1 (1997) Clay Roofing Tiles for Discontinuous

Laying - Determination of Physical

Characteristics. Part 1 - Impermeability

Test.

ITALIAN NATIONAL INSTITUTE FOR THE UNIFICATION OF STANDARDS (UNI)

PUBLICATIONS:

UNI 8635-1 (1984) Buildings - Tests of Products for

Discontinuous Roofing - Part 1 - Appearance and Preparation Examination.

UNI 8635-2 (1984) Buildings - Tests of Products for

Discontinuous Roofing - Part 2 -

Determination of Length.

UNI 8635-3 (1984) Buildings - Tests of Products for

Discontinuous Roofing - Part 3 -

Determination of Width.

UNI 8626 (1984) Buildings - Products for

Discontinuous Roofing; Characteristics, Sampling Plan and Limits of Acceptance.

UNI 9460 (1989) Discontinuous Roofing - Practical

Instruction Code for the Design and

Execution of Clay and Cement Tile Roofing.

ITALIAN / EUROPEAN HARMONIZATION STANDARDS (EN, UNI EN, ISO)

FINAL (100% design) SECTION 07321/R Page 84

UNI EN 196-1 (2016) Methods of testing cement - Part 1:

Determination of strength

UNI EN 196-2 (2013) Method of testing cement - Part 2:

Chemical analysis of cement

UNI EN 196-3 (2017) Methods of testing cement - Part 3:

Determination of setting times and soundness

UNI EN 196-4 (2008) Methods of testing cement - Part 4:

Quantitative determination of constituents

UNI EN 196-5 (2011) Methods of testing cement - Part 5:

Pozzolanicity test for pozzolanic cement

UNI EN 196-6 (2010) Methods of testing cement - Part 6:

Determination of fineness

UNI EN 196-7 (2010) Methods of testing cement - Part 7:

Methods of taking and preparing samples of cement

UNI EN 413 (2011) Masonry cement - Part 1: Composition, specifications and conformity criteria

UNI EN 538 (1997) Clay Roofing Tiles for Discontinuous

Laying - Flexural Strength Test

UNI EN 539-1 (2006) Clay roofing tiles for discontinuous laying - Determination of physical characteristics - Part 1: Impermeability test

UNI EN 539-2 (2013) Clay roofing tiles for discontinuous laying - Determination of physical characteristics - Part 2: Test for frost resistance

UNI EN 1024 (2012) Clay roofing tiles for discontinuous laying - Determination of geometric characteristics

UNI EN 1304 (2013) Clay roofing tiles and fittings -

Product definitions and specifications

UNI 9460 (2008) Discontinuous Roofing - Practical

Instruction Code for the Design and

Execution of Clay and Cement Tile Roofing

UNI EN 14437 (2005) Determination of the uplift resistance of installed clay or concrete tiles for roofing - Roof system test method

UNI CEN/TS 15087 (2006) Determination of the uplift resistance of installed clay and concrete interlocking tiles for roofing - Test method for mechanical fasteners

FINAL (100% design) SECTION 07321/R Page 85

Paragraph 1.6 SAFETY PRECAUTIONS

Delete “D.L. 624 and D.L. 494” and replace with “D.Lgs. 09 Apr 2008, n.81”

Paragraph 2.1 CLAY ROOFING TILES

Products meeting the requirements of these specifications are manufactured by the following:

PICA

Strada Montefeltro, 83

Pesaro (PS)

Tel: 0721/440-1

Fax: 0721/201-370

COTTO TOSCANO

52043 Castiglion Fiorentino (AR)

Tel: 0575/680-131

Fax: 0575/657-455

AGRICOLA INDUSTRIALE DELLA FAELLA S.P.A.

Castelfranco di Sopra (AR)

Tel: 055/914-6063

Fax: 055/965-651

FORNACE (GRUPPO SILA)

Via Ghiarola Nuova, 120

Fiorano Modenese (MO)

Tel: 0536/83-0232

Fax: 0536/83-27764

Products of other manufacturers meeting the requirements of these

Specifications are also acceptable.

Add the following sentence at the end of Paragraph 2.1:

"Other manufacturers meeting the requirements of this specification are acceptable.”

Paragraph “2.4 ROOF INSULATION AND VAPOR BARRIER”

Delete the whole paragraph.

FINAL (100% design) SECTION 07600/R Page 86

SECTION 07600/R

FLASHING AND SHEET METAL

Paragraph 1.1

ITALIAN LAWS AND NORMS

D.Lgs. 09 Apr 2008, n.81 Unified Text, Safety Regulations;

realization of Article 1 of the Law 03 Aug the health and safety on the work place

ITALIAN NATIONAL INSTITUTE FOR THE UNIFICATION OF STANDARDS (UNI)

PUBLICATIONS:

UNI EN 13605 (2004) Copper and copper alloys - Copper profiles and profiled wire for electrical purposes.

UNI 4157 (1987) Bitumen for Roofing. Sampling and

Acceptance Limits.

UNI 9001-2 (1987) Wrought primary aluminum and aluminum alloys. Aluminum group. Al 99,5

(1050 a).

UNI 5649-1 (1988) Copper. Wrought coppers. Qualities, requirements and tests.

UNI EN 10142 (2002) Continuously hot-dip zinc coated low carbon steels strip and sheet for cold forming. Technical Delivery Conditions.

UNI EN 10130 (2000) Cold rolled low carbon steel flat products for cold forming. Technical

Delivery Conditions.

UNI EN 10051 (2000) Continuously hot-rolled uncoated plate, sheet and strip of non-alloy and alloy steels. Tolerances on dimensions and shape.

UNI EN 10152 (1994) Electrolytically zinc coated cold rolled steel flat products. Technical delivery conditions.

