ANNEX_A-D_-_MECHANICAL_Part2.pdf
PDF 2 MB Posted
- Attached to
- Multiple Award Construction Contract (MACC) Italy Federal contract opportunity
- Solicitation number
- FA568219RA001
About this file
This document is a pre-solicitation notice for an indefinite delivery indefinite quantity multiple award construction contract for design-build construction services in Italy. The scope of work will primarily involve design, repair, alteration, renovation, maintenance, and minor construction projects across multiple trades at Aviano Air Base. Work may include grading, utilities, painting, roofing, building construction, electrical systems, HVAC, refrigeration, fire suppression, fuel systems, power generation, communications, abatement, and site work. The contract will be awarded competitively using best value tradeoff. The minimum guarantee is 2500 Euros payable after mandatory training, and the maximum total value for all contracts is estimated at 96 million Euros. The minimum task order value is 2500 Euros and maximum is 7 million Euros. Comments on the draft attachments are due by April 19, 2019. The solicitation will be issued on FBO and no paper copies will be provided.
The document is a pre-solicitation notice for a multiple award construction contract at Aviano Air Base in Italy. The scope of work involves design, repair, renovation, maintenance, and minor construction across various trades. Specific work may include utilities, buildings, electrical systems, HVAC, and site work. Contracts will be awarded using best value tradeoff. The minimum guarantee is 2500 Euros after training, and maximum total value is 96 million Euros. The minimum task order is 2500 Euros and maximum is 7 million Euros. Comments on draft attachments are due by April 19, 2019, and the solicitation will be on FBO with no paper copies.
ANNEX A-D MECHANICAL PART 2
View the file
Other files for this federal contract opportunity
Show all 50
Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 59
COMPONENTE PONTE TERMICO
Codice PT_1_N Descrizione Window Thermal bridge Note Origine dei dati Da abaco CENED
DATI PONTE TERMICO
Archetipo Parete esterna con serramento Tipologia Serramento a filo interno su parete isolata all'esterno, con risvolto dell'isolante Descrizione Ponte termico formato dal contatto tra serramento e parete isolata dall'esterno, serramento a filo interno a contatto con risvolto dell'isolante
Dimensioni Interne
Trasmittanza termica lineica [W/(m·K)] 0,035
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 60
Codice PT_2 Descrizione thermal bridge wall-roof Note Origine dei dati Da abaco CENED
DATI PONTE TERMICO
Archetipo Parete verticale con copertura piana Tipologia Parete isolata all'esterno con copertura isolata e trave isolata Descrizione Ponte termico formato dalla giunzione di una parete isolata dall'esterno con una copertura piana isolata superiormente, con trave isolata
Trasmittanza termica lineica [W/(m·K)] 0,046
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 61
Codice PT_2_N Descrizione thermal bridge wall-roof Note Origine dei dati Da abaco CENED
DATI PONTE TERMICO
Archetipo Parete verticale con copertura piana Tipologia Parete isolata all'esterno con copertura isolata e trave isolata Descrizione Ponte termico formato dalla giunzione di una parete isolata dall'esterno con una copertura piana isolata superiormente, con trave isolata
Trasmittanza termica lineica [W/(m·K)] -0,032
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 62
Codice PT_3 Descrizione Corner thermal bridge Note Origine dei dati Inserimento manuale
DATI PONTE TERMICO
Trasmittanza termica lineica [W/(m·K)] 0,077
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 63
Codice PT_3_N Descrizione Corner thermal bridge Note Origine dei dati Inserimento manuale
Trasmittanza termica lineica [W/(m·K)] 0,077
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 64
Codice PT_4 Descrizione roof ridge Thermal bridge Note Origine dei dati Da abaco CENED
DATI PONTE TERMICO
Archetipo Displuvi di copertura Tipologia Displuvio isolato esternamente Descrizione Ponte termico, di tipo geometrico, formato dal displuvio di una copertura isolata esternamente
Trasmittanza termica lineica [W/(m·K)] 0,003
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 65
Codice PT_5 Descrizione Thermal bridge - existing column on the wall Note design Origine dei dati Inserimento manuale
Trasmittanza termica lineica [W/(m·K)] 0,072
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 66
COMPONENTE FINESTRATO
Codice FIN_01 Descrizione Window 1.93x1.56 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,613 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 1,93 Altezza m 1,56
Dati apporti solari:
Emissività 0,100 Trasmittanza solare g gl,n 0,34
TELAIO
Serramento interno:
Area vetro Ag m² 2,250 Area telaio Af m² 0,760 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 8,820 Trasmittanza termica telaio Uf W/(m²·K) 2,500
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,620 Trasmittanza termica W/(m²·K) 1,613 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,613
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,613 Verifica trasmittanza Positiva
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 67
Codice FIN_01 Descrizione Window 1.93x1.56
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,835 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 fRsi 0,47 si [°C] 16,71
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 68
Codice FIN_02 Descrizione Window 0.87x1.56 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,650 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 0,87 Altezza m 1,56
