This document outlines infrastructure upgrades required at the Chillicothe VA Medical Center campus in Chillicothe, Ohio. The scope of work includes upgrading telecommunications rooms, installing new fiber optic and copper backbone cabling both underground and within buildings, upgrading wireless networks, and renovating electrical systems. The project will be awarded on a firm-fixed price basis. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center with an response due date of May 18, 2023 and period of performance of 540 calendar days.
View the file
Other files
Show 40 more
Latest 50 of 65 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CC6
COMM CLOSET
212-T402
2-48 PORT PATCH PANELS
2-4" C. DN
2-4" C.
A/C
15C
Space
212-T402
8 1 8
10 9 10
BLANKING PANELS
BLANKING PANELS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:1
P
M
212-T402
ENLARGED TR RM 125
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTS 212
CHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: 1/2" = 1'-0"
B212 - ENLARGED TR RM 125 - REMOVALS
SCALE: 1/2" = 1'-0"
B212 - ENLARGED TR RM 102 - NEW WORK
SCALE: 1 1/2" = 1'-0"
BLDG 212 TR ROOM 125 ELEVATION - REMOVALS
PLAN NOTES
1. EXISTING 2 POST RACK TO BE REMOVED.
2. EXISTING DATA STATION PATCH PANELS TO BE REMOVED.
3. EXISTING FIBER TERMINATION PANELS TO BE REMOVED.
4. EXISTING NETWORK ELECTRONICS TO BE REMOVED BY GOVERNMENT.
5. EXISTING UPS TO BE REMOVED.
6. EXISTING VIDEO CAMERA TO BE REINSTALLED IN NEW LOCATION.
7. EXISTING LADDER RACK TO BE REMOVED.
8. EXISTING VERTICAL WIRE MANAGER TO BE REMOVED.
9. NEW WHITE, 30" CHANNEL STYLE, 45RU RACK TO BE INSTALLED.
10. NEW VERTICAL WIRE MANAGER TO BE INSTALLED.
11. NEW 12'' x 4" WIRE BASKET CABLE TRAY WITH LINER TO BE INSTALLED.
12. NEW DATA STATION CABLING PATCH PANEL.
13. NEW FIBER TERMINATION PANEL.
14. NEW HORIZONTAL CABLE MANAGER.
15. NEW RACK MOUNTED UPS.
16. NETWORK SWITCH BY GOVERNMENT.
17. EXISTING ACCESS CONTROL EQUIPMENT TO BE MAINTAINED.
18. EXISTING ANALOG VOICE 110 WALL FIELD TO BE MAINTAINED.
19. EXISTING HORIZONTAL WIRE MANAGER TO BE REMOVED.
20. NEW PLYWOOD BACKBOARD
21. NEW TELECOMMUNICATIONS GROUND BAR.
SCALE: 1 1/2" = 1'-0"
BLDG 212 TR ROOM 102 RACK ELEVATION - NEW WORK
No. Revisions: Date:
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
CONSTRUCTION DOCUMENTS - 100% QC SUBMITTAL 03/31/2023
CONSTRUCTION DOCUMENTS - 95% 04/14/2023
CC
212-T403
6-48 PORT PATCH PANELS
1-24 PORT PATCH PANEL
212-T403
4-4" C.
2-4" C. DN
1 88
10 9 10
BLANKING PANELS
BLANKING PANELS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:4
P
M
212-T403
ENLARGED TR RM 225
04/14/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTSCHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: 1/2" = 1'-0"
B212 - ENLARGED TR RM 225 - NEW WORK
SCALE: 1/2" = 1'-0"
B212 - ENLARGED TR RM 225 - REMOVALS
PLAN NOTESPLAN NOTES
1. EXISTING 2 POST RACK TO BE REMOVED.
2. EXISTING DATA STATION PATCH PANELS TO BE REMOVED.
3. EXISTING FIBER TERMINATION PANELS TO BE REMOVED.
4. EXISTING NETWORK ELECTRONICS TO BE REMOVED BY GOVERNMENT.
5. EXISTING UPS TO BE REMOVED.
6. EXISTING VIDEO CAMERA TO BE REINSTALLED IN NEW LOCATION.
7. EXISTING LADDER RACK TO BE REMOVED.
8. EXISTING VERTICAL CABLE MANAGER TO BE REMOVED.
9. NEW WHITE, 30" CHANNEL STYLE, 45RU RACK TO BE INSTALLED.
10. NEW VERTICAL WIRE MANAGER TO BE INSTALLED.
11. NEW 12'' x 4" WIRE BASKET CABLE TRAY WITH LINER TO BE INSTALLED.
12. NEW DATA STATION CABLING PATCH PANEL.
13. NEW FIBER TERMINATION PANEL.
14. NEW HORIZONTAL CABLE MANAGER.
15. NEW RACK MOUNTED UPS.
16. NETWORK SWITCH BY GOVERNMENT.
17. NEW 24 PORT PATCH PANEL.
18. EXISTING ACCESS CONTROL EQUIPMENT TO BE MAINTAINED.
19. EXISTING ANALOG VOICE 110 WALL FIELD TO BE MAINTAINED.
20. NEW PLYWOOD BACKBOARD
SCALE: 1 1/2" = 1'-0"
BLDG 212 TR ROOM 225 RACK ELEVATION - REMOVALS
SCALE: 1 1/2" = 1'-0"
BLDG 212 TR ROOM 225 RACK ELEVATION - NEW WORK
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:1
P
M
247-TA100
BASEMENT PLAN
04/14/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTSCHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: 1/8" = 1'-0"
B247 - BASEMENT
N
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
DN
D W
247-T400
247-T400
TECH
ROOM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:2
P
M
247-TA101
FIRST FLOOR PLAN
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTS 247
CHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: 1/8" = 1'-0"
B247 - FIRST FLOOR
N
No. Revisions: Date:
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
BLANKING PANELS
25 PAIR PROTECTOR PANEL
RACK SHELF
247-T400 1
G021
1-48 PORT SWITCH, NO PATCH
PANEL, CABLES DIRECT
CONNECTED.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:5
P
M
247-T400
ENLARGED TR ROOM 109
04/14/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTSCHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: 1 1/2" = 1'-0"
BLDG 247 TR ROOM 109 RACK ELEVATION - NEW WORK
SCALE: 1/2" = 1'-0"
B247 - ENLARGED TR RM 109 - NEW WORK
SCALE: 1/2" = 1'-0"
B247 - ENLARGED TR RM 109 - REMOVALS
PLAN NOTES
1. EXISTING EQUIPMENT CABINET WITH NETWORK SWITCH AND DIRECT CONNECT
CABLES TO BE REMOVED.
2. EXISTING DATA STATION PATCH PANELS TO BE REMOVED.
3. EXISTING FIBER TERMINATION PANELS TO BE REMOVED.
4. EXISTING NETWORK ELECTRONICS TO BE REMOVED BY GOVERNMENT.
5. EXISTING UPS TO BE REMOVED.
6. EXISTING VIDEO CAMERA TO BE REINSTALLED IN NEW LOCATION.
7. EXISTING LADDER RACK TO BE REMOVED.
8. EXISTING LADDER RACK TO BE MAINTAINED.
9. NEW WHITE, 30" CHANNEL STYLE, 45RU RACK TO BE INSTALLED.
10. NEW VERTICAL WIRE MANAGER TO BE INSTALLED.
11. NEW 12'' x 4" WIRE BASKET CABLE TRAY WITH LINER TO BE INSTALLED.
12. NEW DATA STATION CABLING PATCH PANEL.
13. NEW FIBER TERMINATION PANEL.
14. NEW HORIZONTAL CABLE MANAGER.
15. NEW RACK MOUNTED UPS.
16. NETWORK SWITCH BY GOVERNMENT.
17. EXISTING ACCESS CONTROL EQUIPMENT TO BE MAINTAINED.
18. EXISTING ANALOG VOICE 110 WALL FIELD TO BE MAINTAINED.
19. NEW PLYWOOD BACKBOARD
20. NEW WALL MOUNTED TELECOMMUNICATIONS ENCLOSURE, NEMA 12 STEEL SWING
OUT CABINET WITH LOCKING TEMPERED GLASS FRONT DOOR, 26RU, 30" DEPTH, 24"
WIDTH, ACTIVE COOLING FANS.
21. NEW MULTI-OUTLET PDU, 1-UPS, 1-NORMAL.
22. NEW TELECOMMUNICATIONS GROUND BAR.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
AP
AP
AP
AP
2D/1V
2D/1V 2D/1V
2D/1V 3D/1V
2D/1V
2D/1V
AP
2D/1V
252-T400
3252-T400
ROOM
TECH RM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:0
P
M
252-TA101
FIRST FLOOR PLAN
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTS 252
CHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
NSCALE: 1/8" = 1'-0"
B252 - FIRST FLOOR PLAN
No. Revisions: Date:
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
252-T4001
4-24 PORT PATCH PANELS.
