This notice is for a draft request for proposal for multiple award construction contracts in Italy. The proposed contracts would be for design-build construction services including grading, water and sewer lines, painting, roofing, building renovation, new construction, electrical work, and other facility projects at Aviano Air Base. The contracts would have a one year base period with four optional one-year extensions. The minimum order value is $2,500 and maximum total value of all contracts combined is estimated at $96 million. Interested offerors are requested to submit comments on draft attachments by April 19, 2019. The solicitation is expected to be issued in May 2019 via www.fbo.gov. The North American Industry Classification System code is 236220. The contracting office is located at Aviano Air Base. Task orders will primarily be for work at Aviano but could be at other locations in Italy.
ANNEX E- ELECTRICAL PART 14
View the file
Other files for this federal contract opportunity
Show all 50
Multiple Award Construction Contract (MACC) Italy has more files on GovTribe.
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROJECT: ASHE 18-1025
RENOVATE/EXPAND FAC. 939
DESIGN PHASE: 60% Page 28 of 122
CALCULATIONS AND VERIFICATIONS
DISTRIBUTION BOARD: [B939-MDP] B939-MDP
LINE: QF-GATE
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,8 3,86 0 0 3,86 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other circuits
K
L1.1.11 F+N+PE uni 50 61 30 1,08 0,8 side by
2 1
Conductors cross-section [mm2] phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 1,5 1x 1,5 1x 1,5 600,0 8,4 610,65 19,71 2,25 2,98 4
Ib
[A] Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
[kA]
3,86 16,87 7,95 0,18 0,11 0,11
Designation
FG16R16-0,6/1 kV - Cca-s3,d1,a3/Cu
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF-GATE C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.11 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
Overload Maximum short-circuit Minimum short-circuit Indirect contact
SI SI SI SI
DESIGN PHASE: 60% Page 29 of 122
LINE: QF-GATE
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,3 1,44 0 0 1,44 0,9
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.12 F+N+PE uni 50 31 30 0,8 by
10 1 phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 225,0 7,15 235,65 18,46 0,31 1,05 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
1,44 18,9 7,95 0,48 0,3 0,3
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF-GATE C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.12 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 30 of 122
LINE: QF1
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 5,79 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.13 F+N+PE uni 55 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 247,5 7,87 258,15 19,17 1,4 2,14 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
5,79 18,9 7,95 0,44 0,28 0,28
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF1 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.13 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 31 of 122
LINE: QF2
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 0 5,79 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.14 F+N+PE uni 55 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF2 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.14 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 32 of 122
LINE: QF3
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 0 0 5,79 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.15 F+N+PE uni 55 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF3 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.15 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 33 of 122
LINE: QF4
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 5,79 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.16 F+N+PE uni 55 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF4 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.16 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 34 of 122
LINE: QF5
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 0 5,79 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.17 F+N+PE uni 55 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF5 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.17 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 35 of 122
LINE: QF6
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 0 0 5,79 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.18 F+N+PE uni 55 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF6 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.18 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 36 of 122
LINE: QF7
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 5,79 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.19 F+N+PE uni 55 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF7 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.19 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 37 of 122
LINE: QF8
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,6 7,72 0 7,72 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.20 F+N+PE uni 55 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 247,5 7,87 258,15 19,17 1,87 2,6 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
7,72 18,9 7,95 0,44 0,28 0,28
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF8 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.20 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 38 of 122
LINE: QF9
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,2 0,96 0 0 0,96 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.21 F+N+PE uni 10 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 1,5 1x 1,5 1x 1,5 120,0 1,68 130,65 12,99 0,11 0,84 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,96 10,35 7,95 0,85 0,55 0,55
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF9 C40N Vigi 1+N C 10 10 - 0,1 0,1
Q1.1.21 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 39 of 122
LINE: QF10
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,2 0,96 0 0 0,96 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.22 F+N+PE uni 40 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 180,0 5,72 190,65 17,03 0,17 0,9 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,96 18,9 7,95 0,59 0,38 0,38
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF10 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.22 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 40 of 122
LINE: QF11
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 5,79 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.23 F+N+PE uni 40 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 180,0 5,72 190,65 17,03 1,02 1,75 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
5,79 18,9 7,95 0,59 0,38 0,38
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF11 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.23 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 41 of 122
LINE: QF12
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 0 5,79 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.24 F+N+PE uni 40 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF12 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.24 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 42 of 122
LINE: QF13
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 0 0 5,79 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.25 F+N+PE uni 40 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF13 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.25 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 43 of 122
LINE: QF14
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,5 2,41 2,41 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.26 F+N+PE uni 40 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 180,0 5,72 190,65 17,03 0,42 1,16 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,41 18,9 7,95 0,59 0,38 0,38
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF14 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.26 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 44 of 122
LINE: QF15
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,5 2,41 2,41 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.27 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 145,65 15,6 0,31 1,05 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,41 18,9 7,95 0,77 0,49 0,49
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF15 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.27 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 45 of 122
LINE: QF16
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
1,2 5,79 0 0 5,79 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.28 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 145,65 15,6 0,76 1,5 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
5,79 18,9 7,95 0,77 0,49 0,49
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF16 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.28 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 46 of 122
LINE: QF17
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,1 0,48 0,48 0 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.29 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 145,65 15,6 0,06 0,79 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
0,48 18,9 7,95 0,77 0,49 0,49
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF17 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.29 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS
DESIGN PHASE: 60% Page 47 of 122
LINE: QF18
GENERAL FEATURES OF THE LINE
P [kW] Ib [A]/Inm [A] IR [A] IS [A] IT [A] cos b Kutilization Kdiversity.
0,5 2,41 0 2,41 0 0,9 1
CABLE
Initialling Ph/N/PE
Distribution
Cable type
Lenght
[m]
Inst.
method
Temp.
[°C] Nr.
supp.
Resis.ty [°K m/W]
Installation depht [m]
Prox.
circuit
Other
L1.1.30 F+N+PE uni 30 31 30 -by phase neutral PE
Rcable
[m] Xcable
[m] Rtot
[m] Xtot
[m] Vcable
Vtot
Vmax
(limit)
1x 4 1x 4 1x 4 135,0 4,29 145,65 15,6 0,31 1,05 4
Iz
[A] Icc max (start of line)
[kA] Icc max (end of line)
[kA] Icc min (end of line)
[kA] Icc (ground fault)
2,41 18,9 7,95 0,77 0,49 0,49
CIRCUIT-BREAKER
User Circuit-breaker
Poles Tripping characteristics In [A] Ir [A] Tr [s] Im [kA] Isd [kA]
Initialling/
Description Tsd [s] Ii [kA]
Ig
[xIn - A] Tg [s]
Residual current device
Class In [A] Tn
[ms]
QF18 C40N Vigi 1+N C 16 16 - 0,16 0,16
Q1.1.30 1+N - - - Embedded AC 0,03 inst.
PROTECTIONS VERIFICATIONS