Dati apporti solari:
Area vetro Ag m² 0,990 Area telaio Af m² 0,360 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 4,220 Trasmittanza termica telaio Uf W/(m²·K) 2,500
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,606 Trasmittanza termica W/(m²·K) 1,650 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,650
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,650
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 69
Codice FIN_02 Descrizione Window 0.87x1.56
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,832 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,65
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 70
Codice FIN_03 Descrizione Window 1.2X1.2 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,798 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 1,20 Altezza m 1,20
Dati apporti solari:
Area vetro Ag m² 0,920 Area telaio Af m² 0,520 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 5,920 Trasmittanza termica telaio Uf W/(m²·K) 2,300
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,556 Trasmittanza termica W/(m²·K) 1,798 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,798
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,798
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 71
Codice FIN_03 Descrizione Window 1.2X1.2
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,821 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,42
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 72
Codice FIN_04 Descrizione Window 1.2X0.6 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,618 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 1,20 Altezza m 0,60
Dati apporti solari:
Area vetro Ag m² 0,460 Area telaio Af m² 0,260 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 2,960 Trasmittanza termica telaio Uf W/(m²·K) 1,800
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,618 Trasmittanza termica W/(m²·K) 1,618 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,618
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,618
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 73
Codice FIN_04 Descrizione Window 1.2X0.6
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,835 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,70
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 74
Codice FIN_05 Descrizione Window 0.6X1.2 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,618 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 0,60 Altezza m 1,20
Dati apporti solari:
Area vetro Ag m² 0,460 Area telaio Af m² 0,260 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 2,960 Trasmittanza termica telaio Uf W/(m²·K) 1,800
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,618 Trasmittanza termica W/(m²·K) 1,618 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,618
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,618
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 75
Codice FIN_05 Descrizione Window 0.6X1.2
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,835 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,70
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 76
Codice FIN_06 Descrizione Window 1.8x1.2 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,694 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 1,80 Altezza m 1,20
Dati apporti solari:
Area vetro Ag m² 1,540 Area telaio Af m² 0,620 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 7,120 Trasmittanza termica telaio Uf W/(m²·K) 2,500
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,590 Trasmittanza termica W/(m²·K) 1,694 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,694
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,694
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 77
Codice FIN_06 Descrizione Window 1.8x1.2
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,829 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,58
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 78
Codice FIN_07 Descrizione Window 2.59x1.8 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 0,589 Trasmittanza solo vetro Ug W/(m²·K) 0,100
Dimensioni del serramento:
Larghezza m 2,59 Altezza m 1,80
Dati apporti solari:
Area vetro Ag m² 3,990 Area telaio Af m² 0,680 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 8,140 Trasmittanza termica telaio Uf W/(m²·K) 2,500
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 0,100 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 1,698 Trasmittanza termica W/(m²·K) 0,589 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 0,589
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 0,589
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 79
Codice FIN_07 Descrizione Window 2.59x1.8
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,930 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 18,61
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 80
Codice FIN_08 Descrizione Window 0.66x1,56 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,551 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 0,66 Altezza m 1,56
Dati apporti solari:
Area vetro Ag m² 0,700 Area telaio Af m² 0,330 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 3,800 Trasmittanza termica telaio Uf W/(m²·K) 1,800
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,645 Trasmittanza termica W/(m²·K) 1,551 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,551
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,551
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 81