6 18
BLANKING PANELS
25 PAIR PROTECTOR PANEL
RACK SHELF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:4
P
M
252-T400
ENLARGED TR ROOM 110
04/14/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTSCHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: 1/2" = 1'-0"
B252 - ENALRGED TR ROOM 103 - NEW WORK
SCALE: 1/2" = 1'-0"
B252 - ENLARGED TR ROOM 112 - REMOVALS
PLAN NOTES
1. EXISTING WALL MOUNTED RACK TO BE REMOVED.
2. EXISTING DATA STATION PATCH PANELS TO BE REMOVED.
3. EXISTING FIBER TERMINATION PANELS TO BE REMOVED.
4. EXISTING NETWORK ELECTRONICS TO BE REMOVED BY GOVERNMENT.
5. EXISTING UPS TO BE REMOVED.
6. EXISTING VIDEO CAMERA TO BE REINSTALLED IN NEW LOCATION.
7. EXISTING LADDER RACK TO BE REMOVED.
8. EXISTING LADDER RACK TO BE MAINTAINED.
9. NEW WHITE, 30" CHANNEL STYLE, 45RU RACK TO BE INSTALLED.
10. NEW VERTICAL WIRE MANAGER TO BE INSTALLED.
11. NEW 12'' x 4" WIRE BASKET CABLE TRAY WITH LINER TO BE INSTALLED.
12. NEW DATA STATION CABLING PATCH PANEL.
13. NEW FIBER TERMINATION PANEL.
14. NEW HORIZONTAL CABLE MANAGER.
15. NEW RACK MOUNTED UPS.
16. NETWORK SWITCH BY GOVERNMENT.
17. EXISTING ACCESS CONTROL EQUIPMENT TO BE MAINTAINED.
18. EXISTING ANALOG VOICE 110 WALL FIELD TO BE MAINTAINED.
19. NEW PLYWOOD BACKBOARD
20. NEW WALL MOUNTED TELECOMMUNICATIONS ENCLOSURE, NEMA 12 STEEL SWING
OUT CABINET WITH LOCKING TEMPERED GLASS FRONT DOOR, 26RU, 30" DEPTH, 24"
WIDTH, ACTIVE COOLING FANS.
21. NEW MULTI-OUTLET PDU, 1-UPS, 1-NORMAL.
22. NEW TELECOMMUNICATIONS GROUND BAR.
SCALE: 1 1/2" = 1'-0"
BLDG 252 TR ROOM 103 RACK ELEVATION - NEW WORK
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
46" MH
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
AP
2D/1V
2D/1V
46" MH
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
AP
AP
259-T400
259-T400
ROOM
2-1A
ROOM
2-9
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:3
P
M
259-TA101
FLOOR PLANS
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTS 259
CHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: 1/8" = 1'-0"
B259 - FIRST FLOOR PLAN
SCALE: 1/8" = 1'-0"
B259 - SECOND FLOOR PLAN
N
N
No. Revisions: Date:
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
259-T400
ROOM
2-9
ROOM
2-1A
BLANKING PANELS
BLANKING PANELS
910 10
25 PAIR PROTECTOR PANEL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:2
P
M
259-T400
ENLARGED TR ROOM 2-9
04/14/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTSCHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: 1/2" = 1'-0"
B259 - ENLARGED TR ROOM 2-9 - NEW WORK
SCALE: 1/2" = 1'-0"
B259 - ENLARGED TR ROOM 2-1A - REMOVALS
PLAN NOTES
1. EXISTING WALL MOUNTED RACK TO BE REMOVED.
2. EXISTING DATA STATION PATCH PANELS TO BE REMOVED.
3. EXISTING FIBER TERMINATION PANELS TO BE REMOVED.
4. EXISTING NETWORK ELECTRONICS TO BE REMOVED BY GOVERNMENT.
5. EXISTING UPS TO BE REMOVED.
6. EXISTING VIDEO CAMERA TO BE REINSTALLED IN NEW LOCATION.
7. EXISTING LADDER RACK TO BE REMOVED.
8. EXISTING LADDER RACK TO BE MAINTAINED.
9. NEW WHITE, 30" CHANNEL STYLE, 45RU RACK TO BE INSTALLED.
10. NEW VERTICAL WIRE MANAGER TO BE INSTALLED.
11. NEW 12'' x 4" WIRE BASKET CABLE TRAY WITH LINER TO BE INSTALLED.
12. NEW PLYWOOD BACKBOARD
13. NEW DATA STATION CABLING PATCH PANEL.
14. NEW FIBER TERMINATION PANEL.
15. NEW HORIZONTAL CABLE MANAGER.
16. NEW RACK MOUNTED UPS.
17. NETWORK SWITCH BY GOVERNMENT.
18. EXISTING ACCESS CONTROL EQUIPMENT TO BE MAINTAINED.
19. EXISTING ANALOG VOICE 110 WALL FIELD TO BE MAINTAINED.
SCALE: 1 1/2" = 1'-0"
BLDG 259 DARA ROOM RACK ELEVATION - NEW WORK
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
UP
UP
AP
22D/1V
2D/1V
AP
2V
1V1D/1V
261-T400
COMM ROOM
261-T400
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:0
P
M
261-TA101
FIRST FLOOR PLAN
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTS 261
CHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
PLAN NOTESPLAN NOTES
N
SCALE: 1/8" = 1'-0"
B261 - FIRST FLOOR PLAN
1. UNIT DISCONNECTED.
2. CABLING DROPPED FROM CEILING.
No. Revisions: Date:
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
261-T400
COMM ROOM
1 2
2-48 PORT PATCH PANELS
COMM ROOM
45 5
BLANKING PANELS
BLANKING PANELS
25 PAIR PROTECTOR PANEL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
HEAPY ENGINEERING
1400 W. DOROTHY LANE
DAYTON, OHIO 45409
937.224.0861
NOT FOR CONSTRUCTION
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:5
P
M
261-T400
ENLARGED TR RM 103
04/14/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTSCHILLICOTHE
VAMC
Approved: VAMC
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
CONSTRUCTION DOCUMENTS - 100% QC SUBMITTAL 03/31/2023
CONSTRUCTION DOCUMENTS - 95% 04/14/2023
SCALE: 1/2" = 1'-0"
B261 - ENLARGED TR RM 103 - NEW WORK
1SCALE: 1/2" = 1'-0"
B261 - ENLARGED TR RM 103 - REMOVALS
SCALE: 1 1/2" = 1'-0"
BLDG 261 TR ROOM 1 RACK ELEVATION - NEW WORK
PLAN NOTES
1. EXISTING CISCO 3850 TO BE REMOVED AND TURNED OVER TO OWNER.
2. EXISTING VIDEO CAMERA TO BE REMOVED AND TURNED OVER TO OWNER.
3. EXISTING CCTV SHELF TO REMAIN.
4. NEW WHITE, 30" CHANNEL STYLE, 45RU RACK TO BE INSTALLED.
5. NEW VERTICAL WIRE MANAGER TO BE INSTALLED.
6. NEW 12'' x 4" WIRE BASKET CABLE TRAY WITH LINER TO BE INSTALLED.
7. NEW FIBER TERMINATION PANEL.
8. NEW HORIZONTAL CABLE MANAGER.
9. NEW DATA STATION CABLING PATCH PANEL.
10. NETWORK SWITCH BY GOVERNMENT.
11. NEW RACK MOUNTED UPS.
12. NEW PLYWOOD BACKBOARD.
A
A
SECTION A-A
4 3
FIRESTOP ASSEMBLY NOTES
1. FLOOR OR WALL ASSEMBLY.
2. STEEL SLEEVE.
3. FIRESTOP DEVICE MODULE CENTERED WITHIN OPENING.
4. LOW VOLTAGE CABLING AREA.
A
A
SECTION A-A
4 2
FIRESTOP ASSEMBLY NOTES
1. FLOOR OR WALL ASSEMBLY.
2. STEEL SLEEVE.
3. FIRESTOP DEVICE MODULE CENTERED WITHIN OPENING.
4. LOW VOLTAGE CABLING AREA.
5. WALL FRAMING - WOOD OR STEEL CHANNEL STUDS.
6. GYPSUM BOARD.
CEILING LINE
1-POSITION SURFACE MOUNT ASSEMBLY FOR DATA JACK ABOVE CEILING:
• TWO (2) MODULAR 8-POSITION JACK "GREEN"
• TWO (2) CATEGORY 6A UTP CABLE "GREEN"
CONTRACTOR SHALL FURNISH AND TERMINATE CABLES WITH A 20 FT. SLACK
COIL AT EACH LOCATION.