ITALIAN / EUROPEAN HARMONIZATION STANDARDS (EN, UNI EN, ISO)

UNI EN 485-1 (2016) Aluminum and Aluminum Alloys - Sheet, Strip and Plate - Part 1: Technical

Conditions for inspection and delivery

FINAL (100% design) SECTION 07600/R Page 87

UNI EN 485-2 (2016) Aluminium and aluminium alloys -

Sheet, strip and plate - Part 2: Mechanical properties

UNI EN 485-3 (2005) Aluminium and aluminium alloys -

Sheet, strip and plate - Part 3: Tolerances on dimensions and form for hot-rolled products

UNI EN 485-4 (1996) Aluminium and aluminium alloys -

Sheet, strip and plate - Part 4: Tolerances on shape and dimensions for cold-rolled products

UNI EN 755-3 (2008) Aluminium and aluminium alloys -

Extruded rod/bar, tube and profiles - Part

3: Round bars, tolerances on dimensions and form

UNI EN 755-4 (2008) Aluminium and aluminium alloys -

Extruded rod/bar, tube and profiles - Part

4: Square bars, tolerances on dimensions and form

UNI EN 755-5 (2008) Aluminium and aluminium alloys -

Extruded rod/bar, tube and profiles - Part

5: Rectangular bars, tolerances on dimensions and form

UNI EN 988 (1998) Zinc and zinc alloys -

Specifications for rolled flat products for building

UNI EN 1172 (2012) Copper and copper alloys - Sheet and strip for building purposes

UNI EN 1173 (2008) Copper and copper alloys - Material condition designation

UNI EN 1412 (2017) Copper and copper alloys - European numbering system

UNI EN ISO 9453 (2014) Soft solder alloys - Chemical compositions and forms)

UNI EN 10051 (2011) Continuously hot-rolled strip and plate/sheet cut from wide strip of non-alloy and alloy steels - Tolerances on dimensions and shape

UNI EN 10088-1 (2014) Stainless steels - Part 1: List of stainless steels

UNI EN 10088-2 (2014) Stainless steels - Part 2: Technical delivery conditions for sheet/plate and strip of corrosion resisting steels for general purposes

UNI EN 10130 (2007) Cold rolled low carbon steel flat products for cold forming - Technical delivery conditions

FINAL (100% design) SECTION 07600/R Page 88

UNI EN 10143 (2006) Continuously hot-dip coated steel sheet and strip - Tolerances on dimensions and shape

UNI EN 10152 (2017) Electrolytically zinc coated cold rolled steel flat products for cold forming

- Technical delivery conditions

UNI EN 10346 (2015) Continuously hot-dip coated steel flat products for cold forming - Technical delivery conditions

UNI EN 13707 (2013) Flexible sheets for waterproofing -

Reinforced bitumen sheets for roof waterproofing - Definitions and characteristics

UNI EN ISO 15614-2 (2006) Specification and qualification of welding procedures for metallic materials -

Welding procedure test - Part 4: Finishing welding of aluminium castings

Paragraph 2.2.1 Steel Sheet, Zinc Coated (Galvanized)

Delete “UNI EN 10142” and replace with “UNI EN 10346”

Paragraph 2.2.3 Aluminum Alloy Sheet and Plate

Delete “UNI 9001-2” and replace with “UNI EN 485-1, UNI EN 485-2, UNI EN 485-

3, UNI EN 485-4, form alloy, and temper appropriate for use”

Paragraph 2.2.5 Solder

Delete “50 percent pig lead and 50 percent pure block tin” and replace with

“UNI EN ISO 9453”

Paragraph 2.2.8 Copper

Add: UNI EN 1412, UNI EN 1172, UNI EN 1173, cold-rolled temper

FINAL (100% design) SECTION 07920/R Page 89

SECTION 07920/R

JOINT SEALANTS

Paragraph 1.1

Delete:

UNI EN 26927 (1992) Building Construction - Jointing.

Products - Sealants-Vocabulary.

Add:

UNI EN ISO 6927 (2012) Buildings and civil engineering works - Sealants – Vocabulary

Paragraph 1.4.3 Definitions and Abbreviations

Delete “UNI EN 26927” and replace with “UNI EN ISO 6927”

Paragraph 2.2

Add the following sentence at the end of paragraph:

"Other manufacturers meeting the requirements of this specification are acceptable.”

FINAL (100% design) SECTION 08110/R Page 90

Section 08110/R

STEEL DOORS AND STEEL FRAMES

Paragraph 1.1

Delete:

EN 9774 (1990) Thermal Insulation Materials

Application Categories and Basic

Requirements - Guidelines for the

Harmonization of International Standards and Other Specifications.

ISO 834 (1975) Fire Resistance Tests – Elements of

Building Construction; Amendment 1:1979;

Amendment 2: 1980.

ISO 3008 (1976) Fire-Resistance Tests - Door and

Shutter Assemblies.

ISO 3009 (1976) Fire Resistance Tests – Glazed

Elements.

ISO 4898 (1984) Cellular Plastics – Specification for Rigid Materials Used in the Thermal

Insulation of Buildings.

ISO 5925/1 (1981) Fire Tests - Evaluation of

Performance of Smoke Control Door

Assemblies - Part 1: Ambient Temperature

Test.

UNI 7962 Buildings, Doors, Terminology and

Symbology.

Add:

EN 9774 (2004) Thermal Insulation for Building

Application - Guidelines for Selecting

Properties.

ISO 834 (2003) Fire Resistance Tests – Elements of

Building Construction.

ISO 3008 (2007) Fire-Resistance Tests - Door and

Shutter Assemblies.

ISO 3009 (2003) Fire Resistance Tests - Elements of

Building Construction – Glazed Elements.

ISO 4898 (2010) Rigid Cellular Plastics – Thermal

Insulation Products for Buildings -

Specifications.

ISO 5925-1 (2007) Fire Tests – Smoke-control Door and

Shutter Assemblies - Part 1: Ambient and

Medium Temperature Leakage Tests.

FINAL (100% design) SECTION 08110/R Page 91

ASTM E 90 (2001) Standard Test Method for Laboratory

Measurement of Airborne Sound Transmission

Loss of Building Partitions and Elements

UNI EN 12519 (2005) Windows and Pedestrian Doors.

Terminology.

UNI EN 10346 (2015) Continuously hot-dip coated steel flat products for cold forming - Technical delivery conditions.