Codice FIN_08 Descrizione Window 0.66x1,56
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,840 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,81
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 82
Codice PFIN_01 Descrizione Window door 1.25x2.20 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,778 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 1,20 Altezza m 2,20
Dati apporti solari:
Area vetro Ag m² 1,800 Area telaio Af m² 0,840 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 9,920 Trasmittanza termica telaio Uf W/(m²·K) 2,500
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,562 Trasmittanza termica W/(m²·K) 1,778 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,778
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,778
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 83
Codice PFIN_01 Descrizione Window door 1.25x2.20
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,822 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,45
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 84
Codice PFIN_02 Descrizione Window door 1.2x2.20 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,482 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 1,20 Altezza m 2,20
Dati apporti solari:
Area vetro Ag m² 2,120 Area telaio Af m² 0,520 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 6,160 Trasmittanza termica telaio Uf W/(m²·K) 2,500
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,675 Trasmittanza termica W/(m²·K) 1,482 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,482
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,482
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 85
Codice PFIN_02 Descrizione Window door 1.2x2.20
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,846 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,92
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 86
Codice PFIN_03 Descrizione Window door 1.5x2.20 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,660 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 1,50 Altezza m 2,20
Dati apporti solari:
Area vetro Ag m² 2,410 Area telaio Af m² 0,890 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 10,520 Trasmittanza termica telaio Uf W/(m²·K) 2,500
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,602 Trasmittanza termica W/(m²·K) 1,660 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,660
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,660
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 87
Codice PFIN_03 Descrizione Window door 1.5x2.20
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,832 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,63
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 88
Codice PFIN_04 Descrizione Window door 1.8x2.20 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,581 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 1,80 Altezza m 2,20
Dati apporti solari:
Area vetro Ag m² 3,020 Area telaio Af m² 0,940 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 11,120 Trasmittanza termica telaio Uf W/(m²·K) 2,500
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,633 Trasmittanza termica W/(m²·K) 1,581 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,581
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,581
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 89
Codice PFIN_04 Descrizione Window door 1.8x2.20
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,838 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,76
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 90
Codice PFIN_05 Descrizione Window door 1.6x2.2 Note design Origine dei dati Procedura analitica (UNI EN ISO 10077-1:2007)
Caratteristiche del serramento:
Tipo di serramento Finestra singola Trasmittanza termica Uw W/(m²·K) 1,631 Trasmittanza solo vetro Ug W/(m²·K) 1,000
Dimensioni del serramento:
Larghezza m 1,60 Altezza m 2,20
Dati apporti solari:
Area vetro Ag m² 2,610 Area telaio Af m² 0,910 Area pannelli Ap m² 0,000 Perimetro vetro Lg m 10,720 Trasmittanza termica telaio Uf W/(m²·K) 2,500
VETRO
Serramento:
Trasmittanza termica vetro W/(m²·K) 1,000 Trasmittanza termica distanziatore W/(m·K) 0,080
RISULTATI
Resistenza m²·K/W 0,613 Trasmittanza termica W/(m²·K) 1,631 Resistenza termica aggiuntiva m²·K/W 0,000 Trasmittanza totale W/(m²·K) 1,631
VERIFICA DI TRASMITTANZA TERMICA
Riferimento normativo 2015 Verifica limiti come Verso l'esterno e verso ambienti non climatizzati Zona climatica E Trasmittanza limite [W/(m²·K)] 1,800 Trasmittanza termica [W/(m²·K)] 1,631
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 91
Codice PFIN_05 Descrizione Window door 1.6x2.2
VERIFICA IGROMETRICA
Condizioni al contorno
Ambiente confinante Esterno Temperatura esterna UNI 10349 - Media mensile Umidità relativa esterna UNI 10349 - Media mensile Temperatura interna UNI EN ISO 13788 N.A. 1.2 Struttura leggera Si Classe di umidità 2 - Uffici, negozi Media delle temperature esterne minime annuali 0,0 °C
GEN FEB MAR APR MAG GIU LUG AGO SET OTT NOV DIC
e [°C] 1,98 3,88 7,78 12,08 17,88 21,48 22,78 21,48 17,48 12,68 7,98 3,78 pe [Pa] 553 630 774 925 1.378 1.645 1.888 1.930 1.480 1.200 932 651 i [°C] 20,00 20,00 20,00 20,00 20,00 21,48 22,78 21,48 20,00 20,00 20,00 20,00 pi [Pa] 1.089 1.108 1.137 1.160 1.441 1.645 1.888 1.930 1.555 1.418 1.289 1.133
Verifica della temperatura superficiale (UNI EN ISO 13788 §5)
Mese critico - Fattore di temperatura, fRsi 0,834 Fattore di temperatura massimo, fRsi,max 0,467 Il componente non è soggetto a fenomeni di condensa superficiale.
