This document contains construction drawings and details for technology infrastructure upgrades at the Chillicothe VA Medical Center in Chillicothe, Ohio. The drawings specify requirements for exterior hand holes, exterior wall penetrations, underground duct banks, and telecommunications manholes. Details include specifications for materials, dimensions, conduits, cables, grounding and other components of the infrastructure upgrade. This work is solicited under Solicitation Number 36C77623B0058 by the Department of Veterans Affairs Technology Acquisition Center for their project numbered 538-21-701 to upgrade the EHRM infrastructure at the Chillicothe VA campus located at 538-21-701 Chillicothe, Ohio. The solicitation is for a construction contract.
View the file
Other files
Show 40 more
Latest 50 of 65 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
LID SHALL BE MARKED
"TELECOMMUNICATIONS"
MOUSE HOLES - (4).
CONDUIT ENTRY PENETRATION NOT TO
EXCEED 25 PERCENT OF SIDE WALL AREA
STAINLESS STEEL HEX
HEAD BOLT W/WASHER
PULL SLOT
SKID RESISTANT SURFACE
EXTENSIONS AS
REQUIRED BY
CONDUIT DEPTH
KNOCKOUTS - (8)
SLOPE GRADE AWAY
FROM COVER 1" IN 3'
GRAVEL DRAINAGE BED MINIMUM 6"
DEPTH. MINIMUM SIZE GRAVEL 1"
NOTES:
1. ALL DIMENSIONS ARE NOMINAL INSIDE CLEARANCES.
2. ANY SPLICES OR DEVICES IN HANDHOLE SHALL BE SUBMERGIBLE.
8" E
XTENSIO
N
LOG
O
LENGTH
W
IDTH
DEPTH
BELOW GRADE CONCRETE WALL OR FLOOR
HYDROSTATIC SEAL ASSEMBLY. INSTALL
ASSEMBLY SO BOLT HEADS ARE ACCESSIBLE
FROM INTERIOR FOR DISASSEMBLY.
"LINK-SEAL", OZ-GEDNEY "CSM" SERIES,
CROUSE-HINDS "TW" SERIES, REFER TO NOTE #1
DUCT SEALING COMPOUND IN INTERIOR OF CONDUIT.
JM CLIPPER DUXSEAL OR EQUIVALENT PULL BOX, CONDUIT
FITTING OR AUXILIARY
GUTTER, REFER TO
NOTE #2
APPLY CAULK FLUSH WITH SURFACE AND PROVIDE
CHROME ESCUTCHEON RING FOR FINISHED WALLS
CAST OR MALLEABLE IRON SLEEVE WITH WATER
STOP, IF NOT CORE DRILLED
IF APPLICABLE, DOWEL DUCT BANK TO CONCRETE
WALL WITH MINIMUM OF (4) #4 EMBEDDED
MINIMUM OF 4" AND EPOXY ANCHORED
NOTES:
1. HYDROSTATIC SEAL SELECTION BASED ON OUTSIDE DIAMETER OF CONDUIT AND INSIDE
DIAMETER OF SLEEVE OR BORE.
2. PROVIDE PULL BOX, CONDUIT FITTING OR AUXILIARY GUTTER, SIZED PER N.E.C. WITHIN 5' OF
CONDUIT ENTER TO ALLOW SEALING OF CONDUITS. BOX ORIENTATION IS DIAGRAMMATIC
SEALING COMPOUND SHALL BE NON-HARDENING MATERIAL FOR WATERSTOP AND MOISTURE
BARRIER, OZ/GEDNEY "DUX" OR APPROVED EQUIVALENT SEAL BOTH ENDS OF EXTERIOR
CONDUITS.
3. THIS DETAIL APPLIES TO ALL BELOW GRADE WALL AND FLOOR CONDUIT ENTRIES INTO
BUILDING.
RIGID METAL CONDUIT THRU WALL
MARKER TAPE WITH
METALLIC TRACER, 12"
ABOVE DUCT BANK
(4) #4 BARS CONTINUOUS
ON TOP AND BOTTOM
4" SCHEDULE 40 PVC
4" MINIMUM COMPACTED
AGGREGATE BASE.
[PRECAST CONCRETE PADS
ON UNDISTURBED EARTH
UNDER EACH SPACER]
#4 TIE BARS AT 3'-0" ON CENTER
INTERMEDIATE SPACER
CONDUIT NONMETALLIC SPACER,
MAXIMUM 5' ON CENTER. [CARLON
S288 SERIES, UNDERGROUND
DEVICES WUNPEECE, OSBORN
ASSOCIATES 5100 SERIES]
3" MIN. 3" MIN.
