This document contains a draft request for proposal (RFP) and pre-solicitation notice for a multiple award construction contract in Italy. The scope of work includes design-build construction services for projects such as grading, utilities infrastructure, building construction and renovation, HVAC, fire suppression and electrical systems at Aviano Air Base. The contract will be awarded as an indefinite delivery indefinite quantity contract with a one year base period and four option years. The minimum guaranteed amount is $2,500 Euro and the maximum aggregate value is estimated at $96 million USD. The minimum task order value is $2,500 and maximum is $7 million. Interested parties must submit any comments on the draft RFP attachments by April 19, 2019 to the 31st Contracting Squadron at Aviano Air Base.

ANNEX E- ELECTRICAL PART 7

View the file

Other files for this federal contract opportunity

Other files attached to Multiple Award Construction Contract (MACC) Italy, newest first.
File Type Posted
38BOQ0~1.PDF PDF
H2UST0~1.PDF PDF
Attachment_5_Past_Performance_Questionnaire_(PPQ)_REV_03.doc DOC document
MACC_Questions_and_Answers_10162019.pdf PDF
Attachment_1_Section_L_REV_01.pdf PDF
Solicitation_Amendment_FA568219RA0010001_SF_30.pdf PDF
ATTACH~4.DOC DOC document
ANNEX_E_-_ELECTRICAL_Part16.pdf PDF
ANNEX_E_-_ELECTRICAL_Part11.pdf PDF
ANNEX_E_-_ELECTRICAL_Part15.pdf PDF
ANNEX_S_-_STRUCTURAL_Part3.pdf PDF
ANNEX_F_-_FIRE_PROTECTION.pdf PDF
ANNEX_S_-_STRUCTURAL_Part6.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_Project)__Part1.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part5.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part15_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part13_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part15_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part1_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part2_Part2.pdf PDF
Attachment_10_ASHE_18-1025_TS__(Seed_project)_Part5.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part13_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part6.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part10_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part9_Part3.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part13_Part3.pdf PDF
Attachment_10_ASHE_18-1025_TS__Part6_Part5_Part2.pdf PDF
Attachment_10_ASHE_18-1025_TS__(Seed_project)_Part3.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part10_Part1.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part1_Part2.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part17.pdf PDF
Attachment_13_Physical_Data.pdf PDF
Attachment_10_ASHE_18-1025_TS_(Seed_project)_Part6_Part6.pdf PDF
Attachment_11_ASHE_18-1025_Drawings_(Seed_project)_Part7.pdf PDF
Attachment_2_Section_M.pdf PDF
Attachment_8_Client_Authorization_Letter.pdf PDF
Attachment_9_Questions_and_Answers.pdf PDF
Attachment_4_Past_Performance_Information_(PPI).pdf PDF
Solicitation_-_FA568219RA001.pdf PDF
Attachment_3_CEN_-MACC_SOW_v3.pdf PDF
Questions_and_Answers_draft_RFP_FA568219RA0001_May_03_2019.pdf PDF
Questions_and_Answers_draft_RFP_FA568219RA0001_May_02_2019.pdf PDF
(draft)_Attachment_10_Questions_and_Answers.pdf PDF
(draft)_Attachment_7_Experience_Information_Sheet.pdf PDF
(draft)_Attachment_6_Experience_Overview_Sheet.pdf PDF
(draft)_Attachment_9_Client_Authorization_Letter.pdf PDF
(draft)_Attachment_1_Section_L__20_March.pdf PDF
Show all 50

Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Aviano Air Base - Building 939 22.02.2018

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #18 TRAINING ROOM / Workplane / Isolinee (E)

Valori in Lux, Scala 1 : 91 Posizione della superficie nel locale:

Superficie utile con 0.400 m Zona margine Punto contrassegnato:

(41.517 m, 2.922 m, 0.760 m)

Reticolo: 32 x 64 Punti

Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax

403 251 537 0.621 0.466

Pagina 114

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #18 TRAINING ROOM / Workplane / Livelli di grigio (E)

