This document is a pre-solicitation notice for an indefinite delivery indefinite quantity multiple award construction contract for design-build construction services in Italy. The scope of work will primarily involve design, repair, alteration, renovation, maintenance, and minor construction projects across multiple trades at Aviano Air Base. Services may include grading, utilities infrastructure, building construction and renovation, HVAC, electrical, fire suppression, fuel systems, generators, communications systems, and asbestos abatement. The base period is one year with four option years, and the minimum guaranteed amount is $2,500 Euro equivalent. The total maximum value for all awarded contracts is estimated at $96 million. The minimum task order value is $2,500 while the maximum is $7 million. Comments on the draft solicitation attachments are due by April 19, 2019 to the 31st Contracting Squadron at Aviano Air Base. The Department of the Air Force United States Air Forces in Europe - Air Forces Africa will issue the solicitation on www.fbo.gov in May 2019.
ANNEX E- ELECTRICAL PART 11
View the file
Other files for this federal contract opportunity
Show all 50
Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Aviano Air Base - Building 939 22.02.2018
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #20-22-23 CORRIDORS - Emergency / Workplane / Livelli di grigio (E)
Scala 1 : 277 Posizione della superficie nel locale:
Superficie utile con 0.300 m Zona margine Punto contrassegnato:
(2.572 m, 7.852 m, 0.000 m)
Reticolo: 128 x 64 Punti
Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax
11 2.11 21 0.191 0.101
Pagina 194
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR -Emergency / Riepilogo
Altezza locale: 2.600 m, Altezza di montaggio: 2.785 m, Fattore di manutenzione: 0.85
Valori in Lux, Scala 1:95
Superficie r [%] Em [lx] Emin [lx] Emax [lx] Emin / Em
Workplane / 9.81 3.59 16 0.366
Floor 0 9.08 2.54 16 0.280
Ceiling 0 0.00 0.00 0.00 0.000
Pareti (4) 0 6.21 0.04 50 /
Workplane:
Altezza: 0.000 m Reticolo: 128 x 8 Punti Zona margine: 0.400 m
Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 0.635, Soffitto / superficie utile: 0.000.
Distinta lampade
Potenza allacciata specifica: 0.00 W/m² = 0.00 W/m²/ lx (Base: 21.14 m²)
No. Pezzo Denominazione (Fattore di correzione) F (Lampada) [lm] F (Lampadine) [lm] P [W]
1 2 LINERGY s.r.l. EL18N10EBRT
EVOLUTION LED 415LM 1H SE IP42
ENERGY TEST (1.000)
398 398 0.0
Totale: 796 Totale: 796 0.0
Pagina 195
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR -Emergency / Lista pezzi lampade
2 Pezzo LINERGY s.r.l. EL18N10EBRT EVOLUTION LED
415LM 1H SE IP42 ENERGY TEST
Articolo No.: EL18N10EBRT Flusso luminoso (Lampada): 398 lm Flusso luminoso (Lampadine): 398 lm Potenza lampade: 0.0 W Classificazione lampade secondo CIE: 99 CIE Flux Code: 47 80 97 99 100 Dotazione: 1 x 20LED (Fattore di correzione 1.000).
Per un'immagine della lampada consultare il nostro catalogo lampade.
Pagina 196
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR -Emergency / Risultati illuminotecnici
Flusso luminoso sferico: 796 lm Potenza totale: 0.0 W Fattore di manutenzione:
0.85
Zona margine: 0.400 m
Superficie Illuminamenti medi [lx] Coefficiente di riflessione [%] Luminanza medio [cd/m²] diretto indiretto totale
Workplane 9.81 0.00 9.81 / /
Floor 9.08 0.00 9.08 0 0.00
Ceiling 0.00 0.00 0.00 0 0.00
Wall 1 6.78 0.00 6.78 0 0.00
Wall 2 2.38 0.00 2.38 0 0.00
Wall 3 6.60 0.00 6.60 0 0.00
Wall 4 2.26 0.00 2.26 0 0.00
Regolarità sulla superficie utile Emin / Em: 0.366 (1:3)
Emin / Emax: 0.230 (1:4)
Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 0.635, Soffitto / superficie utile: 0.000.
