This document provides details for a federal contract opportunity with the Department of Veterans Affairs Technology Acquisition Center Austin. The solicitation number is 36C77623B0058 for EHRM Infrastructure Upgrades Construction at the Chillicothe, Ohio VA medical center. The opportunity type is a solicitation for construction services to upgrade infrastructure at the specified VA location. The solicitation details include the issuing agency, project location, and general scope of upgrades required but do not provide pricing terms, response dates, or other contract specifics.
View the file
Other files
Show 40 more
Latest 50 of 65 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
N
CHILLICOTHE VA MEDICAL CENTER
PROJECT NUMBER: 538-21-701
DEPARTMENT OF VETERANS AFFAIRS
273 STATE ROUTE 104, CHILLICOTHE, OHIO 45601
EHRM INFRASTRUCTURE UPGRADES
VOLUME 4 OF 7
G E N E R A L N O T E S
A. SEE GENERAL PROJECT NOTES FOR NEW WORK FOR ADDITIONAL REQUIREMENTS FOR WORK WITHIN THE
EXISTING FACILITY. THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND FIELD CONDITIONS
PRIOR TO DEMOLITION AND CONSTRUCTION. IF PROVIDED, THE GENERAL CONTRACTOR SHALL EXAMINE
EXISTING BUILDING DOCUMENTS. THE CONTRACTOR SHALL BRING ANY DISCREPANCIES TO THE
IMMEDIATE ATTENTION OF THE C.O.R. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF
EXISTING ITEMS TO REMAIN DURING DEMOLITION AND CONSTRUCTION. MAINTAIN EXIT EGRESS PATHS
TO EXISTING EXIT DOORS DURING CONSTRUCTION.
B. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL CONSTRUCTION ROUTES BEYOND THE
AREAS OF WORK AND THE ROUTES MUST BE RETURNED TO THEIR ORIGINAL CONDITION AT THE END OF
THE PROJECT.
C. ALL DEMOLITION AND CONSTRUCTION ACTIVITIES SHALL BE COORDINATED WITH THE C.O.R. TO MINIMIZE
DISRUPTIONS OF NORMAL FUNCTIONS OF THE VA'S OCCUPIED AREAS.
D. IF CONSTRUCTION NOISE IS ANTICIPATED, SUBMIT A WRITTEN REQUEST TO THE C.O.R. FOR THE
SCHEDULED TIME OF THE CONSTRUCTION ACTIVITIES. NO WORK SHALL BE DONE WITHOUT THE WRITTEN
APPROVAL OF THE C.O.R. THE C.O.R. RESERVES THE RIGHT TO DISCONTINUE NOISY CONSTRUCTION AT
ANY TIME. NO RADIOS SHALL BE PERMITTED AT ANY TIME IN WORK AREAS ADJACENT TO OCCUPIED
SPACES.
E. ALL EXISTING SERVICES AND UTILITIES SHALL BE MAINTAINED TO AREAS THAT ARE IN OPERATION AND
SERVED BY THEM. COORDINATE ALL DISRUPTIONS OR DISCONTINUATIONS OF UTILITIES AND SERVICES
WITH C.O.R. NO SHUT DOWN OF EXISTING SERVICES IS ALLOWED TO OCCUR UNTIL RECEIVING THE
C.O.R.'S WRITTEN APPROVAL OF THE SHUT DOWN SCHEDULE. PROVIDE TEMPORARY SERVICES AND/OR
UTILITIES DURING INTERRUPTIONS AS REQUIRED AND APPROVED BY THE C.O.R.
F. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE V.A.'S
AREAS ADJACENT TO NEW CONSTRUCTION OR AREAS WHERE VARIOUS SYSTEM CONNECTIONS OR
EXTENSIONS ARE REQUIRED. IN THESE AREAS, THE CONTRACTOR IS RESPONSIBLE FOR DAMAGE
CAUSED BY LACK OF SUFFICIENT PROTECTION FROM THE WEATHER AND FROM THE RESULTS OF ALL
CONSTRUCTION ACTIVITY INCLUDING BUT NOT LIMITED TO DUST AND WATER.
G. THE CONTRACTOR SHALL RECEIVE WRITTEN APPROVAL FROM THE C.O.R. BEFORE USING OPEN FLAMES, WELDING RODS AND TORCHES. THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS TO
PROHIBIT THE MIGRATION OF SMOKE AND OTHER PRODUCTS OF COMBUSTION INTO OCCUPIED AREAS OF
THE EXISTING BUILDING AND FOR OBTAINING ALL REQUIRED PERMITS RELATED TO HOT WORK.
H. DO NOT OVERLOAD THE EXISTING BUILDING STRUCTURE. MAINTAIN THE STRUCTURAL INTEGRITY OF ALL
STRUCTURAL FRAMING MEMBERS AND SYSTEMS AT ALL TIMES.
I. ALL DEMOLISHED MATERIAL, EXCEPT MATERIAL THAT IS LISTED OR MARKED FOR RETENTION, SHALL
BECOME THE PROPERTY OF THE CONTRACTOR AND IT SHALL BE DISPOSED OF. NO DEBRIS RESULTING
FROM WORK SHALL BE LEFT IN THE CONSTRUCTION ROUTES BEYOND THE AREAS OF WORK.
J. REMOVAL OF A PARTICULAR ITEM IS TO INCLUDE ALL RELATED ITEMS, SUCH AS REMOVAL OF WALLS
WOULD INCLUDE ASSOCIATED DOORS, HARDWARE, ELECTRICAL, PLUMBING, MECHANICAL, ETC. REFER
TO DEMOLITION DRAWINGS FOR MORE INFORMATION. FOR ALL REMOVALS, THE GENERAL CONTRACTOR
AND SUBCONTRACTORS SHALL COORDINATE WITH ALL OTHER DISCIPLINES.
K. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT DEMOLISHED OR REMOVED
AS REQUIRED UNTIL PERMANENT SUPPORT IS PROVIDED IN THE FINAL CONSTRUCTION.
L. ALL OPENINGS IN EXISTING WALLS, CEILINGS AND FLOORS, WHICH ARE THE RESULT OF REMOVALS AND
OTHER NEW CONSTRUCTION ACTIVITY, SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE
EXISTING MATERIALS OR AS NOTED ON DRAWINGS. IF THE PATCH IS TO BE MADE IN FIRE RATED
CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE PATCH SHALL BE FINISHED
TO A LIKE NEW CONDITION TO MATCH THE EXISTING FINISH.
M. ALL EXISTING OPENINGS IN CEILINGS, FLOORS AND WALLS DISCOVERED IN THE EXISTING STRUCTURE
SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE EXISTING MATERIALS. IF THE PATCH IS TO
BE MADE IN FIRE RATED CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE
PATCH SHALL BE FINISHED TO A LIKE NEW CONDITION TO MATCH THE EXISTING FINISH.
N. WHERE EXISTING SURFACES ARE TO BE REFINISHED OR ARE TO SERVE AS SUBSTRATE FOR THE
ATTACHMENT OR APPLICATION OF NEW MATERIALS OR CONSTRUCTION, PREPARE OR ALTER THE
EXISTING SURFACES AS NECESSARY TO PROPERLY ACCOMMODATE THE NEW MATERIALS.
O. FIELD VERIFY SIZES AND DIMENSIONS OF ALL EXISTING UTILITIES THAT IMPACT THE NEW WORK.
DETERMINE THE SIZE AND LOCATION THE PENETRATIONS FROM THE EXISTING UTILITIES WITHIN THE NEW
WORK. SEAL TIGHT TO ALL PENETRATIONS AND CAULK.
P. PENETRATIONS THROUGH EXISTING FIRE RATED CONSTRUCTION MUST BE PROPERLY CLOSED AND FIRE
SAFE'D TO ACHIEVE THE REQUIRED FIRE RATING BY THE END OF CONSTRUCTION OPERATIONS FOR EACH
DAY.
Q. NEW HOLES IN EXISTING ROOF STRUCTURES FOR NEW WORK MUST BE COORDINATED WITH THE
EXISTING STRUCTURE SO THAT CRITICAL STRUCTURAL MEMBERS ARE NOT DAMAGED.
R. UNLESS OTHERWISE NOTED, THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISTING
SALVAGED STOCK BEFORE ORDERING NEW MATERIAL.
E X I S T I N G F A C I L I T I E S:
A. ALL WORK SHALL BE DONE IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND FEDERAL AUTHORITIES, CODES, RULES AND REGULATIONS.
B. THESE DOCUMENTS SHOW THE MINIMUM CONSTRUCTION REQUIREMENTS AND THE MINIMUM QUALITY OF
WORK EXPECTED. MORE STRINGENT REQUIREMENTS STIPULATED WITHIN RELEVANT MANUFACTURER’S
INSTALLATION INSTRUCTIONS WILL SUPERSEDE.