Scala 1 : 91 Posizione della superficie nel locale:

Superficie utile con 0.400 m Zona margine Punto contrassegnato:

(41.517 m, 2.922 m, 0.760 m)

Reticolo: 32 x 64 Punti

Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax

403 251 537 0.621 0.466

Pagina 115

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #19 ELECTRIC ROOM / Riepilogo

Altezza locale: 3.300 m, Altezza di montaggio: 3.300 m, Fattore di manutenzione: 0.80

Valori in Lux, Scala 1:18

Superficie r [%] Em [lx] Emin [lx] Emax [lx] Emin / Em

Workplane / 373 340 399 0.912

Floor 20 273 237 302 0.868

Ceiling 80 353 177 782 0.500

Pareti (4) 50 400 112 1282 /

Workplane:

Altezza: 0.500 m Reticolo: 16 x 8 Punti Zona margine: 0.200 m

Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 1.186, Soffitto / superficie utile: 0.947.

Distinta lampade

Potenza allacciata specifica: 14.26 W/m² = 3.82 W/m²/100 lx (Base: 3.33 m²)

No. Pezzo Denominazione (Fattore di correzione) F (Lampada) [lm] F (Lampadine) [lm] P [W]

1 1 Disano Illuminazione SpA 963 44w CLD CELL 963 - Hydro LED - High performance (1.000)

7525 7525 47.5

Totale: 7525 Totale: 7525 47.5

Pagina 116

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #19 ELECTRIC ROOM / Lista pezzi lampade

1 Pezzo Disano Illuminazione SpA 963 44w CLD CELL 963 - Hydro LED - High performance Articolo No.: 963 44w CLD CELL Flusso luminoso (Lampada): 7525 lm Flusso luminoso (Lampadine): 7525 lm Potenza lampade: 47.5 W Classificazione lampade secondo CIE: 94 CIE Flux Code: 44 74 91 94 100 Dotazione: 1 x led_44w_963 (Fattore di correzione 1.000).

Per un'immagine della lampada consultare il nostro catalogo lampade.

Pagina 117

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #19 ELECTRIC ROOM / Risultati illuminotecnici

Flusso luminoso sferico: 7525 lm Potenza totale: 47.5 W Fattore di manutenzione:

0.80

Zona margine: 0.200 m

Superficie Illuminamenti medi [lx] Coefficiente di riflessione [%] Luminanza medio [cd/m²] diretto indiretto totale

Workplane 196 177 373 / /

Floor 141 132 273 20 17

Ceiling 90 264 353 80 90

Wall 1 235 193 428 50 68

Wall 2 161 188 348 50 55

Wall 3 235 193 428 50 68

Wall 4 161 188 349 50 55

Regolarità sulla superficie utile Emin / Em: 0.912 (1:1)

Emin / Emax: 0.854 (1:1)

Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 1.186, Soffitto / superficie utile: 0.947.

Potenza allacciata specifica: 14.26 W/m² = 3.82 W/m²/100 lx (Base: 3.33 m²)

Pagina 118

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #19 ELECTRIC ROOM / Rendering 3D

Pagina 119

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #19 ELECTRIC ROOM / Workplane / Isolinee (E)

Valori in Lux, Scala 1 : 18 Posizione della superficie nel locale:

Superficie utile con 0.200 m Zona margine Punto contrassegnato:

(38.667 m, 12.972 m, 0.500 m)

Reticolo: 16 x 8 Punti

Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax

373 340 399 0.912 0.854

Pagina 120

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #19 ELECTRIC ROOM / Workplane / Livelli di grigio (E)

Scala 1 : 18 Posizione della superficie nel locale:

Superficie utile con 0.200 m Zona margine Punto contrassegnato:

(38.667 m, 12.972 m, 0.500 m)

Reticolo: 16 x 8 Punti

Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax

373 340 399 0.912 0.854

Pagina 121

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #20-22-23 CORRIDORS - 70% lumen / Riepilogo