ISO 16283-1 (2014) Acoustics -- Field measurement of sound insulation in buildings and of building elements Airborne sound.

Paragraph 1.2.1

Delete “blast resistant” and read the sentence as follows: “Submit door and frame locations, architectural door number, fire rating and indication of the construction details referring to the submitted shop drawings.”

Paragraph 1.2.4

Delete “blast resistant” and read the sentence as follows: “Structural calculations.”

Paragraph 1.2.5

Delete: “Resistance to blast loads”

Add “REI tests.”

Paragraph 1.3.2

Delete: “and/or blast resistant” and read the sentence as follows:

“Contractor shall coordinate selection of steel door and frame materials and products specified herein with door hardware to ensure that fire rated assemblies meet all U.S. and Italian related requirements.”

Paragraph 1.4.1

Paragraph 2.1.4

Paragraph 3.1.4:

Delete from title and sentence: “Blast resistant”

FINAL (100% design) SECTION 08120/R Page 92

SECTION 08120/R

ALUMINUM DOORS, FRAMES AND SIDELIGHTS

Paragraph 1.1 Applicable publications:

Delete:

UNI EN 288-4 (1993) Specification and Qualification of

Welding Procedures for Metallic Materials

- Part 4: Welding Procedure Tests for the

Arc Welding of Aluminum and its Alloys.

UNI EN ISO 10077-1 (2002) Thermal Performance of Windows, Doors and Shutters - Calculation of Thermal

Transmittance - Simplified Method.

UNI 10680 (1997) Aluminum and Aluminum Alloys.

Aluminum Alloys Thermal Break Profiles.

Requirements and Test Methods.

Add:

UNI EN ISO 15614-2 (2006) Specification and Qualification of

Welding Procedures for Metallic Materials -

Welding Procedure Test - Part 2: Arc Welding of Aluminum and its Alloys

UNI EN ISO 10077-1 (2018) Thermal performance of windows, doors and shutters - Calculation of thermal transmittance - Part 1: General

UNU EN 14024 (2005) Metal profiles with thermal barrier

- Mechanical performance - Requirements, proof and tests for assessment

Paragraph 1.2.4 Design data:

Delete the whole paragraph.

Paragraph 1.2.5 Test Reports:

Delete the whole paragraph.

Paragraph 2.2.1 Doors, Frames and Accessories:

Delete the end of fourth sentence:

“in any case they shall resist to the blast.”

Subparagraph “c.”:

“UNI EN 288-4.” in first sentence and the whole second sentence.

FINAL (100% design) SECTION 08120/R Page 93

Add:

“UNI EN ISO 15614-2.”

Subparagraph “f.”:

Delete the whole paragraph

Paragraph 2.2.4 Provisions for Glazing:

Delete last sentence.

Paragraph 2.2.5 Anchors:

Delete second sentence.

Paragraph 2.4.1 Available Manufacturers:

Delete:

NORMANT SECURITY GROUP

3224 Mobile Hwy

Montgomery, AL 36108

ATTN: Steve Scoggin

Tel: (334) 286-4246

Fax: (334) 286-4399

Email: steve-scoggin@normantind.com

SAELZER GMBH

Dietrich-Bonhoeffer-Str.1-3

D-35037 Marburg

ATTN: Frank Rummler

Tel: 49 (0) 6421/938-100

Fax: 49 (0) 6421/938-190

Email: rummler@saelzer.de

Or suelzer@saelzer.de

PENSHER SKYTECH LTD

Felling Works, William Street, Felling, Gateshead

Tyne & Wear NE 100JP – U.K.

Tel: 0044(0)1914380455

Fax: 0044(0)19114302328

Add:

Not Used

Paragraph 2.9 FABRICATION OF ALUMINUM FRAMES:

Delete second and third sentence.

mailto:suelzer@saelzer.de

FINAL (100% design) SECTION 08120/R Page 94

Paragraph 2.10.1 Sizes, Clearance and Edge Treatment:

Delete from first sentence: “and not less than 75 mm thick, and in any case they shall resist to the blast.”

FINAL (100% design) SECTION 08210/R Page 95

Section 08210/R

WOOD DOOR

Paragraph 1.1:

Delete:

ISO-140/III Laboratory Measurement of Airborne Sound

Insulation of Building Elements.

UNI 3252 (1987) General Conditions for Physical

Mechanical Tests.

UNI 7961 (1987) Buildings, Doors, Criteria for

Classification.

UNI 8200 (1981) Buildings, Interior Doors. Impact

Test.

UNI 8328 (1981) Buildings Heat Test for Interior

Doors.

UNI EN 950 (2000) Door Shutter. Impact Test.

Add:

UNI 4143 (2011) Tests on wood - Axial split test

UNI EN 204 (2002) Classification of thermoplastic wood adhesives for non-structural applications

UNI EN 205 (2006) Adhesives - Wood adhesives for non-structural applications - Determination of tensile shear strength of lap joints

UNI EN 1191 (2011) Windows and doors. Resistance to repeated opening and closing – Test method

UNI EN 1634-1 (2001) Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware. Fire resistance test for door and shutter assemblies and openable windows

UNI EN 15269-3 (2012) Extended application of test results for fire resistance and/or smoke control for door, shutter and openable window assemblies, including their elements of building hardware. Fire resistance of hinged and pivoted timber door sets and openable timber framed windows

UNI ISO 8275 (1985) Door sets - Vertical load test

FINAL (100% design) SECTION 08520/R Page 96

Section 08520/R

ALUMINUM WINDOW

PREN 12365-1 (1996) Building Hardware – Gaskets and

Weather-stripping for Doors, Windows, Shutters, and Curtain Walls. Part 1:

Performance Requirements and

Classification.

UNI EN 1026 (2001) Windows and Doors. Air Permeability.

Test Method.

UNI EN 12211 (2001) Windows and Doors - Resistance to

Wind Load - Test Method.

UNI EN 1027 (2001) Windows and Doors. Water Tightness.

Test Method.