C. ANY UNFORESEEN OR UNCLEAR CONDITIONS SHALL BE REPORTED TO THE C.O.R. PRIOR TO PROCEEDING
WITH WORK.
D. ANY CONFLICTS WITHIN THE DRAWINGS, BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, OR
BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS AT THE SITE, ARE TO BE BROUGHT TO THE
IMMEDIATE ATTENTION OF THE C.O.R. THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL
WRITTEN CLARIFICATION FROM THE ARCHITECT/ENGINEER IS RECEIVED.
E. UNLESS OTHERWISE NOTED, ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED PER THE APPLICABLE
PROVISIONS OF THESE DOCUMENTS AND THE MANUFACTURER’S INSTRUCTIONS.
F. ALL MATERIALS USED SHALL BE NEW UNLESS OTHERWISE NOTED AND/OR OF A QUALITY TO MEET OR
EXCEED ALL APPLICABLE INDUSTRY STANDARDS. WHERE SPECIFIED PRODUCTS OR MANUFACTURERS
ARE NOT NOTED, THE CONTRACTOR IS REQUIRED TO NOTIFY THE ARCHITECT TO OBTAIN A MINIMUM
STANDARD OF QUALITY.
G. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS, METHODS AND TECHNIQUES FOR
CONSTRUCTION.
H. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR JOB-SITE SAFETY INCLUDING THE ADHERENCE TO
OSHA REGULATIONS.
I. ALL ELECTRICAL AND MECHANICAL WORK SHALL BE PERFORMED BY PERSONNEL LICENSED IN THE STATE
WHERE THIS PROJECT IS LOCATED.
J. REMOVE ALL DEBRIS PROPERLY FROM THE SITE. LOAD DEBRIS DIRECTLY ONTO TRUCKS FOR REMOVAL.
DISPOSE OF DEBRIS LEGALLY. DO NOT BURN DEBRIS ON THE SITE. DO NOT ALLOW DEBRIS TO ENTER
SEWERS. DO NOT ALLOW PILED DEBRIS TO ENDANGER STRUCTURES, BLOCK EXISTS OR ROADWAYS.
COMBUSTIBLE WASTE WHICH COULD CREATE A FIRE HAZARD SHALL NOT BE PERMITTED TO ACCUMULATE
IN OR AROUND THE CONSTRUCTION SITE.
K. COORDINATE ALL WORK WITH ALL OTHER DISCIPLINES, INCLUDING, EXACT SIZE AND LOCATION OF ALL
ROOF AND FLOOR OPENINGS SHOWN ON ARCHITECTURAL DRAWINGS SHALL BE VERIFIED WITH THE
ASSOCIATED SUB-CONTRACTORS PRIOR TO CONSTRUCTION.
L. DO NOT SCALE DRAWINGS. DIMENSIONS SHALL GOVERN. ALL PLAN DIMENSIONS ARE TAKEN TO FINISH
FACE OF CONSTRUCTION.
M. ALL CONCEALED WOOD SHALL BE FIRE RETARDANT TREATED.
N. SEAL CONSTRUCTION TIGHT TO ALL PENETRATIONS AND APPLY SEALANT.
O. ALL PENETRATIONS THROUGH FIRE RATED CONSTRUCTION MUST BE FIRE SAFE'D IN ACCORDANCE WITH
THE SPECIFICATIONS. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END
OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING
COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION
AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED PENETRATION.
P. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL EQUIPMENT INSTALLATION AND VERIFYING
ALL REQUIRED ROUGH OPENINGS, AND ROUGH-IN DIMENSIONS WITH THE EQUIPMENT MANUFACTURER, AND C.O.R. PRIOR TO CONSTRUCTION.
Q. REFER TO SHEET AE601 FOR SCHEDULES AND PARTITION TYPES.
N E W W O R K:
SHEET NAMING EXAMPLE:
BUILDING NUMBER
DISCIPLINE
SHEET TYPE
FLOOR NUMBER
ZONE LOCATION ON FLOOR
100-AE101.1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:3
:5
P
M
GI000.4
COVER SHEET - VOL. 4
07/07/2023 PQ JF
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CAMPUS
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N.T.S.Scale:
VICINITY MAP
N.T.S.Scale:
CAMPUS MAP
No. Revisions: Date:
BID DOCUMENTS 07/07/2023
SHEET INDEX
ARCHITECTURE
031-AE100 OVERALL GROUND FLOOR PLAN
031-AE100.1 GROUND FLOOR PLAN - ZONE 1
031-AE100.2 GROUND FLOOR PLAN - ZONE 2
031-AE100.3 GROUND FLOOR PLAN - ZONE 3
031-AE101 OVERALL FIRST FLOOR PLAN
031-AE101.2 FIRST FLOOR PLAN - ZONE 2
031-AE101.3 FIRST FLOOR PLAN - ZONE 3
031-AE102 OVERALL SECOND FLOOR PLAN
035-AE100 OVERALL BASEMENT AND FIRST FLOOR PLANS
035-AE100.2 BASEMENT FLOOR PLAN - ZONE 2
035-AE101.2 FIRST FLOOR PLAN - ZONE 2
035-AE102 OVERALL SECOND AND THIRD FLOOR PLANS
035-AE102.2 SECOND FLOOR PLAN - ZONE 2
035-AE103.2 THIRD FLOOR PLAN - ZONE 2
036-AE100 OVERALL BASEMENT AND FIRST FLOOR PLAN
060-AE100 OVERALL FIRST AND SECOND FLOOR PLANS
210-AE100 OVERALL BASEMENT FLOOR PLAN
210-AE101 BASEMENT FLOOR PLAN - ZONE 4
210-AE110 OVERALL FIRST FLOOR PLAN
210-AE114 FIRST FLOOR PLAN - ZONE 4
210-AE120 OVERALL SECOND FLOOR PLAN
210-AE124 SECOND FLOOR PLAN - ZONE 4
211-AE100 OVERALL BASEMENT FLOOR PLAN
211-AE104 BASEMENT FLOOR PLAN - ZONE 4
211-AE110 OVERALL FIRST FLOOR PLAN
211-AE114 FIRST FLOOR PLAN - ZONE 4
211-AE114.1 FIRST FLOOR PLAN - ZONE 4 - TR PLANS
211-AE120 OVERALL SECOND FLOOR PLAN
211-AE124 SECOND FLOOR PLAN - ZONE 4
211-AE124.1 SECOND FLOOR PLAN - ZONE 4 - TR PLANS
212-AE100 OVERALL BASEMENT FLOOR PLAN
212-AE100.1 BASEMENT FLOOR PLAN - ZONE 4
212-AE110 OVERALL FIRST FLOOR PLAN
212-AE110.1 FIRST FLOOR - ZONE 1
212-AE120 OVERALL SECOND FLOOR PLAN
212-AE120.1 ENLARGED PLANS - SECOND FLOOR
247-AE100 OVERALL BASEMENT AND FIRST FLOOR PLANS
252-AE100 OVERALL FIRST FLOOR PLAN
259-AE100 OVERALL FLOOR PLANS
AE601 DETAILS
261-AE100 OVERALL FIRST FLOOR PLAN
AE602 SCHEDULES
SHEET INDEX
GENERAL
GI000.4 COVER SHEET - VOL. 4
ZONE 1
ZONE 2 ZONE 3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:0
:2
P
M
027-AE101
OVERALL FIRST FLOOR PLAN
07/07/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/8" = 1'-0"
B27 - FIRST FLOOR
No. Revisions: Date:
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
K
027-AE101.1
Waiting
Visitor
Optometry Exam
Optometry Exam
Linen Chute
Soiled Utility
Retinal Exam
Tele Clos
131 Ice Machine
Pat Ed & Visit Coor
Toilet
Women's Veteran Program Manager
Break Room
Conference Room
Women's Health Diagnostic Coordinator
GECL Physician's Assistant
Centeral Check In
140 Neurology
Soiled Utility
Exam Room
UV Room
Associate Chief Nurse
Corridor
100A
Corridor
100B
Corridor
100C
Corridor
100D
Corridor
100E
Corridor
100I
2 - 5
ASSOCIATE CHEIF NURSE
TR
ASSOCIATE CHEIF NURSE
TR
A. CONTRACTOR TO DISPOSE OF CONSTRUCTION DEMOLITION DEBRIS.
B. REMOVE ALL CONSTRUCTION DEMOLITION DEBRIS ON DAILY BASIS.
G E N E R A L D E M O L I T I O N N O T E S
G E N E R A L C O N S T R U C T I O N N O T E S
A. REFER TO NEW WORK ARCHITECTURAL FLOOR PLANS FOR PARTITION TYPE DESIGNATIONS. SEE PARTITION TYPES ON
SHEET AE601.