Verifica Positiva
Risultati di calcolo e [°C] 0,00 pe [Pa] 580 i [°C] 20,00 pi [Pa] 1.174 ps [Pa] 1.174 si,min [°C] 9,34 si [°C] 16,68
20/02/2018 12:25:20 AERMEC MC Impianti 11300 Pagina 92
Simboli e unità di misura
Simbolo Quantità Unità di misura cp capacità termica specifica J/(kg·K) Ag area (vetro) m² Af area (telaio) m² Ap area (pannello) m² C conduttanza unitaria W/(m²·K) d spessore m fRsi fattore di temperatura in corrispondenza alla superficie interna -fRsi,max fattore di temperatura di progetto in corrispondenza alla superficie interna per il mese critico -gc densità di flusso di vapore (condensazione) Kg/m² gev densità di flusso di vapore (evaporazione) Kg/m² Uf trasmittanza termica (telaio) W/(m²·K) Ug trasmittanza termica (elemento vetrato) W/(m²·K) Ψg trasmittanza termica (lineare del distanziatore) W/(m²·K) Up trasmittanza termica (pannello) W/(m²·K) Uw trasmittanza termica (totale del serramento) W/(m²·K) Lg lunghezza perimetrale della superficie vetrata m Ma massa di vapore per unità di superficie accumulata in corrispondenza di un’interfaccia Kg/m² pi pressione parziale del vapore (aria interna) Pa pe pressione parziale del vapore (aria esterna) Pa R resistenza termica di progetto (da superficie a superficie) m²·K/W
Rsi resistenza superficiale (interna) m²·K/W Rse resistenza superficiale (esterna) m²·K/W sd spessore equivalente di aria per la diffusione del vapore m λ conduttività utile di calcolo W/(m·K) µ fattore di resistenza igroscopica -ρ massa volumica Kg/m³ i temperatura (aria interna) °C e temperatura (aria esterna) °C t sfasamento h
Calcoli eseguiti con il software IRIS 4.1 1
Progetto: Renovate /Expand Fac. 939 for EOD
Committente 31st Fighter Wing Indirizzo Aviano Air Base Telefono E-mail Calcolo eseguito da Commento
Località: Saccolongo (PN)
Descrizione Coefficiente lineico interno [W/m K]
Coefficiente lineico esterno [W/m K]
Rischio condensa
Rischio muffa
1 PT_3N 0,077 -0,087
2 PT_5 - existing column on the wall 0,072 0,072 3 PT_6 - new column on the wall 0,028 0,028 4 linda 0,244 0,073
Calcoli eseguiti con il software IRIS 4.1 2
Ponte: PT_3N
Descrizione ponte Parete inferiore
Materiale Conduttività [W/m K]
Fattore di resistenza al vapore
Spessore [m]
1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 0,120 2 Calcestruzzo - 2400 kg/m³ 2,000 80 0,250 3 Pannello in lana di roccia (densità 40 kg/m³ ) 0,035 1 0,060 4 Cartongesso (densità 700 kg/m³) 0,210 4 0,025
Parete superiore Materiale Conduttività
[W/m K] Fattore di resistenza al vapore
Spessore [m]
1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 0,120 2 Calcestruzzo - 2400 kg/m³ 2,000 80 0,250 3 Pannello in lana di roccia (densità 40 kg/m³ ) 0,035 1 0,060 4 Cartongesso (densità 700 kg/m³) 0,210 4 0,025
Nodo Materiale Conduttività
[W/m K] Fattore di resistenza al vapore
1,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 1,2 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 1,3 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 1,4 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 2,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 2,2 Calcestruzzo - 2400 kg/m³ 2,000 80 2,3 Calcestruzzo - 2400 kg/m³ 2,000 80 2,4 Calcestruzzo - 2400 kg/m³ 2,000 80 3,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 3,2 Calcestruzzo - 2400 kg/m³ 2,000 80 3,3 Pannello in lana di roccia (densità 40 kg/m³ ) 0,035 1 3,4 Pannello in lana di roccia (densità 40 kg/m³ ) 0,035 1 4,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 4,2 Calcestruzzo - 2400 kg/m³ 2,000 80 4,3 Pannello in lana di roccia (densità 40 kg/m³ ) 0,035 1 4,4 Cartongesso (densità 700 kg/m³) 0,210 4
Calcoli eseguiti con il software IRIS 4.1 3
Condizioni al contorno Temperatura esterna 8,0°C Umidità relativa esterna 87% Temperatura interna 20,0°C Umidità relativa interna 58%
Calcoli eseguiti con il software IRIS 4.1 4
Risultati Temperatura
Flusso
Calcoli eseguiti con il software IRIS 4.1 5
Umidità relativa