UNI EN 288-4 (1993) Specification and Qualification of

Welding Procedures for Metallic Materials -

Part 4: Welding Procedure Tests for the Arc

Welding of Aluminum and its Alloys.

UNI EN 573-1 (1996) Aluminum and Aluminum Alloys -

Chemical Composition and Form of Wrought

Products - Part 1: Numerical Designation

System.

UNI EN 107 (1983) Methods of Testing Windows.

Mechanical Tests.

ISO 6613 (1980) Windows and Door Height Windows -

Air Permeability Test.

UNI EN 107 (1980) Methods of testing windows -

Mechanical tests

UNI EN 573-1 (2005) Aluminum and aluminum alloys -

Chemical composition and form of wrought products - Part 1: Numerical designation system

UNI EN 755-1/9 (2008) Aluminum and aluminum alloys -

Extruded rod/bar, tube and profiles

UNI EN 1026 (2001) Windows and doors – Air permeability

- Test method

UNI EN 1027 (2001) Windows and doors – Water tightness

- Test method

FINAL (100% design) SECTION 08520/R Page 97

UNI EN 12020-1 (2008) Aluminum and aluminum alloys.

Extruded precision profiles in alloys EN

AW-6060 and EN AW-6063 – Technical conditions for inspection and delivery

UNI EN 12020-2 (2008) Aluminum and aluminum alloys.

Extruded precision profiles in alloys EN

AW-6060 and EN AW-6063 - Tolerances on dimensions and form

UNI EN 12207 (2000) (EC 1-2007) Windows and doors - Air permeability – Classification

UNI EN 12206-1 (2005) Paints and varnishes. Coating of aluminum and aluminum alloys for architectural purposes. Coatings prepared from coating powder

UNI EN 12208 (2000) (EC 1-2007) Windows and doors – Water tightness – Classification

UNI EN 12210 (2001) Windows and doors - Resistance to wind load – Classification

UNI EN 12211 (2001) Windows and doors - Resistance to wind load - Test method

UNI EN 12519 (2005) Windows and Pedestrian Doors –

Terminology

UNI EN ISO 15614-2 (2006) Specification and qualification of welding procedures for metallic materials -

Welding procedure test - Part 4: Finishing welding of aluminum castings

UNI 3952 (1998) Aluminum and Aluminum Alloy Frames in Construction. Norms for the Selection, Use and Testing of Materials.

UNI 7697 (2015) Safety criteria for glazing application

FINAL (100% design) SECTION 08800/R Page 98

Section 08800/R

GLAZING

Paragraph 1.1:

Delete:

UNI EN 572-2 (1996) Glass in Building - Basic Sode Lime

Silicate Glass Products. Part 2: Float

Glass.

ISO 11600 (1993) Building Construction - Sealants -

Classification and Requirements.

UNI EN ISO 12543-1-6 (2000) Glazing in Building Construction -

Laminated and Laminated Safety Glass

Definitions and Descriptions of

Components/Appearance.

UNI 7697 (2002) Safety Criteria for Glazing.

UNI 10593/1 (1996) Glass for Building Construction, Insulating Glass - Generalities and

Dimensional Tolerances.

UNI 10593/2 (1996) Glass for Building Construction, Insulating Glass - Tests of Aging, Measurement of Penetration of Water Vapor and Requirements.

UNI 10593/3 (1996) Glass for Building Construction, Insulating Glass - Initial Type of Tests for the Measurement of the Speed of the Loss of Gas from Insulated Glass Filled with Gas.

UNI 10593/4 (1996) Glass for Building Construction, Insulating Glass - Method of Tests for

Determining the Physical Properties of

Sealing the Edges.

Add:

UNI EN 572-2 (2012) Glass in Building - Basic Sode Lime

Silicate Glass Products. Part 2: Float

Glass

UNI EN 572-3 (2012) Glass in Building - Basic Soda Lime

Silicate Glass Products. Part 3: Polished

Wired Glass

UNI EN 1279-1 (2004) Glass in Building – Insulating glass units - Part 1: Generalities, dimensional tolerances and rules for the system description

FINAL (100% design) SECTION 08800/R Page 99

UNI EN 1279-2 (2004) Glass in building – Insulating glass units - Part 2: Long term test method and requirements for moisture

UNI EN 1279-3 (2004) Glass in building – Insulating glass units - Part 3: Long term test method and requirements for gas leakage rate and for gas concentration tolerances

UNI EN 1279-4 (2004) Glass in building – Insulating glass units - Part 4: Methods of test for the physical attributes of edge seals

UNI EN ISO 11600 (2011) Building construction – Jointing products - Classification and requirements for sealants

UNI EN ISO 12543-2 (2011) Glass in building – Laminated glass and laminated safety glass Laminated safety glass

UNI 7142 (1988) Flat Glass - Tempered Glass for

Buildings and Furnishings

EC 1-2015 UNI 7697 (2015) Flat Glass - Glass in Building

Construction - Safety Criteria

FINAL (100% design) SECTION 08800/R Page 100

Section 09100/R

METAL SUPPORT ASSEMBLIES

Paragraph 1.1:

Delete:

UNI EN 10142 (2002) Continuously Hot Dip Zinc Coated Low

Carbon Steel Sheet and Strip for Cold

Forming - Technical Delivery Conditions, Including Amendment 1

UNI EN 10218-1 (1995) Steel Wire and Wire Products -

General, Part 1: Test Methods.

UNI EN 10218-2 (1997) Steel Wire and Wire Products -

General - Part 2, Wire Dimensions and

Tolerances

UNI 7344 (1985) Cold formed steel sections -

Requirements and tolerances.

Add:

UNI EN 10162 (2006) Cold-Formed Steel Profiles -

Technical supply conditions – Dimensional tolerances and on the transversal section

UNI EN 10218-1 (2012) Steel Wire and Wire Products -

General - Part 1, Test Methods

UNI EN 10218-2 (2012) Steel Wire and Wire Products -

General - Part 2, Wire Dimensions and

Tolerances

UNI EN 10346 (2015) Continuously hot-dip coated steel flat products for cold forming. Technical delivery conditions

UNI EN 14195 (2015) Metal framing components for gypsum board system. Definitions, requirements and test methods

FINAL (100% design) SECTION 09212/R Page 101

SECTION 09212/R

EXTERIOR STUCCO

Paragraph 1.1 Applicable publications:

Delete:

UNI ENV 413-1 (1994) Masonry Cement - Part 1:

Specification.