B. ALL GYPSUM BOARD IS TO BE TYPE "X" UNLESS NOTED OTHERWISE.
C. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE. WHERE PARTITIONS OF DIFFERENT THICKNESSES MEET, MAINTAIN A FLUSH SURFACE ON THE SIDE WHERE
FACES ARE STRAIGHT AND CONTINUOUS, UNLESS NOTED OTHERWISE.
D. ALL COLD-FORMED STEEL FRAMING SHALL BE 20 GUAGE OR HEAVIER.
E. EDGES OF GYPSUM BOARD LEFT EXPOSED TO VIEW, OR ABUTTING DISSIMILAR MATERIAL, IS TO BE FINISHED WITH METAL "L"
BEAD TRIM AND COMPOUND UNLESS NOTED OTHERWISE.
F. ALL FIRE RATED WALL AND FLOOR PENETRATION MUST COMPLY WITH ASTM-E814
G. ALL DOOR OPENINGS SHALL BE 4" FROM A PERPENDICULAR PARTITION TO OUTSIDE FACE OF FRAME, UNLESS NOTED OR
DETAILED OTHERWISE.
H. ALL PARTITIONS, INCL. STUDS, BOARD, ETC. SHALL EXTEND FROM TOP OF FLOOR SLAB TO UNDERSIDE OF CONCRETE SLAB
ABOVE UNLESS OTHERWISE NOTED.
I. CONTRACTOR SHALL CLOSE OFF ANY VOIDS LEFT AS A RESULT OF ANY REMOVALS AND NEW CONSTRUCTION, AS WELL AS INFILL ANY EXISTING VOIDS IN NEWLY DESIGNATED FIRE RATED PARTITIONS. ALL PATCHES SHALL MATCH AND ALIGN WITH
SURROUNDING MATERIALS AND SHALL BE IN ACCORDANCE WITH NFPA CODE.
J. CONTRACTOR SHALL SEAL AROUND ALL M.E.P. PENETRATIONS OR OPENINGS, RESULTING FROM M.E.P. INSTALLATIONS INCLUDING BUT NOT LIMITED TO THE SLAB AND PARTITION WALLS ABOVE AND BELOW CEILINGS.
K. NO EXISTING FIREPROOFING IS TO BE REMOVED FROM EXISTING BUILDING STRUCTURE FOR ANY NEW INSTALLATION FOR
ANY REASON.
L. LABEL ALL RATED PARTITIONS (FIRE & SMOKE) ABOVE THE CEILING, ON BOTH SIDES OF THE WALL.
M. PROVIDE A MINIMUM OF ONE STUD SEPARATION BETWEEN OUTLET BOXES AND OTHER PENETRATIONS OCCURRING AT
OPPOSITE FACE OF WALLS.
N. PROVIDE CONTINUOUS NON-HARDENING ACOUSTICAL SEALANT AT TOP, SIDES AND EDGES OF BOTH SIDES OF WALL AT ALL NON-RATED GYPSUM BOARD PARTITIONS SCHEDULED TO RECEIVE SOUND ATTENUATION BLANKETS.
O. ALL PENETRATIONS AT NON-RATED WALLS SHALL BE SLEEVED AND PACKED AIRTIGHT WITH SAFING INSULATION AND SEALANT. ALL JOINT OF GYPSUM BOARD PANELS SHALL BE STAGGERED, TAPED, AND SEALED. FRAMING TO 1/2" +/-
CLEARANCE AT PERIMETER OF MECHANICAL DUCTWORK.
P. CONTRACTOR TO PROVIDE ALL RELATED FASTENERS, TRIM AND ACCESSORIES FOR INSTALL PRODUCTS PER
MANUFACTURER'S WRITTEN INSTRUCTIONS.
Q. COLD-FORMED STEEL (CFS) FRAMING SUPPLIER SHALL PROVIDE ENGINEERED DRAWINGS.
R. PROVIDE DOUBLE CFS FRAMING STUDS AT JAMBS OF DOOR AND FIXED GLASS FRAMES, AT OPEN PARTITION ENDS, AND WHERE PARTITION IS TO RECEIVE WALL MOUNTED SHELVES, CASEWORK, PLUMBING FIXTURES, ETC.
S. PROVIDE ADDITIONAL BRACING AS REQUIRED AT ALL CFS FRAMING STUD INSTALLATIONS EXCEEDING STUD MANUFACTURER
REQUIREMENTS FOR MAXIMUM ALLOWED HEIGHT AND DEFLECTION.
T. REFER TO MECHANICAL DRAWINGS FOR QUANTITY AND TYPE OF DIFFUSERS, RETURN AIR GRILLES, AND EXHAUST GRILLES.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
U. REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND TYPES OF LIGHTS, SPEAKERS, DETECTORS, POWER OUTLETS, ETC.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
V. BUILD PARTITIONS IN ACCORDANCE WITH PARTITION TYPE AND DESIGN REFERENCED. REFERENCES ARE TO LATEST EDITION OF GYPSUM ASSOCIATION (GA) FIRE RESISTANCE DESIGN MANUAL, OR TO UNDERWRITERS LABORATORY (UL) FIRE
RESISTANCE DIRECTORY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:0
:4
P
M
027-AE101.1
FIRST FLOOR ZONE 1 - TR PLANS
07/07/2023 PQ JF
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/8" = 1'-0"
B27 - FIRST FLOOR - ZONE 1
N
1/4" = 1'-0"
B27 - FIRST FLOOR - TR - DEMO
N
1/4" = 1'-0"
B27 - FIRST FLOOR - TR - NEW WORK
N
1/4" = 1'-0"
B27 - FIRST FLOOR PLAN - TR - DEMO RCP
N
1/4" = 1'-0"
B27 - FIRST FLOOR PLAN - TR - NEW WORK RCP
D R A W I N G N O T E S :
1 REMOVE EXISTING CARPET AND MASTIC MATERIAL FROM FLOOR. CLEAN AND PREPARE FLOOR FOR INSTALLATION OF
ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT.
2 ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT - SEE HATCHED AREA.
3 REMOVE CEILING SYSTEMS AND SUPPORTS
4 WALL MOUNTED FIRE EXTINGUISHER CABINET. PROVIDE NEW 10LB. CLASS C FIRE EXTINGUISHER FOR CABINET. SEE
FIRE CABINET ELEVATION ON SHEET GI001 FOR INSTALLATION HEIGHT.
5 3/4" FIRE-RETARDANT TREATED PLYWOOD - 4' X 8' SHEETS ALIGN WITH EXISTING - CUT AROUND OUTLETS AND CONDUIT.
PAINT WHITE ALL BUT FIRE RATING LABEL.
6 WINDOW SECURITY BARS - REFER TO DETAILS ON SHEET AE601 FOR BASIS OF DESIGN AND DETAILS.
7 NO CEILING IN THIS AREA
8 REMOVE ALL CASEWORK
9 REMOVE EXISTING DOOR FRAME, DOOR, AND HARDWARE; TURN DOOR AND HARDWARE OVER TO VA TO ADD TO
EXISTING STOCK.
10 CARD READER - REFER TO ELECTRICAL DRAWINGS
ZONE 2 ZONE 3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:0
:5
P
M
027-AE102
OVERALL SECOND FLOOR PLAN
07/07/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
1/8" = 1'-0"
B27 - SECOND FLOOR PLAN - OVERALL
027-AE102.1
Pain Clinic Check In
Release of Information
Pain Clinic Waiting
Toilet
Chiropractor
Pain Coordinator
GI Clerical
Linen Chute
GI Clinic Lounge
Tele Clos
235 Storage
PBS Kitchenette
Toilet
Exam Room
Pain Management Storage
Conference Room
Psychologist
Clinical Pharmacist
Physician
Physician
OPTOMETRY STAFF
Corridor
200A
Corridor
200C
Corridor
200B
Corridor
200D
Corridor
200B1
Corridor
200B2
Toilet
234A
OFFICE
OFFICE
TR
2' - 0"
OFFICE
TR
A. CONTRACTOR TO DISPOSE OF CONSTRUCTION DEMOLITION DEBRIS.
B. REMOVE ALL CONSTRUCTION DEMOLITION DEBRIS ON DAILY BASIS.
G E N E R A L D E M O L I T I O N N O T E S
G E N E R A L C O N S T R U C T I O N N O T E S
A. REFER TO NEW WORK ARCHITECTURAL FLOOR PLANS FOR PARTITION TYPE DESIGNATIONS. SEE PARTITION TYPES ON
SHEET AE601.
B. ALL GYPSUM BOARD IS TO BE TYPE "X" UNLESS NOTED OTHERWISE.
C. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE. WHERE PARTITIONS OF DIFFERENT THICKNESSES MEET, MAINTAIN A FLUSH SURFACE ON THE SIDE WHERE
FACES ARE STRAIGHT AND CONTINUOUS, UNLESS NOTED OTHERWISE.
