ANNEX_E_-_ELECTRICAL_Part15.pdf

PDF 880 KB Posted

Attached to
Multiple Award Construction Contract (MACC) Italy
Solicitation number
FA568219RA001
Issued by

About this file

This pre-solicitation notice announces a draft request for proposal for multiple award construction contracts to provide design-build construction services in Italy. The scope of work includes various repair, renovation, maintenance, and minor construction projects across multiple trades at Aviano Air Base. Work may involve grading, utilities, buildings, HVAC, fire suppression, fuel systems, electrical work, asbestos abatement, and site work. The North American Industry Classification System code is 236220.

The proposed contracts will be firm-fixed-price and competitively awarded using a price-past performance evaluation. The minimum guarantee is 2,500 Euro per contractor and the maximum total value is estimated at 96 million dollars. The base period of performance is one year with four optional years. The minimum task order is 2,500 dollars and maximum is 7 million dollars. Interested parties must submit any comments on the draft attachments by April 19, 2019 to be considered for the formal solicitation planned for May 2019. The contracting office is located at Aviano Air Base in Italy.

ANNEX E- ELECTRICAL PART 15

View the file

Other files

File Type Posted
AMENDMENT 0005 TO FA568219RA001.pdf PDF
Attachment 2 Section M REV 03.pdf PDF
Attachment 12 ASHE 18-1025 CCEB (Seed project) REV 01.xlsx XLSX spreadsheet
Attachment 1 Section L REV 03.pdf PDF
MACC Questions and Answers 11122019.pdf PDF
FBO_NOTICE_11072019.pdf PDF
Solicitation_Amendment_FA568219RA0010004_SF_30.pdf PDF
MFAB80~1.PDF PDF
ATTACH~2.PDF PDF
38BOQ0~1.PDF PDF
ATTACH~3.PDF PDF
29UOI0~1.PDF PDF
ATTACH~4.PDF PDF
ATTACH~1.PDF PDF
JA6P70~1.PDF PDF
Attachment_5_Past_Performance_Questionnaire_(PPQ)_REV_03.doc DOC document
H2UST0~1.PDF PDF
83BLD0~1.PDF PDF
FRLEQ0~1.PDF PDF
B3P850~1.PDF PDF
D7JPR0~1.PDF PDF
F91E70~1.PDF PDF
Solicitation_Amendment_FA568219RA0010003_SF_30.pdf PDF
FEGMC0~1.PDF PDF
MACC_Questions_and_Answers_10162019.pdf PDF
Attachment_5_Past_Performance_Questionnaire_(PPQ)_REV_02.doc DOC document
Solicitation_Amendment_FA568219RA0010002_SF_30.pdf PDF
Attachment_1_Section_L_REV_02.pdf PDF
Attachment_2_Section_M_REV_02.pdf PDF
MACC_Questions_and_Answers_10012019.pdf PDF
Attachment_3_CEN_-MACC_SOW_v3_REV_01.pdf PDF
Attachment_1_Section_L_REV_01.pdf PDF
Solicitation_Amendment_FA568219RA0010001_SF_30.pdf PDF
ATTACH~4.DOC DOC document
ATTACH~1.DOC DOC document
ATTACH~2.DOC DOC document
Attachment_9_Questions_and_Answers.docx DOCX document
ATTACH~3.DOC DOC document
BIPHM0~1.DOC DOC document
ANNEX_E_-_ELECTRICAL_Part6.pdf PDF
ANNEX_E_-_ELECTRICAL_Part4.pdf PDF
ANNEX_E_-_ELECTRICAL_Part2.pdf PDF
ANNEX_E_-_ELECTRICAL_Part17.pdf PDF
ANNEX_A-D_-_MECHANICAL_Part2.pdf PDF
ANNEX_S_-_STRUCTURAL_Part6.pdf PDF
ANNEX_E_-_ELECTRICAL_Part7.pdf PDF
ANNEX_S_-_STRUCTURAL_Part12.pdf PDF
ANNEX_S_-_STRUCTURAL_Part2.pdf PDF
ANNEX_S_-_STRUCTURAL_Part7.pdf PDF
ANNEX_E_-_ELECTRICAL_Part16.pdf PDF
Show 40 more

