PH-103-K-01 - 2021 Inspection.pdf

PDF 3 MB Posted

Attached to
Prospect Harbor Space Force Station (SFS) Base Operations Support (BOS)
Solicitation number
FA255024R0003
Issued by

About this file

This notice provides details for the Prospect Harbor Space Force Station Base Operations Support contract opportunity. The solicitation seeks base operations support services at the government-owned, contractor-operated Prospect Harbor SFS in Maine. Services include physical security, civil engineering, communications systems operations and maintenance, logistics management, and environmental and safety compliance. The contract type will be non-personal services at the GOCO facility. The procurement is planned as a 100% small business set-aside using tradeoff best value source selection. The solicitation is expected to release in January 2024 via the PIEE Solicitation Module. Offerors must register in PIEE and the Solicitation module to submit proposals. This notice requests market research and identifies points of contact but does not commit the government to an award.

View the file

Other files

File Type Posted
PHSFS_BOS_RFP_Questions_SET_5_20240301.pdf PDF
FA255024R0003_Amend_0002_240301.pdf PDF
FA255024R0003_SF1449_Amend_0002_240301.pdf PDF
Atch_5_FFP_NTE_Task_Pricing_Template_Amend_0002_240229.xlsx XLSX spreadsheet
PHSFS_BOS_RFP_Questions_SET_2_20240226.pdf PDF
PHSFS_BOS_RFP_Questions_SET 4_20240226.pdf PDF
PHSFS_BOS_RFP_Questions_SET 3_20240226.pdf PDF
20240221_PHSFS_BOS_RFP_Questions.pdf PDF
Atch_8_ITO_Amend_0001_20240221.pdf PDF
FA255024R0003_Amend_0001_20240221.pdf PDF
Atch_9_Evaluation_Amend_0001_20240207.pdf PDF
Atch_16_PPQ_20240104.docx DOCX document
PH B104 Heat PM 9-18.pdf PDF
Report 2305 PH B103 OVHD PM 6-14-22.pdf PDF
Report 1844 PH B101 FM200 Fire System PM 4-5-21.pdf PDF
Report 259 PH B103 BFP Annual PM 3-28-23.pdf PDF
Report 1847 PH B112 Fire Alarm PM 4-5-21.pdf PDF
Report 1175 PH B105 Heat PM 9-27-19.pdf PDF
Report 1456 PH B110 Fire Alarm PM 6-30-20.pdf PDF
Report 2324 PH B104 Annual Heating PM 9-15-21.pdf PDF
Report 1359 PH B101 HVAC Compressor Nr 2 PM 6-10-20.pdf PDF
Report 2443 PH B101 Annual Heating PM 9-29-22.pdf PDF
PH B101 Boiler PM 10-18.pdf PDF
Report 1855 PH B101 Condenser B HVAC PM 4-20-21.pdf PDF
Report 1845 PH B102 CO2Fire System PM 4-5-21.pdf PDF
Report 1356 PH B101 HVAC Air Handler Nr 2 PM 6-10-20.pdf PDF
Report 2174 PH B102 CO2Fire System Annual PM SC 3-9-22.pdf PDF
PH inside Generator SC 3-29-19.pdf PDF
Report 1828 PH B104 OVHD Nr 2 PM 5-24-2021.pdf PDF
PH B112 F7P9ZP-PH-BURNER 2-03-21.pdf PDF
Report 1831 PH B102 Outside Generator SC 5-25-2021.pdf PDF
Report 2252 PH B102 Roof Inspection 6-6-2022.pdf PDF
PH-110-K-02 - 2021 Inspection.pdf PDF
Report 645 PH B102 Outside Generator Annual PM 9-6-23.pdf PDF
Report 1680 PH B103 No heat ESC 12-12-20.pdf PDF
Report 1082 PH B102 inside Generator PM 8-22-18.pdf PDF
Report 1851 Anual Extinguisher PMs 4-5-21.pdf PDF
Report 2241 PH B102 Outside Generator PM 5-18-22.pdf PDF
PH B103 Replace Window Glass 20190820.pdf PDF
Report 402 PH B101 HVAC Nr 1 PM 9-17.pdf PDF
Report 2448 PH B104 Annual Heating PM 9-28-22.pdf PDF
Report 1296 PH B102 Inside Generator PM 2-20-20.pdf PDF
PH B110 Boiler Nr 1 PM 9-18.pdf PDF
Report 367 PH B112 FA Install.pdf PDF
Report 1357 PH B103 HVAC PM 6-10-20.pdf PDF
Report 2175 PH B103 Fire Alarm PM 3-9-22.pdf PDF
Report 2047 PH B101 HVAC Air Handler Side A 9-30-21.pdf PDF
Report 658 PH B104 OVHDR eplace Push Button 7-25-18.pdf PDF
Report 645 PH Outside Generator repair SC 6-20-18.pdf PDF
Report 1829 PH B105 OVHD PM 5-24-2021.pdf PDF
Show 40 more