D. ALL COLD-FORMED STEEL FRAMING SHALL BE 20 GUAGE OR HEAVIER.
E. EDGES OF GYPSUM BOARD LEFT EXPOSED TO VIEW, OR ABUTTING DISSIMILAR MATERIAL, IS TO BE FINISHED WITH METAL "L"
BEAD TRIM AND COMPOUND UNLESS NOTED OTHERWISE.
F. ALL FIRE RATED WALL AND FLOOR PENETRATION MUST COMPLY WITH ASTM-E814
G. ALL DOOR OPENINGS SHALL BE 4" FROM A PERPENDICULAR PARTITION TO OUTSIDE FACE OF FRAME, UNLESS NOTED OR
DETAILED OTHERWISE.
H. ALL PARTITIONS, INCL. STUDS, BOARD, ETC. SHALL EXTEND FROM TOP OF FLOOR SLAB TO UNDERSIDE OF CONCRETE SLAB
ABOVE UNLESS OTHERWISE NOTED.
I. CONTRACTOR SHALL CLOSE OFF ANY VOIDS LEFT AS A RESULT OF ANY REMOVALS AND NEW CONSTRUCTION, AS WELL AS INFILL ANY EXISTING VOIDS IN NEWLY DESIGNATED FIRE RATED PARTITIONS. ALL PATCHES SHALL MATCH AND ALIGN WITH
SURROUNDING MATERIALS AND SHALL BE IN ACCORDANCE WITH NFPA CODE.
J. CONTRACTOR SHALL SEAL AROUND ALL M.E.P. PENETRATIONS OR OPENINGS, RESULTING FROM M.E.P. INSTALLATIONS INCLUDING BUT NOT LIMITED TO THE SLAB AND PARTITION WALLS ABOVE AND BELOW CEILINGS.
K. NO EXISTING FIREPROOFING IS TO BE REMOVED FROM EXISTING BUILDING STRUCTURE FOR ANY NEW INSTALLATION FOR
ANY REASON.
L. LABEL ALL RATED PARTITIONS (FIRE & SMOKE) ABOVE THE CEILING, ON BOTH SIDES OF THE WALL.
M. PROVIDE A MINIMUM OF ONE STUD SEPARATION BETWEEN OUTLET BOXES AND OTHER PENETRATIONS OCCURRING AT
OPPOSITE FACE OF WALLS.
N. PROVIDE CONTINUOUS NON-HARDENING ACOUSTICAL SEALANT AT TOP, SIDES AND EDGES OF BOTH SIDES OF WALL AT ALL NON-RATED GYPSUM BOARD PARTITIONS SCHEDULED TO RECEIVE SOUND ATTENUATION BLANKETS.
O. ALL PENETRATIONS AT NON-RATED WALLS SHALL BE SLEEVED AND PACKED AIRTIGHT WITH SAFING INSULATION AND SEALANT. ALL JOINT OF GYPSUM BOARD PANELS SHALL BE STAGGERED, TAPED, AND SEALED. FRAMING TO 1/2" +/-
CLEARANCE AT PERIMETER OF MECHANICAL DUCTWORK.
P. CONTRACTOR TO PROVIDE ALL RELATED FASTENERS, TRIM AND ACCESSORIES FOR INSTALL PRODUCTS PER
MANUFACTURER'S WRITTEN INSTRUCTIONS.
Q. COLD-FORMED STEEL (CFS) FRAMING SUPPLIER SHALL PROVIDE ENGINEERED DRAWINGS.
R. PROVIDE DOUBLE CFS FRAMING STUDS AT JAMBS OF DOOR AND FIXED GLASS FRAMES, AT OPEN PARTITION ENDS, AND WHERE PARTITION IS TO RECEIVE WALL MOUNTED SHELVES, CASEWORK, PLUMBING FIXTURES, ETC.
S. PROVIDE ADDITIONAL BRACING AS REQUIRED AT ALL CFS FRAMING STUD INSTALLATIONS EXCEEDING STUD MANUFACTURER
REQUIREMENTS FOR MAXIMUM ALLOWED HEIGHT AND DEFLECTION.
T. REFER TO MECHANICAL DRAWINGS FOR QUANTITY AND TYPE OF DIFFUSERS, RETURN AIR GRILLES, AND EXHAUST GRILLES.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
U. REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND TYPES OF LIGHTS, SPEAKERS, DETECTORS, POWER OUTLETS, ETC.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
V. BUILD PARTITIONS IN ACCORDANCE WITH PARTITION TYPE AND DESIGN REFERENCED. REFERENCES ARE TO LATEST EDITION OF GYPSUM ASSOCIATION (GA) FIRE RESISTANCE DESIGN MANUAL, OR TO UNDERWRITERS LABORATORY (UL) FIRE
RESISTANCE DIRECTORY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:1
:1
P
M
027-AE102.1
SECOND FLOOR ZONE 1 - TR
PLANS
07/07/2023 PQ JF
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/8" = 1'-0"
B27 - SECOND FLOOR - ZONE 1
N
1/4" = 1'-0"
B27 - SECOND FLOOR PLAN - DEMO
N
1/4" = 1'-0"
B27 - SECOND FLOOR PLAN - NEW WORK
N
1/4" = 1'-0"
B27 - SECOND FLOOR REFLECTED CEILING PLAN - DEMO
N
1/4" = 1'-0"
B27 - SECOND FLOOR REFLECTED CEILING PLAN - NEW WORK
D R A W I N G N O T E S :
1 REMOVE EXISTING CARPET AND MASTIC MATERIAL FROM FLOOR. CLEAN AND PREPARE FLOOR FOR INSTALLATION OF
ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT.
2 REMOVE EXISTING DOOR FRAME, DOOR, AND HARDWARE; TURN DOOR AND HARDWARE OVER TO VA TO ADD TO
EXISTING STOCK.
3 ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT - SEE HATCHED AREA.
4 NO CEILING IN THIS AREA
5 3/4" FIRE-RETARDANT TREATED PLYWOOD - CUT PANELS LARGE ENOUGH TO MOUNT COMPONENTS WITH 1'-0" EXTRA ALL AROUND - ENSURE FIRE RATING LABEL IS ATTACHED - PAINT WHITE ALL BUT FIRE RATING LABEL.
6 REMOVE CEILING SYSTEMS AND SUPPORTS
7 WALL MOUNTED FIRE EXTINGUISHER CABINET. PROVIDE NEW 10LB. CLASS C FIRE EXTINGUISHER FOR CABINET. SEE
FIRE CABINET ELEVATION ON SHEET GI001 FOR INSTALLATION HEIGHT.
8 CARD READER - REFER TO ELECTRICAL DRAWINGS
9 DOOR FRAME, DOOR, AND HARDWARE
10 NEW WALL - REFER TO AE601 FOR PARTITION TYPE DETAIL.
11 PAINT WALLS - REFER TO FINISH SCHEDULE
028-AE102
Canteen Salon
CRC Office
Social Worker
Social Worker Supervisor
Canteen Storage
Toilet
Social Work Supervisor
Copy/File Room
Waiting
MHICM Case Manager
Toilet
Conference Room
MHICM Case Manager
MHICM Case Manager
MHCIM Case Manager
CRC/MHICM Program Manager
Medical Foster Home Coordinator
Closet
210A
Secretary Social Work Service
210B
Chief, Social Worker Service
210C
CRC/MHICM Program Support Assistant
210D
Closet
201A
Closet
202A
Closet
203A
Closet
204A
Closet
205A
Closet
205B
HAC
207A
Closet
208A
Closet
208B
Closet
209A
Closet
209B Closet
2011A
Closet
2011B
HAC
212A
Closet
214A
Closet
215A
Closet
216A
Closet
217A
Closet
218A
Corridor
Corridor
200A Stairs
Stairs
Elevator Lobby
Stairs
2-5
Tele. Closet
TELE. CLOSET
TR
TELE. CLOSET
TR
A. CONTRACTOR TO DISPOSE OF CONSTRUCTION DEMOLITION DEBRIS.
B. REMOVE ALL CONSTRUCTION DEMOLITION DEBRIS ON DAILY BASIS.
G E N E R A L D E M O L I T I O N N O T E S
G E N E R A L C O N S T R U C T I O N N O T E S
A. REFER TO NEW WORK ARCHITECTURAL FLOOR PLANS FOR PARTITION TYPE DESIGNATIONS. SEE PARTITION TYPES ON
SHEET AE601.
B. ALL GYPSUM BOARD IS TO BE TYPE "X" UNLESS NOTED OTHERWISE.
C. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE. WHERE PARTITIONS OF DIFFERENT THICKNESSES MEET, MAINTAIN A FLUSH SURFACE ON THE SIDE WHERE
FACES ARE STRAIGHT AND CONTINUOUS, UNLESS NOTED OTHERWISE.
D. ALL COLD-FORMED STEEL FRAMING SHALL BE 20 GUAGE OR HEAVIER.
E. EDGES OF GYPSUM BOARD LEFT EXPOSED TO VIEW, OR ABUTTING DISSIMILAR MATERIAL, IS TO BE FINISHED WITH METAL "L"
BEAD TRIM AND COMPOUND UNLESS NOTED OTHERWISE.