Altezza locale: 2.600 m, Fattore di manutenzione: 0.85 Valori in Lux, Scala 1:288

Superficie r [%] Em [lx] Emin [lx] Emax [lx] Emin / Em

Workplane / 207 105 298 0.504

Floor 25 200 89 302 0.446

Ceiling 80 69 41 138 0.603

Pareti (20) 55 135 45 464 /

Workplane:

Altezza: 0.000 m Reticolo: 128 x 64 Punti Zona margine: 0.300 m

Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 0.641, Soffitto / superficie utile: 0.331.

Distinta lampade

Potenza allacciata specifica: 3.83 W/m² = 1.84 W/m²/100 lx (Base: 112.92 m²)

No. Pezzo Denominazione (Fattore di correzione) F (Lampada) [lm] F (Lampadine) [lm] P [W]

1 16 Thorn 96628244 BETA OFFICE LED4000- 840 HF Q597 [STD] (Tipo 1)* (1.000)

2890 2890 27.0

*Dati tecnici modificati Totale: 46240 Totale: 46240 432.0

Pagina 122

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #20-22-23 CORRIDORS - 70% lumen / Lista pezzi lampade

16 Pezzo Thorn 96628244 BETA OFFICE LED4000-840 HF Q597 [STD] (Tipo 1) Articolo No.: 96628244 Flusso luminoso (Lampada): 2890 lm Flusso luminoso (Lampadine): 2890 lm Potenza lampade: 27.0 W Classificazione lampade secondo CIE: 100 CIE Flux Code: 58 87 97 100 100 Dotazione: 1 x Definito dall'utente (Fattore di correzione 1.000).

Pagina 123

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #20-22-23 CORRIDORS - 70% lumen / Risultati illuminotecnici

Flusso luminoso sferico: 46240 lm Potenza totale: 432.0 W Fattore di manutenzione:

0.85

Zona margine: 0.300 m

Superficie Illuminamenti medi [lx] Coefficiente di riflessione [%] Luminanza medio [cd/m²] diretto indiretto totale

Workplane 140 67 207 / /

Floor 133 67 200 25 16

Ceiling 0.09 69 69 80 17

Wall 1 66 56 122 55 21

Wall 2 76 65 141 55 25

Wall 3 47 62 110 55 19

Wall 4 79 62 141 55 25

Wall 5 70 56 126 55 22

Wall 6 24 48 72 55 13

Wall 7 52 58 110 55 19

Wall 8 92 81 173 55 30

Wall 9 91 75 166 55 29

Wall 10 47 67 114 55 20

Wall 11 86 80 166 55 29

Wall 12 47 71 118 55 21

Wall 13 95 76 171 55 30

Wall 14 93 85 178 55 31

Wall 15 50 60 109 55 19

Wall 16 38 57 96 55 17

Wall 17 42 57 99 55 17

Wall 18 38 55 93 55 16

Wall 19 57 60 117 55 20

Wall 20 24 46 70 55 12

Regolarità sulla superficie utile Emin / Em: 0.504 (1:2)

Emin / Emax: 0.351 (1:3)

Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 0.641, Soffitto / superficie utile: 0.331.

Potenza allacciata specifica: 3.83 W/m² = 1.84 W/m²/100 lx (Base: 112.92 m²)

Pagina 124

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #20-22-23 CORRIDORS - 70% lumen / Rendering 3D

Pagina 125

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #20-22-23 CORRIDORS - 70% lumen / Workplane / Isolinee (E)

Valori in Lux, Scala 1 : 277 Posizione della superficie nel locale:

Superficie utile con 0.300 m Zona margine Punto contrassegnato:

(2.572 m, 7.852 m, 0.000 m)

Reticolo: 128 x 64 Punti

Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax

207 105 298 0.504 0.351

Pagina 126

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #20-22-23 CORRIDORS - 70% lumen / Workplane / Livelli di grigio (E)

