This pre-solicitation notice is for multiple indefinite delivery indefinite quantity construction contracts for design-build services in Italy. The scope of work includes repair, alteration, renovation, maintenance, and minor construction projects across multiple trades at Aviano Air Base. Work may include grading, utilities infrastructure, buildings, HVAC systems, fire suppression, fuel systems, generators, communications systems, and asbestos abatement. The base period is one year with four option years. The minimum contract value is $2,500 and the maximum for all contracts combined is $96 million. The minimum task order value is $2,500 and maximum is $7 million. Interested parties must submit any comments on the draft attachments by April 19, 2019. The solicitation is expected to be issued on www.fbo.gov in May 2019. The North American Industry Classification System code is 236220 and work will primarily be located in Italy.
ANNEX E- ELECTRICAL PART 17
View the file
Other files for this federal contract opportunity
Show all 50
Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT: ASHE 18-1025
RENOVATE/EXPAND FAC. 939
DESIGN PHASE: 60% Page 88 of 122
CALCULATIONS AND VERIFICATIONS
DISTRIBUTION BOARD: [B939-MDP-2] B939-MDP-2
LINE: QF-UPS5
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,1 0,48 0,48 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other circuits
K
L2.2.5 F+N+PE uni 10 31 30 -side by
2 1
Conductors cross-section [mm2] phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 72,0 1,56 95,5 15,39 0,03 1,05 4
Ib
[A] Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
[kA]
0,48 21,7 4,18 1,15 0,75 0,7
Designation
FG16R16-0,6/1 kV - Cca-s3,d1,a3/Cu
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF-UPS5 C40 a 1+N C 10 10 - 0,1 0,1
Q2.2.5 1+N - - -
PROTECTIONS VERIFICATIONS
Overload Maximum short-circuit Minimum short-circuit Indirect contact
SI SI SI SI
DESIGN PHASE: 60% Page 89 of 122
DISTRIBUTION BOARD: [B939-MDP-UPS] B939-MDP-UPS
LINE: 1
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
6,8 14,49 8,69 9,66 14,49 0,9 1
SWITCH-DISCONNECTOR
Initialling/
Description Type In [A] Uimp [kV] Icm [kA peak] Icw [kA rms]
Upstream circuit-breaker protection [kA]
S1 iSW 40 6 0,00 0,00 10
DESIGN PHASE: 60% Page 90 of 122
LINE: QF.UPS1
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 5,79 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L3.1.1 F+N+PE uni 40 31 30 -by
8 1 phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 180,0 5,72 248,5 22,53 1,02 2,37 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
5,79 21 1,58 0,45 0,29 0,28
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF.UPS1 C40 a 1+N C 16 16 - 0,16 0,16
Q3.1.1 1+N - - -
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 91 of 122
LINE: QF.UPS2
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
2 9,66 0 9,66 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L3.1.2 F+N+PE uni 40 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 180,0 5,72 248,5 22,53 1,7 3,05 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
9,66 21 1,58 0,45 0,29 0,28
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF.UPS2 C40 a 1+N C 16 16 - 0,16 0,16
Q3.1.2 1+N - - -
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 92 of 122
LINE: QF.UPS3
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,5 7,24 0 0 7,24 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L3.1.3 F+N+PE uni 10 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 45,0 1,43 113,5 18,24 0,31 1,67 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
7,24 21 1,58 0,98 0,63 0,59
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF.UPS3 C40 a 1+N C 16 16 - 0,16 0,16
Q3.1.3 1+N - - -
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 93 of 122
LINE: QF.UPS4
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,5 7,24 0 0 7,24 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L3.1.4 F+N+PE uni 10 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 45,0 1,43 113,5 18,24 0,31 1,67 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
7,24 21 1,58 0,98 0,63 0,59
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF.UPS4 C40 a 1+N C 16 16 - 0,16 0,16