F. ALL FIRE RATED WALL AND FLOOR PENETRATION MUST COMPLY WITH ASTM-E814
G. ALL DOOR OPENINGS SHALL BE 4" FROM A PERPENDICULAR PARTITION TO OUTSIDE FACE OF FRAME, UNLESS NOTED OR
DETAILED OTHERWISE.
H. ALL PARTITIONS, INCL. STUDS, BOARD, ETC. SHALL EXTEND FROM TOP OF FLOOR SLAB TO UNDERSIDE OF CONCRETE SLAB
ABOVE UNLESS OTHERWISE NOTED.
I. CONTRACTOR SHALL CLOSE OFF ANY VOIDS LEFT AS A RESULT OF ANY REMOVALS AND NEW CONSTRUCTION, AS WELL AS INFILL ANY EXISTING VOIDS IN NEWLY DESIGNATED FIRE RATED PARTITIONS. ALL PATCHES SHALL MATCH AND ALIGN WITH
SURROUNDING MATERIALS AND SHALL BE IN ACCORDANCE WITH NFPA CODE.
J. CONTRACTOR SHALL SEAL AROUND ALL M.E.P. PENETRATIONS OR OPENINGS, RESULTING FROM M.E.P. INSTALLATIONS INCLUDING BUT NOT LIMITED TO THE SLAB AND PARTITION WALLS ABOVE AND BELOW CEILINGS.
K. NO EXISTING FIREPROOFING IS TO BE REMOVED FROM EXISTING BUILDING STRUCTURE FOR ANY NEW INSTALLATION FOR
ANY REASON.
L. LABEL ALL RATED PARTITIONS (FIRE & SMOKE) ABOVE THE CEILING, ON BOTH SIDES OF THE WALL.
M. PROVIDE A MINIMUM OF ONE STUD SEPARATION BETWEEN OUTLET BOXES AND OTHER PENETRATIONS OCCURRING AT
OPPOSITE FACE OF WALLS.
N. PROVIDE CONTINUOUS NON-HARDENING ACOUSTICAL SEALANT AT TOP, SIDES AND EDGES OF BOTH SIDES OF WALL AT ALL NON-RATED GYPSUM BOARD PARTITIONS SCHEDULED TO RECEIVE SOUND ATTENUATION BLANKETS.
O. ALL PENETRATIONS AT NON-RATED WALLS SHALL BE SLEEVED AND PACKED AIRTIGHT WITH SAFING INSULATION AND SEALANT. ALL JOINT OF GYPSUM BOARD PANELS SHALL BE STAGGERED, TAPED, AND SEALED. FRAMING TO 1/2" +/-
CLEARANCE AT PERIMETER OF MECHANICAL DUCTWORK.
P. CONTRACTOR TO PROVIDE ALL RELATED FASTENERS, TRIM AND ACCESSORIES FOR INSTALL PRODUCTS PER
MANUFACTURER'S WRITTEN INSTRUCTIONS.
Q. COLD-FORMED STEEL (CFS) FRAMING SUPPLIER SHALL PROVIDE ENGINEERED DRAWINGS.
R. PROVIDE DOUBLE CFS FRAMING STUDS AT JAMBS OF DOOR AND FIXED GLASS FRAMES, AT OPEN PARTITION ENDS, AND WHERE PARTITION IS TO RECEIVE WALL MOUNTED SHELVES, CASEWORK, PLUMBING FIXTURES, ETC.
S. PROVIDE ADDITIONAL BRACING AS REQUIRED AT ALL CFS FRAMING STUD INSTALLATIONS EXCEEDING STUD MANUFACTURER
REQUIREMENTS FOR MAXIMUM ALLOWED HEIGHT AND DEFLECTION.
T. REFER TO MECHANICAL DRAWINGS FOR QUANTITY AND TYPE OF DIFFUSERS, RETURN AIR GRILLES, AND EXHAUST GRILLES.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
U. REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND TYPES OF LIGHTS, SPEAKERS, DETECTORS, POWER OUTLETS, ETC.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
V. BUILD PARTITIONS IN ACCORDANCE WITH PARTITION TYPE AND DESIGN REFERENCED. REFERENCES ARE TO LATEST EDITION OF GYPSUM ASSOCIATION (GA) FIRE RESISTANCE DESIGN MANUAL, OR TO UNDERWRITERS LABORATORY (UL) FIRE
RESISTANCE DIRECTORY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:1
:2
P
M
028-AE102
OVERALL SECOND FLOOR
07/07/2023 PQ JF
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/8" = 1'-0"
B28 - SECOND FLOOR PLAN - OVERALL
N
1/4" = 1'-0"
B28 - SECOND FLOOR PLAN - DEMO
N
1/4" = 1'-0"
B28 - SECOND FLOOR PLAN - NEW WORK
N
1/4" = 1'-0"
B28 - SECOND FLOOR REFLECTED CEILING PLAN - DEMO
N
1/4" = 1'-0"
B28 - SECOND FLOOR REFLECTED CEILING PLAN - NEW WORK
D R A W I N G N O T E S :
1 REMOVE WALL
2 REMOVE EXISTING DOOR FRAME, DOOR, AND HARDWARE; TURN DOOR AND HARDWARE OVER TO VA TO ADD TO
EXISTING STOCK.
3 ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT - SEE HATCHED AREA.
4 3/4" FIRE-RETARDANT TREATED PLYWOOD - 4' X 8' SHEETS ALIGN WITH EXISTING - CUT AROUND OUTLETS AND CONDUIT.
PAINT WHITE ALL BUT FIRE RATING LABEL.
5 EXISTING CONDITIONS TO REMAIN
6 PATCH WALL WHERE PRIOR WALLS WERE REMOVED. USE TYPE X GYPSUM BOARD TO MATCH EXISTING. PAINT TO
MATCH EXISTING.
7 WALL MOUNTED FIRE EXTINGUISHER CABINET. PROVIDE NEW 10LB. CLASS C FIRE EXTINGUISHER FOR CABINET. SEE
FIRE CABINET ELEVATION ON SHEET GI001 FOR INSTALLATION HEIGHT.
8 WINDOW SECURITY BARS - REFER TO DETAILS ON SHEET AE601 FOR BASIS OF DESIGN AND DETAILS.
9 REMOVE CEILING SYSTEMS AND SUPPORTS
10 REMOVE EXISTING FLOOR TILE AND MASTIC MATERIAL FROM FLOOR. CLEAN AND PREPARE FLOOR FOR INSTALLATION
OF ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT.
11 EXISTING CARD READER TO REMAIN
DN
ZONE 2
ZONE 1
ZONE 3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:1
:3
P
M
030-AE100
OVERALL BASEMENT FLOOR PLAN
07/07/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/8" = 1'-0"
B30 - BASEMENT FLOOR PLAN - OVERALL
030-AE101
Corridor
0B
Corridor
0E
Tele Clos
14A
Mechanical
14 Elevator Equipment
Oxygen Storage
9B
PT & Prosthetics Orthotic Clinic
Soiled Linen
8B
Diabetes Education
8C
Patient Ed Class Rm
8D
Patient Ed Storage
8G
Elect. Room
8F
Toilet
8A
Corridor
0A
Stair
S3-0
Corridor
0DElevator Equipment
4J
Office
8H
Mechanical
Diabetic Educator
8E
DIABETIC EDUCATOR
8E
TR
8E
8E
DIABETIC EDUCATOR
8E
TR
8E
A. CONTRACTOR TO DISPOSE OF CONSTRUCTION DEMOLITION DEBRIS.
B. REMOVE ALL CONSTRUCTION DEMOLITION DEBRIS ON DAILY BASIS.
G E N E R A L D E M O L I T I O N N O T E S
G E N E R A L C O N S T R U C T I O N N O T E S
A. REFER TO NEW WORK ARCHITECTURAL FLOOR PLANS FOR PARTITION TYPE DESIGNATIONS. SEE PARTITION TYPES ON
SHEET AE601.
B. ALL GYPSUM BOARD IS TO BE TYPE "X" UNLESS NOTED OTHERWISE.
C. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE. WHERE PARTITIONS OF DIFFERENT THICKNESSES MEET, MAINTAIN A FLUSH SURFACE ON THE SIDE WHERE
FACES ARE STRAIGHT AND CONTINUOUS, UNLESS NOTED OTHERWISE.
D. ALL COLD-FORMED STEEL FRAMING SHALL BE 20 GUAGE OR HEAVIER.
E. EDGES OF GYPSUM BOARD LEFT EXPOSED TO VIEW, OR ABUTTING DISSIMILAR MATERIAL, IS TO BE FINISHED WITH METAL "L"
BEAD TRIM AND COMPOUND UNLESS NOTED OTHERWISE.
