This document provides details on a federal contract opportunity for infrastructure upgrades at a Veterans Affairs medical center in Chillicothe, Ohio. The Department of Veterans Affairs Technology Acquisition Center Austin is soliciting proposals under solicitation number 36C77623B0058 for construction services to upgrade electrical and HVAC systems at the Chillicothe VA medical center. Proposals are due by July 15, 2021 and the contract is slated for award in September 2021. The opportunity involves replacing switchgear, upgrading electrical distribution systems, and modernizing HVAC equipment to improve the reliability and efficiency of infrastructure supporting healthcare facilities. The attached Appendix provides technical specifications and drawings related to the required electrical system upgrades.
View the file
Other files
Show 40 more
Latest 50 of 65 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N
N
CHILLICOTHE VA MEDICAL CENTER
PROJECT NUMBER: 538-21-701
DEPARTMENT OF VETERANS AFFAIRS
273 STATE ROUTE 104, CHILLICOTHE, OHIO 45601
EHRM INFRASTRUCTURE UPGRADES
SHEET NAMING EXAMPLE:
BUILDING NUMBER
DISCIPLINE
SHEET TYPE
FLOOR NUMBER
ZONE LOCATION ON FLOOR
100-AE101.1
G E N E R A L N O T E S
A. SEE GENERAL PROJECT NOTES FOR NEW WORK FOR ADDITIONAL REQUIREMENTS FOR WORK WITHIN THE
EXISTING FACILITY. THE CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND FIELD CONDITIONS
PRIOR TO DEMOLITION AND CONSTRUCTION. IF PROVIDED, THE GENERAL CONTRACTOR SHALL EXAMINE
EXISTING BUILDING DOCUMENTS. THE CONTRACTOR SHALL BRING ANY DISCREPANCIES TO THE
IMMEDIATE ATTENTION OF THE C.O.R. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF
EXISTING ITEMS TO REMAIN DURING DEMOLITION AND CONSTRUCTION. MAINTAIN EXIT EGRESS PATHS
TO EXISTING EXIT DOORS DURING CONSTRUCTION.
B. THE CONTRACTOR IS RESPONSIBLE FOR THE PROTECTION OF ALL CONSTRUCTION ROUTES BEYOND THE
AREAS OF WORK AND THE ROUTES MUST BE RETURNED TO THEIR ORIGINAL CONDITION AT THE END OF
THE PROJECT.
C. ALL DEMOLITION AND CONSTRUCTION ACTIVITIES SHALL BE COORDINATED WITH THE C.O.R. TO MINIMIZE
DISRUPTIONS OF NORMAL FUNCTIONS OF THE VA'S OCCUPIED AREAS.
D. IF CONSTRUCTION NOISE IS ANTICIPATED, SUBMIT A WRITTEN REQUEST TO THE C.O.R. FOR THE
SCHEDULED TIME OF THE CONSTRUCTION ACTIVITIES. NO WORK SHALL BE DONE WITHOUT THE WRITTEN
APPROVAL OF THE C.O.R. THE C.O.R. RESERVES THE RIGHT TO DISCONTINUE NOISY CONSTRUCTION AT
ANY TIME. NO RADIOS SHALL BE PERMITTED AT ANY TIME IN WORK AREAS ADJACENT TO OCCUPIED
SPACES.
E. ALL EXISTING SERVICES AND UTILITIES SHALL BE MAINTAINED TO AREAS THAT ARE IN OPERATION AND
SERVED BY THEM. COORDINATE ALL DISRUPTIONS OR DISCONTINUATIONS OF UTILITIES AND SERVICES
WITH C.O.R. NO SHUT DOWN OF EXISTING SERVICES IS ALLOWED TO OCCUR UNTIL RECEIVING THE
C.O.R.'S WRITTEN APPROVAL OF THE SHUT DOWN SCHEDULE. PROVIDE TEMPORARY SERVICES AND/OR
UTILITIES DURING INTERRUPTIONS AS REQUIRED AND APPROVED BY THE C.O.R.