Scala 1 : 277 Posizione della superficie nel locale:

Superficie utile con 0.300 m Zona margine Punto contrassegnato:

(2.572 m, 7.852 m, 0.000 m)

Reticolo: 128 x 64 Punti

Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax

207 105 298 0.504 0.351

Pagina 127

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #24 CORRIDOR - 80% lumen / Riepilogo

Altezza locale: 2.600 m, Altezza di montaggio: 2.785 m, Fattore di manutenzione: 0.85

Valori in Lux, Scala 1:95

Superficie r [%] Em [lx] Emin [lx] Emax [lx] Emin / Em

Workplane / 204 132 255 0.649

Floor 25 194 110 254 0.565

Ceiling 80 76 43 145 0.564

Pareti (4) 55 141 54 467 /

Workplane:

Altezza: 0.000 m Reticolo: 64 x 8 Punti Zona margine: 0.300 m

Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 0.693, Soffitto / superficie utile: 0.371.

Distinta lampade

Potenza allacciata specifica: 4.36 W/m² = 2.14 W/m²/100 lx (Base: 21.14 m²)

No. Pezzo Denominazione (Fattore di correzione) F (Lampada) [lm] F (Lampadine) [lm] P [W]

1 3 Thorn 96628244 BETA OFFICE LED4000- 840 HF Q597 [STD] (Tipo 1)* (1.000)

3300 3300 30.7

*Dati tecnici modificati Totale: 9900 Totale: 9900 92.1

Pagina 128

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #24 CORRIDOR - 80% lumen / Lista pezzi lampade

3 Pezzo Thorn 96628244 BETA OFFICE LED4000-840 HF Q597 [STD] (Tipo 1) Articolo No.: 96628244 Flusso luminoso (Lampada): 3300 lm Flusso luminoso (Lampadine): 3300 lm Potenza lampade: 30.7 W Classificazione lampade secondo CIE: 100 CIE Flux Code: 58 87 97 100 100 Dotazione: 1 x Definito dall'utente (Fattore di correzione 1.000).

Pagina 129

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #24 CORRIDOR - 80% lumen / Risultati illuminotecnici

Flusso luminoso sferico: 9900 lm Potenza totale: 92.1 W Fattore di manutenzione:

0.85

Zona margine: 0.300 m

Superficie Illuminamenti medi [lx] Coefficiente di riflessione [%] Luminanza medio [cd/m²] diretto indiretto totale

Workplane 133 71 204 / /

Floor 126 68 194 25 15

Ceiling 0.00 76 76 80 19

Wall 1 78 69 147 55 26

Wall 2 37 57 94 55 16

Wall 3 78 69 147 55 26

Wall 4 37 57 94 55 16

Regolarità sulla superficie utile Emin / Em: 0.649 (1:2)

Emin / Emax: 0.518 (1:2)

Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 0.693, Soffitto / superficie utile: 0.371.

Potenza allacciata specifica: 4.36 W/m² = 2.14 W/m²/100 lx (Base: 21.14 m²)

Pagina 130

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #24 CORRIDOR - 80% lumen / Rendering 3D

Pagina 131

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #24 CORRIDOR - 80% lumen / Workplane / Isolinee (E)

Valori in Lux, Scala 1 : 95 Posizione della superficie nel locale:

Superficie utile con 0.300 m Zona margine Punto contrassegnato:

(17.292 m, 25.342 m, 0.000 m)

Reticolo: 64 x 8 Punti

Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax

204 132 255 0.649 0.518

Pagina 132

Redattore Bruno Benincà Telefono 348 7494611

Fax e-Mail

Room #24 CORRIDOR - 80% lumen / Workplane / Livelli di grigio (E)

Scala 1 : 95 Posizione della superficie nel locale:

Superficie utile con 0.300 m Zona margine Punto contrassegnato:

(17.292 m, 25.342 m, 0.000 m)

Reticolo: 64 x 8 Punti

Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax

204 132 255 0.649 0.518

Pagina 133