Verifica del rischio di condensazione superficiale e di formazione di muffe Temperatura superficiale minima di progetto 19,3°C Temperatura superficiale minima per non avere condensa 11,5°C Verificato Temperatura superficiale minima per non avere formazione di muffe 14,9°C Verificato
Calcolo delle trasmittanze termiche lineari attraverso parete 1 attraverso parete 2 totale
Flusso interno [W] 3,418 3,418 6,836Flusso esterno [W] 3,418 3,418 Coefficiente di accoppiamento L2D [W/m K] 0,568
Y totale attraverso parete 1 attraverso parete 2
Trasmittanza lineare interna [W/m K] 0,077 0,038 0,038
Trasmittanza lineare esterna [W/m K] -0,087 -0,043 -0,043
Calcoli eseguiti con il software IRIS 4.1 6
Ponte: PT_5 - existing column on the wall
Descrizione ponte Parete inferiore
Materiale Conduttività [W/m K]
Fattore di resistenza al vapore
Spessore [m]
1 1000,000 0 0,110 2 1000,000 0 0,040 3 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 0,120 4 Intonaco di cemento sabbia e calce per esterno 0,900 20 0,015 5 Blocchi di cemento multicamera 0,564 40 0,250 6 Intonaco di cemento sabbia e calce per esterno 0,900 20 0,015 7 Cartongesso (densità 700 kg/m³) 0,210 4 0,013
Parete superiore Materiale Conduttività
[W/m K] Fattore di resistenza al vapore
Spessore [m]
1 1000,000 0 0,110 2 1000,000 0 0,040 3 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 0,120 4 Intonaco di cemento sabbia e calce per esterno 0,900 20 0,015 5 Blocchi di cemento multicamera 0,564 40 0,250 6 Intonaco di cemento sabbia e calce per esterno 0,900 20 0,015 7 Cartongesso (densità 700 kg/m³) 0,210 4 0,013
Nodo Materiale Conduttività
[W/m K] Fattore di resistenza al vapore
1,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 1,2 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 1,3 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 1,4 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 2,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 2,2 Calcestruzzo - 2400 kg/m³ 2,000 80 2,3 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 2,4 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 3,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 3,2 Calcestruzzo - 2400 kg/m³ 2,000 80
Calcoli eseguiti con il software IRIS 4.1 7
3,3 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 3,4 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 4,1 Intonaco di cemento sabbia e calce per esterno 0,900 20 4,2 Calcestruzzo - 2400 kg/m³ 2,000 80 4,3 Intonaco di cemento sabbia e calce per esterno 0,900 20 4,4 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 5,1 Blocchi di cemento multicamera 0,564 40 5,2 Calcestruzzo - 2400 kg/m³ 2,000 80 5,3 Blocchi di cemento multicamera 0,564 40 5,4 Laterizi doppiouni sp.25 cm.rif.1.1.04 0,532 15 6,1 Intonaco di cemento sabbia e calce per esterno 0,900 20 6,2 Intonaco di cemento sabbia e calce per esterno 0,900 20 6,3 Intonaco di cemento sabbia e calce per esterno 0,900 20 6,4 Laterizi doppiouni sp.25 cm.rif.1.1.04 0,532 15 7,1 Cartongesso (densità 700 kg/m³) 0,210 4 7,2 Cartongesso (densità 700 kg/m³) 0,210 4 7,3 Cartongesso (densità 700 kg/m³) 0,210 4 7,4 Malta di calce o di calce e cemento 0,900 20
Condizioni al contorno Temperatura esterna 8,0°C Umidità relativa esterna 87%
Calcoli eseguiti con il software IRIS 4.1 8
Calcoli eseguiti con il software IRIS 4.1 9
Verifica del rischio di condensazione superficiale e di formazione di muffe Temperatura superficiale minima di progetto 19,3°C Temperatura superficiale minima per non avere condensa 11,5°C Verificato Temperatura superficiale minima per non avere formazione di muffe 14,9°C Verificato
Calcolo delle trasmittanze termiche lineari attraverso parete 1 attraverso parete 2 totale
Flusso interno [W] 6,490 5,361 11,851Flusso esterno [W] 6,554 5,297 Coefficiente di accoppiamento L2D [W/m K] 0,985
Y totale attraverso parete 1 attraverso parete 2
Trasmittanza lineare interna [W/m K] 0,072 0,039 0,033 esterna [W/m K] 0,072 0,040 0,032
Calcoli eseguiti con il software IRIS 4.1 10
