This document contains electrical plans for upgrades to the EHRM infrastructure at the Chillicothe VA Medical Center in Chillicothe, Ohio. The plans show new and updated electrical work on the first floor of Building 23, including installing a new busbar grounding electrode and bonding conductor, adding keypads, card readers, door contacts and motion sensors to doors, installing an 8-door access control panel and power supply, and running new electrical lines to indoor and outdoor HVAC units. The related federal contract opportunity is solicitation number 36C77623B0058 for the construction project to complete the EHRM Infrastructure Upgrades at the Chillicothe VAMC, with an estimated value of $538,210. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas.

View the file

Other files

File Type Posted
Abstract of offers - Chillicothe Bid Opening 01172024 signed.pdf PDF
S06 - Amendment 0009 Bid Opening.pdf PDF
S06 - Amendment 0008 Extend due date to 01172024.pdf PDF
S06 - 36C77623B0058 0007.pdf PDF
S06 - Amendment 0007 Att 10 - 14.063_024-EP100 - ELECTRICAL PLAN - BASEMENT FLOOR.pdf PDF
S06 - Amendment 0007 Att 13 - 14.116_E616.31 - PANELBOARD SCHEDULES.pdf PDF
S06 - Amendment 0007 Att 4 - Chiillicothe VA Lead Paint Survey Report.pdf PDF
S06 - Amendment 0007 Att 7 - 000-TS100 - CAMPUS TECHNOLOGY SITE PLAN.pdf PDF
S06 - Amendment 0007 Att 6 - 000-TN500 - TECHNOLOGY DETAILS.pdf PDF
S06 - Amendment 0007 Att 3 - 2023-01 AHERA.pdf PDF
S06 - Amendment 0007 Att 11 - 14.077_031-EP100 - ELECTRICAL PLAN - GROUND FLOOR.pdf PDF
S06 - Amendment 0007 Att 16 - 026-TN100 - BASEMENT PLAN -TECHNOLOGY.pdf PDF
S06 - Amendment 0007 Att 14 - 018-TN209 - TECHNOLOGY ENLARGEMENT.pdf PDF
S06 - Amendment 0007 Att 8 - 13.038_030-MD101 - MECHANICAL DEMOLITION PLAN - FIRST FLOOR.pdf PDF
S06 - Amendment 0007 Att 12 - 14.080_035-EP100 - ELECTRICAL PLAN - BASEMENT.pdf PDF
S06 - Amendment 0007 Att 1 Technical questions Round 2 responses.pdf PDF
S06 - Amendment 0007 Att 2 - Final SWP3.pdf PDF
S06 - Amendment 0007 Att 15 - 018-TN210 - TECHNOLOGY ENLARGEMENT.pdf PDF
S06 - Amendment 0007 Att 5 - 000-TN400 - TECHNOLOGY RISER DIAGRAMS.pdf PDF
Amendment 0006 36C77623B0058.pdf PDF
Amendment 0005 36C77623B0058.pdf PDF
Amendment 0005 - Attachment Addendum 1.zip ZIP file
Amendment 0005 - Attachment - Vendor Questions_Responses final.pdf PDF
Amendment 0004 36C77623B0058.pdf PDF
Amendment 0003 36C77623B0058.docx DOCX document
Att 10 Volume 10 - Technology_Combined.pdf PDF
Att 8 Volume 8 - Electrical_Combined.pdf PDF
Att 6 Volume 6 - Mechanical_Combined.pdf PDF
Att 9 Volume 9 - Electrical_Combined.pdf PDF
Att 13 Volume 13 - Fiber_Combined.pdf PDF
Att 4 Volume 4 - Architectural_Combined.pdf PDF
Att 5 Volume 5 - Fire Suppression_Combined.pdf PDF
Att 14 S04 - Site Visit sign in 10-11-2023.pdf PDF
Att 7 Volume 7 - Mechanical_Combined.pdf PDF
Att 12 Volume 12 - Fiber_Combined.pdf PDF
Att 11 Volume 11 - Technology_Combined.pdf PDF
Att 3 Volume 3 - Architectural_Combined.pdf PDF
Att 2 Volume 2 - Civil_Combined (1).pdf PDF
36C77623B0058 0002.docx DOCX document
Att 1 Volume 1 - General and Civil_Combined.pdf PDF
DBA Wage Rates Construction - Ross Cty.pdf PDF
36C77623B0058 0001.docx DOCX document
Attachment 04 - DBA Wage Determination.pdf PDF
Updated _Specifications_Combined.pdf PDF
Attachment 08 - SOW attach Volume 1 Part 3.pdf PDF
Attachment 09 - SOW attach Volume 1 Part 4.pdf PDF
Attachment 04 - Wage Rate Determination - Chillicothe.pdf PDF
Attachment 11 - SOW attach Volume 1 Part 6.pdf PDF
Attachment 19 - SOW attach Volume 3 Part 4.pdf PDF
Attachment 17 - SOW attach Volume 3 Part 2.pdf PDF
Show 40 more

Latest 50 of 65 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

DN

DN

DN

DN

UP

UP

AP

CC

K DCES

RX

T

023-EP101

Warehouse #2-2

121-2

TR

121A

(E) (B23) N

(E) (B23) D

C1

C1

SYMMETRY PACS

CONTROLLER

GROUNDING BUS

BAR

IDU-1

(E) (B23) D - 7

(E) (B23) D - 7

(E) (B23) D - 7

(E) (B23) D - 20,22,24 (E) (B23) D - 7

(E) (B23) D - 7

(E) (B23) D - 26,28

(E) (B23) D-13

(E) (B23) D-13

ODU-2

(E) (B23) D - 7

TR

121A

(E) (B23) N - 15,17,19

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

A u to d e s k D o c s /C h ill ic o th e

V A

E

H R

M /F

F E

C h ill ic o th e

E H

R M

M

E P rv t

/1

/2

:1

:0

P M

023-EP101

ELECTRICAL PLAN - FIRST FLOOR

07/07/2023 JB CLG

EHRM INFRASTRUCTURE

UPGRADES

538-21-701

CHILLICOTHE, OH

BID DOCUMENTS

CHILLICOTHE

VAMC

Approved: Owner

1/8" = 1'-0"

BLDG 23 - OVERALL FIRST FLOOR - ELECTRICAL NEW WORK PLAN

1/4" = 1'-0"

BLDG 23 - TR 121B - ELECTRICAL NEW WORK PLAN

D R A W I N G N O T E S :

1 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.

2 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM

ITS POINT OF ENTRANCE TO THE BUILDING.

3 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.

4 INSTALL NEW 8 DOOR SYMMETRY PACS PANEL CONTROLLER AND POWER SUPPLY.

5 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT

TO CASSETTE UNIT.

6 INSTALL NEW 120V 30A HEAVY DUTY NON-FUSED DISCONNECT AND FEED (2)#12, #12 GROUND, 3/4"C TO SPLIT SYSTEM

UNIT MOTOR.

No. Revisions: Date:

BID DOCUMENTS 07/07/2023

2 ADDENDUM #2 12/11/2023

Sheets
023-EP101 - ELECTRICAL PLAN - FIRST FLOOR