Report 1851 Anual Extinguisher PMs 4-5-21.pdf

PDF 494 KB Posted

Attached to
Prospect Harbor Space Force Station (SFS) Base Operations Support (BOS)
Solicitation number
FA255024R0003
Issued by

About this file

This document contains a federal contract opportunity notice and a related maintenance inspection report. The notice announces a forthcoming solicitation in January 2024 for base operations support services at Prospect Harbor Space Force Station, a facility transitioning from Navy to Space Force responsibility. The small business set-aside contract will require operation of the government-owned, contractor-operated facility, including physical security, civil engineering, communications systems administration, logistics, environmental services, and occupational health compliance. The inspection report provides details on the annual maintenance of 22 portable fire extinguishers at the property, with one hose replacement noted.

View the file

Other files

File Type Posted
PHSFS_BOS_RFP_Questions_SET_5_20240301.pdf PDF
FA255024R0003_Amend_0002_240301.pdf PDF
FA255024R0003_SF1449_Amend_0002_240301.pdf PDF
Atch_5_FFP_NTE_Task_Pricing_Template_Amend_0002_240229.xlsx XLSX spreadsheet
PHSFS_BOS_RFP_Questions_SET_2_20240226.pdf PDF
PHSFS_BOS_RFP_Questions_SET 4_20240226.pdf PDF
PHSFS_BOS_RFP_Questions_SET 3_20240226.pdf PDF
20240221_PHSFS_BOS_RFP_Questions.pdf PDF
Atch_8_ITO_Amend_0001_20240221.pdf PDF
FA255024R0003_Amend_0001_20240221.pdf PDF
Atch_9_Evaluation_Amend_0001_20240207.pdf PDF
Atch_16_PPQ_20240104.docx DOCX document
PH B104 Heat PM 9-18.pdf PDF
Report 2305 PH B103 OVHD PM 6-14-22.pdf PDF
Report 1844 PH B101 FM200 Fire System PM 4-5-21.pdf PDF
PH-103-K-01 - 2021 Inspection.pdf PDF
Report 259 PH B103 BFP Annual PM 3-28-23.pdf PDF
Report 1847 PH B112 Fire Alarm PM 4-5-21.pdf PDF
Report 1175 PH B105 Heat PM 9-27-19.pdf PDF
Report 1456 PH B110 Fire Alarm PM 6-30-20.pdf PDF
Report 2324 PH B104 Annual Heating PM 9-15-21.pdf PDF
Report 1359 PH B101 HVAC Compressor Nr 2 PM 6-10-20.pdf PDF
Report 2443 PH B101 Annual Heating PM 9-29-22.pdf PDF
PH B101 Boiler PM 10-18.pdf PDF
Report 1855 PH B101 Condenser B HVAC PM 4-20-21.pdf PDF
Report 1845 PH B102 CO2Fire System PM 4-5-21.pdf PDF
Report 1356 PH B101 HVAC Air Handler Nr 2 PM 6-10-20.pdf PDF
Report 2174 PH B102 CO2Fire System Annual PM SC 3-9-22.pdf PDF
PH inside Generator SC 3-29-19.pdf PDF
Report 1828 PH B104 OVHD Nr 2 PM 5-24-2021.pdf PDF
PH B112 F7P9ZP-PH-BURNER 2-03-21.pdf PDF
Report 1831 PH B102 Outside Generator SC 5-25-2021.pdf PDF
Report 2252 PH B102 Roof Inspection 6-6-2022.pdf PDF
PH-110-K-02 - 2021 Inspection.pdf PDF
Report 645 PH B102 Outside Generator Annual PM 9-6-23.pdf PDF
Report 1680 PH B103 No heat ESC 12-12-20.pdf PDF
Report 1082 PH B102 inside Generator PM 8-22-18.pdf PDF
Report 2241 PH B102 Outside Generator PM 5-18-22.pdf PDF
PH B103 Replace Window Glass 20190820.pdf PDF
Report 402 PH B101 HVAC Nr 1 PM 9-17.pdf PDF
Report 2448 PH B104 Annual Heating PM 9-28-22.pdf PDF
Report 1296 PH B102 Inside Generator PM 2-20-20.pdf PDF
PH B110 Boiler Nr 1 PM 9-18.pdf PDF
Report 367 PH B112 FA Install.pdf PDF
Report 1357 PH B103 HVAC PM 6-10-20.pdf PDF
Report 2175 PH B103 Fire Alarm PM 3-9-22.pdf PDF
Report 2047 PH B101 HVAC Air Handler Side A 9-30-21.pdf PDF
Report 658 PH B104 OVHDR eplace Push Button 7-25-18.pdf PDF
Report 645 PH Outside Generator repair SC 6-20-18.pdf PDF
Report 1829 PH B105 OVHD PM 5-24-2021.pdf PDF
Show 40 more