20 FT. SLACK COIL
AP
CEILING LINE
1-POSITION SURFACE MOUNT ASSEMBLY FOR DATA JACK ABOVE CEILING:
• ONE (1) MODULAR 8-POSITION JACK "PURPLE"
• ONE (1) CATEGORY 6 UTP CABLES "PURPLE"
CONTRACTOR SHALL FURNISH AND TERMINATE CABLES WITH A 20 FT. SLACK
COIL AT EACH LOCATION.
20 FT. SLACK COIL
CC
DATA
DATA
3 FT. SLACK COIL
2-POSITION SYSTEMS FURNITURE FACEPLATE
WITH CLEAR LABEL WINDOWS:
• ONE (1) MODULAR 8-POSITION JACK "BLUE"
• ONE (1) MODULAR 8-POSITION JACK "YELLOW"
• ONE (1) 4-PAIR CATEGORY 6 UTP CABLE "BLUE"
• ONE (1) 4-PAIR CATEGORY 6 UTP CABLE "YELLOW"
ROUTING = ROUTE CABLE DOWN WALL INTO
UNDERFLOOR CONDUIT TO POKE-THROUGH AND
INTO THE SYSTEMS FURNITURE.
W
3 FT. SLACK COIL
4-POSITION SYSTEMS FURNITURE FACEPLATE
WITH CLEAR LABEL WINDOWS:
• TWO (2) MODULAR 8-POSITION JACK "BLUE"
• TWO (2) MODULAR 8-POSITION JACK "YELLOW"
• TWO (2) 4-PAIR CATEGORY 6 UTP CABLE "BLUE"
• TWO (2) 4-PAIR CATEGORY 6 UTP CABLE "YELLOW"
ROUTING = ROUTE CABLE DOWN WALL INTO
UNDERFLOOR CONDUIT TO POKE-THROUGH AND
INTO THE SYSTEMS FURNITURE.
W
DATA DATA
DATA DATA DATA DATA
DATA DATA
3 FT., MIN. SLACK
COIL
4-11/16" BOX
3 FT., MIN. SLACK
COIL
4-11/16" BOX
PHONE
3 FT., MIN. SLACK
COIL
4-11/16" BOX
1.25" BUSHED
CONDUIT
TO LOCAL CABLE TRAY
DATA DATA
DATA DATA
• ONE (1) BLUE CAT 6A JACK MODULE
• ONE (1) BLUE CAT 6A CABLE
• ONE (1) BLUE CAT 6A JACK MODULE
• ONE (1) YELLOW CAT 6A JACK MODULE
• ONE (1) BLUE CAT 6A CABLE
• ONE (1) YELLOW CAT 6A CABLE
• TWO (2) BLUE CAT 6A JACK MODULES
• TWO (2) YELLOW CAT 6A JACK MODULES
• TWO (2) BLUE CAT 6A CABLES
• TWO (2) YELLOW CAT 6A CABLES
1.25" BUSHED
CONDUIT
TO LOCAL CABLE TRAY
1.25" BUSHED
CONDUIT
TO LOCAL CABLE TRAY
2 4
DATA
A
A
SECTION A-A
FIRESTOP ASSEMBLY NOTES
1. FLOOR OR WALL ASSEMBLY.
2. STEEL SLEEVE.
3. FIRESTOP DEVICE MODULE CENTERED WITHIN OPENING.
4. LOW VOLTAGE CABLING AREA.3
A
A
SECTION A-A
FIRESTOP ASSEMBLY NOTES
1. FLOOR OR WALL ASSEMBLY.
2. STEEL SLEEVE.
3. FIRESTOP DEVICE MODULE CENTERED WITHIN OPENING.
4. LOW VOLTAGE CABLING AREA.3
A
A
SECTION A-A
FIRESTOP ASSEMBLY NOTES
1. FLOOR OR WALL ASSEMBLY.
2. STEEL SLEEVE.
3. FIRESTOP DEVICE MODULE CENTERED WITHIN OPENING.
4. LOW VOLTAGE CABLING AREA.
5. WALL FRAMING - WOOD OR STEEL CHANNEL STUDS.
6. GYPSUM BOARD.
SINGLE RACK TR DUAL RACK TR
SINGLE RACK TRDUAL RACK TR
10 10 10
11 11 11 11 11 11
12 12 12
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:2
P
M
T501
DETAILS
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTSCHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: NONE
FIRESTOP - CONCRETE WALL/ FLOOR MUTLI-CELL
SCALE: NONE
FIRESTOP - STUD WALL MULTI-CELL
SCALE: NONE
FIRESTOP - CONCRETE FLOOR/ WALL
SCALE: NONE
FIRESTOP - CONCRETE WALL
SCALE: NONE
FIRESTOP - STUD WALL
SCALE: 1 1/2" = 1'-0"
TYPICAL RACK-FRONT ELEVATION
SCALE: 1 1/2" = 1'-0"
TYPICAL RACK-REAR ELEVATION
TYPICAL RACK ELEVATION GENERAL NOTES
A. REFER TO DRAWINGS FOR EACH TR FOR FINAL QUANTITY OF HORIZONTAL CABLING PATCH PANELS
AND NETWORK EDGE SWITCHES.
B. ALL WORK SHALL BE IN CONFORMANCE WITH INFRASTRUCTURE STANDARD FOR
TELECOMMUNICATIONS SPACES VERSION 3.1 JULY 1, 2021 | SOLUTION DELIVERY-DATA CENTER AND
INFRASTRUCTURE ENGINEERING.
C. FINAL RACK CONFIGURATIONS INCLUDING LOCATION AND ORIENTATION IN EACH ROOM SHALL BE
COORDINATED WITH STATION OIT PRIOR TO INSTALLATION AND CABLING TERMINATION.
D. PROVIDE BLANKING PANELS FOR ALL UNUSED RACK SPACE.
E. RACKS SHALL BE 30" CHANNEL STYLE, 45RU, WHITE.
F. EACH RACK SHALL INCLUDE A FULL HEIGHT FRONT/REAR 6" VERTICAL CABLE MANAGER ON EACH
SIDE. TWO RACKS SHALL INCLUDE A SINGLE CABLE MANAGER BETWEEN RACKS.
RACK ELEVATION NOTES
1. RACK MOUNTED, 1RU, HIGH DENSITY ANGLED FIBER TERMINATION PANEL WITH LC BULKHEADS.
LEVITON OPT-X UHDX. PROVIDE ONE (1) IN EVERY TR. TRs WITH MULTIPLE RACKS SHAL HAVE
THE PANEL LOCATED ON THE RACK CLOSEST TO THE DOOR.
2. 1RU FLAT BLANKING PANELS. PROVIDE QUANTITY IN EACH RACK AS REQUIRED TO FILL ALL
UNUSED RACK SPACES.
3. 24 PORT CATEGORY 5E COPPER/ANALOG VOICE CABLING TERMINATION PANEL. PROVIDE ONE
(1) IN MCR IN EACH BUILDING. TRs WITH MULTIPLE RACKS SHAL HAVE THE PANEL LOCATED ON
THE RACK CLOSEST TO THE DOOR .
4. 25 PAIR PRIMARY PROTECTOR PANEL FOR COPPER BACKBONE. PROVIDE ONE (1) IN MCR IN EACH BUILDING. TRs WITH MULTIPLE RACKS SHAL HAVE THE PANEL LOCATED ON THE RACK
CLOSEST TO THE DOOR
5. CATEGORY 6A, 48 PORT, 1RU HIGH DENSITY ANGLED PATCH PANEL FOR NEW DATA STATION
CABLING. FINAL QUANTITY IN EACH RACK AS SHOWN ON TR DRAWINGS FOR EACH TR. PANELS
TO HAVE REAR CABLE MANAGERS AND ANGLED PANEL COVERS, LEVITON e2XHD SERIES, BLACK
6. 1RU, HORIZONTAL, FRONT/REAR, CABLE MANAGEMENT PANEL.
7. NETWORK EDGE SWITCH BY VA.
8. 2RU, HORIZONTAL, FRONT/REAR, CABLE MANAGEMENT PANEL.
9. 30A-3PH ZONE PDU WITH TWO (2) 30A-3PH WYE CIRCUITS. PROVIDE IN TRs WITH TWO RACKS.
10. 5KW, 208V UPS. PROVIDE IN EVERY RACK IN EVERY TR.