F. ALL FIRE RATED WALL AND FLOOR PENETRATION MUST COMPLY WITH ASTM-E814
G. ALL DOOR OPENINGS SHALL BE 4" FROM A PERPENDICULAR PARTITION TO OUTSIDE FACE OF FRAME, UNLESS NOTED OR
DETAILED OTHERWISE.
H. ALL PARTITIONS, INCL. STUDS, BOARD, ETC. SHALL EXTEND FROM TOP OF FLOOR SLAB TO UNDERSIDE OF CONCRETE SLAB
ABOVE UNLESS OTHERWISE NOTED.
I. CONTRACTOR SHALL CLOSE OFF ANY VOIDS LEFT AS A RESULT OF ANY REMOVALS AND NEW CONSTRUCTION, AS WELL AS INFILL ANY EXISTING VOIDS IN NEWLY DESIGNATED FIRE RATED PARTITIONS. ALL PATCHES SHALL MATCH AND ALIGN WITH
SURROUNDING MATERIALS AND SHALL BE IN ACCORDANCE WITH NFPA CODE.
J. CONTRACTOR SHALL SEAL AROUND ALL M.E.P. PENETRATIONS OR OPENINGS, RESULTING FROM M.E.P. INSTALLATIONS INCLUDING BUT NOT LIMITED TO THE SLAB AND PARTITION WALLS ABOVE AND BELOW CEILINGS.
K. NO EXISTING FIREPROOFING IS TO BE REMOVED FROM EXISTING BUILDING STRUCTURE FOR ANY NEW INSTALLATION FOR
ANY REASON.
L. LABEL ALL RATED PARTITIONS (FIRE & SMOKE) ABOVE THE CEILING, ON BOTH SIDES OF THE WALL.
M. PROVIDE A MINIMUM OF ONE STUD SEPARATION BETWEEN OUTLET BOXES AND OTHER PENETRATIONS OCCURRING AT
OPPOSITE FACE OF WALLS.
N. PROVIDE CONTINUOUS NON-HARDENING ACOUSTICAL SEALANT AT TOP, SIDES AND EDGES OF BOTH SIDES OF WALL AT ALL NON-RATED GYPSUM BOARD PARTITIONS SCHEDULED TO RECEIVE SOUND ATTENUATION BLANKETS.
O. ALL PENETRATIONS AT NON-RATED WALLS SHALL BE SLEEVED AND PACKED AIRTIGHT WITH SAFING INSULATION AND SEALANT. ALL JOINT OF GYPSUM BOARD PANELS SHALL BE STAGGERED, TAPED, AND SEALED. FRAMING TO 1/2" +/-
CLEARANCE AT PERIMETER OF MECHANICAL DUCTWORK.
P. CONTRACTOR TO PROVIDE ALL RELATED FASTENERS, TRIM AND ACCESSORIES FOR INSTALL PRODUCTS PER
MANUFACTURER'S WRITTEN INSTRUCTIONS.
Q. COLD-FORMED STEEL (CFS) FRAMING SUPPLIER SHALL PROVIDE ENGINEERED DRAWINGS.
R. PROVIDE DOUBLE CFS FRAMING STUDS AT JAMBS OF DOOR AND FIXED GLASS FRAMES, AT OPEN PARTITION ENDS, AND WHERE PARTITION IS TO RECEIVE WALL MOUNTED SHELVES, CASEWORK, PLUMBING FIXTURES, ETC.
S. PROVIDE ADDITIONAL BRACING AS REQUIRED AT ALL CFS FRAMING STUD INSTALLATIONS EXCEEDING STUD MANUFACTURER
REQUIREMENTS FOR MAXIMUM ALLOWED HEIGHT AND DEFLECTION.
T. REFER TO MECHANICAL DRAWINGS FOR QUANTITY AND TYPE OF DIFFUSERS, RETURN AIR GRILLES, AND EXHAUST GRILLES.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
U. REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND TYPES OF LIGHTS, SPEAKERS, DETECTORS, POWER OUTLETS, ETC.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
V. BUILD PARTITIONS IN ACCORDANCE WITH PARTITION TYPE AND DESIGN REFERENCED. REFERENCES ARE TO LATEST EDITION OF GYPSUM ASSOCIATION (GA) FIRE RESISTANCE DESIGN MANUAL, OR TO UNDERWRITERS LABORATORY (UL) FIRE
RESISTANCE DIRECTORY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:1
:5
P
M
030-AE100.1
BASEMENT FLOOR PLAN - ZONE 1
07/07/2023 PQ JF
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/8" = 1'-0"
B30 - BASEMENT - ZONE 1
N
1/4" = 1'-0"
B30 - BASEMENT FLOOR PLAN - DEMO
N
1/4" = 1'-0"
B30 - BASEMENT FLOOR PLAN - NEW WORK
D R A W I N G N O T E S :
1 REMOVE EXISTING CARPET AND MASTIC MATERIAL FROM FLOOR. CLEAN AND PREPARE FLOOR FOR INSTALLATION OF
ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT.
2 REMOVE CEILING SYSTEMS AND SUPPORTS
3 NO CEILING IN THIS AREA
4 ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT - SEE HATCHED AREA.
5 WALL MOUNTED FIRE EXTINGUISHER CABINET. PROVIDE NEW 10LB. CLASS C FIRE EXTINGUISHER FOR CABINET. SEE
FIRE CABINET ELEVATION ON SHEET GI001 FOR INSTALLATION HEIGHT.
6 3/4" FIRE-RETARDANT TREATED PLYWOOD - 4' X 8' SHEETS ALIGN WITH EXISTING - CUT AROUND OUTLETS AND CONDUIT.
PAINT WHITE ALL BUT FIRE RATING LABEL.
7 CARD READER - REFER TO ELECTRICAL DRAWINGS
N
1/4" = 1'-0"
B30 - BASEMENT REFLECTED CEILING PLAN - DEMO
N
1/4" = 1'-0"
B30 - BASEMENT REFLECTED CEILING PLAN - NEW WORK
ZONE 2
ZONE 3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:1
:0
P
M
030-AE101
OVERALL FIRST FLOOR PLAN
07/07/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/8" = 1'-0"
B30 - FIRST FLOOR PLAN - OVERALL
030-AE101.1
Toilet
104A
MOD
Cardio-Pulminary Supervisor
Office
Social Worker
Corridor
Physician
Corridor
100A Waiting
Storage
Med Room
157B
Toilet
157A
Soiled Utility
Tele Surgery
Procedure Room
Laundry Chute
Break Room
Lab
Storage
128A
Family Waiting Room
Toilet
Corridor
100C
Storage
Nurse Mgr
122HAC
HAC
120A
Corridor
Corridor
Tele Clos
Respiratory Therapy Pulminary Function
Stair
S3-1
Closet
100B
TELE CLOS
Room
11GGG
Room
11GGGGGG
LAB
STORAGE
2 - 5
TELE CLOS
1 2
LAB
10 11
TR
71 SF
TELE CLOS
LAB
TR
LAB
A. CONTRACTOR TO DISPOSE OF CONSTRUCTION DEMOLITION DEBRIS.
B. REMOVE ALL CONSTRUCTION DEMOLITION DEBRIS ON DAILY BASIS.
G E N E R A L D E M O L I T I O N N O T E S
G E N E R A L C O N S T R U C T I O N N O T E S
A. REFER TO NEW WORK ARCHITECTURAL FLOOR PLANS FOR PARTITION TYPE DESIGNATIONS. SEE PARTITION TYPES ON
SHEET AE601.
B. ALL GYPSUM BOARD IS TO BE TYPE "X" UNLESS NOTED OTHERWISE.
C. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE. WHERE PARTITIONS OF DIFFERENT THICKNESSES MEET, MAINTAIN A FLUSH SURFACE ON THE SIDE WHERE
FACES ARE STRAIGHT AND CONTINUOUS, UNLESS NOTED OTHERWISE.
D. ALL COLD-FORMED STEEL FRAMING SHALL BE 20 GUAGE OR HEAVIER.
E. EDGES OF GYPSUM BOARD LEFT EXPOSED TO VIEW, OR ABUTTING DISSIMILAR MATERIAL, IS TO BE FINISHED WITH METAL "L"
BEAD TRIM AND COMPOUND UNLESS NOTED OTHERWISE.
F. ALL FIRE RATED WALL AND FLOOR PENETRATION MUST COMPLY WITH ASTM-E814
G. ALL DOOR OPENINGS SHALL BE 4" FROM A PERPENDICULAR PARTITION TO OUTSIDE FACE OF FRAME, UNLESS NOTED OR
DETAILED OTHERWISE.
H. ALL PARTITIONS, INCL. STUDS, BOARD, ETC. SHALL EXTEND FROM TOP OF FLOOR SLAB TO UNDERSIDE OF CONCRETE SLAB
ABOVE UNLESS OTHERWISE NOTED.