UNI EN 459-1 (2002) Building Lime - Part 1: Definitions, Specifications and Conformity Criteria.

UNI EN 459-2 (2002) Building Lime - Part 2: Test Methods.

UNI EN 932-1 (1998) Tests for General Properties of

Aggregates - Part 1: Methods for Sampling.

UNI EN 932-3 (1998) Tests of General Properties of

Aggregates - Part 3: Procedure and

Terminology for Simplified Petrographic

Description.

Add:

ITALIAN / EUROPEAN HARMONIZATION STANDARDS (EN, UNI EN, ISO)

UNI EN 413-1 (2011) Masonry cement - Part 1: Composition, specifications and conformity criteria

UNI EN 413-2 (2016) Masonry cement - Part 2: Test methods

UNI EN 459-1 (2015) Building lime - Part 1: Definitions, specifications and conformity criteria

UNI EN 459-2 (2010) Building lime - Part 2: Test methods

UNI EN 459-3 (2015) Building lime - Part 3: Conformity evaluation

UNI EN 932-1 (1998) Tests for general properties of aggregates - Part 1: Methods for sampling

UNI EN 932-3 (2004) Tests for general properties of aggregates - Part 3: Procedure and terminology for simplified petrographic description

UNI EN 1008 (2003) Mixing water for concrete -

Specification for sampling, testing and assessing the suitability of water, including water recovered from processes in the concrete industry, as mixing water for concrete

Paragraph 2.1.8

Add the following sentence at the end of paragraph:

FINAL (100% design) SECTION 09212/R Page 102

"Other manufacturers meeting the requirements of this specification are acceptable.”

Add:

Paragraph 2.1.9: special humidity proof (deumidificante) plaster

Furnish and install special humidity proof (deumidificante) plaster up to

85 cm from floor type Caparol cycle or equal approved as follows:

- Rough mortar (rinzaffo) type Capatec Vorspritz 030

- micro-porous plaster type Capatec Sanierputz Rapid, above 15 cm from floor, total thickness equal to existing, about 2 – 2.,5 cm

Item includes any other work to provide a job performed in a workmanlike manner. Contractor to ensure even surface, equivalent thickness with non-humidity proof plaster.

Add:

Paragraph 2.1.10: reinforced plaster (rasantatura armata)

Furnish and install reinforced plaster (rasantatura armata) type Caparol cycle or equal approved as follows:

- One coat of high penetration acrylic resin base colorless primer, to consolidate surfaces, conform to DIN 4108.3, type Acryl Konsilidierug

- First layer thin plaster, type Capatec Klebe und- Armierungsmasse 186

- embed fiber glass mesh, 4 x 4 mm, 160 gr / m² conform to DIN 53854, overlap 10 cm, type Capatec Gewebe 650, consider extra mesh for areas that require more resistance.

- Second layer thin plaster, cover embedded mesh, total 1st and 2nd layers of thin plaster thickness 3 - 4 mm, type Capatec Klebe und-

Armierungsmasse 186

- One coat colored primer type Putzground

- one thin layer of finishing siloxane thin colored plaster, grade 1,00 mm, thickness 1 – 1,5 mm.

Item includes the removal of metal corner guards (paraspogoli) and installation on all corners of pvc corner guards with mesh, type Capatec

Gewebe Eckschutz 656/02. The Contractor during execution of plastering cycle will level uneven surfaces in order to have a nice smooth and uniform wall surface without defects. Strictly follow installation instructions during plastering cycle including curing time.

Transportation of resulting material to authorized dump and any other work including accessories to provide a job performed in a workmanlike manner. Contractor to ensure even surface, equivalent thickness with humidity proof plaster.

Add:

Paragraph 2.1.11: finishing plaster (rasante di finitura)

Furnish and install finishing plaster (rasante di finitura) type Caparol cycle or equal approved as follows:

- One coat of high penetration acrylic resin base colorless primer, to consolidate surfaces, conform to DIN 4108.3, type Acryl Konsilidierug

- One coat colored primer type Putzground

- One thin layer of finishing siloxane thin colored plaster, , grade 1,00 mm, thickness 1 – 1,5 mm.

FINAL (100% design) SECTION 09212/R Page 103

Item includes the removal of rusted metal corner guards (paraspigoli) and installation of pvc corner guards with mesh if necessary, type Capatec

Gewebe Eckschutz 656/02. Also the contractor during execution of plastering cycle will level uneven surfaces in order to have a nice smooth and uniform wall surface without defects. Strictly follow installation instructions during plastering cycle including curing time.

Transportation of resulting material to authorized dump and any other work including accessories provide a job performed in a workmanlike manner.

FINAL (100% design) SECTION 09220/R Page 104

Section 09220/R

INTERIOR PLASTER

Paragraph 1.1

Delete:

UNI ENV 413-1 (1994) Masonry Cement - Part 1:

Specification

UNI EN 459-1 (2002) Building Lime - Part 1: Definitions, Specifications and Conformity Criteria

UNI EN 459-2 (2002) Building Lime - Part 2: Test Methods

UNI EN 932-3 (1998) Tests of General Properties of

Aggregates - Part 3: Procedure and

Terminology for Simplified Petrographic

Description

Add:

UNI EN 413-1 (2011) Masonry Cement - Part 1:

Composition, specification and conformity criteria

UNI EN 413-2 (2005) Masonry Cement - Part 2: Test methods

UNI EN 459-1 (2015) Building Lime - Part 1:

Definitions, Specifications and Conformity

Criteria

UNI EN 459-2 (2010) Building Lime - Part 2: Test Methods

UNI EN 932-3 (2004) Tests of General Properties of

Aggregates - Part 3: Procedure and

Terminology for Simplified Petrographic

Description

UNI EN 1008 (2003) Mixing Water for Concrete -

Specification for Sampling, Testing and

Assessing the suitability of Water, ..., as

Mixing Water for Concrete

Paragraph 2.11

Add at the end the following sentence: "Other manufacturers meeting the requirements of this specification are acceptable.”