Latest 50 of 292 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

(ATTACH ADDITIONAL SHEETS IF NECESSARY)

YES NO

YES NO

YES NO

MATERIALS USED

MAINTENACE & INSPECTION REPORT

(ONE FOR EACH PIECE OF EQUIPMENT)

WILL MATERIALS NEED TO BE ORDERED? HOW LONG IS THE LEED TIME?

EXPLAIN BELOW

HAVE NOT BEEN MET

(BELOW) FOR ADMINISTRATION USE ONLY

DATE IT WILL BE RECEIVED :

PROPER PPE BEING WORN

YES

CONTRACTOR: TECHNICIANS NAME:

LOCATION WEATHERBUILDING NAME or #

CONTRACTOR/SIGNATURE CCI/ SIGNATURE SITE INSPECTOR/SIGNATURE

CONTRACT # ELIN # REPORT NO.

HAVE BEEN MET

DATE:

General Direct Condition Rating

TYPE OF EQUIPMENT MAKE MODEL

WORK DESCRIPTION & PROBLEMS FOUNDS

TIME TO COMPLETE TASK

IS INSPECTION CHECK LIST ATTACHED?

SAFETY REQUIREMENTS

WAS WORK COMPLETED?

IF NO EXPLAIN BELOW

General Direct Condition Rating Notes ( Explain Conditions found for the Rating given above)

N40085-17-D-7201

NO

HOUSE KEEPING COMPLETE

YES

NO

MAXIMO # Work Order #

4/5/2021

Fire extinguisher Amerex ABC 2 Dean & Allyn, Inc. Barry Prescott

Prospect Harbor Various Cool/drizzle Green +

Annual inspection of 22 portable fire extinguishers x

1851E002AM

Barry Prescott #135

200000044219Inspection Ref:

Conducted by:

Report of Inspection/Test

Property Owner/Agent

526 Western Ave.

Augusta, ME 04430

CCI Group, LLCProspect Harbor

Annual Extinguisher

Derek McCaslin

(207)620-7172 x111 Print Date: 5/3/2021

April 5, 2021

Equipment Summary

Site

Description

Inspected Unable to

Inspect Serviced

Repaired Failed

%Qty%Qty%Qty%QtyQty

Extinguisher Extinguisher

ABC 19 19 0 0100.0% 0.0% 0.0% 0 0.0%

K-class 1 1 0 1100.0% 0.0% 100.0% 0 0.0%

Inspector's Recommendations

The inspector recommends the following system changes/improvements.