11. ZERO U RACK MOUNT VERTICAL PDU, APC AP8861 RPDU OR EQUIVALENT; RACK PDU 2G,
METERED; L21-20 PLUG; 120/208V INPUT; 20A. PROVIDE ON EACH SIDE OF EVERY RACK IN EVERY
TR.
12. RACK MOUNTED TELECOMMUNICATIONS EQUIPMENT GROUND BAR (RBB) PRE-DRILLED FOR 2- HOLE LUGS. ALL EQUIPMENT WITHIN RACK TO BE BONDED TO BAR UTILIZING #6awg BONDING CONDUCTORS. BOND BAR TO SBB WITHIN EACH TR. PROVIDE AT TOP OF EVERY RACK IN EVERY
TR.
No. Revisions: Date:
BASIS OF DESIGN - 10% 05/23/2022
SCHEMATIC DESIGN - 35% 07/18/2022
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
BUSBAR IDENTIFICATION PLACARD (TYP.)
TWO-HOLE, LONG BARREL COMPRESSION
LUG WITH WINDOW (TYP.)
TELECOM SECONDARY
BONDING BAR(SBB)
TO ADDITIONAL BLDG. GROUND RISER (TBB)
500 KCMIL, INSULATED
TO STATIC DISSIPATIVE FLOORING
BONDING CONDUCTOR (BC), MINIMUM
6AWG, STRANDED COPPER, INSULATED
TO METAL BLDG. FRAME
BONDING CONDUCTOR (BC), MINIMUM
6AWG, STRANDED COPPER, INSULATED
TO LOCAL ELECTRICAL PANEL
BONDING CONDUCTOR (BC), MINIMUM
6AWG, STRANDED COPPER, INSULATED
TO RACKS, CABLE RUNWAY & EQUIPMENT
SEPARATE BONDING CONDUCTORS (BC), MINIMUM
6AWG, STRANDED COPPER, INSULATED (TYP.)
COMPRESSION TYPE "H" TAP
(TYPICAL)
TELECOM BONDING BACKBONE (TBB),
500 KCMIL, INSULATED (TYPICAL)
TO STATIC DISSIPATIVE FLOORING
BONDING CONDUCTOR (BC), MINIMUM
6AWG, STRANDED COPPER, INSULATED
TO METAL BLDG. FRAME
BONDING CONDUCTOR (BC), MINIMUM
6AWG, STRANDED COPPER, INSULATED
TO LOCAL ELECTRICAL PANEL
BONDING CONDUCTOR (BC), MINIMUM
6AWG, STRANDED COPPER, INSULATED
TO RACKS, CABLE RUNWAY & EQUIPMENT
SEPARATE BONDING CONDUCTORS (BC), MINIMUM
6AWG, STRANDED COPPER, INSULATED (TYP.)
TELECOM PRIMARY BONDING BAR (PBB)
TYPICAL WITHIN EACH MAIN TR SPACES
BUSBAR IDENTIFICATION PLACARD (TYP.)
TO ALL OTHER TR SPACES
GROUNDING
ELECTRODE
CONDUCTOR
(GEC)
TO MAIN ELECTRICAL SERVICE GROUND
BONDING CONDUCTOR (BC), 500 KCMIL, INSULATED
WARNING: TECHNOLOGY GROUND BUSBAR FOR
DATA, VOICE, AND LOW VOLTAGE EQUIPMENT
ONLY.
DO NOT USE AS AN ELECTRICAL OR MECHANICAL
SYSTEM GROUND. IF CONNECTORS OR CABLES
SHOW SIGNS OF BECOMING LOOSE, OR REQUIRE
REMOVAL, CONTACT VA, INFORMATION
TECHNOLOGY DIVISION.
BUSBAR IDENTIFICATION PLACARD
9/16" D
6/32" D (TYP. OF 6)
1-1/8" O.C.
9/32" D (TYP. OF 12)
1-1/8" O.C.
DETAIL NOTES
1. 4"x1/4"x10" MIN. LENGTH GROUNDING BAR #A-6163
ACTUAL LENGTH REQUIRED BY QUANTITY OF GROUND
CONNECTIONS.
2. WALL MOUNTING BRACKET
3. INSULATORS.
4. 5/8-11X1 H.H.C.S.
5. 5/8" LOCKWASHER.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
HEAPY ENGINEERING
1400 W. DOROTHY LANE
DAYTON, OHIO 45409
937.224.0861
NOT FOR CONSTRUCTION
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:2
:4
P
M
T502
TECHNOLOGY DETAILS
04/14/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTSCHILLICOTHE
VAMC
Approved: VAMC
No. Revisions: Date:
CONSTRUCTION DOCUMENTS - 95% 04/14/2023
SCALE: 1/8" = 1'-0"
Tech Grounding System
SCALE: 12" = 1'-0"
GROUND BAR DETAIL
TR
1-12 PORT
PATCH PANEL
020-T401
PDU
BLANKING PANELS
25 PAIR PROTECTOR PANEL
RACK SHELF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:5
:5
A
M
020-T401
ENLARGED TR RM 206 & 105
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTS 20
CHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
PLAN NOTES
SCALE: 1/2" = 1'-0"
020 - T401 - ENLARGED TR RM 1 - REMOVALS
1. EXISTING 2 POST RACK TO BE REMOVED.
2. EXISTING DATA STATION PATCH PANELS TO BE REMOVED.
3. EXISTING FIBER TERMINATION PANELS TO BE REMOVED.
4. EXISTING NETWORK ELECTRONICS TO BE REMOVED BY GOVERNMENT.
5. EXISTING UPS TO BE REMOVED.
6. EXISTING VIDEO CAMERA TO BE REINSTALLED IN NEW LOCATION.
7. EXISTING LADDER RACK TO BE REMOVED.
8. EXISTING LADDER RACK TO BE MAINTAINED.
9. NEW WHITE, 30" CHANNEL STYLE, 45RU RACK TO BE INSTALLED.
10. NEW VERTICAL WIRE MANAGER TO BE INSTALLED.
11. NEW 12'' x 4" WIRE BASKET CABLE TRAY WITH LINER TO BE INSTALLED.
12. NEW DATA STATION CABLING PATCH PANEL.
13. NEW FIBER TERMINATION PANEL.
14. NEW HORIZONTAL CABLE MANAGER.
15. NEW RACK MOUNTED UPS.
16. NETWORK SWITCH BY GOVERNMENT.
17. EXISTING ACCESS CONTROL EQUIPMENT TO BE MAINTAINED.
18. EXISTING ANALOG VOICE 110 WALL FIELD TO BE MAINTAINED.
19. NEW PLYWOOD BACKBOARD
20. NEW WALL MOUNTED TELECOMMUNICATIONS ENCLOSURE, NEMA 12 STEEL SWING
OUT CABINET WITH LOCKING TEMPERED GLASS FRONT DOOR, 26RU, 30" DEPTH, 24"
WIDTH, ACTIVE COOLING FANS.
21. NEW TELECOMMUNICATIONS GROUND BAR.
22. FIRE RATED RE-ENTERABLE ASSEMBLY, 4" CONDUIT EQUIVALENT, THROUGH FLOOR.
SCALE: 1/2" = 1'-0"
020 - T401 - ENLARGED TR RM 2 - NEW WORK
SCALE: 1 1/2" = 1'-0"
BLDG 020 TR ROOM MEZZ RACK ELEVATION - NEW WORK
No. Revisions: Date:
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
AP
AP
AP
AP
AP
AP
AP
AP
AP
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
W
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
021-T401
021-T401
TR
28A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:5
:4
A
M
021-TA101
FIRST FLOOR PLAN
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTS 21
CHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: 1/8" = 1'-0"
B21 - FIRST FLOOR PLAN
N
No. Revisions: Date:
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
910 10
BLANKING PANELS
BLANKING PANELS
25 PAIR PROTECTOR PANEL
021-T401 4
2-48 PORT PATCH PANELS
4-24 PORT PATCH PANELS
TR
002J
021-T4013
TR
002J
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:5
:2
A
M
021-T401
ENLARGED TR RM 28A
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTS 21
CHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
PLAN NOTES
SCALE: 1 1/2" = 1'-0"
BLDG 021 TR ROOM 28A RACK ELEVATION - NEW WORK
SCALE: 1/2" = 1'-0"
B21 - ENLARGED TR RM 28A - REMOVALS
SCALE: 1/2" = 1'-0"
B21 - ENLARGED TR RM 28A - NEW WORK
SCALE: 1 1/2" = 1'-0"
BLDG 021 TR ROOM 28A ELEVATION - REMOVALS
1. EXISTING 2 POST RACK TO BE REMOVED.
2. EXISTING DATA STATION PATCH PANELS TO BE REMOVED.
3. EXISTING FIBER TERMINATION PANELS TO BE REMOVED.
4. EXISTING NETWORK ELECTRONICS TO BE REMOVED BY GOVERNMENT.
5. EXISTING UPS TO BE REMOVED.
6. EXISTING VIDEO CAMERA TO BE REINSTALLED IN NEW LOCATION.
7. EXISTING LADDER RACK TO BE REMOVED.
8. EXISTING HORIZONTAL CABLE MANAGER TO BE REMOVED.
9. NEW WHITE, 30" CHANNEL STYLE, 45RU RACK TO BE INSTALLED.
10. NEW VERTICAL WIRE MANAGER TO BE INSTALLED.
11. NEW 12'' x 4" WIRE BASKET CABLE TRAY WITH LINER TO BE INSTALLED.
12. NEW DATA STATION CABLING PATCH PANEL.
13. NEW FIBER TERMINATION PANEL.
14. NEW HORIZONTAL CABLE MANAGER.
15. NEW RACK MOUNTED UPS.
16. NETWORK SWITCH BY GOVERNMENT.
17. EXISTING ACCESS CONTROL EQUIPMENT TO BE MAINTAINED.
18. EXISTING ANALOG VOICE 110 WALL FIELD TO BE MAINTAINED.
No. Revisions: Date:
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
UP
UP
UP
UP
AP
W
D
/1 V
D
/1 V
D
/1 V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
1V
DN
DN
DN
DN
UP
UP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
AP
W
W 2 D
/1 V
D
/1 V
D
/1 V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
1V
023-T401
023-T401
PC
FLOOR
MOUNTED
TR
121A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:5
:1
A
M
023-TA100
BASEMENT, FIRST FLOOR PLAN
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTS 23
CHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
SCALE: 1/8" = 1'-0"
B23 - BASEMENT PLAN
SCALE: 1/8" = 1'-0"
B23 - FIRST FLOOR PLAN
N N
No. Revisions: Date:
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
TR
002A
TR 2 WILL BE USING
NEW TR 121
1-48 PORT PATCH
PANEL
023-T401
10 109
TR
BLANKING PANELS
BLANKING PANELS
25 PAIR PROTECTOR PANEL
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
STAMP
321 4 5 6 7 8 9 10
ARCHITECT/ENGINEER OF RECORDCONSULTANT
PROJECT NO.
STATE COA FIRM NO.
A u to d e s k D o c s /C h il li c o th e
V A
E
H R
M /2
-0
-T
E C
H C e n tr a l.
rv t
/1
/2
:5
:5
A
M
023-T401
ENLARGED TR RM 002A
04/14/2023 RSG GES/JWE
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
100% CONSTRUCTION
DOCUMENTS 23
CHILLICOTHE
VAMC
Approved: VAMC
2022-05041
01528
PLAN NOTES
SCALE: 1/2" = 1'-0"
B23 - ENLARGED TR RM 002A - REMOVALS
SCALE: 1/2" = 1'-0"
B23 - ENLARGED TR RM 121 - NEW WORK
1. EXISTING WALL RACK TO BE REMOVED.
2. EXISTING DATA STATION PATCH PANELS TO BE REMOVED.
3. EXISTING FIBER TERMINATION PANELS TO BE REMOVED.
4. EXISTING NETWORK ELECTRONICS TO BE REMOVED BY GOVERNMENT.
5. EXISTING UPS TO BE REMOVED.
6. EXISTING VIDEO CAMERA TO BE REINSTALLED IN NEW LOCATION.
7. EXISTING LADDER RACK TO BE REMOVED.
8. EXISTING LADDER RACK TO BE MAINTAINED.
9. NEW WHITE, 30" CHANNEL STYLE, 45RU RACK TO BE INSTALLED.
10. NEW VERTICAL WIRE MANAGER TO BE INSTALLED.
11. NEW 12'' x 4" WIRE BASKET CABLE TRAY WITH LINER TO BE INSTALLED.
12. NEW DATA STATION CABLING PATCH PANEL.
13. NEW FIBER TERMINATION PANEL.
14. NEW HORIZONTAL CABLE MANAGER.
15. NEW RACK MOUNTED UPS.
16. NETWORK SWITCH BY GOVERNMENT.
17. EXISTING ACCESS CONTROL EQUIPMENT TO BE MAINTAINED.
18. EXISTING ANALOG VOICE 110 WALL FIELD TO BE MAINTAINED.
19. NEW PLYWOOD BACKBOARD.
20. NEW TELECOMMUNICATIONS GROUND BAR.
SCALE: 1 1/2" = 1'-0"
BLDG 023 TR ROOM 121A RACK ELEVATION - NEW WORK
No. Revisions: Date:
QC DESIGN - 65% 09/06/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
QC DESIGN - 95% 02/21/2023
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
TECHNOLOGY SYMBOL LIST
SYMBOL: DESCRIPTION: NOTE:
EQUIPMENT
LIST ABBREV.:
TECHNOLOGY ABBREVIATION KEY
ENTRANCE FACILITYEF-#
MAIN CROSS-CONNECTMC-#
TELECOMMUNICATIONS ROOMTR-#
ABOVE FINISHED FLOORAFF
BELOW FINISHED CEILINGBFC
CONDUITC
SIMILARSIM
TYPICALTYP
MOUNTING HEIGHT ABOVE FINISHED FLOOR+#
JUNCTION BOXJ-BOX
ABBR: DESCRIPTION:
UNLESS OTHERWISE NOTEDUON
FIELD OF VIEWFOV
DOUBLE POLE DOUBLE THROWDPDT
PAN TILT ZOOMPTZ
POWER OVER ETHERNETPOE
ABOVE FINISHED GRADEAFG
DELAYED EGRESSDE
TECHNOLOGY GENERAL NOTES:
1. ##-###-# INDICATES TECHNOLOGY EQUIPMENT SCHEDULE ITEM LABELED AS "EQUIPMENT
LIST ABBREVIATION"
2. REFER TO TECHNOLOGY EQUIPMENT SCHEDULE AND SPECIFICATIONS FOR FULL
DESCRIPTIONS AND MANUFACTURERS OF ALL DEVICES.
TECHNOLOGY MOUNTING SUBSCRIPT KEY:
A MOUNT AT +6" TO CENTERLINE ABOVE COUNTER OR BACKSPLASH
H MOUNT ORIENTED HORIZONTALLY
L MOUNT IN CASEWORK
M MOUNT IN MODULAR FURNITURE
S MOUNT IN SURFACE RACEWAY
A SLASH IS USED BETWEEN TWO SUBSCRIPTS, E.G., A/H.
1. THE LOCATION OF THE CONDUIT, HAND HOLES AND/OR MAINTENANCE HOLES SHOWN ARE
APPROXIMATE LOCATIONS. FIELD VERIFY THE LOCATION OF ALL UTILITIES PRIVATE AND/OR
PUBLIC PRIOR TO THE INSTALLATION OF THE COMPONENT. FIELD COORDINATE THE FINAL
LOCATION WITH THE OWNER AND ENGINEER PRIOR TO INSTALLATION.
2. POTHOLING TO LOCATE EXISTING UNDERGROUND UTILITIES, IF APPLICABLE, SHALL BE
INCLUDED IN THE CONTRACTOR'S BID. CONTRACTOR IS RESPONSIBLE FOR FINAL
PLACEMENT OF HAND HOLES AND/OR MAINTENANCE HOLES AND SHALL NOTIFY THE
ENGINEER OF FINAL LOCATIONS PRIOR TO INSTALLATION.
3. HAND HOLES AND/OR MAINTENANCE HOLES SHALL BE CONSTRUCTED SO THAT THE TOP OF
THE FRAME WILL BE FLUSH WITH THE GROUND LINE.
4. REMOVAL AND REPLACEMENT OF THE EXISTING UNDERGROUND UTILITIES THAT ARE
REQUIRED TO COMPLETE THE INSTALLATION SHALL BE INCLUDED IN THE CONTRACTOR'S
BID.
5. CONTRACTOR SHALL INCLUDE IN THEIR BID ANY REMOVAL AND REPLACEMENT OF EXISTING
SIDEWALK, PAVEMENT, GRASS, SHRUBS, TREES, ETC. THAT WILL BE IMPACTED BY THE
INSTALLATION OF THE NEW CONDUITS SHOWN ON THE DRAWINGS. IF TREES ARE REQUIRED
TO BE REMOVED THE CONTRACTOR SHALL CONTACT THE OWNER AND DISCUSS OPTIONS
PRIOR TO CUTTING DOWN ANY TREE OR SHRUB OVER 5' IN HEIGHT.
6. NO ADDITIONAL COST SHALL BE APPROVED FOR PLACING CONDUITS DEEPER THAN
REQUIRED MINIMUM DEPTH TO AVOID EXISTING UNDERGROUND UTILITIES.
