This pre-solicitation notice is for an indefinite delivery, indefinite quantity multiple award construction contract to provide design-build construction services in Italy. The contract will have a one-year base period and four option years, with a minimum guaranteed amount of $2,500 EURO per contractor and a total maximum value of $96 million across all contracts. Services will include various construction, repair, renovation, and facility maintenance projects at Aviano Air Base and other locations in Italy. Response is due by April 19, 2019 for comments on draft documents, with award anticipated in May 2019. Task order minimum is $2,500 and maximum is $7 million. The North American Industry Classification System code is 236220.
ANNEX E- ELECTRICAL PART 16
View the file
Other files for this federal contract opportunity
Show all 50
Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT: ASHE 18-1025
RENOVATE/EXPAND FAC. 939
DESIGN PHASE: 60% Page 68 of 122
CALCULATIONS AND VERIFICATIONS
DISTRIBUTION BOARD: [B939-MDP-2] B939-MDP-2
LINE: QF3
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1 4,83 0 0 4,83 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other circuits
K
L2.1.6 F+N+PE uni 30 31 30 -side by
5 1
Conductors cross-section [mm2] phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 0,63 1,66 4
Ib
[A] Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
[kA]
4,83 23,94 4,18 0,7 0,45 0,43
Designation
FG16R16-0,6/1 kV - Cca-s3,d1,a3/Cu
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF3 C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.6 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
Overload Maximum short-circuit Minimum short-circuit Indirect contact
SI SI SI SI
DESIGN PHASE: 60% Page 69 of 122
LINE: QF4
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,5 2,41 2,41 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.7 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 0,31 1,34 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,41 23,94 4,18 0,7 0,45 0,43
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF4 C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.7 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 70 of 122
LINE: QF5
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,5 2,41 0 2,41 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.8 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 0,31 1,34 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,41 23,94 4,18 0,7 0,45 0,43
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF5 C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.8 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 71 of 122
LINE: QF6
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,6 2,89 0 2,89 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.9 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 0,38 1,4 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,89 23,94 4,18 0,7 0,45 0,43
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF6 C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.9 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 72 of 122
LINE: QF7
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,3 1,44 1,44 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.10 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 0,19 1,21 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,44 23,94 4,18 0,7 0,45 0,43
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF7 C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.10 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 73 of 122
LINE: QF8
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,2 0,96 0 0,96 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.11 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 216,0 4,68 239,5 18,51 0,2 1,22 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,96 17,66 4,18 0,47 0,3 0,29
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF8 C40a Vigi 1+N C 10 10 - 0,1 0,1
Q2.1.11 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 74 of 122
LINE: QF9
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,2 0,96 0 0 0,96 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.12 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF9 C40a Vigi 1+N C 10 10 - 0,1 0,1
Q2.1.12 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 75 of 122
LINE: QF10
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,3 1,44 1,44 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.13 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 216,0 4,68 239,5 18,51 0,3 1,33 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,44 17,66 4,18 0,47 0,3 0,29
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF10 C40a Vigi 1+N C 10 10 - 0,1 0,1
Q2.1.13 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 76 of 122
LINE: QF11
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,4 1,93 0 1,93 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.14 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 216,0 4,68 239,5 18,51 0,4 1,43 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,93 17,66 4,18 0,47 0,3 0,29
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF11 C40a Vigi 1+N C 10 10 - 0,1 0,1
Q2.1.14 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 77 of 122
LINE: QF12
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,3 1,44 0 0 1,44 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.15 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 216,0 4,68 239,5 18,51 0,3 1,33 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,44 17,66 4,18 0,47 0,3 0,29
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF12 C40a Vigi 1+N C 10 10 - 0,1 0,1
Q2.1.15 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 78 of 122
LINE: QF13
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,64 3,09 3,09 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.16 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 216,0 4,68 239,5 18,51 0,65 1,67 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
3,09 17,66 4,18 0,47 0,3 0,29
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF13 C40a Vigi 1+N C 10 10 - 0,1 0,1
Q2.1.16 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 79 of 122
LINE: QF14
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,2 0,96 0 0,96 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.17 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF14 C40a Vigi 1+N C 10 10 - 0,1 0,1
Q2.1.17 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 80 of 122
LINE: QF15
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,1 0,48 0 0 0,48 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.18 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 216,0 4,68 239,5 18,51 0,1 1,12 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,48 17,66 4,18 0,47 0,3 0,29
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF15 C40a Vigi 1+N C 10 10 - 0,1 0,1
Q2.1.18 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 81 of 122
LINE: QF16
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,8 8,69 0 0 8,69 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.19 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 1,15 2,17 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
8,69 23,94 4,18 0,7 0,45 0,43
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF16 C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.19 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 82 of 122
LINE: QF17
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,3 1,44 1,44 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.20 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 0,19 1,21 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,44 23,94 4,18 0,7 0,45 0,43
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF17 C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.20 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 83 of 122
LINE: QF.UPS-IN
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
7,99 14,97 11,59 12,07 14,97 0,9 1 1
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF.UPS-IN C40 N 3+N C 40 40 - 0,4 0,4
Q2.1.21 3+N - - - Embedded AC
DESIGN PHASE: 60% Page 84 of 122
LINE: QF-UPS1
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
6,8 14,49 8,69 9,66 14,49 0,9
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.2.1 3F+N+PE uni 25 61 30 1,08 0,8 by
2 1 phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 10 1x 10 1x 10 45,0 2,97 68,5 16,81 0,32 1,35 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
14,49 41,48 8,46 3,27 1,04 0,94
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF-UPS1 C40 N 3+N C 20 20 - 0,2 0,2
Q2.2.1 3+N - - -
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 85 of 122
LINE: QF-UPS2
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,5 2,41 2,41 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.2.2 F+N+PE uni 10 31 30 0,8 by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 72,0 1,56 95,5 15,39 0,16 1,19 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,41 21,7 4,18 1,15 0,75 0,7
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF-UPS2 C40 a 1+N C 10 10 - 0,1 0,1
Q2.2.2 1+N - - -
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 86 of 122
LINE: QF-UPS3
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,5 2,41 0 2,41 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.2.3 F+N+PE uni 10 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 72,0 1,56 95,5 15,39 0,16 1,19 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,41 21,7 4,18 1,15 0,75 0,7
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF-UPS3 C40 a 1+N C 10 10 - 0,1 0,1
Q2.2.3 1+N - - -
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 87 of 122
LINE: QF-UPS4
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,1 0,48 0 0 0,48 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.2.4 F+N+PE uni 10 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 72,0 1,56 95,5 15,39 0,03 1,05 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,48 21,7 4,18 1,15 0,75 0,7
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF-UPS4 C40 a 1+N C 10 10 - 0,1 0,1
Q2.2.4 1+N - - -
PROTECTIONS VERIFICATIONS
File details come from the government source that posted it. Updated .