This pre-solicitation notice announces a draft request for proposal for multiple award construction contracts to provide design-build construction services in Italy. The scope of work includes various repair, renovation, maintenance, and minor construction projects across multiple trades at Aviano Air Base. Work may involve grading, utilities, buildings, HVAC, fire suppression, fuel systems, electrical work, asbestos abatement, and site work. The North American Industry Classification System code is 236220.
The proposed contracts will be firm-fixed-price and competitively awarded using a price-past performance evaluation. The minimum guarantee is 2,500 Euro per contractor and the maximum total value is estimated at 96 million dollars. The base period of performance is one year with four optional years. The minimum task order is 2,500 dollars and maximum is 7 million dollars. Interested parties must submit any comments on the draft attachments by April 19, 2019 to be considered for the formal solicitation planned for May 2019. The contracting office is located at Aviano Air Base in Italy.
ANNEX E- ELECTRICAL PART 15
View the file
Other files for this federal contract opportunity
Show all 50
Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT: ASHE 18-1025
RENOVATE/EXPAND FAC. 939
DESIGN PHASE: 60% Page 48 of 122
CALCULATIONS AND VERIFICATIONS
DISTRIBUTION BOARD: [B939-MDP] B939-MDP
LINE: QF19
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,1 0,48 0 0,48 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other circuits
K
L1.1.31 F+N+PE uni 30 31 30 -side by
10 1
Conductors cross-section [mm2] phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 1,5 1x 1,5 1x 1,5 360,0 5,04 370,65 16,35 0,16 0,9 4
Ib
[A] Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
[kA]
0,48 10,35 7,95 0,3 0,19 0,19
Designation
FG16R16-0,6/1 kV - Cca-s3,d1,a3/Cu
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF19 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.31 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
Overload Maximum short-circuit Minimum short-circuit Indirect contact
SI SI SI SI
DESIGN PHASE: 60% Page 49 of 122
LINE: QF20
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,4 1,93 1,93 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.32 F+N+PE uni 55 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 396,0 8,58 406,65 19,89 0,74 1,48 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,93 13,95 7,95 0,28 0,17 0,17
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF20 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.32 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 50 of 122
LINE: QF21
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,4 1,93 0 1,93 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.33 F+N+PE uni 45 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 324,0 7,02 334,65 18,33 0,61 1,34 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,93 13,95 7,95 0,34 0,21 0,21
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF21 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.33 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 51 of 122
LINE: QF22
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,56 2,7 0 2,7 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.34 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 216,0 4,68 226,65 15,99 0,57 1,3 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,7 13,95 7,95 0,5 0,32 0,32
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF22 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.34 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 52 of 122
LINE: QF23
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,2 0,96 0,96 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.35 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 216,0 4,68 226,65 15,99 0,2 0,93 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,96 13,95 7,95 0,5 0,32 0,32
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF23 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.35 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 53 of 122
LINE: QF24
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,32 1,54 0 1,54 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.36 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 216,0 4,68 226,65 15,99 0,32 1,05 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,54 13,95 7,95 0,5 0,32 0,32
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF24 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.36 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 54 of 122
LINE: QF25
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,44 2,12 2,12 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.37 F+N+PE uni 50 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 360,0 7,8 370,65 19,11 0,74 1,48 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,12 13,95 7,95 0,3 0,19 0,19
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF25 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.37 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 55 of 122
LINE: QF26
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,1 0,48 0,48 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.38 F+N+PE uni 50 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 360,0 7,8 370,65 19,11 0,16 0,9 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,48 13,95 7,95 0,3 0,19 0,19
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF26 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.38 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 56 of 122
LINE: QF27
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,1 0,48 0 0,48 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.39 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 2,5 1x 2,5 1x 2,5 216,0 4,68 226,65 15,99 0,1 0,83 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,48 13,95 7,95 0,5 0,32 0,32
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF27 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.39 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 57 of 122
LINE: QF28
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,1 0,48 0 0 0,48 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.40 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 1,5 1x 1,5 1x 1,5 360,0 5,04 370,65 16,35 0,16 0,9 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,48 10,35 7,95 0,3 0,19 0,19
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF28 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.40 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 58 of 122
LINE: QF29
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,35 1,69 0 0 1,69 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.41 F+N+PE uni 70 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 1,5 1x 1,5 1x 1,5 840,0 11,76 850,65 23,07 1,37 2,11 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,69 10,35 7,95 0,13 0,08 0,08
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF29 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.41 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 59 of 122
LINE: QF30
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,4 1,93 0 0 1,93 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.42 F+N+PE uni 70 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 1,5 1x 1,5 1x 1,5 840,0 11,76 850,65 23,07 1,57 2,3 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,93 10,35 7,95 0,13 0,08 0,08
DESIGN PHASE: 60% Page 60 of 122
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF30 C40N Vigi 1+N C 10 10 -
0,1
0,1
Q1.1.42 1+N - - - Embedded AC
0,03 inst.
PROTECTIONS VERIFICATIONS
Overload Maximum short-circuit Minimum short-circuit Indirect contact
SI SI SI
SI
DESIGN PHASE: 60% Page 61 of 122
LINE: QF31
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,1 0,48 0 0 0,48 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.43 F+N+PE uni 70 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 1,5 1x 1,5 1x 1,5 840,0 11,76 850,65 23,07 0,39 1,12 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,48 10,35 7,95 0,13 0,08 0,08
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF31 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.43 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 62 of 122
DISTRIBUTION BOARD: [B939-MDP-2] B939-MDP-2
LINE: MDP2-MAIN
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
23,04 43,47 35,94 31,88 43,47 0,9 1
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
MDP2-MAIN iC60 N 4 C 63 63 - 0,63 0,63
Q1 4 - - -
DESIGN PHASE: 60% Page 63 of 122
LINE: QF.KC1
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
2 9,66 9,66 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.1 F+N+PE uni 20 31 30 -by
5 1 phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 6 1x 6 1x 6 60,0 2,7 83,5 16,53 0,57 1,59 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
9,66 30,77 4,18 1,31 0,86 0,79
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF.KC1 C40a Vigi 1+N C 25 25 - 0,25 0,25
Q2.1.1 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 64 of 122
LINE: QF.KC2
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 0 5,79 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.2 F+N+PE uni 10 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 45,0 1,43 68,5 15,26 0,25 1,28 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
5,79 23,94 4,18 1,58 1,04 0,94
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF.KC2 C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.2 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 65 of 122
LINE: QF.LAU
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
2,5 12,07 0 0 12,07 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.3 F+N+PE uni 15 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 67,5 2,15 91,0 15,98 0,79 1,82 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
12,07 23,94 4,18 1,21 0,79 0,73
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF.LAU C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.3 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 66 of 122
LINE: QF1
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1 4,83 4,83 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.4 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 0,63 1,66 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
4,83 23,94 4,18 0,7 0,45 0,43
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF1 C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.4 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 67 of 122
LINE: QF2
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1 4,83 0 4,83 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L2.1.5 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 0,63 1,66 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
4,83 23,94 4,18 0,7 0,45 0,43
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF2 C40a Vigi 1+N C 16 16 - 0,16 0,16
Q2.1.5 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS