Report 1190 PH B102 outdoor Gen Fuel Gauge SC 10-24-19.pdf

PDF 91 KB Posted

Attached to
Prospect Harbor Space Force Station (SFS) Base Operations Support (BOS)
Solicitation number
FA255024R0003
Issued by

About this file

This document contains a federal contract opportunity notice and a related maintenance inspection report for a generator at Prospect Harbor Space Force Station in Maine.

The federal contract opportunity is for base operations support services at Prospect Harbor Space Force Station, including staffing and managing physical security, civil engineering, communications systems, logistics, and environmental and safety compliance. The non-personal services contract will operate and maintain the government-owned facility. The solicitation is planned for release in January 2024 as a 100% small business set-aside best-value procurement. The maintenance inspection report documents a service call to disable nuisance high and low fuel alarms on a Kohler 300REOZJ generator, which were triggering frequently due to fluctuations in the fuel level reading. The fuel gauge and alarm settings could not be adjusted on-site and require follow-up from the generator OEM.

View the file

Other files

File Type Posted
PHSFS_BOS_RFP_Questions_SET_5_20240301.pdf PDF
FA255024R0003_Amend_0002_240301.pdf PDF
FA255024R0003_SF1449_Amend_0002_240301.pdf PDF
Atch_5_FFP_NTE_Task_Pricing_Template_Amend_0002_240229.xlsx XLSX spreadsheet
PHSFS_BOS_RFP_Questions_SET_2_20240226.pdf PDF
PHSFS_BOS_RFP_Questions_SET 4_20240226.pdf PDF
PHSFS_BOS_RFP_Questions_SET 3_20240226.pdf PDF
20240221_PHSFS_BOS_RFP_Questions.pdf PDF
Atch_8_ITO_Amend_0001_20240221.pdf PDF
FA255024R0003_Amend_0001_20240221.pdf PDF
Atch_9_Evaluation_Amend_0001_20240207.pdf PDF
Atch_16_PPQ_20240104.docx DOCX document
PH B104 Heat PM 9-18.pdf PDF
Report 2305 PH B103 OVHD PM 6-14-22.pdf PDF
Report 1844 PH B101 FM200 Fire System PM 4-5-21.pdf PDF
PH-103-K-01 - 2021 Inspection.pdf PDF
Report 259 PH B103 BFP Annual PM 3-28-23.pdf PDF
Report 1847 PH B112 Fire Alarm PM 4-5-21.pdf PDF
Report 1175 PH B105 Heat PM 9-27-19.pdf PDF
Report 1456 PH B110 Fire Alarm PM 6-30-20.pdf PDF
Report 2324 PH B104 Annual Heating PM 9-15-21.pdf PDF
Report 1359 PH B101 HVAC Compressor Nr 2 PM 6-10-20.pdf PDF
Report 2443 PH B101 Annual Heating PM 9-29-22.pdf PDF
PH B101 Boiler PM 10-18.pdf PDF
Report 1855 PH B101 Condenser B HVAC PM 4-20-21.pdf PDF
Report 1845 PH B102 CO2Fire System PM 4-5-21.pdf PDF
Report 1356 PH B101 HVAC Air Handler Nr 2 PM 6-10-20.pdf PDF
Report 2174 PH B102 CO2Fire System Annual PM SC 3-9-22.pdf PDF
PH inside Generator SC 3-29-19.pdf PDF
Report 1828 PH B104 OVHD Nr 2 PM 5-24-2021.pdf PDF
PH B112 F7P9ZP-PH-BURNER 2-03-21.pdf PDF
Report 1831 PH B102 Outside Generator SC 5-25-2021.pdf PDF
Report 2252 PH B102 Roof Inspection 6-6-2022.pdf PDF
PH-110-K-02 - 2021 Inspection.pdf PDF
Report 645 PH B102 Outside Generator Annual PM 9-6-23.pdf PDF
Report 1680 PH B103 No heat ESC 12-12-20.pdf PDF
Report 1082 PH B102 inside Generator PM 8-22-18.pdf PDF
Report 1851 Anual Extinguisher PMs 4-5-21.pdf PDF
Report 2241 PH B102 Outside Generator PM 5-18-22.pdf PDF
PH B103 Replace Window Glass 20190820.pdf PDF
Report 402 PH B101 HVAC Nr 1 PM 9-17.pdf PDF
Report 2448 PH B104 Annual Heating PM 9-28-22.pdf PDF
Report 1296 PH B102 Inside Generator PM 2-20-20.pdf PDF
PH B110 Boiler Nr 1 PM 9-18.pdf PDF
Report 367 PH B112 FA Install.pdf PDF
Report 1357 PH B103 HVAC PM 6-10-20.pdf PDF
Report 2175 PH B103 Fire Alarm PM 3-9-22.pdf PDF
Report 2047 PH B101 HVAC Air Handler Side A 9-30-21.pdf PDF
Report 658 PH B104 OVHDR eplace Push Button 7-25-18.pdf PDF
Report 645 PH Outside Generator repair SC 6-20-18.pdf PDF
Show 40 more