7. PROVIDE A MINIMUM OF 25'-0" SLACK LOOP WITHIN EACH HAND HOLES AND/OR
MAINTENANCE HOLES. SLACK LOOP SHALL BE SECURE SO COPPER OR FIBER IS NOT
RESTING ON EARTH AFTER FINAL INSTALLATION.
TECHNOLOGY OUTSIDE PLANT NOTES
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE ADA STANDARDS FOR
ACCESSIBLE DESIGN. REFER TO THE ADA GUIDELINES FOR ALL CONFIGURATION DETAILS
ON THIS PAGE FOR ADDITIONAL INFORMATION.
2. CONCEAL ALL CONDUIT IN WALLS, PARTITIONS, ABOVE CEILING, IN FLOOR SLAB, ETC.
UNLESS OTHERWISE INDICATED ON THE PLANS OR IN THE SPECIFICATIONS. CONDUIT IN
MECHANICAL ROOMS AND STORAGE ROOMS WITHOUT CEILINGS MAY BE EXPOSED ON
BUILDING STRUCTURE.
3. BOXES LOCATED ON OPPOSITE SIDES OF NON-RATED WALLS SHALL BE OFFSET A MINIMUM
OF 6" HORIZONTALLY. BOXES ON OPPOSITE SIDES OF FIRE RATED WALLS SHALL BE
OFFSET A MINIMUM OF 24" HORIZONTALLY. "THRU-THE-WALL" BOXES SHALL NOT BE
ALLOWED WITHOUT PRIOR WRITTEN APPROVAL OF THE ARCHITECT/ENGINEER.
4. VERIFY ALL FURNITURE, MODULAR FURNITURE, AND EQUIPMENT LOCATIONS WITH
ARCHITECTURAL PLANS, ELEVATIONS, AND REVIEWED SHOP DRAWINGS. PRIOR TO MAKING
THE ACTUAL TELECOMMUNICATIONS INSTALLATION, ADJUST OUTLETS OR CONNECTION
LOCATIONS TO ACCOMMODATE FURNITURE AND/OR EQUIPMENT.
5. TELECOMMUNICATIONS EQUIPMENT SHALL BE MOUNTED TO ALLOW ACCESS TO
ELECTRICAL AND MECHANICAL EQUIPMENT. ALL MOUNTING OF TELECOMMUNICATION
DEVICES ON EQUIPMENT SUPPLIED BY ANOTHER CONTRACTOR SHALL BE APPROVED IN
ADVANCE BY THE OTHER CONTRACTOR.
6. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL OPENINGS REQUIRED IN WALLS. ALL
OPENINGS SHALL BE REPAIRED TO MATCH EXISTING BY A QUALIFIED CONTRACTOR AT THE
EXPENSE OF THIS CONTRACTOR. ALL CONDUITS THROUGH WALLS SHALL BE GROUTED OR
SEALED INTO OPENINGS.
7. ALL MATERIALS USED TO SEAL PENETRATIONS OF FIRE RATED WALLS AND FLOORS SHALL
BE TESTED AND CERTIFIED AS A SYSTEM PER ASTM E814 STANDARDS FOR FIRE TESTS OF
THROUGH-PENETRATION FIRESTOPS. REFER TO 27 05 03 AND 28 05 03 AND 26 05 03 FOR
ADDITIONAL INFORMATION AND REQUIREMENTS SPECIFIC TO FIRESTOPPING.
8. THE TECHNOLOGY CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF
THE CEILINGS, CEILING TILES, AND CEILING GRID ASSOCIATED WITH THE AREAS OF WORK
BY ALL CONTRACTORS.
9. ALL LADDER RACK AND CABLE TRAY SIZES ARE AS DEFINED ON THE DRAWINGS. REFER TO
SPECIFICATION SECTIONS 27 05 28 AND 27 11 00 FOR APPROVED MANUFACTURERS AND
INSTALLATION REQUIREMENTS.
10. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO THE
WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES
DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE
RATING, AND FINISH.
11. FLUSH MOUNT ALL TELECOMMUNICATION OUTLETS AT +18" FROM FLOOR (CENTERLINE
DIMENSION), EXCEPT WHERE OTHERWISE NOTED. OUTLETS MAY BE SURFACE MOUNTED
WHEN CONDUIT IS SPECIFIED EXPOSED.
TECHNOLOGY INSTALLATION NOTES:
GENERAL NOTES:
1. ALL SYMBOLS AND ABBREVIATIONS LISTED MAY NOT BE APPLICABLE TO THIS PROJECT.
REFER TO THE TECHNOLOGY EQUIPMENT SCHEDULE FOR MORE COMPLETE DESCRIPTION
AND ITEMS.
2. ALL SYMBOLS AND ABBREVIATIONS REFER TO TECHNOLOGY SHEETS ONLY AS DEFINED ON
THE SHEET INDEX. REFER TO THE GENERAL TECHNOLOGY NOTES FOR ADDITIONAL
INFORMATION.
3. ALL SYMBOLS LISTED ABOVE ARE FOR REFERENCE ONLY. REFER TO PLANS AND LINE TYPE
KEY FOR NEW, EXISTING TO REMAIN AND TO BE REMOVED ITEMS FOR ADDITIONAL
INFORMATION.
4. REFER TO RISERS ON SHEET(S): TN400
CABLE TRAY, CHANNEL TRAY, BASKET
TRAY
LADDER RACK
WIDTH X HEIGHT
WIDTH X HEIGHT
DIAMETERø C CONDUIT
CONDUIT DOWN
CONDUIT UP OR UP/DOWN
CONDUIT SLEEVE
CONTINUATION
PLAN OR DETAIL NUMBER
PLAN OR DETAIL NAME
PLAN OR DETAIL SCALE
DETAIL REFERRED TO BY SECTION CUT
SHEET DETAIL IS LOCATED ON
NAME
VIEW NAME
1/8" = 1'-0"
M101
SIMSIM
INDICATES SIMILAR DETAIL REFERENCED
IN MULTIPLE LOCATIONS
LEVEL NAME
10'-0" HEIGHT ABOVE
PROJECT 0'-0"
1 INDICATES NOTE USED TO DESCRIBE
ADDITIONAL INFORMATION ABOUT
WORK REQUIRED, SPECIFIC TO THE
SHEET AND/OR DETAIL
N O R
HT
INDICATES DIRECTION OF TRUE NORTH
VIEW KEY
LINE TYPE AND TAG KEY:
NEW WORK BY THIS CONTRACTOR (WIDE LINE)
NEW
EXISTING TO BE REMOVED (SHORT DASHED PATTERN)
NEW UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
EXISTING TO REMAIN OR WORK BY OTHERS (NARROW LINE)
EXISTING
EXISTING TO BE REMOVED BY OTHERS (SHORT DASHED PATTERN)
EXISTING UNDERFLOOR OR UNDERGROUND (LONG DASHED PATTERN)
HALFTONING DOES NOT MODIFY SCOPE.
'TAG'-E TAGS WITH DASH 'E' INDICATES THE REFERENCED OBJECT IS EXISTING
TAG UNDERLINED TAG INDICATES OBJECT IS IN-SCOPE. IF NEW, ADDITIONAL
INFORMATION IS AVAILABLE IN A SCHEDULE, MATERIAL LIST, OR SYMBOL LIST
INDICATES AN EXISTING SYSTEM'S POINT OF CONNECTION/REMOVAL
T101
BUILDING CODE: IBC 20** EDITION
UBC 20**
FIRE CODE: IFC 20** EDITION -OR-
NFPA: 1 20** EDITION
PLUMBING CODE: IPC 20** EDITION
UPC 20**
MECHANICAL CODE: IMC 20** EDITION
UMC 20**
ELECTRICAL CODE: NFPA 70 (NEC) 20** EDITION
LIFE SAFETY CODE: NFPA 101 20** EDITION
ENERGY CONSERVATION CODE: IECC 20**
ASHRAE 90.1 20**
HEALTH DEPARTMENT CODE: CURRENT EDITION
LOCAL BUILDING CODE: CURRENT EDITION
APPLICABLE CODES
CONTRACTOR SHALL COMPLY WITH APPLICABLE CODES AND LOCAL AMENDMENTS.
TEMPERATURE CONTROLS CONTRACTORT.C.C.
SECURITY CONTRACTORS.C.
AUDIO/VISUAL CONTRACTORA.V.C.
NURSE CALL CONTRACTORN.C.C.
CIVIL CONTRACTORC.C.
ASBESTOS ABATEMENT CONTRACTOR
FIRE PROTECTION CONTRACTORF.P.C.
