This notice provides details for the Prospect Harbor Space Force Station Base Operations Support contract opportunity. The solicitation seeks base operations support services at the government-owned, contractor-operated Prospect Harbor SFS in Maine. Services include physical security, civil engineering, communications systems operations and maintenance, logistics management, and environmental and safety compliance. The contract type will be non-personal services at the GOCO facility. The procurement is planned as a 100% small business set-aside using tradeoff best value source selection. The solicitation is expected to release in January 2024 via the PIEE Solicitation Module. Offerors must register in PIEE and the Solicitation module to submit proposals. This notice requests market research and identifies points of contact but does not commit the government to an award.
View the file
Other files
Show 40 more
Latest 50 of 292 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
APPLIED TECHNICAL SERVICES, INC.
Approved by:
STI
API-653
YES
Project Manager
Chuck Morissette
YES
Senior Consultant
Prospect Harbor, ME
CCI Construction Services
636 Waldo Street • Rumford, ME 04276 • 207-364-4200
Inspection Report
PH-103-K-01
for
In states where Applied Technical Services, Inc. does not provide engineering services, engineering services will be provided by ATS Engineering, (P)LLC or a licensed contractor.
Professional Engineers and Scientists: Design • Consulting • Testing • Inspection
External Inspection:
Internal Inspection:
Jun 02, 2021 Not in scope of work
Elizabeth Ray
AC44195
62886
Job Number: 350727
Prepared by:
UT Thickness Inspection: Not in scope of work
451A (01-2019)
Future Inspections
Visual Inspection
Personnel Qualifications
Photographs
Reference Standards
Table of Contents 350727
Job Number
General Equipment Information
Executive Summary
Recommendations
S.G. S.G. S.G.
NDT Technician Name(s)
Relief Press (psig)
Design Temp (°F)
Design Vac (psig)
Design Press (psig) Design Press (psig)Unknown n/a
Customer
Prospect Harbor, ME
CCI Construction Services
City, State
(assumed)
Year of Construction
Operating Temp (°F)
Vent Press (psig)
Design Temp (°F)
Shell-Side Service Tube-Side Service
Previous Internal Visual n/a
Design Vac (psig)
Operating Temp (°F)
Other Test Methods Performed
Contents Kerosene
Design Press (psig)
STI-SP001Inspection / Analysis Standard(s)
Historical Documentation
None
0.82
Roth
MaineState Where Equipment is Located
Date
-NoPrevious UTT DataNot ApplicableService Category
Not in scope
Unknown
Cert.
-No
Mat'l Construction of Shell Unknown n/an/a
Unknown n/a n/a n/a
Yes/No n/aContentsn/aContents n/a n/a n/a
Operating Temp (°F)
Relief Press (psig)
Design Temp (°F)
Design Vac (psig) n/a
Ambient
Atmospheric
Unknown n/a
Job Number
AST: Rectangular
Manufacturer
UL 2258
Unknown
Construction Information
Joint Efficiency of Shell
06-2020YesPrevious External Visual
PH-103-K-01
Not in scope
Method
Equipment Identification
Equipment Name
This area intentionally left blank
350727 General Equipment Information
N/A
Inspection Guidelines
Construction Standard
Inspection Scope
Equipment Number
STI AC44195
Approximate Volume
Equipment Type
Elizabeth Ray
Cert.
UT Thickness
Yes - while in serviceExternal Visual
Internal Visual
N/A
Cert. #Inspector Name(s) gallons275
Jacket-Side Service
NoDrawings Available
STI Category 3: without spill control
STI Category 2: with spill control & without CRDM
STI Category 1: with spill control & with CRDM
Analysis
As this is a double-wall tank, only the external wall was inspected. No visible deterioration or damage was observed at the time of inspection.
Analysis was performed in general accordance with STI-SP001.
This report contains the results of the field inspections performed. Inspections and analysis were performed in general accordance with the standards listed in "General Equipment Information". Inspections were limited to areas of accessibility. Prioritized action items and subsequent inspection frequencies have been outlined in this report and should be addressed.
Any non-destructive testing (NDT) performed within this scope of work was completed utilizing trained personnel meeting the requirements of SNT-TC-1A. NDT methods were performed in accordance with the codes, standards, or client specifications agreed upon with the client/owner.