M
IN
M A
X
/2
/4
2500 PSI CONCRETE
7 1/2" 7 1/2" 7 1/2" 7 1/2"
CLEAN EARTH
BACKFILL PLACED PER
SPECIFICATIONS
FINISHED GRADE
NOTES:
1. INSTALL 2000LB TENSILE STRENGTH BRAIDED POLYPROPYLENE
PULLCORD IN ALL CONDUITS.
2. TRENCHING AND BACKFILL ACCORDING TO SPECIFICATIONS.
3. MINIMUM OF 4'-0" CLEAR BETWEEN ADJACENT DUCTBANKS.
4. DOWEL ENDS OF DUCTBANK TO FOUNDATION OR MANHOLE WITH A
MINIMUM OF (4) #4 DOWELS.
(4) FIBER INNERDUCTS &
CAT5E COPPER CABLES
IN EACH CONDUIT
(4) FIBER INNERDUCTS &
OS2 OPTICAL FIBER
CABLES IN EACH CONDUIT
(4) FIBER INNERDUCTS &
CAT5E COPPER CABLES
IN EACH CONDUIT
/2
(4) FIBER INNERDUCT &
OS2 OPTICAL FIBER
CABLES IN EACH CONDUIT
SPARE CONDUITS
SPARE CONDUITS
PULLING IRONS, COORDINATE
LOCATIONS OPPOSITE CONDUIT
ENTRY LOCATIONS
MANHOLE FRAME AND LID AND
OPENING SHOWN DIAGRAMMATICALLY.
LOCATE IN CORNER AS INDICATED ON
PLAN OR AS REQUIRED FOR ACCESS
AS COORDINATED WITH CABLE
PENETRATIONS IN MANHOLE
SECTION VIEW
FINISH GRADE
SLOPE CONDUIT TO
MANHOLE (TYP.)
5/8" x 8'-0" COPPER GROUND ROD. BOND
TO ALL STEEL IN MANHOLE WITH 1-#6 AWG.
BOND TO ALL GROUND CONDUCTORS
ROUTED IN MANHOLE
COORDINATE CONDUIT ENTRY
LOCATIONS WITH SITE PLAN (TYP.)
PROVIDE FIBERGLASS MANHOLE LADDER
FOR ACCESS. COORDINATE LOCATION
WITH MANHOLE FRAME AND LID. PROVIDE
AND INSTALL ALL NECESSARY EQUIPMENT
TO SECURE LADDER TO MANHOLE. REFER
TO SPECIFICATIONS FOR DETAILS
#4 AT 6" O.C. EACH WAY
R-1640 MANHOLE FRAME WITH SOLID LID
MANUFACTURED BY NEENAH FOUNDRY
COMPANY, THE LID SHALL BE MARKED
"TELECOMMUNICATIONS". LID SHALL BE
LOCKABLE.
GROUT
PRE CAST BOTTOM SECTION
#4`S AT 6" O.C. BOTTOM
EACH WAY
#4 TOP AND BOTTOM ON
FOUR SIDES OF OPENING
PROVIDE PRE CAST
EXTENSIONS AS NEEDED
TO REACH GRADE
MINIMUM OF 1/3 CU. YD
OF CRUSHED GRAVEL
2" PVC DRAIN PIPE, SLOPE
DOWN TOWARDS GRAVEL
AWAY FROM THE MANHOLE
DRAIN COVER
CAST-IN-PLACE OR
PRE-CAST CONCRETE TOP
PRE CAST TOP SECTION
INSIDE MANHOLE DIMENSIONS
SHALL BE 72"W X 72"Dx 72"H
M
IN
IM
U
M
(1
(1
(7
/2
M
IN
IM
U
M
(6
M
IN
IM
U
M
(36")
(6") (6")
(1
(1
MALLEABLE IRON
BELL END (TYP.)
NOTES:
1. DETAIL SHOWN DIAGRAMMATICALLY.REFER TO 0-TG003 FOR MANHOLE LOCATIONS.
2. DETAIL IS TYPICAL OF ALL MANHOLES.
3. A MINIMUM OF 50' OF EACH FIBER CABLE SHALL BE COILED IN EACH MAINTENANCE HOLE.
4. MINIMUM INTERIOR DIMENSIONS OF 72" X 72" X 72".
20'-0" MINIMUM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/T
.0
V A
-C h ill ic o th e
C a m p u s
C .r v t
/1 /2
:1
:2
P M
000-TN500
TECHNOLOGY DETAILS
07/07/2023 ACA ECW
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
NO SCALE
EXTERIOR HAND HOLE DETAIL
NO SCALE
EXTERIOR WALL PENETRATION DETAIL
NO SCALE
DUCTBANK DETAIL
NO SCALE
TELECOMMUNICATIONS MANHOLE DETAIL
No. Revisions: Date:
BID DOCUMENTS 07/07/2023
1 Addendum #1 10/30/2023
2 Addendum #2 12/11/2023