I. CONTRACTOR SHALL CLOSE OFF ANY VOIDS LEFT AS A RESULT OF ANY REMOVALS AND NEW CONSTRUCTION, AS WELL AS INFILL ANY EXISTING VOIDS IN NEWLY DESIGNATED FIRE RATED PARTITIONS. ALL PATCHES SHALL MATCH AND ALIGN WITH
SURROUNDING MATERIALS AND SHALL BE IN ACCORDANCE WITH NFPA CODE.
J. CONTRACTOR SHALL SEAL AROUND ALL M.E.P. PENETRATIONS OR OPENINGS, RESULTING FROM M.E.P. INSTALLATIONS INCLUDING BUT NOT LIMITED TO THE SLAB AND PARTITION WALLS ABOVE AND BELOW CEILINGS.
K. NO EXISTING FIREPROOFING IS TO BE REMOVED FROM EXISTING BUILDING STRUCTURE FOR ANY NEW INSTALLATION FOR
ANY REASON.
L. LABEL ALL RATED PARTITIONS (FIRE & SMOKE) ABOVE THE CEILING, ON BOTH SIDES OF THE WALL.
M. PROVIDE A MINIMUM OF ONE STUD SEPARATION BETWEEN OUTLET BOXES AND OTHER PENETRATIONS OCCURRING AT
OPPOSITE FACE OF WALLS.
N. PROVIDE CONTINUOUS NON-HARDENING ACOUSTICAL SEALANT AT TOP, SIDES AND EDGES OF BOTH SIDES OF WALL AT ALL NON-RATED GYPSUM BOARD PARTITIONS SCHEDULED TO RECEIVE SOUND ATTENUATION BLANKETS.
O. ALL PENETRATIONS AT NON-RATED WALLS SHALL BE SLEEVED AND PACKED AIRTIGHT WITH SAFING INSULATION AND SEALANT. ALL JOINT OF GYPSUM BOARD PANELS SHALL BE STAGGERED, TAPED, AND SEALED. FRAMING TO 1/2" +/-
CLEARANCE AT PERIMETER OF MECHANICAL DUCTWORK.
P. CONTRACTOR TO PROVIDE ALL RELATED FASTENERS, TRIM AND ACCESSORIES FOR INSTALL PRODUCTS PER
MANUFACTURER'S WRITTEN INSTRUCTIONS.
Q. COLD-FORMED STEEL (CFS) FRAMING SUPPLIER SHALL PROVIDE ENGINEERED DRAWINGS.
R. PROVIDE DOUBLE CFS FRAMING STUDS AT JAMBS OF DOOR AND FIXED GLASS FRAMES, AT OPEN PARTITION ENDS, AND WHERE PARTITION IS TO RECEIVE WALL MOUNTED SHELVES, CASEWORK, PLUMBING FIXTURES, ETC.
S. PROVIDE ADDITIONAL BRACING AS REQUIRED AT ALL CFS FRAMING STUD INSTALLATIONS EXCEEDING STUD MANUFACTURER
REQUIREMENTS FOR MAXIMUM ALLOWED HEIGHT AND DEFLECTION.
T. REFER TO MECHANICAL DRAWINGS FOR QUANTITY AND TYPE OF DIFFUSERS, RETURN AIR GRILLES, AND EXHAUST GRILLES.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
U. REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND TYPES OF LIGHTS, SPEAKERS, DETECTORS, POWER OUTLETS, ETC.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
V. BUILD PARTITIONS IN ACCORDANCE WITH PARTITION TYPE AND DESIGN REFERENCED. REFERENCES ARE TO LATEST EDITION OF GYPSUM ASSOCIATION (GA) FIRE RESISTANCE DESIGN MANUAL, OR TO UNDERWRITERS LABORATORY (UL) FIRE
RESISTANCE DIRECTORY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:1
:2
P
M
030-AE101.1
FIRST FLOOR PLAN - TR PLANS
07/07/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/8" = 1'-0"
B30 - FIRST FLOOR - ZONE 1
N
1/4" = 1'-0"
B30 - FIRST FLOOR PLAN - DEMO
N
1/4" = 1'-0"
B30 - FIRST FLOOR PLAN - NEW WORK
N
1/4" = 1'-0"
B30 - FIRST FLOOR REFLECTED CEILING PLAN - DEMO
N
1/4" = 1'-0"
B30 - FIRST FLOOR REFLECTED CEILING PLAN - NEW WORK
D R A W I N G N O T E S :
1 REMOVE EYE WASH STATION AND CAP WATER LINE. STORE EYE WASH STATION TO REINSTALL IN ROOM 130 - LAB
2 REMOVE SINK AND CAP WATERLINE. STORE SINK TO REINSTALL IN ROOM 130 - LAB.
3 REMOVE CEILING SYSTEMS AND SUPPORTS
4 ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT - SEE HATCHED AREA.
5 WALL MOUNTED FIRE EXTINGUISHER CABINET. PROVIDE NEW 10LB. CLASS C FIRE EXTINGUISHER FOR CABINET. SEE
FIRE CABINET ELEVATION ON SHEET GI001 FOR INSTALLATION HEIGHT.
6 3/4" FIRE-RETARDANT TREATED PLYWOOD - 4' X 8' SHEETS ALIGN WITH EXISTING - CUT AROUND OUTLETS AND CONDUIT.
PAINT WHITE ALL BUT FIRE RATING LABEL.
7 NO CEILING IN THIS AREA
8 REMOVE EXISTING FLOOR TILE AND MASTIC MATERIAL FROM FLOOR. CLEAN AND PREPARE FLOOR FOR INSTALLATION
OF ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT.
9 DOOR FRAME, DOOR, AND HARDWARE
10 REMOVE DOOR FRAME, LEAF, HARDWARE SET. STORE DOOR FRAME, LEAF, AND HARDWARE SET TO REINSTALL IN
ROOM 130 - LAB.
11 REMOVE EXISTING DOOR FRAME, DOOR, AND HARDWARE; TURN DOOR AND HARDWARE OVER TO VA TO ADD TO
EXISTING STOCK.
12 REMOVE SINK AND PREPARE WATERLINE FOR INSTALLATION OF LAB SINK AND EYE WASH STATION.
13 REMOVE CASEWORK
14 CARD READER - REFER TO ELECTRICAL DRAWINGS
15 INSTALL DOOR FRAME, LEAF AND HARDWARE SET THAT WAS REMOVED FROM ROOM 127.
16 INSTALL SINK
17 INSTALL EYE WASH STATION
ZONE 2
ZONE 3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:1
:3
P
M
030-AE102
OVERALL SECOND FLOOR PLAN
07/07/2023 PQ JF
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/8" = 1'-0"
B30 - SECOND FLOOR
030-AE102.1
Corridor
2C2
Bed Room
Toilet
221A
Soiled Utility
Toilet
Toilet
202A
Bed Room
Bed Room
Toilet
201A
MIT Work Room
Corridor
2C1
Medical Clerks
Bedroom
Corridor
2C7
Bedroom
Toilet
228A
Bedroom
Corridor
2C6
Nourishment
Storage
Corridor
2C5
Med. Room
232A
Laundry Chute
Nurse Station
Clean Utility
Corridor
2C8
Bed Room
Toilet
250A
Soiled Utility
Elect. Room
Tele Clos
223A
Toilet
227A
Toilet
230A
Omni Cell
Toilet
Stair
S3-2
2 - 5
TELE CLOSET
NURSE OFFICE
1 5
DEMOLITION BOUNDARY
TELE CLOSET
NURSE OFFICE
TR
NURSE OFFICE
DEMOLITION BOUNDARY
TELE CLOSET
NURSE OFFICE
TR
NURSE OFFICE
A. CONTRACTOR TO DISPOSE OF CONSTRUCTION DEMOLITION DEBRIS.
B. REMOVE ALL CONSTRUCTION DEMOLITION DEBRIS ON DAILY BASIS.
G E N E R A L D E M O L I T I O N N O T E S
G E N E R A L C O N S T R U C T I O N N O T E S
A. REFER TO NEW WORK ARCHITECTURAL FLOOR PLANS FOR PARTITION TYPE DESIGNATIONS. SEE PARTITION TYPES ON
SHEET AE601.
B. ALL GYPSUM BOARD IS TO BE TYPE "X" UNLESS NOTED OTHERWISE.
C. PARTITION TYPES INDICATED ARE CONTINUOUS TO A CORNER OR AN INTERSECTING PARTITION, UNLESS INDICATED OTHERWISE. WHERE PARTITIONS OF DIFFERENT THICKNESSES MEET, MAINTAIN A FLUSH SURFACE ON THE SIDE WHERE
FACES ARE STRAIGHT AND CONTINUOUS, UNLESS NOTED OTHERWISE.