Ponte: PT_6 - new column on the wall
Descrizione ponte Parete inferiore
Materiale Conduttività [W/m K]
Fattore di resistenza al vapore
Spessore [m]
1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 0,110 2 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 0,010 3 Intonaco di cemento sabbia e calce per esterno 0,900 20 0,015 4 Blocchi di cemento multicamera 0,564 40 0,260 5 Intonaco di cemento sabbia e calce per esterno 0,900 20 0,015 6 Cartongesso (densità 700 kg/m³) 0,210 4 0,013
Parete superiore Materiale Conduttività
[W/m K] Fattore di resistenza al vapore
Spessore [m]
1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 0,110 2 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 0,010 3 Intonaco di cemento sabbia e calce per esterno 0,900 20 0,015 4 Blocchi di cemento multicamera 0,564 40 0,260 5 Intonaco di cemento sabbia e calce per esterno 0,900 20 0,015 6 Cartongesso (densità 700 kg/m³) 0,210 4 0,013
Nodo Materiale Conduttività
[W/m K] Fattore di resistenza al vapore
1,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 1,2 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 1,3 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 1,4 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 2,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 2,2 Calcestruzzo - 2400 kg/m³ 2,000 80 2,3 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 2,4 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 3,1 Intonaco di cemento sabbia e calce per esterno 0,900 20 3,2 Calcestruzzo - 2400 kg/m³ 2,000 80 3,3 Intonaco di cemento sabbia e calce per esterno 0,900 20 3,4 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60
Calcoli eseguiti con il software IRIS 4.1 11
4,1 Blocchi di cemento multicamera 0,564 40 4,2 Calcestruzzo - 2400 kg/m³ 2,000 80 4,3 Blocchi di cemento multicamera 0,564 40 4,4 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 5,1 Intonaco di cemento sabbia e calce per esterno 0,900 20 5,2 Calcestruzzo - 2400 kg/m³ 2,000 80 5,3 Intonaco di cemento sabbia e calce per esterno 0,900 20 5,4 Laterizi doppiouni sp.25 cm.rif.1.1.04 0,532 15 6,1 Cartongesso (densità 700 kg/m³) 0,210 4 6,2 Calcestruzzo - 2400 kg/m³ 2,000 80 6,3 Cartongesso (densità 700 kg/m³) 0,210 4 6,4 Laterizi doppiouni sp.25 cm.rif.1.1.04 0,532 15 7,1 Cartongesso (densità 700 kg/m³) 0,210 4 7,2 Cartongesso (densità 700 kg/m³) 0,210 4 7,3 Cartongesso (densità 700 kg/m³) 0,210 4 7,4 Malta di calce o di calce e cemento 0,900 20
Condizioni al contorno Temperatura esterna 8,0°C Umidità relativa esterna 87%
Calcoli eseguiti con il software IRIS 4.1 12
Calcoli eseguiti con il software IRIS 4.1 13
Verifica del rischio di condensazione superficiale e di formazione di muffe Temperatura superficiale minima di progetto 19,4°C Temperatura superficiale minima per non avere condensa 11,5°C Verificato Temperatura superficiale minima per non avere formazione di muffe 14,9°C Verificato
Calcolo delle trasmittanze termiche lineari attraverso parete 1 attraverso parete 2 totale
Flusso interno [W] 5,055 4,479 9,534Flusso esterno [W] 5,083 4,451 Coefficiente di accoppiamento L2D [W/m K] 0,792
Y totale attraverso parete 1 attraverso parete 2
Trasmittanza lineare interna [W/m K] 0,028 0,015 0,013 esterna [W/m K] 0,028 0,015 0,013
Calcoli eseguiti con il software IRIS 4.1 14
Ponte: linda
Descrizione ponte Parete
Materiale Conduttività [W/m K]
Fattore di resistenza al vapore
Spessore [m]
1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 0,060 2 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 0,120 3 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 0,250 4 Pannello in lana di roccia (densità 40 kg/m³ ) 0,035 1 0,060 5 Cartongesso (densità 700 kg/m³) 0,210 4 0,025
Solaio Materiale Conduttività
[W/m K] Fattore di resistenza al vapore
Spessore [m]
1 Bitume polimero su PPL sp.4 mm. 0,300 80000 0,008 2 Pannello in lana di roccia a doppia densità (densità media 150 kg/m³) 0,038 1 0,080