HEATING CONTRACTORH.C.
PLUMBING CONTRACTORP.C.
GENERAL CONTRACTORG.C.
MECHANICAL CONTRACTORM.C.
VENTILATION CONTRACTORV.C.
ELECTRICAL CONTRACTORE.C.
A.C.
CONTRACTOR ABBREVIATION KEY
ABBR: DESCRIPTION:
TECHNOLOGY CONTRACTORT.C.
CONSTRUCTION MANAGERC.M.
FOOD SERVICE CONTRACTORF.S.C.
M
A X
20" MAX.
M
A X
20"-25" MAX.
M
A X
M
IN
. 4
M
A X
M
A X
10" MAX. 10"-24" MAX.
ADA GUIDELINES - FRONT ACCESS
ADA STANDARDS FOR ACCESSIBLE DESIGN
INSTALL ABOVE COUNTER
DEVICE AT 44" ABOVE
FINISHED FLOOR.
INSTALL ABOVE COUNTER
DEVICE AT 40" ABOVE
FINISHED FLOOR.
INSTALL DEVICE AT 18"
ABOVE FINISHED FLOOR.
ADA GUIDELINES - SIDE ACCESS
INSTALL DEVICE AT 44"
ABOVE FINISHED FLOOR.
INSTALL DEVICE AT 42"
ABOVE FINISHED FLOOR.
TECHNOLOGY SHEET INDEX
000-TN000 TECHNOLOGY COVERSHEET
000-TN400 TECHNOLOGYRISER DIAGRAM
000-TN500 TECHNOLOGY DETAILS
000-TS100 CAMPUS TECHNOLOGY SITE PLAN
001-TN100 BASEMENT PLAN - TECHNOLOGY
001-TN101 LEVEL 01 PLAN - TECHNOLOGY
001-TN102 LEVEL 02 PLAN - TECHNOLOGY
003-TN100 BASEMENT PLAN - TECHNOLOGY
003-TN101 LEVEL 01 PLAN - TECHNOLOGY
007-TN100 BASEMENT PLAN - TECHNOLOGY
007-TN101 LEVEL 01 PLAN - TECHNOLOGY
009-TN100 BASEMENT PLAN - TECHNOLOGY
009-TN101 LEVEL 01 PLAN - TECHNOLOGY
009-TN102 LEVEL 02 PLAN - TECHNOLOGY
018-TD101 LEVEL 01 DEMOLITION PLAN - TECHNOLOGY
018-TN100 BASEMENT PLAN - TECHNOLOGY
018-TN101 LEVEL 01 PLAN - TECHNOLOGY
018-TN102 LEVEL 02 PLAN - TECHNOLOGY
018-TN200 DATA CENTER #122 PATHWAY LAYOUT - TECHNOLOGY
018-TN201 DATA CENTER #122 PHASE 1 PLAN - TECHNOLOGY
018-TN202 DATA CENTER #122 PHASE 2 PLAN - TECHNOLOGY
018-TN203 DATA CENTER #122 PHASE 3 PLAN - TECHNOLOGY
018-TN204 DATA CENTER #122 PHASE 4 PLAN - TECHNOLOGY
018-TN205 COPPER BACKBONE EQUIPMENT DETAIL
018-TN206 DATA CENTER STRUCTURED CABLING SYSTEM DIAGRAM
020-TN101 LEVEL 01 PLAN - TECHNOLOGY
020-TN102 LEVEL 02 PLAN - TECHNOLOGY
020-TN103 LEVEL 03 PLAN - TECHNOLOGY
021-TN101 LEVEL 01 PLAN - TECHNOLOGY
021-TN102 LEVEL 02 PLAN - TECHNOLOGY
023-TN100 BASEMENT PLAN - TECHNOLOGY
023-TN101 LEVEL 01 PLAN - TECHNOLOGY
024-TN100 BASEMENT PLAN - TECHNOLOGY
024-TN101 LEVEL 01 PLAN - TECHNOLOGY
024-TN102 LEVEL 02 PLAN - TECHNOLOGY
024-TN103 LEVEL 03 PLAN - TECHNOLOGY
025-TN100 BASEMENT PLAN - TECHNOLOGY
025-TN101 LEVEL 01 PLAN - TECHNOLOGY
026-TN100 BASEMENT PLAN - TECHNOLOGY
026-TN101 LEVEL 01 PLAN - TECHNOLOGY
026-TN102 LEVEL 02 PLAN - TECHNOLOGY
026-TN103 LEVEL 03 PLAN - TECHNOLOGY
027-TN100 BASEMENT PLAN - TECHNOLOGY
027-TN101 LEVEL 01 PLAN - TECHNOLOGY
027-TN102 LEVEL 02 PLAN - TECHNOLOGY
027-TN103 LEVEL 03 PLAN - TECHNOLOGY
028-TN100 BASEMENT PLAN - TECHNOLOGY
028-TN101 LEVEL 01 PLAN - TECHNOLOGY
028-TN102 LEVEL 02 PLAN - TECHNOLOGY
030-TN100 BASEMENT PLAN - TECHNOLOGY
030-TN101 LEVEL 01 PLAN - TECHNOLOGY
030-TN102 LEVEL 02 PLAN - TECHNOLOGY
030-TN103 LEVEL 03 PLAN - TECHNOLOGY
031-TN100 OVERALL BASEMENT FLOOR PLAN - TECHNOLOGY
031-TN101 OVERALL GROUND FLOOR PLAN - TECHNOLOGY
031-TN102 OVERALL FIRST FLOOR PLAN - TECHNOLOGY
031-TN103 OVERALL SECOND FLOOR PLAN - TECHNOLOGY
031-TN104 OVERALL THIRD FLOOR PLAN - TECHNOLOGY
035-TN0SB SUB BASEMENT PLAN - TECHNOLOGY
035-TN100 BASEMENT PLAN - TECHNOLOGY
035-TN101 LEVEL 01 PLAN - TECHNOLOGY
035-TN102 LEVEL 02 PLAN - TECHNOLOGY
035-TN103 LEVEL 03 PLAN - TECHNOLOGY
036-TN100 BASEMENT AND FIRST FLOOR PLAN - TECHNOLOGY
060-TN100 LEVEL 01 PLAN - TECHNOLOGY
210-TN100 BASEMENT PLAN - TECHNOLOGY
210-TN101 LEVEL 01 PLAN - TECHNOLOGY
210-TN102 LEVEL 02 PLAN - TECHNOLOGY
210-TN103 LEVEL 03 PLAN - TECHNOLOGY
211-TN100 BASEMENT PLAN - TECHNOLOGY
211-TN101 LEVEL 01 PLAN - TECHNOLOGY
211-TN102 LEVEL 02 PLAN - TECHNOLOGY
211-TN103 LEVEL 03 PLAN - TECHNOLOGY
212-TN100 BASEMENT PLAN - TECHNOLOGY
212-TN101 LEVEL 01 PLAN - TECHNOLOGY
212-TN102 LEVEL 02 PLAN - TECHNOLOGY
247-TN100 BASEMENT PLAN - TECHNOLOGY
247-TN110 LEVEL 01 PLAN - TECHNOLOGY
252-TN101 LEVEL 01 PLAN - TECHNOLOGY
259-TN101 LEVEL 01 PLAN - TECHNOLOGY
259-TN102 LEVEL 02 PLAN - TECHNOLOGY
261-TN101 LEVEL 01 PLAN - TECHNOLOGY
GRAND TOTAL: 82
SUGGESTED MATRIX OF RESPONSIBILITY
ITEM: SHOWN ON:
FURNISHED
BY:
INSTALLED
BY: NOTES:
TECHNOLOGY ROUGH-IN, REFER TO
TECHNOLOGY EQUIPMENT SCHEDULE
AND SPECIFICATIONS FOR DEFINITION
T-SERIES E.C. E.C. 3. 4.
INFORMATION OUTLET FACEPLATES,
JACKS, AND TERMINATIONS
T-SERIES T.C. T.C.
CONDUIT SLEEVES (WHEN SHOWN ON
DRAWINGS)
T-SERIES E.C. E.C.
CONDUIT SLEEVES (NOT SHOWN BUT
REQUIRED FOR PROPER INSTALLATION
OF SYSTEM)
N/A T.C. T.C. 2. 4.
TELECOMMUNICATION SYSTEMS
ROUGH-IN
T-SERIES E.C. [T.C] E.C. 1.
TELECOMMUNICATION EQUIPMENT,
CABLING, AND TERMINATIONS
T-SERIES T.C. T.C.
CABLE TRAY (INCLUDING WIRE BASKET
TRAY) REFER TO SPECIFICATION
SECTION 27 05 28 FOR DEFINITION
T-SERIES E.C. E.C.
