Attachment 11 - SOW attach Volume 1 Part 6.pdf
PDF 10 MB Posted
- Attached to
- Y1DA--538-21-701 EHRM Infrastructure Upgrades Construction Chillicothe, OH (VA-23-00066755)
- Solicitation number
- 36C77623B0058
About this file
This attachment is a statement of work for infrastructure upgrades to construction facilities at the Chillicothe VA Medical Center in Ohio. The related federal contract opportunity is solicitation number 36C77623B0058 issued by the Department of Veterans Affairs Technology Acquisition Center Austin. The solicitation seeks proposals for upgrading the EHRM infrastructure including installing new network switches, servers, storage, and related equipment. The construction work must be completed within 365 calendar days of the award date. Offerors must submit proposals by July 15, 2021. The contract is set aside for verified service-disabled veteran-owned small businesses. The awarded contractor will be responsible for project management, site assessments, procurement, installation, configuration, testing and training activities to modernize the medical center's IT infrastructure and ensure compliance with VA and OSHA standards.
View the file
Other files
Show 40 more
Latest 50 of 65 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
UP
DN
UP
HMR ASSISTANT
Tele Clos
Nurse Training Storage
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
Training Room
TR
284B
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:1
A
M
001-FX102
FIRE SUPPRESSION PLAN -
SECOND FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 001
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - SECOND FLOOR
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM MODIFIED. REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO
ACCOMMODATE NEW CEILING.
2 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
CONSTRUCTION DOCUMENTS - 95% SUBMITTAL 03/17/2023
CONSTRUCTION DOCUMENTS - 95% 04/14/2023
TR
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:0
A
M
003-FX101
FIRE SUPPRESSION PLAN - FIRST
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 003
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR - OVERALL
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
No. Revisions: Date:
Tele Clos
108D
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:2
A
M
007-FX101
FIRE SUPPRESSION PLAN - FIRST
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 007
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
DN DN
UP
DN
Volunteer Work Room
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
Closet
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:4
A
M
009-FX101
FIRE SUPPRESSION PLAN - FIRST
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 009
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM MODIFIED. REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO
ACCOMMODATE NEW CEILING.
2 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
TR
Office
OFFICE
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
11 2
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:5
A
M
018-FX102
FIRE SUPPRESSION PLAN -
SECOND FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 018
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - SECOND FLOOR - OVERALL
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM MODIFIED. REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO
ACCOMMODATE NEW CEILING.
2 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
No. Revisions: Date:
DN
DN
UP
UP
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
TR
121A
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:3
A
M
023-FX101
FIRE SUPPRESSION PLAN - FIRST
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 023
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR
D R A W I N G N O T E S :
1 REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO ACCOMMODATE NEW ROOM
LAYOUT.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
Tele Clos
Conference Room
124A
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:5
A
M
024-FX101
FIRE SUPPRESSION PLAN - FIRST
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 024
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN BRANCH
PIPING UP.
2 CEILING IN THIS ROOM MODIFIED. REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO
ACCOMMODATE NEW CEILING.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
Tele Clos
ELEC CLOS
002U
ELEC CLOS
002V
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:0
A
M
024-FX102
FIRE SUPPRESSION PLAN -
SECOND FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 024
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - SECOND FLOOR
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
LIGHT HAZARD
TR
102D
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:3
A
M
025-FX101
FIRE SUPPRESSION PLAN - FIRST
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 025
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR
D R A W I N G N O T E S :
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
CIO
TR
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:5
A
M
026-FX100
FIRE SUPPRESSION PLAN -
BASEMENT
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 026
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - BASEMENT - OVERALL
D R A W I N G N O T E S :
1 REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO ACCOMMODATE NEW ROOM
LAYOUT.
No. Revisions: Date:
200A
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:5
A
M
026-FX102
FIRE SUPPRESSION PLAN -
SECOND FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 026
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - SECOND FLOOR - OVERALL
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
No. Revisions: Date:
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:1
A
M
027-FX101
FIRE SUPPRESSION PLAN - FIRST
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 027
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:3
A
M
027-FX102
FIRE SUPPRESSION PLAN -
SECOND FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 027
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - SECOND FLOOR
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN BRANCH
PIPING UP.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:1
A
M
028-FX102
FIRE SUPPRESSION PLAN -
SECOND FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 028
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - SECOND FLOOR - OVERALL
D R A W I N G N O T E S :
1 REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO ACCOMMODATE NEW ROOM
LAYOUT.
No. Revisions: Date:
TR
8E
Elect. Room
8F
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:5
A
M
030-FX100
FIRE SUPPRESSION PLAN -
BASEMENT
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 030
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - BASEMENT
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
Tele Clos
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:5
A
M
030-FX101
FIRE SUPPRESSION PLAN - FIRST
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 030
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM MODIFIED. REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO
ACCOMMODATE NEW CEILING.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
Room
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:0
A
M
030-FX102
FIRE SUPPRESSION PLAN -
SECOND FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 030
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - SECOND FLOOR
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
2 REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO ACCOMMODATE NEW ROOM
LAYOUT.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
UP
DN
UP
DN
DN
DN
DN
DN
UP
REF.