Ground only
Not in scope of work
Atmospheric venting was observed on the tank. No visible deterioration or damage was observed at the time of inspection.
The tank was determined to be Category 1 per STI SP001. The basis for this determination is spill control was observed
(double-wall tank) and inherent CRDM was observed (means for interstitial space monitoring). The owner should verify the merits of this assumption and adequacy of the spill control to fully contain a release.
External access gained via:
Executive Summary
External Condition Summary
Job Number
Scope of Work
Equipment Access
Over-Pressure Protection
350727
STI-SP001 Category
Internal access gained via:
Observation Recommended Action Priority
Priority 1 - High likelihood/consequence of failure (or) Critical code/standard deficiency (or) May not be fit for service without action
Priority 2 - Med likelihood/consequence of failure (or) Add'l info needed for evaluation (or) Repair may be considered for continued service
Priority 3 - Low likelihood/consequence of failure (or) Non-critical code/standard deficiency (or) Best practice/preventative maintenance
Action items listed in the table below are based upon observations recorded at the time of the on-site inspection and/or as determined during the post-inspection data evaluation. Prioritization has been applied, and is defined as "1", "2", "3":
Job Number
Recommendations
Ensure both normal and emergency venting is functional on the tank. Because process variables can change over time, the Owner should verify the venting capacity for the system meet the requirements of an applicable standard.
(e.g. API 2000, NFPA 30).
2One (1) vent observed on the tank shell.
350727
If the contents are flammable, the Owner should verify or install proper grounding in accordance to API RP-2003 and/or NFPA 77.
No dedicated grounding cable was observed.
❶
STI SP001: Standard for the Inspection of Aboveground Storage Tanks1)
N/A year(s)
Job Number
Date of Next InspectionFrequency
Assuming a continued service of the equipment in its existing service, the recommended frequencies for re-inspection are listed below. These frequencies are based on applicable industry codes, standards, best practices, and the judgement of the inspector/evaluator considering the results of this inspection.
NotesInspection Type
Future Inspections 350727
Reference Standards
Personnel Qualifications
Elizabeth Ray Mechanical Engineer with 7+ years experience with inspection, evaluation, repair, and design in various industries; API 510 / 653 / 570 certified inspector; FTPI certified inspector; STI certified inspector, Pennsylvania DEP IAF and IAM certified inspector.
N/A year(s) N/A
N/A continual year(s) month1
N/A
❶ Per STI-SP001, "Periodic Owner Inspections" include monthly and annual inspections which should be performed utilizing the checklists provided within
STI-SP001.
Leak Testing N/A
Internal Visual Inspection
External and UT Thickness Inspection
Periodic Owner Inspection
Yes No NA NI a) b)
c) x
d) x
Yes No NA NI a)
b) x
c) x
d) x
e) x
f) x
g) x h)
i) x
j) x
k) x
Yes No NA NI a)
b) x
c) x
d) x
e) x
f) x
g) x
h) x
i) x
Yes No NA NI a)
b) x
c) x
d) x
e) x
f) x
g) x
h) x
i) x
Yes No NA NI a)
b) x
c) x
d) x
e) x
f) x
g) x
h) x
i) x
Defects observed (bulges, dents, holes)
Condition / Comments
Coating failure (peeling, disbond)
Nozzle issues (leaks, corrosion, deformation)
Nozzle bolt issues (corrosion, loose, missing)
Insulation damage (wet, staining, missing, CUI)
Coating failure (peeling, disbond)
Visual limitations (access, insulation, cleanliness)
NA = Not Applicable
NI = Not Inspected
Condition / Comments
Visual limitations (access, insulation, cleanliness) No Limitations
No mechanical damages or defects were observed.
Corrosion or pitting observed
Defects observed (bulges, dents, holes)
Weld or rivet defects (cracks, leaks, corrosion)
Attachment defects (brackets, stiffening, etc.)
South Side Condition / Comments
East Side
North Side
Limited Access
No mechanical damages or defects were observed.
Corrosion or pitting observed
Nozzle issues (leaks, corrosion, deformation)
Nozzle bolt issues (corrosion, loose, missing)
Attachment defects (brackets, stiffening, etc.)