Latest 50 of 292 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

APPLIED TECHNICAL SERVICES, INC.

Approved by:

STI

API-653

YES

Project Manager

Chuck Morissette

YES

Senior Consultant

Prospect Harbor, ME

CCI Construction Services

636 Waldo Street • Rumford, ME 04276 • 207-364-4200

Inspection Report

PH-103-K-01

for

In states where Applied Technical Services, Inc. does not provide engineering services, engineering services will be provided by ATS Engineering, (P)LLC or a licensed contractor.

Professional Engineers and Scientists: Design • Consulting • Testing • Inspection

External Inspection:

Internal Inspection:

Jun 02, 2021 Not in scope of work

Elizabeth Ray

AC44195

62886

Job Number: 350727

Prepared by:

UT Thickness Inspection: Not in scope of work

451A (01-2019)

Future Inspections

Visual Inspection

Personnel Qualifications

Photographs

Reference Standards

Table of Contents 350727

Job Number

General Equipment Information

Executive Summary

Recommendations

S.G. S.G. S.G.

NDT Technician Name(s)

Relief Press (psig)

Design Temp (°F)

Design Vac (psig)

Design Press (psig) Design Press (psig)Unknown n/a

Customer

Prospect Harbor, ME

CCI Construction Services

City, State

(assumed)

Year of Construction

Operating Temp (°F)

Vent Press (psig)

Design Temp (°F)

Shell-Side Service Tube-Side Service

Previous Internal Visual n/a

Design Vac (psig)

Operating Temp (°F)

Other Test Methods Performed

Contents Kerosene

Design Press (psig)

STI-SP001Inspection / Analysis Standard(s)

Historical Documentation

None

0.82

Roth

MaineState Where Equipment is Located

Date

-NoPrevious UTT DataNot ApplicableService Category

Not in scope

Unknown

Cert.

-No

Mat'l Construction of Shell Unknown n/an/a

Unknown n/a n/a n/a

Yes/No n/aContentsn/aContents n/a n/a n/a

Operating Temp (°F)

Relief Press (psig)

Design Temp (°F)

Design Vac (psig) n/a

Ambient

Atmospheric

Unknown n/a

Job Number

AST: Rectangular

Manufacturer

UL 2258

Unknown

Construction Information

Joint Efficiency of Shell

06-2020YesPrevious External Visual

PH-103-K-01

Not in scope

Method

Equipment Identification

Equipment Name

This area intentionally left blank

350727 General Equipment Information

N/A

Inspection Guidelines

Construction Standard

Inspection Scope

Equipment Number

STI AC44195

Approximate Volume

Equipment Type

Elizabeth Ray

Cert.

UT Thickness

Yes - while in serviceExternal Visual

Internal Visual

N/A

Cert. #Inspector Name(s) gallons275

Jacket-Side Service

NoDrawings Available

STI Category 3: without spill control

STI Category 2: with spill control & without CRDM

STI Category 1: with spill control & with CRDM

Analysis

As this is a double-wall tank, only the external wall was inspected. No visible deterioration or damage was observed at the time of inspection.

Analysis was performed in general accordance with STI-SP001.

This report contains the results of the field inspections performed. Inspections and analysis were performed in general accordance with the standards listed in "General Equipment Information". Inspections were limited to areas of accessibility. Prioritized action items and subsequent inspection frequencies have been outlined in this report and should be addressed.

Any non-destructive testing (NDT) performed within this scope of work was completed utilizing trained personnel meeting the requirements of SNT-TC-1A. NDT methods were performed in accordance with the codes, standards, or client specifications agreed upon with the client/owner.