Potenza allacciata specifica: 0.00 W/m² = 0.00 W/m²/ lx (Base: 21.14 m²)
Pagina 197
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR -Emergency / Rendering 3D
Pagina 198
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR -Emergency / Workplane / Isolinee (E)
Valori in Lux, Scala 1 : 95 Posizione della superficie nel locale:
Superficie utile con 0.400 m Zona margine Punto contrassegnato:
(17.392 m, 25.442 m, 0.000 m)
Reticolo: 128 x 8 Punti
Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax
9.81 3.59 16 0.366 0.230
Pagina 199
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR -Emergency / Workplane / Livelli di grigio (E)
Scala 1 : 95 Posizione della superficie nel locale:
Superficie utile con 0.400 m Zona margine Punto contrassegnato:
(17.392 m, 25.442 m, 0.000 m)
Reticolo: 128 x 8 Punti
Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax
9.81 3.59 16 0.366 0.230
Pagina 200
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #20-22-23 CORRIDORS - 20% NIGHT / Riepilogo
Altezza locale: 2.600 m, Fattore di manutenzione: 0.85 Valori in Lux, Scala 1:288
Superficie r [%] Em [lx] Emin [lx] Emax [lx] Emin / Em
Workplane / 59 30 85 0.504
Floor 25 57 25 86 0.446
Ceiling 80 20 12 39 0.603
Pareti (20) 55 39 13 133 /
Workplane:
Altezza: 0.000 m Reticolo: 128 x 64 Punti Zona margine: 0.300 m
Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 0.641, Soffitto / superficie utile: 0.331.
Distinta lampade
Potenza allacciata specifica: 1.13 W/m² = 1.91 W/m²/100 lx (Base: 112.92 m²)
No. Pezzo Denominazione (Fattore di correzione) F (Lampada) [lm] F (Lampadine) [lm] P [W]
1 16 Thorn 96628244 BETA OFFICE LED4000- 840 HF Q597 [STD] (Tipo 1)* (1.000)
825 825 8.0
*Dati tecnici modificati Totale: 13200 Totale: 13200 128.0
Pagina 201
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #20-22-23 CORRIDORS - 20% NIGHT / Lista pezzi lampade
16 Pezzo Thorn 96628244 BETA OFFICE LED4000-840 HF Q597 [STD] (Tipo 1) Articolo No.: 96628244 Flusso luminoso (Lampada): 825 lm Flusso luminoso (Lampadine): 825 lm Potenza lampade: 8.0 W Classificazione lampade secondo CIE: 100 CIE Flux Code: 58 87 97 100 100 Dotazione: 1 x Definito dall'utente (Fattore di correzione 1.000).
Pagina 202
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #20-22-23 CORRIDORS - 20% NIGHT / Risultati illuminotecnici
Flusso luminoso sferico: 13200 lm Potenza totale: 128.0 W Fattore di manutenzione:
0.85
Zona margine: 0.300 m
Superficie Illuminamenti medi [lx] Coefficiente di riflessione [%] Luminanza medio [cd/m²] diretto indiretto totale
Workplane 40 19 59 / /
Floor 38 19 57 25 4.54
Ceiling 0.03 20 20 80 4.99
Wall 1 19 16 35 55 6.08
Wall 2 22 18 40 55 7.02
Wall 3 14 18 31 55 5.47
Wall 4 22 18 40 55 7.02
Wall 5 20 16 36 55 6.31
Wall 6 6.98 14 21 55 3.60
Wall 7 15 16 31 55 5.50
Wall 8 26 23 49 55 8.65
Wall 9 26 21 47 55 8.28
Wall 10 13 19 33 55 5.70
Wall 11 25 23 47 55 8.30
Wall 12 13 20 34 55 5.88
Wall 13 27 22 49 55 8.55
Wall 14 26 24 51 55 8.88
Wall 15 14 17 31 55 5.47
Wall 16 11 16 27 55 4.79
Wall 17 12 16 28 55 4.97
Wall 18 11 16 27 55 4.66
Wall 19 16 17 33 55 5.82
Wall 20 6.92 13 20 55 3.51
Regolarità sulla superficie utile Emin / Em: 0.504 (1:2)
Emin / Emax: 0.351 (1:3)
Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 0.641, Soffitto / superficie utile: 0.331.