Latest 50 of 292 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(ATTACH ADDITIONAL SHEETS IF NECESSARY)

x YES NO

YES x NO x YES NO x x x

MAINTENACE & INSPECTION REPORT

(ONE FOR EACH PIECE OF EQUIPMENT)

WILL MATERIALS NEED TO BE ORDERED? HOW LONG IS THE LEED TIME?

EXPLAIN BELOW

HAVE NOT BEEN MET

(BELOW) FOR ADMINISTRATION USE ONLY

DATE IT WILL BE RECEIVED :

PROPER PPE BEING WORN

YES

10.24/19

Kohler 300 REOZJ

Maine Generator Tech Name :Kent Ladd

LOCATION

WEATHERBUILDING NAME or #

CONTRACTOR/SIGNATURE CCI/ SIGNATURE SITE INSPECTOR/SIGNATURE

CONTRACT # ELIN # REPORT NO.

HAVE BEEN MET

DATE:

SERIAL#

TYPE OF EQUIPMENT MAKE MODEL

WORK DESCRIPTION & PROBLEMS FOUNDS

TIME TO COMPLETE TASK

Prospect harbor

IS INSPECTION CHECK LIST ATTACHED?

SAFETY REQUIREMENTS

WAS WORK COMPLETED?

IF NO EXPLAIN BELOW

See attached

Generator

N40085-17-D-7201

D002AB #1190

NO

HOUSE KEEPING COMPLETE

YES

NO

MAXIMO # Work Order #

MAINE GENERATOR & SOLAR POWER, INC.

P.O. BOX 126

2 Park St.

Milo, ME 04463

(207)943-5070 office

(207)943-5050 fax www.mainegenerator.com

E-mail: info@mainegenerator.com

SERVICE REPORT

Date: 10/25/2019

Service Technician: Kent Ladd

Customer Name: Navy

Generator Make & Model: Kohler 300 REOZJ

Address:

Generator Serial #: SGM32G8VI

City: Prospect Harbor Outdoor Unit

Transfer Switch Make & Model:

Phone:

Transfer Switch Serial #:

PO/WO #:

Customer Contact: Derek McCaslin

Problem Reported:

Received call for nuisance fuel alarms.

Problems Found/Repaired:

Travelled to site to check unit for nuisance high and low fuel alarms. Upon arrival at the site: Fuel gauge is reading at 93%. Accessed auxiliary inputs, which the fuel alarms are tied in to. The high fuel alarm is set to ring in at 93%, which is exactly what the fuel level is right now. With the engine running, this percentage changes from 93% down to 92% and fluctuates back and forth between those two numbers so every time it goes to 92% the alarm clears and when it hits 93% it rings back in. The controllers in the office have to silence that alarm every time that high alarm comes back in. I entered the passwords provided by the Kohler factory rep and attempted to change the high level parameter to move it up to 95 or 96 percent. The controller would not allow me to change that parameter, however, I can enable or disable that alarm. I talked with Patrick at the Navy base and we have disabled the alarms for high fuel alarm and the low fuel alarm, which was set at 60%. But, I was unable to change these two parameters. I did export a file from the computer system on the generator to my laptop and spoke with the factory rep while on site. I can e-mail the file to them, they can change the parameters and they can e-mail that file back to me with the changes made. I should be able to upload that computer change in to the generator controller and at the same time reactivate the alarms. Advice from John Stiles needs to be obtained on what fuel percentages we want these alarms to be set at or do we monitor the fuel gauges and leave the high and low fuel alarms turned off. Please advise.

Original factory programming is set through the Kohler engineering department which follows NFPA100

Fire and Protection codes per hospital standards. These parameters can be changed to anything we want where this unit is not being used in a hospital.