Report 1456 PH B110 Fire Alarm PM 6-30-20.pdf
PDF 652 KB Posted
- Solicitation number
- FA255024R0003
About this file
This document contains a report of an annual fire alarm inspection at Prospect Harbor Space Force Station Building 110 and a related pre-solicitation notice for base operations support services at the station.
The fire alarm inspection report details the inspection of the site's alarm panel and devices, including batteries, pull stations, smoke detectors and horns. It notes that all equipment tested was found to be in good working order. The pre-solicitation notice indicates that the Department of the Air Force will be soliciting proposals in January 2024 for base operations support services at Prospect Harbor Space Force Station under solicitation FA255024R0003. The services will include staffing and security, facilities maintenance, communications systems administration, logistics and environmental compliance. The contract is planned as a 100% small business set-aside and will utilize a best value tradeoff source selection method. The solicitation and proposal submissions will utilize the Procurement Integrated Enterprise Environment system.
View the file
Other files
Show 40 more
Latest 50 of 292 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
x
1456D002AM
Barry Prescott #135
200000030928Inspection Ref:
Conducted by:
Report of Inspection/Test
Property Owner/Agent
526 Western Ave.
Augusta, ME 04430
CCI Group, LLCUS Navy - Prospect Harbor -
Bldg 110
Light House Point Road
Prospect Harbor, ME
Annual Alarm
Derek McCaslin
(207)620-7172 x111 Print Date: 7/31/2020
06/30/2020
Signatures
Inspector - Printed Date CompletedInspector - Signature
Barry Prescott 6/30/20
I state that the information on this form is correct at the time and place of my inspection, and all equipment tested at this time was left in operational condition upon completion of this inspection except as noted.
Equipment Summary
Site
Description
Inspected Unable to
Inspect
Serviced
Repaired Failed
%Qty%Qty%Qty%QtyQty
Alarm Alarm Panel 2
1 1 0 0100.0% 0.0% 0.0% 0 0.0%
Alarm Battery
Sealed Lead Acid 1 1 0 0100.0% 0.0% 0.0% 0 0.0%
Alarm Panel Information
Panel Manufacturer Model Serial No. Location
Simplex 4001 outside of bldg
Software Rev Software Updated
Overcurrent Protect Type Overcurrent Size (Amps) Primary Supply Disconnect Location / Panel # / Breaker #
Fuse outside of bldg20
Battery Test
Location / Description Type Manufacturer
Model
R e p la ce m e n t
D a te
Measured Voltage
Qty
C o n d iti o n
E le ct ro ly te
L e a ks o r
C o rr o si o n
C o n n e ct io n s
L o a d C u rr e n t
(A m p s)
W ith
C h a rg e r
N o L o a d
U n d e r
L o a d
N o L o a d
A ft e r
T e st
Sealed Lead
Acid
Ok Ok OkOk2 12-7
Print Date: 7/31/2020 Copyright 2002-2020 Life Safety Inspector, OnSite Software
Report of Inspection/Test
US Navy - Prospect Harbor - Bldg 110Property:
Owner: CCI Group, LLC 200000030928Inspection Ref:
Annual Alarm
06/30/2020
Device Summary
Device Qty Manufacturer Model Quantity
Failed
% of Total
Tested
Quantity
Tested
Intiating Devices
Pull Station 3 3 0100%
Smoke PE 8 8 0100%
Heat Detector 7 Fixed Temp 7 0100%
Indicating Devices
Horn/Strobe 3 3 0100%
Strobe 3 3 0100%
System Function Summary & Test
Function Description Test Result
Alarm Functions
Alarm Bells/Horns/Strobes Evacuation Alarm functions including Bells/Horns/Strobes actuate properly Pass
Alarm Panel Supervisory Functions
Panel AC Power Loss Loss of AC power to the alarm panel is detected by the alarm system. Pass
Panel Sec Power Loss Loss of Secondary power to the alarm panel is detected by the alarm system. Pass
Open Alarm Circuits Electrical opens in initiating and indicating circuits are detected. Pass
Short Alarm Circuits Electrical shorts in initiating and indicating circuits are detected. Pass
Ground Faults Detected Ground faults in alarm circuits are detected Pass
Panel Inspection
Yes Panel and surrounding equipment, conduit and wiring well secured and in good condition
YesSystem was in operation upon arrival?
Yes Primary power supply operates properly under full load ?
YesAre all lamps and displays operating correctly?
Yes Have all fuses been checked for rating and supervision ?
YesTransient suppressors visually inspected?
Yes Are operating instructions posted or available at the panel?
YesAre drawings and wiring diagrams available at the panel?
Yes Are zones labeled and identified?
Battery Replace Sealed Lead Acid
No Battery replaced ?
Central Station Test
Yes Operator spoke toAlarm, Trouble and Supervisory indication tested and verified with the central station?
Print Date: 7/31/2020 Copyright 2002-2020 Life Safety Inspector, OnSite Software