FINAL (100% design) SECTION 09250/R Page 105

SECTION 09250/R

GYPSUM AND CEMENT BOARD

Paragraph 1.1

Delete:

UNI 5371 (1984) Gypsum Rock for Manufacture of

Binders - Classification, Requirements and

Tests.

UNI EN 1363-1 (2001) Fire Resistance Tests – General

Requirements.

UNI EN 932-1 (1998) Tests for General Properties of

Aggregates. Part 1: Methods for Sampling.

UNI EN 932-3 (1998) Tests of General Properties of

Aggregates. Part 3: Procedure and

Terminology for Simplified Petrographic

Description.

Add:

UNI EN 520 (2009) Gypsum Plasterboards - Definition, requirements and test methods

UNI 11424 (2015) Gypsum Plasterboards - Non-

Loadbering Plasterboard System on Metal

Frames - Installations

UNI EN 13501-1 (2009) Fire classifications of constructions products and building elements. Classification using test data from reaction to fire tests

UNI EN 13279-1 (2008) Gypsum binder and gypsum plastera.

Definitions and requirements

UNI EN 13963 (2014) Jointing materials for gypsum plasterboards. Definitions, requirements and test method

UNI EN 14566 (2009) Mechanical fasteners for gypsum plasterboard system. Definitions, requirements and test method

UNI EN 1627 (2011) Pedestrian doorsets, windows, curtain walling, grilles and shutters. Burglar resistance. Requirements and classification

D.M. 26 Jun 1984 Classification of Resistance to Fire and

Ratification of Materials for Fire

Prevention

FINAL (100% design) SECTION 09250/R Page 106

Italian requirements into the European classification system.

D.M. 16 Feb 2007 Classification of fire resistance of construction material and elements activities subject to control by the

National Fire Department stabilizing criteria for determining the fire resistance performance

Paragraph 2.1:

Add at the end the following sentence: "Other manufacturers meeting the

FINAL (100% design) SECTION 09310/R Page 107

Section 09310/R

CERAMIC AND STONE COMPOSITE TILE

Paragraph 1.1:

Delete:

UNI EN 87 (1992) Ceramic Floor and Wall Tiles -

Definitions, Classification, Characteristics and Marking

UNI EN ISO 10545-2 (2000) Ceramic tiles - Determination of dimensions and surface quality

UNI EN ISO 10545-3 (2000) Ceramic tiles - Determination of water absorption, apparent porosity, apparent relative density and bulk density

UNI EN 101 (1992) Ceramic Tiles. Determination of

Scratch Hardness of Surface According to

Mohs’ Scale.

UNI EN ISO 10545-11 (2000) Ceramic tiles - Determination of crazing resistance for glazed tiles

UNI EN ISO 10545-14 (2000) Ceramic tiles - Determination of resistance to stains

UNI EN ISO 10545-7 (2000) Ceramic tiles - Determination of resistance to surface abrasion for glazed tiles

UNI EN ISO 10545-12 (2000) Ceramic tiles - Determination of frost resistance

Regio Decreto No. 2231 (16.11.1939) Norms for Lime Acceptance.

Add:

UNI 8520-22 (1999) Aggregates for use in concrete -

Determinaton of potential reactivity of alcali in aggregates

UNI EN 14411 (2012) Ceramic tiles - Definition, classification, characteristics, assessment and verification of constancy of performance and marking

UNI EN 197-1 (2011) Cement - Composition, Specifications and Conformity Criteria - Part 1: Common

Cements

UNI EN 932-3 (2004) Tests for General Properties of

Aggregates - Part 3: Procedure and

Terminology for Simplified Petrographic

Description

UNI EN 1015-11 (2007) Methods of test for mortar for masonry - Part 11: Determination of

FINAL (100% design) SECTION 09310/R Page 108 flexural and compressive strength of hardened mortar

UNI EN 12004 (2012) Adhesives for tiles - Requirements, evaluation of conformity, classification and designation

UNI EN 459-1 (2015) Building Lime - Part 1: Definitions, Specifications and Conformity Criteria

UNI ENV 459-2 (2010) Building lime - Part 2: Test methods

UNI EN ISO 10545-1 (2014) Ceramic Tiles. Sampling and Basics for acceptance

UNI EN 13888 (2009) Grout for tiles - Requirements, evaluation of conformity, classification and designation

Paragraph 2.2:

Add at the end the following sentence: "Other manufacturers meeting the

FINAL (100% design) SECTION 09510/R Page 109

Section 09510/R

ACOUSTICAL CEILINGS

Paragraph 1.1:

Delete:

UNI EN 10113/1 (1994) Hot Rolled Products in Weldable Fine

Grain Structural Steels, Part 1, General

Delivery Conditions.

UNI EN 10113/2 (1994) Hot Rolled Products in Weldable Fine

Grain Structural Steels, Part 2, Delivery

Conditions for Normalized /Normalized

Rolled Steels.

UNI EN 10113/3 (1994) Hot Rolled Products in Weldable Fine

Grain Structural Steels, Part 3, Delivery Conditions for Thermomechanical

Rolled Steels.

UNI EN 10215 (1996) Continuously Hot-Dip Aluminum, Zinc

Coated Steel Strip and Sheet - Technical delivery Conditions.

UNI EN 10218-1 (1995) Steel Wire and Wire Products -

General, Part 1: Test Methods.

UNI EN 10244-2 (2001) Steel Wire and Wire Products - Non-ferrous Metallic Coatings on Steel Wire, Part 2: Zinc or Zinc Alloy coatings.

UNI EN 20140-9 (1998) Acoustics - Measurement of Sound

Insulation in Building and of Building

Elements - Part 9: Laboratory Measurement of Room-to-Room Airborne Sound

Insulation of a Suspended Ceiling with a

Plenum Above It.