Nozzle issues (leaks, corrosion, deformation)
Nozzle bolt issues (corrosion, loose, missing)
Weld or rivet defects (cracks, leaks, corrosion)
Insulation damage (wet, staining, missing, CUI)
Corrosion, pitting, defects observed
Indication of pluggage observed
Nozzle bolt issues (corrosion, loose, missing)
Coating failure (peeling, disbond)
Attachment defects (brackets, stiffening, etc.)
Defects observed (bulges, dents, holes)
Weld or rivet defects (cracks, leaks, corrosion)
Insulation damage (wet, staining, missing, CUI)
Coating failure (peeling, disbond)
Nozzle issues (leaks, corrosion, deformation)
Attachment defects (brackets, stiffening, etc.)
Location observed On Roof
Atmospheric vent observed.
Visual limitations (access, insulation, cleanliness) No Limitations
Insulation damage (wet, staining, missing, CUI)
Debris build-up observed
Weld or rivet defects (cracks, leaks, corrosion)
Corrosion or pitting observed
Job Number
External Visual Inspection 350727
Defects observed (bulges, dents, holes)
Drainage issues (standing water)
Roof Condition / Comments
Visual limitations (access, insulation, cleanliness) No Limitations
No mechanical damages or defects were observed.
Inspector Name(s): Elizabeth Ray
Visual limitations (access, insulation, cleanliness)
Overflow / Vent Condition / Comments
No Limitations
No mechanical damages or defects were observed.
Corrosion or pitting observed
NA = Not Applicable
NI = Not Inspected
Job Number
External Visual Inspection 350727
Inspector Name(s): Elizabeth Ray
Yes No NA NI a)
b) x
c) x
d) x
e) x
f) x
g) x
h) x
i) x
Yes No NA NI a) b) c)
d) x
e) x
f) x
g) x
Yes No NA NI a)
b) x
c) x
d) x
Yes No NA NI a)
Yes No NA NI a)
b) x
Yes No NA NI a)
Yes No NA NI x x x x
Nozzle issues (leaks, corrosion, deformation)
Coating failure (peeling, disbond)
Weld or rivet defects (cracks, leaks, corrosion)
Additional Conditions / Comments
A stick test was not performed on this tank due to lack of access.
Nozzle bolt issues (corrosion, loose, missing)
Interstitial Space
Attachment defects (brackets, stiffening, etc.)
Secondary Containment Condition / Comments
Type (berm, concrete, steel, curbing) Steel Dike (or Pan)
Type (soil, concrete, structural steel)
The double-wall acts as secondary containment.
Grounding Cables Condition / Comments
Quantity None Observed
Defects observed (cracks, spalling, settling)
Drainage issues (standing water)
Foundation Condition / Comments
No mechanical damages or defects were observed.
Anchor defects (weld cracks, deformation)
Corrosion or pitting observed
Visual limitations (access, insulation, cleanliness) Limited Access The interstitial space should be continuously monitored.
Liquid observed inside
Anchorage Condition / Comments
Type (lugs, chairs, saddles, legs, flange-ring) Saddles
Quantity 3
Visual limitations (access, insulation, cleanliness) Limited Access
Anchor bolt defects (corrosion, necking, broken)
Concrete
Exposed aggregate, debris, vegetation build-up
No mechanical damages or defects were observed.
Coating failure (peeling, disbond)
Condition / Comments
Insulation damage (wet, staining, missing, CUI)
Corrosion or pitting observed
West Side Condition / Comments
Visual limitations (access, insulation, cleanliness)
Defects observed (bulges, dents, holes)
Miscellaneous Condition / Comments
a) Nameplate - was a nameplate observed
Nameplate - was nameplate legible
b) Platforms/Ladders - corrosion
Platforms/Ladders - defects (bent, unsupported)
No Limitations
No mechanical damages or defects were observed.
ATS Job #
Photographs 350727
ATS 451C (09-2018) Proprietary Document. To be reproduced only in full.
Overall view of tank.
South wall.
East wall.
West wall.
North wall.
Support saddle and foundation.
Bottom head.
Interstitial space monitor.
Top head, atmospheric vent.
Fill gauge.
Atmospheric vent.
Fill port.