Potenza allacciata specifica: 1.13 W/m² = 1.91 W/m²/100 lx (Base: 112.92 m²)
Pagina 203
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #20-22-23 CORRIDORS - 20% NIGHT / Rendering 3D
Pagina 204
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #20-22-23 CORRIDORS - 20% NIGHT / Workplane / Isolinee (E)
Valori in Lux, Scala 1 : 277 Posizione della superficie nel locale:
Superficie utile con 0.300 m Zona margine Punto contrassegnato:
(2.572 m, 7.852 m, 0.000 m)
Reticolo: 128 x 64 Punti
Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax
59 30 85 0.504 0.351
Pagina 205
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #20-22-23 CORRIDORS - 20% NIGHT / Workplane / Livelli di grigio (E)
Scala 1 : 277 Posizione della superficie nel locale:
Superficie utile con 0.300 m Zona margine Punto contrassegnato:
(2.572 m, 7.852 m, 0.000 m)
Reticolo: 128 x 64 Punti
Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax
59 30 85 0.504 0.351
Pagina 206
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR - 20% NIGHT / Riepilogo
Altezza locale: 2.600 m, Altezza di montaggio: 2.785 m, Fattore di manutenzione: 0.85
Valori in Lux, Scala 1:95
Superficie r [%] Em [lx] Emin [lx] Emax [lx] Emin / Em
Workplane / 51 33 64 0.649
Floor 25 49 27 64 0.565
Ceiling 80 19 11 36 0.564
Pareti (4) 55 35 13 117 /
Workplane:
Altezza: 0.000 m Reticolo: 64 x 8 Punti Zona margine: 0.300 m
Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 0.693, Soffitto / superficie utile: 0.371.
Distinta lampade
Potenza allacciata specifica: 1.14 W/m² = 2.23 W/m²/100 lx (Base: 21.14 m²)
No. Pezzo Denominazione (Fattore di correzione) F (Lampada) [lm] F (Lampadine) [lm] P [W]
1 3 Thorn 96628244 BETA OFFICE LED4000- 840 HF Q597 [STD] (Tipo 1)* (1.000)
825 825 8.0
*Dati tecnici modificati Totale: 2475 Totale: 2475 24.0
Pagina 207
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR - 20% NIGHT / Lista pezzi lampade
3 Pezzo Thorn 96628244 BETA OFFICE LED4000-840 HF Q597 [STD] (Tipo 1) Articolo No.: 96628244 Flusso luminoso (Lampada): 825 lm Flusso luminoso (Lampadine): 825 lm Potenza lampade: 8.0 W Classificazione lampade secondo CIE: 100 CIE Flux Code: 58 87 97 100 100 Dotazione: 1 x Definito dall'utente (Fattore di correzione 1.000).
Pagina 208
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR - 20% NIGHT / Risultati illuminotecnici
Flusso luminoso sferico: 2475 lm Potenza totale: 24.0 W Fattore di manutenzione:
0.85
Zona margine: 0.300 m
Superficie Illuminamenti medi [lx] Coefficiente di riflessione [%] Luminanza medio [cd/m²] diretto indiretto totale
Workplane 33 18 51 / /
Floor 32 17 49 25 3.86
Ceiling 0.00 19 19 80 4.81
Wall 1 19 17 37 55 6.42
Wall 2 9.15 14 23 55 4.11
Wall 3 19 17 37 55 6.42
Wall 4 9.15 14 23 55 4.11
Regolarità sulla superficie utile Emin / Em: 0.649 (1:2)
Emin / Emax: 0.518 (1:2)
Rapporto di illuminamento (secondo LG7): Pareti / superficie utile: 0.693, Soffitto / superficie utile: 0.371.
Potenza allacciata specifica: 1.14 W/m² = 2.23 W/m²/100 lx (Base: 21.14 m²)
Pagina 209
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR - 20% NIGHT / Rendering 3D
Pagina 210
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR - 20% NIGHT / Workplane / Isolinee (E)
Valori in Lux, Scala 1 : 95 Posizione della superficie nel locale:
Superficie utile con 0.300 m Zona margine Punto contrassegnato:
(17.292 m, 25.342 m, 0.000 m)
Reticolo: 64 x 8 Punti
Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax
51 33 64 0.649 0.518
Pagina 211
Redattore Bruno Benincà Telefono 348 7494611
Fax e-Mail
Room #24 CORRIDOR - 20% NIGHT / Workplane / Livelli di grigio (E)
Scala 1 : 95 Posizione della superficie nel locale:
Superficie utile con 0.300 m Zona margine Punto contrassegnato:
(17.292 m, 25.342 m, 0.000 m)
Reticolo: 64 x 8 Punti
Em [lx] Emin [lx] Emax [lx] Emin / Em Emin / Emax
51 33 64 0.649 0.518
Pagina 212
PROJECT: ASHE 18-1025
RENOVATE/EXPAND FAC. 939
EXTERIOR AREA LIGHTING CALCULATIONS
CALCOLI ILLUMINOTECNICI D’ESTERNI