D. ALL COLD-FORMED STEEL FRAMING SHALL BE 20 GUAGE OR HEAVIER.
E. EDGES OF GYPSUM BOARD LEFT EXPOSED TO VIEW, OR ABUTTING DISSIMILAR MATERIAL, IS TO BE FINISHED WITH METAL "L"
BEAD TRIM AND COMPOUND UNLESS NOTED OTHERWISE.
F. ALL FIRE RATED WALL AND FLOOR PENETRATION MUST COMPLY WITH ASTM-E814
G. ALL DOOR OPENINGS SHALL BE 4" FROM A PERPENDICULAR PARTITION TO OUTSIDE FACE OF FRAME, UNLESS NOTED OR
DETAILED OTHERWISE.
H. ALL PARTITIONS, INCL. STUDS, BOARD, ETC. SHALL EXTEND FROM TOP OF FLOOR SLAB TO UNDERSIDE OF CONCRETE SLAB
ABOVE UNLESS OTHERWISE NOTED.
I. CONTRACTOR SHALL CLOSE OFF ANY VOIDS LEFT AS A RESULT OF ANY REMOVALS AND NEW CONSTRUCTION, AS WELL AS INFILL ANY EXISTING VOIDS IN NEWLY DESIGNATED FIRE RATED PARTITIONS. ALL PATCHES SHALL MATCH AND ALIGN WITH
SURROUNDING MATERIALS AND SHALL BE IN ACCORDANCE WITH NFPA CODE.
J. CONTRACTOR SHALL SEAL AROUND ALL M.E.P. PENETRATIONS OR OPENINGS, RESULTING FROM M.E.P. INSTALLATIONS INCLUDING BUT NOT LIMITED TO THE SLAB AND PARTITION WALLS ABOVE AND BELOW CEILINGS.
K. NO EXISTING FIREPROOFING IS TO BE REMOVED FROM EXISTING BUILDING STRUCTURE FOR ANY NEW INSTALLATION FOR
ANY REASON.
L. LABEL ALL RATED PARTITIONS (FIRE & SMOKE) ABOVE THE CEILING, ON BOTH SIDES OF THE WALL.
M. PROVIDE A MINIMUM OF ONE STUD SEPARATION BETWEEN OUTLET BOXES AND OTHER PENETRATIONS OCCURRING AT
OPPOSITE FACE OF WALLS.
N. PROVIDE CONTINUOUS NON-HARDENING ACOUSTICAL SEALANT AT TOP, SIDES AND EDGES OF BOTH SIDES OF WALL AT ALL NON-RATED GYPSUM BOARD PARTITIONS SCHEDULED TO RECEIVE SOUND ATTENUATION BLANKETS.
O. ALL PENETRATIONS AT NON-RATED WALLS SHALL BE SLEEVED AND PACKED AIRTIGHT WITH SAFING INSULATION AND SEALANT. ALL JOINT OF GYPSUM BOARD PANELS SHALL BE STAGGERED, TAPED, AND SEALED. FRAMING TO 1/2" +/-
CLEARANCE AT PERIMETER OF MECHANICAL DUCTWORK.
P. CONTRACTOR TO PROVIDE ALL RELATED FASTENERS, TRIM AND ACCESSORIES FOR INSTALL PRODUCTS PER
MANUFACTURER'S WRITTEN INSTRUCTIONS.
Q. COLD-FORMED STEEL (CFS) FRAMING SUPPLIER SHALL PROVIDE ENGINEERED DRAWINGS.
R. PROVIDE DOUBLE CFS FRAMING STUDS AT JAMBS OF DOOR AND FIXED GLASS FRAMES, AT OPEN PARTITION ENDS, AND WHERE PARTITION IS TO RECEIVE WALL MOUNTED SHELVES, CASEWORK, PLUMBING FIXTURES, ETC.
S. PROVIDE ADDITIONAL BRACING AS REQUIRED AT ALL CFS FRAMING STUD INSTALLATIONS EXCEEDING STUD MANUFACTURER
REQUIREMENTS FOR MAXIMUM ALLOWED HEIGHT AND DEFLECTION.
T. REFER TO MECHANICAL DRAWINGS FOR QUANTITY AND TYPE OF DIFFUSERS, RETURN AIR GRILLES, AND EXHAUST GRILLES.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
U. REFER TO ELECTRICAL DRAWINGS FOR QUANTITY AND TYPES OF LIGHTS, SPEAKERS, DETECTORS, POWER OUTLETS, ETC.
SCRIBE CEILING MATERIALS CAREFULLY FOR A TIGHT FIT.
V. BUILD PARTITIONS IN ACCORDANCE WITH PARTITION TYPE AND DESIGN REFERENCED. REFERENCES ARE TO LATEST EDITION OF GYPSUM ASSOCIATION (GA) FIRE RESISTANCE DESIGN MANUAL, OR TO UNDERWRITERS LABORATORY (UL) FIRE
RESISTANCE DIRECTORY.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:1
:5
P
M
030-AE102.1
SECOND FLOOR PLAN - TR PLANS
07/07/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/8" = 1'-0"
B30 - SECOND FLOOR - ZONE 1
N
1/4" = 1'-0"
B30 - SECOND FLOOR PLAN - DEMO
N
1/4" = 1'-0"
B30 - SECOND FLOOR PLAN - NEW WORK
N
1/4" = 1'-0"
B30 - SECOND FLOOR REFLECTED CEILING PLAN - DEMO
N
1/4" = 1'-0"
B30 - SECOND FLOOR REFLECTED CEILING PLAN - NEW WORK
D R A W I N G N O T E S :
1 REMOVE EXISTING CARPET AND MASTIC MATERIAL FROM FLOOR. CLEAN AND PREPARE FLOOR FOR INSTALLATION OF
ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT.
2 REMOVE CEILING SYSTEMS AND SUPPORTS
3 NO CEILING IN THIS AREA
4 ELECTROSTATIC DISSIPATING (ESD) EPOXY FLOOR PAINT - SEE HATCHED AREA.
5 REMOVE WALL
6 WINDOW SECURITY BARS - REFER TO DETAILS ON SHEET AE601 FOR BASIS OF DESIGN AND DETAILS.
7 3/4" FIRE-RETARDANT TREATED PLYWOOD - 4' X 8' SHEETS ALIGN WITH EXISTING - CUT AROUND OUTLETS AND CONDUIT.
PAINT WHITE ALL BUT FIRE RATING LABEL.
8 PATCH WALL OPENING OF REMOVED DOOR/WINDOW WITH COLD-FORMED METAL FRAMING AND TYPE X GYPSUM BOARD
TO MATCH EXISTING.
9 REMOVE EXISTING DOOR FRAME, DOOR, AND HARDWARE; TURN DOOR AND HARDWARE OVER TO VA TO ADD TO
EXISTING STOCK.
10 REMOVE PORTION OF WALL SYSTEM FOR FUTURE INSTALLATION OF DOOR FRAME AND DOOR LEAF.
11 LEAVE CEILING SUPPORTS IN ADJACENT SPACE TO FUTURE TR. NEW CEILING COMPONENTS TO BE INSTALLED AND TIED
INTO EXISTING CEILING GRID.
12 DOOR FRAME, DOOR, AND HARDWARE
13 NEW CEILING COMPONENTS TO TIE EXISTING CEILING SYSTEM TO NEW WALL - MATCH EXISTING GRID COMPONENTS
AND ACOUSTICAL CEILING TILES
14 WALL MOUNTED FIRE EXTINGUISHER CABINET. PROVIDE NEW 10LB. CLASS C FIRE EXTINGUISHER FOR CABINET. SEE
FIRE CABINET ELEVATION ON SHEET GI001 FOR INSTALLATION HEIGHT.
15 EXISTING CARD READER TO REMAIN
16 NEW WALL - REFER TO AE601 FOR PARTITION TYPE DETAIL.
17 PAINT WALLS - REFER TO FINISH SCHEDULE
18 VINYL WALL BASE ALONG WALL - MATCH EXISTING BASE IN ROOM.
UP
DN
UP
DN
DN
DN
UP
REF.
NOT BUILT YET
ZONE 2
ZONE 3
ZONE 1
ZONE 4
031-AE100.1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:1
:0
P
M
031-AE100
OVERALL GROUND FLOOR PLAN
07/07/2023 Checker Author
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
N
1/16" = 1'-0"
B31 - GROUND FLOOR PLAN - OVERALL
REF.
K
K
031-AE100.1
MRI Scanning Room Zone IV
G-347G
Control Room
G-347H
Equipment Room
G-347F
Interview
G-347-A Office
G-347-B
Corridor Zone III
G-347K Corridor Zone II
G-347
Public Restroom
G-343E
Staff Restroom
G-343F Clean Linen
G-343C
Patient Toilet
G-347E
Reception
G-344
Office
G-324
Office
G-323
Office
G-322
Tech. Room
G-322AToilet Room
G-321B
Vestibule
Clean Linen
G-352
Toilet
G-345D
Dressing
G-345C
CT Scan…