Q3.1.4 1+N - - -
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 94 of 122
LINE: QF.UPS5
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,5 2,41 2,41 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L3.1.5 F+N+PE uni 10 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 45,0 1,43 113,5 18,24 0,1 1,45 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,41 21 1,58 0,98 0,63 0,59
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF.UPS5 C40 a 1+N C 10 10 - 0,1 0,1
Q3.1.5 1+N - - -
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 95 of 122
LINE: QF.UPS6
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,1 0,48 0,48 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L3.1.6 F+N+PE uni 10 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 45,0 1,43 113,5 18,24 0,02 1,37 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,48 21 1,58 0,98 0,63 0,59
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF.UPS6 C40 a 1+N C 10 10 - 0,1 0,1
Q3.1.6 1+N - - -
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 96 of 122
DISTRIBUTION BOARD: [B939-PB.BR] B939-PB.BR
LINE: PB.BR-MAIN
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
2,5 4,02 4,02 4,02 4,02 0,9 1
SWITCH-DISCONNECTOR
Initialling/
Description Type In [A] Uimp [kV] Icm [kA peak] Icw [kA rms]
Upstream circuit-breaker
S1 INS40 40 8 15,00 3,00 10
DESIGN PHASE: 60% Page 97 of 122
DISTRIBUTION BOARD: [B939-PB.BR] B939-PB.BR
LINE: 2
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
2,5 4 4 4 4 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L4.1.1 3F+N+PE uni 1 11 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 7,2 0,16 62,85 13,49 0,01 0,83 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
4 33 4,03 3,59 1,14 1,14
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 98 of 122
DISTRIBUTION BOARD: [B939-PB.AHU1] B939-PB.AHU1
LINE: PB.AHU1-MAIN
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
5 8,05 8,05 8,05 8,05 0,9 1
SWITCH-DISCONNECTOR
Initialling/
Description Type In [A] Uimp [kV] Icm [kA peak] Icw [kA rms]
Upstream circuit-breaker
S1 iSW 40 6 0,00 0,00 5
DESIGN PHASE: 60% Page 99 of 122
DISTRIBUTION BOARD: [B939-PB.AHU1] B939-PB.AHU1
LINE: AHU1
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
5 8,01 8,01 8,01 8,01 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L5.1.1 3F+N+PE uni 1 11 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 7,2 0,16 92,85 14,84 0,02 1,05 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
8,01 33 2,65 2,45 0,77 0,77
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 100 of 122
DISTRIBUTION BOARD: [B939-PB.AHU2] B939-PB.AHU2
LINE: PB.AHU2-MAIN
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
4 6,44 6,44 6,44 6,44 0,89 1
SWITCH-DISCONNECTOR
Initialling/
Description Type In [A] Uimp [kV] Icm [kA peak] Icw [kA rms]
Upstream circuit-breaker
S1 iSW 40 6 0,00 0,00 5
DESIGN PHASE: 60% Page 101 of 122
DISTRIBUTION BOARD: [B939-PB.AHU2] B939-PB.AHU2
LINE: 2
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
4 6,41 6,41 6,41 6,41 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L6.1.1 3F+N+PE uni 1 11 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 7,2 0,16 92,85 14,84 0,02 0,99 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
6,41 33 2,65 2,45 0,77 0,77
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 102 of 122
DISTRIBUTION BOARD: [B939-PB.SPR] B939-PB.SPR
LINE: PB-SPR-MAIN
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,3 1,44 0 0 1,44 0,9 1
SWITCH-DISCONNECTOR
Initialling/
Description Type In [A] Uimp [kV] Icm [kA peak] Icw [kA rms]
Upstream circuit-breaker
S1 iSW 20 6 0,00 0,00
DESIGN PHASE: 60% Page 103 of 122
DISTRIBUTION BOARD: [B939-PB.SPR] B939-PB.SPR
LINE: SPRINKLER ROOM
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,3 1,44 0 0 1,44 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L7.1.1 F+N+PE uni 1 13 30 1 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 1,5 1x 1,5 1x 1,5 12,0 0,17 247,65 18,63 0,01 1,07 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,44 27 0,48 0,45 0,29 0,29
PROTECTIONS VERIFICATIONS
END of the DOCUMENT