One 10lb ABC extinguisher in Bldg #110 had a broken hose which was replaced from truck stock

Fire Extinguisher Inspection List

Location

Description Size Type

Inspection - Service

G a u g e

P u ll P in

S ig n a g e

C o lla r

H o se /N o zz le

B ra ck e t

W e ig h t

Y e a r In sp

H yd ro T e stSerial #

Manufacturer

Model

Equip ID

(Item #)

Bldg #110

Ok Ok Ok Ok Ok Ok Ok Ok OkABCBoiler Rm 10 lb

Ok Ok Ok Ok Ok Ok Ok Ok OkABCPool Table 10 lb

X Ok Ok Ok Ok Ok Ok Ok OkK-classKitchen 6 liter due for hydro test

Ok Ok Ok Ok Ok Ok Ok Ok OkABCBack Stair 10 lb

Ok Ok Ok Ok Ok Ok Ok Ok OkABCOutside porch 10 lb

Ok Ok Ok Ok Ok Ok Ok Ok OkABCAmmo Locker 10 lb

Bldg #101

Ok Ok Ok Ok Ok Ok Ok Ok OkABCBldg #101 10 lb

Ok Ok Ok Ok Ok Ok Ok Ok OkABCSecure area 10 lb

Ok Ok Ok Ok Ok Ok Ok Ok OkABCBy release FACP 10 lb

Ok Ok Ok Ok Ok Ok Ok Ok OkABCBy entrance 10 lb

Bldg #105

Ok Ok Ok Ok Ok Ok Ok Ok OkABCOffice 10 lb

Print Date: 5/3/2021 Copyright 2002-2018 Life Safety Inspector, OnSite Software

Report of Inspection/Test

Prospect HarborProperty:

Owner: CCI Group, LLC 200000044219Inspection Ref:

Annual Extinguisher

April 5, 2021

Fire Extinguisher Inspection List

Location

Description Size Type

Inspection - Service

G a u g e

P u ll P in

S ig n a g e

C o lla r

H o s e

/N o z zl e

B ra c k e t

W e ig h t

Y e a r In s p

H y d ro T e s t

Serial # Manufacturer

Model

Equip ID

(Item #)

Bldg #105

Ok Ok Ok Ok Ok Ok Ok Ok Ok ABCRear Door 10 lb

Bldg #104

Ok Ok Ok Ok Ok Ok Ok Ok Ok ABCBy Door 10 lb

Admin #112

Ok Ok Ok Ok Ok Ok Ok Ok Ok ABCBy FACP 10 lb

Ok Ok Ok Ok Ok Ok Ok Ok Ok ABCBoiler Rm 10 lb

Bldg #106

Ok Ok Ok Ok Ok Ok Ok Ok Ok ABC5 lb

New Bldg

Ok Ok Ok Ok Ok Ok Ok Ok Ok ABCBy overhead door 10 lb

Ok Ok Ok Ok Ok Ok Ok Ok Ok ABCby office door 10 lb

Bldg #52

Ok Ok Ok Ok Ok Ok Ok Ok Ok firebouy automaticABC15 lb

Bldg #102

Ok Ok Ok Ok Ok Ok Ok Ok Ok ABCBy door 10 lb

Bldg #103

Ok Ok Ok Ok Ok Ok Ok Ok Ok ABCBldg #103 10 lb

Ok Ok Ok Ok Ok Ok Ok Ok Ok ABCBldg #103 10 lb

Fire Extinguisher

Detail Summary Number of Items Requiring Service

Repaired, Replaced and Tested Ok

X

S Number of Items:

Print Date: 5/3/2021

Report of Inspection/Test

Prospect HarborProperty:

Owner: CCI Group, LLC 200000044219Inspection Ref:

Annual Extinguisher

April 5, 2021

Deficiency / Recommendations Summary

These items were deficient and do not meet the requirements of the applicable code at the time of the inspection. Items marked

Recommendation are not required by the applicable code but are opportunities to improve the Life Safety of the property.

Inspector's Recommendations

The inspector recommends the following system changes/improvements.

One 10lb ABC extinguisher in Bldg #110 had a broken hose which was replaced from truck stock

Extinguisher Wet Chem Inspection Kitchen 2-1/2 gal Bldg #110 Kitchen Extinguisher K-class Kitchen

X Hydro Test due for hydro test

Print Date: 5/3/2021