CT Power Equipment
G-345G
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
Conference Room
G182
TR
G182A
Tele Clos
G-202
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:4
:5
A
M
031-FX100
FIRE SUPPRESSION PLAN -
BASEMENT
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 031
CHILLICOTHE
VAMC
Approved: Owner
N
1/16" = 1'-0"
ELECTRICAL DEMOLITION PLAN - GROUND FLOOR - OVERALL
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM MODIFIED. REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO
ACCOMMODATE NEW CEILING.
2 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
3 REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO ACCOMMODATE NEW ROOM
LAYOUT.
No. Revisions: Date:
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
TR
1-210
TR
F204
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:5
:0
A
M
031-FX101
FIRE SUPPRESSION PLAN - FIRST
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 031
CHILLICOTHE
VAMC
Approved: Owner
N
1/16" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN BRANCH
PIPING UP.
2 REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO ACCOMMODATE NEW ROOM
LAYOUT.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
2-207A
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:5
:1
A
M
031-FX102
FIRE SUPPRESSION PLAN -
SECOND FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 031
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - SECOND FLOOR - OVERALL
D R A W I N G N O T E S :
1 CEILING IN THIS ROOM REMOVED. REPLACE EXISTING SPRINKLER HEAD(S) AND TURN
BRANCH PIPING UP.
No. Revisions: Date:
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
TR
3-210
TR
3-210
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
1 1
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:5
:2
A
M
031-FX103
FIRE SUPPRESSION PLAN - THIRD
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 031
CHILLICOTHE
VAMC
Approved: Owner
D R A W I N G N O T E S :
1 REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO ACCOMMODATE NEW ROOM
LAYOUT.
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - THIRD FLOOR - OVERALL
No. Revisions: Date:
B60 First Floor
F I R E H A Z A R D L E G E N D :
LIGHT HAZARD
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE WITH STRUCTURAL, ARCHITECTURAL, AND ALL OTHER
TRADES. EQUIPMENT, SPRINKLERS, AND PIPING SHOWN ON THESE PLANS IS TO
CONVEY DESIGN INTENT AND DOES NOT DICTATE THE MEANS AND METHODS OF
IMPLEMENTATION. ADHERE TO ALL HAZARD CLASSIFICATIONS SHOWN.
F. REFER TO ARCHITECTURAL AND FIRE ALARM DRAWINGS FOR FIRE ALARM ZONES,
SMOKE PARTITIONS, AND FIRE EXTINGUISHER CABINETS.
G. CONTRACTOR TO CONDUCT FIRE WATER FLOW TEST AND SUBMIT RESULTS AND
SPRINKLER DESIGN.
FIRE SPRINKLER HAZARD SCHEDULE
CLASSIFICATION CRITERIA HOSE DURATION SPRINKLER NOTES
LIGHT HAZARD 0.10 GPM/SF OVER 1500
SF
100 GPM 30 MIN QR; K = 5.6 OR K = 8.0 BASE AREA
SPRINKLER DENSITY
1 SPRINKLER PER 225 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/1
/2
:5
:1
A
M
060-FX101
FIRE SUPPRESSION PLAN - FIRST
FLOOR
05/01/2023 GP GP
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
95% CONSTRUCTION
DOCUMENTS 060
CHILLICOTHE
VAMC
Approved: Owner
N
3/32" = 1'-0"
FIRE SUPPRESSION PLAN - FIRST FLOOR
D R A W I N G N O T E S :
1 REPLACE EXISTING SPRINKLER HEADS AND RELOCATE TO ACCOMMODATE NEW ROOM
LAYOUT.
No. Revisions: Date:
DESIGN DEVELOPMENT - 65% SUBMITTAL 10/14/2022
DESIGN DEVELOPMENT - 65% SUBMITTAL REV 1 12/16/2022
ORDINARY HAZARD 2
Equipment Storage
TR
102A
G E N E R A L N O T E S :
A. PROVIDE COMPLETE AUTOMATIC WET PIPE FIRE PROTECTION SYSTEM IN RENOVATED
AREAS IN ACCORDANCE WITH NFPA 13 AND VA FIRE PROTECTION MANUAL. THE AREA
RENOVATED IS CURRENTLY PROTECTED WITH AUTOMATIC FIRE SPRINKLERS. MODIFY
SPRINKLER HEAD AND PIPING LOCATIONS AS NECESSARY.
B. INSTALL SPRINKLER SYSTEM OVER AND UNDER DUCTS, PIPING, AND PLATFORMS
WHEN SUCH EQUIPMENT CAN NEGATIVELY EFFECT OR DISRUPT THE SPRINKLER
DISCHARGE PATTERN AND COVERAGE.
C. FURNISH PIPING OFFSETS, FITTINGS, AND ANY OTHER ACCESSORIES AS REQUIRED
TO PROVIDE A COMPLETE INSTALLATION TO ELIMINATE INTERFERENCE WITH OTHER
CONSTRUCTION.
D. PIPE SIZES SHALL BE DETERMINED BY PIPE SCHEDULE METHOD BY CONTRACTOR.
E. COMPLETELY COORDINATE…