3 Stiferite classe B 0,026 33 0,060 4 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 0,250 5 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 0,050
Nodo Materiale Conduttività
[W/m K] Fattore di resistenza al vapore
1,1 Bitume polimero su PPL sp.4 mm. 0,300 80000 1,2 Bitume polimero su PPL sp.4 mm. 0,300 80000 1,3 Bitume polimero su PPL sp.4 mm. 0,300 80000 1,4 Bitume polimero su PPL sp.4 mm. 0,300 80000 1,5 Bitume polimero su PPL sp.4 mm. 0,300 80000 1,6 Bitume polimero su PPL sp.4 mm. 0,300 80000 1,7 Bitume polimero su PPL sp.4 mm. 0,300 80000 2,1 Pannello in lana di roccia a doppia densità (densità media 150 kg/m³) 0,038 1
2,2 Pannello in lana di roccia a doppia densità (densità media 150 kg/m³)
0,038 1
2,3 Pannello in lana di roccia a doppia densità (densità media 150 kg/m³)
0,038 1
Calcoli eseguiti con il software IRIS 4.1 15
2,4 Pannello in lana di roccia a doppia densità (densità media 150 kg/m³)
0,038 1
2,5 Pannello in lana di roccia a doppia densità (densità media 150 kg/m³)
0,038 1
2,6 Pannello in lana di roccia a doppia densità (densità media 150 kg/m³)
0,038 1
2,7 Pannello in lana di roccia a doppia densità (densità media 150 kg/m³)
0,038 1
3,1 Stiferite classe B 0,026 33 3,2 Stiferite classe B 0,026 33 3,3 Stiferite classe B 0,026 33 3,4 Stiferite classe B 0,026 33 3,5 Stiferite classe B 0,026 33 3,6 Stiferite classe B 0,026 33 3,7 Stiferite classe B 0,026 33 4,1 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 4,2 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 4,3 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 4,4 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 4,5 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 4,6 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 4,7 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 5,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 5,2 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 5,3 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 5,4 Pannello in lana di roccia (densità 40 kg/m³ ) 0,035 1 5,5 Cartongesso (densità 700 kg/m³) 0,210 4 5,6 Cartongesso (densità 700 kg/m³) 0,210 4 5,7 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 6,1 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 6,2 Pannello in polistirene espanso sinterizzato EPS 100 0,035 60 6,3 Calcestruzzo armato (percentuale d'armatura 2%) 2,500 80 6,4 Pannello in lana di roccia (densità 40 kg/m³ ) 0,035 1 6,5 Cartongesso (densità 700 kg/m³) 0,210 4 6,6 Cartongesso (densità 700 kg/m³) 0,210 4
Condizioni al contorno Temperatura esterna 8,0°C Umidità relativa esterna 87%
Calcoli eseguiti con il software IRIS 4.1 16
Calcoli eseguiti con il software IRIS 4.1 17
Verifica del rischio di condensazione superficiale e di formazione di muffe Temperatura superficiale minima di progetto 18,9°C Temperatura superficiale minima per non avere condensa 11,5°C Verificato Temperatura superficiale minima per non avere formazione di muffe 14,9°C Verificato
Calcolo delle trasmittanze termiche lineari attraverso parete attraverso solaio totale
Flusso interno [W] 2,666 6,493 9,159Flusso esterno [W] 4,536 4,623 Coefficiente di accoppiamento L2D [W/m K] 0,761
Y totale attraverso parete attraverso solaio
Trasmittanza lineare interna [W/m K] 0,244 0,071 0,173 esterna [W/m K] 0,073 0,036 0,037
DATI CLIMATICI DI PROGETTO
Località : Aviano (Pordenone) Latitudine nord [°] : 46,04 Altezza s.l.m. [m] : 159,00 Temperatura aria esterna b.s. [°C] : 33,00 Umidità relativa [%] : 45,00 Escursione termica giornaliera [°C] : 10,00 Escursione termica annua [°C] : 15,76 Fattore di foschia : 1,00 Mese di calcolo : (7) Luglio
Temperatura aria esterna di progetto [°C]
Ora solare
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Temperatura b.s. 25,50 25,50 25,50 25,50 25,50 25,50 25,50 25,50 26,50 27,50 28,75 30,00 31,25 32,50 33,00 32,50 32,00 31,50 30,50 29,50 28,25 27,00 25,75 24,50