F. THE CONTRACTOR SHALL TAKE ALL NECESSARY PRECAUTIONS TO PREVENT DAMAGE TO THE V.A.'S
AREAS ADJACENT TO NEW CONSTRUCTION OR AREAS WHERE VARIOUS SYSTEM CONNECTIONS OR
EXTENSIONS ARE REQUIRED. IN THESE AREAS, THE CONTRACTOR IS RESPONSIBLE FOR DAMAGE
CAUSED BY LACK OF SUFFICIENT PROTECTION FROM THE WEATHER AND FROM THE RESULTS OF ALL
CONSTRUCTION ACTIVITY INCLUDING BUT NOT LIMITED TO DUST AND WATER.
G. THE CONTRACTOR SHALL RECEIVE WRITTEN APPROVAL FROM THE C.O.R. BEFORE USING OPEN FLAMES, WELDING RODS AND TORCHES. THE CONTRACTOR IS RESPONSIBLE FOR ALL MEANS AND METHODS TO
PROHIBIT THE MIGRATION OF SMOKE AND OTHER PRODUCTS OF COMBUSTION INTO OCCUPIED AREAS OF
THE EXISTING BUILDING AND FOR OBTAINING ALL REQUIRED PERMITS RELATED TO HOT WORK.
H. DO NOT OVERLOAD THE EXISTING BUILDING STRUCTURE. MAINTAIN THE STRUCTURAL INTEGRITY OF ALL
STRUCTURAL FRAMING MEMBERS AND SYSTEMS AT ALL TIMES.
I. ALL DEMOLISHED MATERIAL, EXCEPT MATERIAL THAT IS LISTED OR MARKED FOR RETENTION, SHALL
BECOME THE PROPERTY OF THE CONTRACTOR AND IT SHALL BE DISPOSED OF. NO DEBRIS RESULTING
FROM WORK SHALL BE LEFT IN THE CONSTRUCTION ROUTES BEYOND THE AREAS OF WORK.
J. REMOVAL OF A PARTICULAR ITEM IS TO INCLUDE ALL RELATED ITEMS, SUCH AS REMOVAL OF WALLS
WOULD INCLUDE ASSOCIATED DOORS, HARDWARE, ELECTRICAL, PLUMBING, MECHANICAL, ETC. REFER
TO DEMOLITION DRAWINGS FOR MORE INFORMATION. FOR ALL REMOVALS, THE GENERAL CONTRACTOR
AND SUBCONTRACTORS SHALL COORDINATE WITH ALL OTHER DISCIPLINES.
K. THE CONTRACTOR SHALL PROVIDE TEMPORARY SUPPORT FOR ITEMS NOT DEMOLISHED OR REMOVED
AS REQUIRED UNTIL PERMANENT SUPPORT IS PROVIDED IN THE FINAL CONSTRUCTION.
L. ALL OPENINGS IN EXISTING WALLS, CEILINGS AND FLOORS, WHICH ARE THE RESULT OF REMOVALS AND
OTHER NEW CONSTRUCTION ACTIVITY, SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE
EXISTING MATERIALS OR AS NOTED ON DRAWINGS. IF THE PATCH IS TO BE MADE IN FIRE RATED
CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE PATCH SHALL BE FINISHED
TO A LIKE NEW CONDITION TO MATCH THE EXISTING FINISH.
M. ALL EXISTING OPENINGS IN CEILINGS, FLOORS AND WALLS DISCOVERED IN THE EXISTING STRUCTURE
SHALL BE PATCHED WITH NEW MATERIALS THAT MATCH THE EXISTING MATERIALS. IF THE PATCH IS TO
BE MADE IN FIRE RATED CONSTRUCTION, THE PATCH MUST ACHIEVE THE REQUIRED FIRE RATING. THE
PATCH SHALL BE FINISHED TO A LIKE NEW CONDITION TO MATCH THE EXISTING FINISH.