Latest 50 of 148 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PROJECT: ASHE 18-1025

RENOVATE/EXPAND FAC. 939

DESIGN PHASE: 60% Page 48 of 122

CALCULATIONS AND VERIFICATIONS

DISTRIBUTION BOARD: [B939-MDP] B939-MDP

LINE: QF19

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,1 0,48 0 0,48 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other circuits

K

L1.1.31 F+N+PE uni 30 31 30 -side by

10 1

Conductors cross-section [mm2] phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 1,5 1x 1,5 1x 1,5 360,0 5,04 370,65 16,35 0,16 0,9 4

Ib

[A] Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

[kA]

0,48 10,35 7,95 0,3 0,19 0,19

Designation

FG16R16-0,6/1 kV - Cca-s3,d1,a3/Cu

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF19 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.31 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

Overload Maximum short-circuit Minimum short-circuit Indirect contact

SI SI SI SI

DESIGN PHASE: 60% Page 49 of 122

LINE: QF20

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,4 1,93 1,93 0 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.32 F+N+PE uni 55 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 2,5 1x 2,5 1x 2,5 396,0 8,58 406,65 19,89 0,74 1,48 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

1,93 13,95 7,95 0,28 0,17 0,17

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF20 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.32 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 50 of 122

LINE: QF21

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,4 1,93 0 1,93 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.33 F+N+PE uni 45 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 2,5 1x 2,5 1x 2,5 324,0 7,02 334,65 18,33 0,61 1,34 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

1,93 13,95 7,95 0,34 0,21 0,21

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF21 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.33 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 51 of 122

LINE: QF22

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,56 2,7 0 2,7 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.34 F+N+PE uni 30 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 2,5 1x 2,5 1x 2,5 216,0 4,68 226,65 15,99 0,57 1,3 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

2,7 13,95 7,95 0,5 0,32 0,32

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF22 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.34 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 52 of 122

LINE: QF23

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,2 0,96 0,96 0 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.35 F+N+PE uni 30 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 2,5 1x 2,5 1x 2,5 216,0 4,68 226,65 15,99 0,2 0,93 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

0,96 13,95 7,95 0,5 0,32 0,32

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF23 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.35 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 53 of 122

LINE: QF24

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,32 1,54 0 1,54 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.36 F+N+PE uni 30 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 2,5 1x 2,5 1x 2,5 216,0 4,68 226,65 15,99 0,32 1,05 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

1,54 13,95 7,95 0,5 0,32 0,32

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF24 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.36 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 54 of 122

LINE: QF25

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,44 2,12 2,12 0 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.37 F+N+PE uni 50 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 2,5 1x 2,5 1x 2,5 360,0 7,8 370,65 19,11 0,74 1,48 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

2,12 13,95 7,95 0,3 0,19 0,19

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF25 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.37 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 55 of 122

LINE: QF26

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,1 0,48 0,48 0 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.38 F+N+PE uni 50 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 2,5 1x 2,5 1x 2,5 360,0 7,8 370,65 19,11 0,16 0,9 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

0,48 13,95 7,95 0,3 0,19 0,19

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF26 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.38 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 56 of 122

LINE: QF27

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,1 0,48 0 0,48 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.39 F+N+PE uni 30 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 2,5 1x 2,5 1x 2,5 216,0 4,68 226,65 15,99 0,1 0,83 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

0,48 13,95 7,95 0,5 0,32 0,32

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF27 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.39 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 57 of 122

LINE: QF28

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,1 0,48 0 0 0,48 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.40 F+N+PE uni 30 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 1,5 1x 1,5 1x 1,5 360,0 5,04 370,65 16,35 0,16 0,9 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

0,48 10,35 7,95 0,3 0,19 0,19

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF28 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.40 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 58 of 122

LINE: QF29

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,35 1,69 0 0 1,69 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.41 F+N+PE uni 70 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 1,5 1x 1,5 1x 1,5 840,0 11,76 850,65 23,07 1,37 2,11 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

1,69 10,35 7,95 0,13 0,08 0,08

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF29 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.41 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 59 of 122

LINE: QF30

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,4 1,93 0 0 1,93 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.42 F+N+PE uni 70 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 1,5 1x 1,5 1x 1,5 840,0 11,76 850,65 23,07 1,57 2,3 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

1,93 10,35 7,95 0,13 0,08 0,08

DESIGN PHASE: 60% Page 60 of 122

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF30 C40N Vigi 1+N C 10 10 -

0,1

0,1

Q1.1.42 1+N - - - Embedded AC

0,03 inst.