LADDER RACK T-SERIES T.C. T.C. 5.
GROUNDING LUGS ON TECHNOLOGY
EQUIPMENT
T-SERIES T.C. E.C. 6.
BONDING SYSTEM FOR TECHNOLOGY
SYSTEM, REFER TO SPECIFICATION
SECTION 27 05 26 FOR DEFINITION
T-SERIES E.C. E.C. 7. 8.
CONNECTION OF TECHNOLOGY
BONDING SYSTEM TO THE ELECTRICAL
GROUND SYSTEM
T-SERIES E.C. E.C.
LINE VOLTAGE POWER (+120V OR
GREATER)
E-SERIES E.C. E.C.
LINE VOLTAGE POWER (NOT SHOWN
BUT REQUIRED FOR PROPER
INSTALLATION OF SYSTEM)
N/A T.C. E.C. 2. 4.
LINE VOLTAGE POWER FOR DOOR
HARDWARE POWER SUPPLIES
ARCH SPEC E.C. E.C.
LOW VOLTAGE CABLING FOR
TECHNOLOGY SYSTEMS
T-SERIES T.C. T.C.
CABLE HANGERS AND SUPPORTS OR
OTHER CABLE ROUTING METHODS
(OTHER THAN CONDUIT AND CABLE
TRAY)
T-SERIES T.C. T.C. 5.
TECHNOLOGY SERVICE ENTRANCE
CONDUITS, HANDHOLES, AND
MANHOLES
[E]T-SERIES E.C. E.C.
FLOOR BOX (ROUGH-IN) T & E SERIES E.C. E.C.
SUGGESTED MATRIX OF RESPONSIBILITY NOTES
1. LOCATIONS OF TELECOMMUNICATIONS ROUGH-INS SHALL BE INDICATED BY THE INFORMATION
OUTLET SYMBOLS ON THE DRAWINGS. REFER TO THE TECHNOLOGY SYMBOL LIST FOR
ADDITIONAL INFORMATION.
2. BASED ON THE INHERENT DIFFERENCES IN PRODUCTS FROM VARIOUS MANUFACTURERS, ALL
REQUIRED EQUIPMENT MAY NOT BE SHOWN ON THE DRAWINGS FOR ALL ACCEPTABLE
MANUFACTURERS.
3. INCLUDES BACKBOXES AND CONDUIT REQUIRED FOR THE TECHNOLOGY SYSTEMS
INSTALLATION. THE E.C. SHALL BASE THE BID ON THE BASIS OF DESIGN SHOWN ON THE
CONTRACT DOCUMENTS.
4. ALL CHANGES TO THE SLEEVES, BACKBOXES, CONDUITS, AND POWER REQUIRED BECAUSE OF
THE T.C.'S SELECTION OF AN ALTERNATE ACCEPTABLE MANUFACTURER OR FROM SYSTEM
CONFIGURATIONS THAT ARE LEFT TO THE CHOICE OF THE CONTRACTOR SHALL BE INCLUDED
IN THE T.C.'S BID. THIS BID SHALL INCLUDE INSTALLATION BY A LICENSED ELECTRICIAN.
5. UNLESS TRADE RULES DICTATE OTHERWISE.
6. FURNISHED AS PART OF THE EQUIPMENT WHEN POSSIBLE, OR FURNISHED TO THE E.C. FOR
INSTALLATION IN THE FIELD.
7. INCLUDES ALL CONDUCTORS, GROUND BARS, AND TERMINATIONS FOR THE COMPLETE
BONDING SYSTEM REQUIRED BY THE SPECIFICATIONS.
8. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF PANELS AND SWITCHBOARDS SHOWN
IN THE TECHNOLOGY BONDING RISER DIAGRAM AND TYPICAL TELECOM ROOM BONDING FLOW
DIAGRAM.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
NOT FOR CONSTRUCTION
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/T
.0
V A
-C h ill ic o th e
C a m p u s
C .r v t
/1
/2
:1
:5
A
M
000-TN000
TECHNOLOGY COVERSHEET
03/17/2023 DLL ECW
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
95% DESIGN
DEVELOPMENT CAMPUS
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
No. Revisions: Date:
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 04/14/2023
THE EQUIPMENT LIST ABBREVIATIONS AND THE GENERAL TECHNOLOGY EQUIPMENT SCHEDULE ARE FOR THE CONVENIENCE OF THE CONTRACTOR. EACH CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF QUANTITIES AND SHALL FURNISH ALL MATERIAL REQUIRED, WHETHER SPECIFIED OR NOT, TO PRODUCE A SATISFACTORY WORKING SYSTEM.
CATALOG NUMBERS ARE NOT TO BE CONSIDERED COMPLETE BUT ARE GIVEN ONLY TO AID THE CONTRACTOR IN THE SEARCH FOR MATERIAL. NO MATERIAL SHALL BE ORDERED BY MANUFACTURER AND CATALOG NUMBER ONLY. EACH CONTRACTOR SHALL FIRST READ THE COMPLETE DESCRIPTION OF THE MATERIAL ON THESE DRAWINGS AND SPECIFICATIONS. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. "STANDARD COLOR" INDICATES FACTORY FINISH AVAILABLE AT NO ADDITIONAL CHARGE.
TECHNOLOGY EQUIPMENT SCHEDULE
EQUIPMENT LIST
ABBREVIATION EQUIPMENT LIST DESCRIPTION
MANUFACTURER AND
MODEL
SC-CT-1 18" W x 4"DEEP WIRE-MESH STYLE CABLE TRAY, HIGH QUALITY WELDED STEEL CONSTRUCTION, ELECTRO-GALVINIZED
FINISH WITH MOUNTING HARDWARE, SPLICE KIT AND GROUNDING JUMPERS
CABLOFIL
CF105/450EZ
OR APPROVED EQUAL
SC-FPW-1 4" FIRE-RATED PATHWAY FLOOR GRID SYSTEM, 14"L x 23"W x 4-1/2"H, STEEL CONSTRUCTION, (4) 4" PATHWAYS, FLOOR FRAME
KIT,
UL CERTIFIED FIRE BARRIER PATHWAY, 4HR FIRE RATING
STI
EZDG444S2
OR APPROVED EQUAL
SC-FPW-2 4" FIRE-RATED PATHWAY FLOOR GRID SYSTEM, 14"L x 23"W x 4-1/2"H, STEEL CONSTRUCTION, (8) 4" PATHWAYS, FLOOR FRAME
KIT,
UL CERTIFIED FIRE BARRIER PATHWAY, 4HR FIRE RATING
STI
EZDG844S2
OR APPROVED EQUAL
SC-LR-1 LADDER RUNWAY, 18"W TUBULAR STEEL CONSTRUCTION, RUST-RESISTANT BLACK ENAMEL FINISH WITH MOUNTING HARDWARE, ADAPTERS, FITTINGS, SUPPORTS WITH CROSS-MEMBER RADIUS DROPS AS REQUIRED, UL LISTED
CHATSWORTH
#11252-718
OR APPROVED ERQUAL
SC-MDA-1
SC-HDA-1
NETWORK CABINET - 83.4"H x 40"W x 43.3"D, 45RMU, SINGLE PERFORATED METAL FRONT DOOR WITH KEYED SWING HANDLE LOCK, DOUBLE PERFORATED METAL REAR DOOR WITH KEYED SWING HANDLE LATCH, STANDARD TOP PANEL WITH 2-PIECE BRUSH, SIDE PANELS WITH BRUSH SEALED CABLE OPENINGS, BOTTOM PANEL WITH BRUSH, INTEGRATED GROUNDING TABS.
CHATSWORTH
#NF8N-113N-E40-1
#39043-E63
OR APPROVED EQUAL
SC-MPP-1 ANGLED, QUICKPORT, 110 STYLE, MODULAR PATCH PANEL, 24-PORT CATEGORY 6 MODULAR RJ45 SNAP IN JACKS,WELEDED STEEL CONSTRUCTION, BLOCK POWDER COAT FINISH, MOUNT DIRECTLY TO EIA STANDARD 19" WIDE RACK MOUNTING
SYSTEM. REQUIRES 1 RMU OF SPACE.
LEVITON
#69587-U24
SC-MPP-2 ANGLED, QUICKPORT, 110 STYLE, HIGH DENSITY, MODULAR PATCH PANEL, 48-PORT CATEGORY 6 MODULAR RJ45 SNAP IN JACKS,WELEDED STEEL CONSTRUCTION, BLOCK POWDER COAT FINISH, MOUNT DIRECTLY TO EIA STANDARD 19" WIDE RACK MOUNTING SYSTEM.
This is the start of the file's text. The full file is on GovTribe.