Temperatura b.u. 21,45 21,45 21,45 21,45 21,45 21,45 21,45 21,45 21,70 21,95 22,45 22,95 23,20 23,45 23,45 23,45 23,20 22,95 22,70 22,45 22,20 21,95 21,70 21,45
Carichi massimi dovuti alla radiazione solare attraverso il vetro semplice [W/m²]
N NE E SE S SO O NO OR
45,36 382,70 517,10 429,39 289,09 429,39 517,10 382,70 696,72
Carichi massimi dovuti alla radiazione solare attraverso il vetro comune [W/(m² di apertura)]
Ora solare
6 7 8 9 10 11 12 13 14 15 16 17 18
N 69,26 37,14 36,13 41,15 44,16 44,16 44,16 44,16 44,16 41,15 36,13 50,19 96,36
NE 350,29 381,41 295,09 165,61 68,25 43,16 44,16 43,16 43,16 40,15 36,13 30,11 21,08
E 397,47 507,88 515,91 448,66 296,09 133,49 43,16 43,16 43,16 40,15 36,13 30,11 21,08
SE 190,70 324,20 403,49 427,58 355,31 270,00 155,58 61,23 43,16 40,15 36,13 30,11 21,08
S 16,06 30,11 56,21 127,47 170,63 210,78 236,88 210,78 170,63 96,36 44,16 30,11 21,08
SO 16,06 30,11 36,13 40,15 43,16 61,23 153,57 271,00 355,31 388,44 371,37 300,11 182,68
O 16,06 30,11 36,13 40,15 43,16 43,16 43,16 133,49 297,10 435,61 511,89 512,90 426,58
NO 16,06 30,11 36,13 40,15 43,16 43,16 44,16 43,16 68,25 188,70 321,19 405,50 393,45
OR 92,34 233,86 382,41 516,91 641,37 701,59 717,65 701,59 641,37 556,06 423,57 268,99 123,46
Edificio : Bldg #939 Zona : Existing bldg #939 Ambiente : room #02
Elemento Ora
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Existing ext. wall - (SE) T 6 6 3 15 22 30 37 37 38 36 34 30 28 27 26 24
Old column on the existing ext. wall - (SE) T 2 2 2 2 2 2 2 3 3 4 4 5 4 4 4 4
New column on the existing ext. wall - (SE) T 4 4 3 3 3 3 3 5 6 6 7 8 7 7 6 6
Window 1.93x1.56 - (SE) T 5 5 5 15 24 36 49 61 73 78 73 68 63 53 44 32
I 72 340 567 722 795 761 656 493 299 227 196 165 124 93 72 62
Existing ext. wall - (NE) T 2 0 1 8 27 29 32 28 23 23 24 26 28 27 27 24
Existing roof - (OR(C)) T 37 34 30 31 35 42 56 79 96 108 124 135 142 140 134 127
Window Thermal bridge - (SE) T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 thermal bridge wall-roof - (SE) T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Thermal bridge - existing column on the wall - (SE) T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Thermal bridge - new column on the existing wall -
(SE)
T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Ambiente : room #03
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Existing ext. wall - (NO) T 1 0 -1 0 1 2 4 7 9 11 13 20 28 31 33 26
Old column on the existing ext. wall - (NO) T 2 2 2 2 2 2 2 2 2 2 2 2 2 3 3 4
New column on the existing ext. wall - (NO) T 2 2 1 1 1 1 1 1 1 1 1 2 2 2 2 3
Window 1.93x1.56 - (NO) T 2 2 2 7 12 18 24 30 36 39 36 34 32 27 22 16
I 73 73 69 64 64 64 64 60 73 166 262 327 217 101 74 55
Existing roof - (OR(C)) T 23 21 19 20 22 27 35 50 60 68 78 85 89 88 84 80
Window Thermal bridge - (NO) T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 thermal bridge wall-roof - (NO) T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Thermal bridge - existing column on the wall - (NO) T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Internal fire resistant wall (insulated) T 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60 60
Thermal bridge - new column on the existing wall -
(NO)
T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Ambiente : room #04
6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21
Existing ext. wall - (SE) T 2 2 0 7 11 15 19 21 24 24 25 24 23 22 23 20
Old column on the existing ext. wall - (SE) T 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2
Window 1.93x1.56 - (SE) T 5 5 5 15 24 36 49 61 73 78 73 68 63 53 44 32
I 72 340 567 722 795 761 656 493 299 227 196 165 124 93 72 62
Existing roof - (OR(C)) T 30 28 24 25 28 34 45 64 78 87 100 109 114 113 108 103
Window Thermal bridge - (SE) T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 thermal bridge wall-roof - (SE) T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Thermal bridge - existing column on the wall - (NE) T 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Internal fire resistant wall…