PROTECTIONS VERIFICATIONS

Overload Maximum short-circuit Minimum short-circuit Indirect contact

SI SI SI

SI

DESIGN PHASE: 60% Page 61 of 122

LINE: QF31

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

0,1 0,48 0 0 0,48 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L1.1.43 F+N+PE uni 70 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 1,5 1x 1,5 1x 1,5 840,0 11,76 850,65 23,07 0,39 1,12 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

0,48 10,35 7,95 0,13 0,08 0,08

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF31 C40N Vigi 1+N C 10 10 - 0,1 0,1

Q1.1.43 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 62 of 122

DISTRIBUTION BOARD: [B939-MDP-2] B939-MDP-2

LINE: MDP2-MAIN

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

23,04 43,47 35,94 31,88 43,47 0,9 1

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

MDP2-MAIN iC60 N 4 C 63 63 - 0,63 0,63

Q1 4 - - -

DESIGN PHASE: 60% Page 63 of 122

LINE: QF.KC1

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

2 9,66 9,66 0 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L2.1.1 F+N+PE uni 20 31 30 -by

5 1 phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 6 1x 6 1x 6 60,0 2,7 83,5 16,53 0,57 1,59 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

9,66 30,77 4,18 1,31 0,86 0,79

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF.KC1 C40a Vigi 1+N C 25 25 - 0,25 0,25

Q2.1.1 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 64 of 122

LINE: QF.KC2

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

1,2 5,79 0 5,79 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L2.1.2 F+N+PE uni 10 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 4 1x 4 1x 4 45,0 1,43 68,5 15,26 0,25 1,28 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

5,79 23,94 4,18 1,58 1,04 0,94

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF.KC2 C40a Vigi 1+N C 16 16 - 0,16 0,16

Q2.1.2 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 65 of 122

LINE: QF.LAU

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

2,5 12,07 0 0 12,07 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L2.1.3 F+N+PE uni 15 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 4 1x 4 1x 4 67,5 2,15 91,0 15,98 0,79 1,82 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

12,07 23,94 4,18 1,21 0,79 0,73

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF.LAU C40a Vigi 1+N C 16 16 - 0,16 0,16

Q2.1.3 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 66 of 122

LINE: QF1

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

1 4,83 4,83 0 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L2.1.4 F+N+PE uni 30 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 0,63 1,66 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

4,83 23,94 4,18 0,7 0,45 0,43

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF1 C40a Vigi 1+N C 16 16 - 0,16 0,16

Q2.1.4 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

DESIGN PHASE: 60% Page 67 of 122

LINE: QF2

GENERAL FEATURES OF THE LINE

P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.

1 4,83 0 4,83 0 0,9 1

CABLE

Initialling Ph/N/PE

Distribution

Cable type

Lenght

[m]

Inst.

method

Temp.

[°C] Nr.

supp.

Resis.ty [°K m/W]

Installation depht [m]

Prox.

circuit

Other

L2.1.5 F+N+PE uni 30 31 30 -by phase neutral PE

Rcable

[m] Xcable

[m] Rtot

[m] Xtot

[m] Vcable

Vtot

Vmax

(limit)

1x 4 1x 4 1x 4 135,0 4,29 158,5 18,12 0,63 1,66 4

Iz

[A] Icc max (start of line)

[kA] Icc max (end of line)

[kA] Icc min (end of line)

[kA] Icc (ground fault)

4,83 23,94 4,18 0,7 0,45 0,43

CIRCUIT-BREAKER

User Circuit-breaker

Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]

Initialling/

Description Tsd [s] Ii [kA]

Ig

[xIn - A] Tg [s]

Residual current device

Class In [A] Tn

[ms]

QF2 C40a Vigi 1+N C 16 16 - 0,16 0,16

Q2.1.5 1+N - - - Embedded AC 0,03 inst.

PROTECTIONS VERIFICATIONS

File details come from the government source that posted it. Updated .