UNI EN ISO 717-1 (1997) Acoustics - Rating of Sound

Insulation in Buildings, Part 1, Airborne

Sound Insulation.

UNI EN ISO 26927 (1992) Building Construction - Jointing

Products.

UNI 5958 (1985) Products of Mineral Fiber for

Thermal and Acoustical Insulation. Terms and Definitions.

Add:

UNI EN 10025-1 (2005) Hot rolled products of structural steels - Part 1: General technical delivery conditions

UNI EN 10025-3 (2005) Hot rolled products of structural steels - Part 3: Technical delivery

FINAL (100% design) SECTION 09510/R Page 110 conditions for normalized/normalized rolled weldable fine grain structural steels

UNI EN 10025-4 (2005) Hot rolled products of structural steels - Part 4: Technical delivery conditions for thermomechanical rolled weldable fine grain structural steels

EC 1-2015 UNI EN 10218-1 (2015) Steel Wire and Wire Products -

General, Part 1: Test Methods

EN 10244-2 (2009) Steel Wire and Wire Products - Non-ferrous Metallic Coatings on Steel Wire, Part 2: Zinc or Zinc Alloy Coatings

UNI EN ISO 10140-3 (2015) Acoustics – Laboratory measurement of sound insulation of building elements -

Part 3: Measurement of impact sound insulation

EC 1-2009 UNI EN ISO 10848-2 (2006) Acoustics – Laboratory measurement of the flanking transmission of airborne and impact sound between adjoining rooms -

Part 2: Application to light elements when the junction has a small influence

EC 1-2016 UNI EN 10346 (2015) Continuously hot-dip coated steel flat products for cold forming - Technical delivery conditions

UNI EN ISO 717-1 (2013) Acoustics - Rating of Sound

Insulation in Buildings, Airborne Sound

Insulation

UNI EN 16487 (2015) Acoustics - Test code for suspended ceilings - Sound absorption

UNI EN 16703 (2015) Acoustics - Test code for drywall systems of plasterboard with steel studs -

Airborne sound insulation

UNI EN ISO 6927 (2012) Buildings and civil engineering works - Sealant

D.M. 15 Mar 2005 Classification of fire resistance of materials used in construction. Integrates

Italian requirements into the European classification system.

D.M. 16 Feb 2007 Classification of fire resistance of construction material and elements

Paragraph 3.1:

Replace: “UNI EN 10113/1” with “UNI EN 10025/1”; “UNI EN 10113/2” with “UNI

EN 10025/3”; “UNI EN 10113/3” with “UNI EN 10025/4”.

Paragraph 2.2

FINAL (100% design) SECTION 09510/R Page 111

Add at the end the following sentence: "Other manufacturers meeting the

FINAL (100% design) SECTION 09900/R Page 112

SECTION 09900/R

PAINTS AND COATINGS

UNI ISO 6504-1 (1990) Paints and Varnishes - Determination of Hiding Power - Part 1: Kubelka-Munk

Method for White and Light-Colored Paints.

UNI EN ISO 3251 (1998) Paints and Varnishes - Determination of Non-Volatile Matter of Paints, Varnishes and Binders for Paints and Varnishes.

UNI EN ISO 6504-1 (2006) Paints and Varnishes - Determination of Hiding Power - Kubelka-Munk Method for

White and Light-Colored Paints.

UNI EN ISO 3251 (2005) Paints, Varnishes and Plastic -

Determination of Non-Volatile Matter

Content.

UNI 8760 (1985) Systems for continuously applied plastic coatings - Criteria for Technical

Information

UNI EN ISO 17491-3 (2008) Protective clothing – Test methods for clothing providing protection against chemicals - Part 3: Determination of resistance to penetration by a jet of liquid

(jet test)

D.Lgs. 05 Feb 1997, n.22 Realization of CEE Requirements for

Disposal of Hazardous Waste Material and

Packaging of Waste Material

D.L. 09 Apr 2008, n.81 Unified Text, Safety Regulations;

realization of Article 1 of the Law 3 Aug classification system

FINAL (100% design) SECTION 10201/R Page 113

Section 10201/R

METAL WALL AND DOOR LOUVERS

UNI EN 10142 (2002) Continuously hot-dip zinc coated low carbon steels strip and sheet for cold forming - Technical delivery conditions.

UNI EN 10143 (1994) Continuously hot-dip metal coated steel sheet and strip. Tolerances on dimensions and shape.

UNI EN 10143 (2006) Continuously hot-dip coated steel sheet and strip - Tolerances on dimensions and shape

UNI EN 10088-1 (2014) Stainless steels - Part 1: List of stainless steels

UNI EN 10088-2 (2014) Stainless steels - Part 2: Technical delivery conditions for sheet/plate and strip of corrosion resisting steels for general purposes

EN ISO 15614-2 (2005) Specification and qualification of welding procedures for metallic materials - Welding procedure test

- Part 2: Arc welding of Aluminum and its alloys

UNI EN 485-1 (2009) Aluminum and Aluminum alloys -

Sheet, strip and plate - Part 1: Technical conditions for inspection and delivery

FINAL (100% design) SECTION 10400/R Page 114

Section 10400/R

IDENTIFICATION DEVICES

UNI EN 755/3-9 (1997-2002) Aluminum and aluminum alloys -

Extruded rod/bar, tube and profiles.