Ground only

Not in scope of work

Atmospheric venting was observed on the tank. No visible deterioration or damage was observed at the time of inspection.

The tank was determined to be Category 1 per STI SP001. The basis for this determination is spill control was observed

(double-wall tank) and inherent CRDM was observed (means for interstitial space monitoring). The owner should verify the merits of this assumption and adequacy of the spill control to fully contain a release.

External access gained via:

Executive Summary

External Condition Summary

Job Number

Scope of Work

Equipment Access

Over-Pressure Protection

350727

STI-SP001 Category

Internal access gained via:

Observation Recommended Action Priority

Priority 1 - High likelihood/consequence of failure (or) Critical code/standard deficiency (or) May not be fit for service without action

Priority 2 - Med likelihood/consequence of failure (or) Add'l info needed for evaluation (or) Repair may be considered for continued service

Priority 3 - Low likelihood/consequence of failure (or) Non-critical code/standard deficiency (or) Best practice/preventative maintenance

Action items listed in the table below are based upon observations recorded at the time of the on-site inspection and/or as determined during the post-inspection data evaluation. Prioritization has been applied, and is defined as "1", "2", "3":

Job Number

Recommendations

Ensure both normal and emergency venting is functional on the tank. Because process variables can change over time, the Owner should verify the venting capacity for the system meet the requirements of an applicable standard.

(e.g. API 2000, NFPA 30).

2One (1) vent observed on the tank shell.

350727

If the contents are flammable, the Owner should verify or install proper grounding in accordance to API RP-2003 and/or NFPA 77.

No dedicated grounding cable was observed.

❶

STI SP001: Standard for the Inspection of Aboveground Storage Tanks1)

N/A year(s)

Job Number

Date of Next InspectionFrequency

Assuming a continued service of the equipment in its existing service, the recommended frequencies for re-inspection are listed below. These frequencies are based on applicable industry codes, standards, best practices, and the judgement of the inspector/evaluator considering the results of this inspection.

NotesInspection Type

Future Inspections 350727

Reference Standards

Personnel Qualifications

Elizabeth Ray Mechanical Engineer with 7+ years experience with inspection, evaluation, repair, and design in various industries; API 510 / 653 / 570 certified inspector; FTPI certified inspector; STI certified inspector, Pennsylvania DEP IAF and IAM certified inspector.

N/A year(s) N/A

N/A continual year(s) month1

N/A

❶ Per STI-SP001, "Periodic Owner Inspections" include monthly and annual inspections which should be performed utilizing the checklists provided within

STI-SP001.

Leak Testing N/A

Internal Visual Inspection

External and UT Thickness Inspection

Periodic Owner Inspection

Yes No NA NI a) b)

c) x

d) x

Yes No NA NI a)

b) x

c) x

d) x

e) x

f) x

g) x h)

i) x

j) x

k) x

Yes No NA NI a)

b) x

c) x

d) x

e) x

f) x

g) x

h) x

i) x

Yes No NA NI a)

b) x

c) x

d) x

e) x

f) x

g) x

h) x

i) x

Yes No NA NI a)

b) x

c) x

d) x

e) x

f) x

g) x

h) x

i) x

Defects observed (bulges, dents, holes)

Condition / Comments

Coating failure (peeling, disbond)

Nozzle issues (leaks, corrosion, deformation)

Nozzle bolt issues (corrosion, loose, missing)

Insulation damage (wet, staining, missing, CUI)

Coating failure (peeling, disbond)

Visual limitations (access, insulation, cleanliness)

NA = Not Applicable

NI = Not Inspected

Condition / Comments

Visual limitations (access, insulation, cleanliness) No Limitations

No mechanical damages or defects were observed.

Corrosion or pitting observed

Defects observed (bulges, dents, holes)

Weld or rivet defects (cracks, leaks, corrosion)

Attachment defects (brackets, stiffening, etc.)

South Side Condition / Comments

East Side

North Side

Limited Access

No mechanical damages or defects were observed.

Corrosion or pitting observed

Nozzle issues (leaks, corrosion, deformation)

Nozzle bolt issues (corrosion, loose, missing)

Attachment defects (brackets, stiffening, etc.)