UNI EN 755-2 (2013) Aluminum and Aluminum alloys -

Extruded rod/bar, tube and profiles - Part

2: Mechanical properties

ISO 3522 (2007) Aluminum and Aluminum alloys -

Castings - Chemical composition and mechanical properties

ISO 8992 (2005) Fasteners - General Requirements for

Bolts, Screws, Studs and Nuts

FINAL (100% design) SECTION 10800/R Page 115

Section 10800/R

TOILET AND BATH ACCESSORIES

UNI 10088-1 (1997) Stainless steels. List of stainless steels

UNI EN 1036-1 (2008) Glass in building - Mirrors from silver-coated float glass for internal use

- Part 1: Definitions, requirements and test methods

UNI EN 10088-1 (2014) Stainless steels - Part 1: List of stainless steels

FINAL (100% design) SECTION 12490/R Page 116

Section 12490/R

BLINDS

UNI 10818 (1999) Windows, doors, blinds and shutters

-Guidelines for installation

Add

UNI 10818 (2015) Windows, doors, blinds and shutters

-Guidelines for installation

FINAL (100% design) SECTION 13855/R Page 117

SECTION 13855/R

ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM

PART 1 - GENERAL

1.1 REFERENCES

THE PUBLICATIONS LISTED BELOW FORM A PART OF THIS SPECIFICATION TO THE EXTENT

REFERENCED. THE PUBLICATIONS ARE REFERRED TO IN THE TEXT BY THE BASIC

DESIGNATION ONLY.

ASME INTERNATIONAL (ASME)

ASME A17.1/CSA B44 (2010) Safety Code for Elevators and

Escalators

FM GLOBAL (FM)

FM APP GUIDE (updated on-line) Approval Guide http://www.approvalguide.com/

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE C62.41.1 (2002; R 2008) Guide on the Surges

Environment in Low-Voltage (1000 V and

Less) AC Power Circuits

IEEE C62.41.2 (2002) Recommended Practice on

Characterization of Surges in Low-Voltage

(1000 V and Less) AC Power Circuits

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 101 (2012) Life Safety Code

NFPA 72 (2010; TIA 10-4) National Fire Alarm and

Signaling Code

NFPA 90A (2009; Errata 09-1) Standard for the

Installation of Air-Conditioning and

Ventilating Systems

UNDERWRITERS LABORATORIES (UL)

UL 1971 (2002; Reprint Oct 2008) Signaling Devices for the Hearing Impaired

UL 228 (2006; Reprint Nov 2008) Door Closers-

Holders, With or Without Integral Smoke

Detectors

UL 268 (2009) Smoke Detectors for Fire Alarm

Systems

UL 464 (2009; Reprint Jan 2011) Standard for

Audible Signal Appliances http://www.approvalguide.com/

FINAL (100% design) SECTION 13855/R Page 118

UL 864 (2003; Reprint Jan 20110) Standard for

Control Units and Accessories for Fire

Alarm Systems

UL Electrical Construction (2009) Electrical Construction Equipment

Directory

UL Fire Prot Dir (2011) Fire Protection Equipment Directory

ITALIAN ELECTRO TECHNICAL COMMISSION (CEI)

CEI EN 61386-21 (CEI 23-81) (2011) Conduits and Accessories for

Electrical Installation - Part 21: Specific

Requirements for Rigid Conduits systems and

Accessories.

CEI 64-8 (2012; V1-2013; V2-2015; V3-2017; V4-2017)

Electrical Systems with Rated Voltage Not

Greater Than 1000V A.C. and 1500V D.C.

CEI EN 60529 (1997; V1-2000; A2-2014; Errata Corrige-

2017) Degrees of Protection Provided By

Enclosures (IP Code).

ITALIAN NATIONAL UNIFICATION (UNI)

UNI 9795 (2013) Fixed Automatic Fire Detection and alarm Systems – Design, Installation and maintenance.

ITALIAN/EUROPEAN HARMONIZATION STANDARDS (UNI EN) (UNI ENV) (UNI EN ISO)

UNI EN ISO 9001 (2015) Quality Management Systems –

1.2 RELATED REQUIREMENTS

Section 16050, "Basic Electrical Materials and Methods," applies to this section, with the additions and modifications specified herein.

1.5.3 Record Drawing Software

Replace the whole paragraph with the following:

Furnish one set of CD-ROMs or DVDs containing CAD based drawings in DWG format of as-built drawings and schematics.

2.2.2 System Operation

The fire alarm system shall comply with UNI 9795. The system shall be a complete, supervised, noncoded, analog/addressable fire alarm system conforming to NFPA 72. The system shall have an interconnected riser loop having Class A supervision that shall not be located in the same room or shaft. The return portion of the loop shall be remote from the supply portion of the loop. Where three or more stairs are provided for egress from floors above grade, a single impairment cannot adversely affect more than 1/2 of any floor. The system shall operate in the alarm mode upon actuation of any alarm initiating device. The system shall remain in the alarm mode until initiating device(s) are reset and the fire alarm control

FINAL (100% design) SECTION 13855/R Page 119 panel is manually reset and restored to normal. The system shall provide the following functions and operating features:

a. The FACP and fire alarm control units, if used, shall provide power, annunciation, supervision, and control for the system.

b. Provide Class A signaling line circuits for each floor.

c. Provide Class B notification appliance circuits. The visual alarm notification appliances shall have the flash rates synchronized if installed in the same area of view. Class A type signalling circuit, shared by initiating device and notification appliances, is acceptable;

d. Provide electrical supervision of the primary power (AC) supply, presence of the battery, battery voltage, and placement of system modules within the control panel.

e. Provide an audible and visual trouble signal to activate upon a single break or open condition, or ground fault. The trouble signal shall also operate upon loss of primary power (AC) supply, absence of a battery supply, low battery voltage, or removal of alarm or supervisory panel modules. Provide a trouble alarm silence feature which shall silence the audible trouble signal, without affecting the visual indicator. After the system returns to normal operating conditions, the trouble signal shall again sound until the trouble is acknowledged. A smoke sensor in the process of being verified for the actual presence of smoke shall not initiate a trouble condition.

f. Provide a notification appliance silencing switch which, when activated, will silence the audible signal appliance, but will not affect the visual alarm indicator, the liquid crystal display, or the automatic notification of the base security office. This switch shall be overridden upon activation of a subsequent alarm.

g. Provide alarm verification capability for smoke sensors. Alarm verification shall initially be set for 30 seconds.

h. Provide program capability via switches in a locked portion of the

FACP to bypass the automatic notification appliance circuits, fire reporting system air handler shutdown smoke control operation elevator recall door release…