Nozzle issues (leaks, corrosion, deformation)

Nozzle bolt issues (corrosion, loose, missing)

Weld or rivet defects (cracks, leaks, corrosion)

Insulation damage (wet, staining, missing, CUI)

Corrosion, pitting, defects observed

Indication of pluggage observed

Nozzle bolt issues (corrosion, loose, missing)

Coating failure (peeling, disbond)

Attachment defects (brackets, stiffening, etc.)

Defects observed (bulges, dents, holes)

Weld or rivet defects (cracks, leaks, corrosion)

Insulation damage (wet, staining, missing, CUI)

Coating failure (peeling, disbond)

Nozzle issues (leaks, corrosion, deformation)

Attachment defects (brackets, stiffening, etc.)

Location observed On Roof

Atmospheric vent observed.

Visual limitations (access, insulation, cleanliness) No Limitations

Insulation damage (wet, staining, missing, CUI)

Debris build-up observed

Weld or rivet defects (cracks, leaks, corrosion)

Corrosion or pitting observed

Job Number

External Visual Inspection 350727

Defects observed (bulges, dents, holes)

Drainage issues (standing water)

Roof Condition / Comments

Visual limitations (access, insulation, cleanliness) No Limitations

No mechanical damages or defects were observed.

Inspector Name(s): Elizabeth Ray

Visual limitations (access, insulation, cleanliness)

Overflow / Vent Condition / Comments

No Limitations

No mechanical damages or defects were observed.

Corrosion or pitting observed

NA = Not Applicable

NI = Not Inspected

Job Number

External Visual Inspection 350727

Inspector Name(s): Elizabeth Ray

Yes No NA NI a)

b) x

c) x

d) x

e) x

f) x

g) x

h) x

i) x

Yes No NA NI a) b) c)

d) x

e) x

f) x

g) x

Yes No NA NI a)

b) x

c) x

d) x

Yes No NA NI a)

Yes No NA NI a)

b) x

Yes No NA NI a)

Yes No NA NI x x x x

Nozzle issues (leaks, corrosion, deformation)

Coating failure (peeling, disbond)

Weld or rivet defects (cracks, leaks, corrosion)

Additional Conditions / Comments

A stick test was not performed on this tank due to lack of access.

Nozzle bolt issues (corrosion, loose, missing)

Interstitial Space

Attachment defects (brackets, stiffening, etc.)

Secondary Containment Condition / Comments

Type (berm, concrete, steel, curbing) Steel Dike (or Pan)

Type (soil, concrete, structural steel)

The double-wall acts as secondary containment.

Grounding Cables Condition / Comments

Quantity None Observed

Defects observed (cracks, spalling, settling)

Drainage issues (standing water)

Foundation Condition / Comments

No mechanical damages or defects were observed.

Anchor defects (weld cracks, deformation)

Corrosion or pitting observed

Visual limitations (access, insulation, cleanliness) Limited Access The interstitial space should be continuously monitored.

Liquid observed inside

Anchorage Condition / Comments

Type (lugs, chairs, saddles, legs, flange-ring) Saddles

Quantity 3

Visual limitations (access, insulation, cleanliness) Limited Access

Anchor bolt defects (corrosion, necking, broken)

Concrete

Exposed aggregate, debris, vegetation build-up

No mechanical damages or defects were observed.

Coating failure (peeling, disbond)

Condition / Comments

Insulation damage (wet, staining, missing, CUI)

Corrosion or pitting observed

West Side Condition / Comments

Visual limitations (access, insulation, cleanliness)

Defects observed (bulges, dents, holes)

Miscellaneous Condition / Comments

a) Nameplate - was a nameplate observed

Nameplate - was nameplate legible

b) Platforms/Ladders - corrosion

Platforms/Ladders - defects (bent, unsupported)

No Limitations

No mechanical damages or defects were observed.

ATS Job #

Photographs 350727

ATS 451C (09-2018) Proprietary Document. To be reproduced only in full.

Overall view of tank.

South wall.

East wall.

West wall.

North wall.

Support saddle and foundation.

Bottom head.

Interstitial space monitor.

Top head, atmospheric vent.

Fill gauge.

Atmospheric vent.

Fill port.