N. WHERE EXISTING SURFACES ARE TO BE REFINISHED OR ARE TO SERVE AS SUBSTRATE FOR THE
ATTACHMENT OR APPLICATION OF NEW MATERIALS OR CONSTRUCTION, PREPARE OR ALTER THE
EXISTING SURFACES AS NECESSARY TO PROPERLY ACCOMMODATE THE NEW MATERIALS.
O. FIELD VERIFY SIZES AND DIMENSIONS OF ALL EXISTING UTILITIES THAT IMPACT THE NEW WORK.
DETERMINE THE SIZE AND LOCATION THE PENETRATIONS FROM THE EXISTING UTILITIES WITHIN THE NEW
WORK. SEAL TIGHT TO ALL PENETRATIONS AND CAULK.
P. PENETRATIONS THROUGH EXISTING FIRE RATED CONSTRUCTION MUST BE PROPERLY CLOSED AND FIRE
SAFE'D TO ACHIEVE THE REQUIRED FIRE RATING BY THE END OF CONSTRUCTION OPERATIONS FOR EACH
DAY.
Q. NEW HOLES IN EXISTING ROOF STRUCTURES FOR NEW WORK MUST BE COORDINATED WITH THE
EXISTING STRUCTURE SO THAT CRITICAL STRUCTURAL MEMBERS ARE NOT DAMAGED.
R. UNLESS OTHERWISE NOTED, THE CONTRACTOR IS RESPONSIBLE FOR VERIFYING ALL EXISTING
SALVAGED STOCK BEFORE ORDERING NEW MATERIAL.
E X I S T I N G F A C I L I T I E S:
A. ALL WORK SHALL BE DONE IN ACCORDANCE WITH APPLICABLE LOCAL, STATE AND FEDERAL AUTHORITIES, CODES, RULES AND REGULATIONS.
B. THESE DOCUMENTS SHOW THE MINIMUM CONSTRUCTION REQUIREMENTS AND THE MINIMUM QUALITY OF
WORK EXPECTED. MORE STRINGENT REQUIREMENTS STIPULATED WITHIN RELEVANT MANUFACTURER’S
INSTALLATION INSTRUCTIONS WILL SUPERSEDE.
C. ANY UNFORESEEN OR UNCLEAR CONDITIONS SHALL BE REPORTED TO THE C.O.R. PRIOR TO PROCEEDING
WITH WORK.
D. ANY CONFLICTS WITHIN THE DRAWINGS, BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, OR
BETWEEN THE DRAWINGS AND THE ACTUAL CONDITIONS AT THE SITE, ARE TO BE BROUGHT TO THE
IMMEDIATE ATTENTION OF THE C.O.R. THE CONTRACTOR SHALL NOT PROCEED WITH WORK UNTIL
WRITTEN CLARIFICATION FROM THE ARCHITECT/ENGINEER IS RECEIVED.
E. UNLESS OTHERWISE NOTED, ALL MATERIALS AND EQUIPMENT SHALL BE INSTALLED PER THE APPLICABLE
PROVISIONS OF THESE DOCUMENTS AND THE MANUFACTURER’S INSTRUCTIONS.
F. ALL MATERIALS USED SHALL BE NEW UNLESS OTHERWISE NOTED AND/OR OF A QUALITY TO MEET OR
EXCEED ALL APPLICABLE INDUSTRY STANDARDS. WHERE SPECIFIED PRODUCTS OR MANUFACTURERS
ARE NOT NOTED, THE CONTRACTOR IS REQUIRED TO NOTIFY THE ARCHITECT TO OBTAIN A MINIMUM
STANDARD OF QUALITY.
G. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ALL MEANS, METHODS AND TECHNIQUES FOR
CONSTRUCTION.
H. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR JOB-SITE SAFETY INCLUDING THE ADHERENCE TO
OSHA REGULATIONS.
I. ALL ELECTRICAL AND MECHANICAL WORK SHALL BE PERFORMED BY PERSONNEL LICENSED IN THE STATE
WHERE THIS PROJECT IS LOCATED.
J. REMOVE ALL DEBRIS PROPERLY FROM THE SITE. LOAD DEBRIS DIRECTLY ONTO TRUCKS FOR REMOVAL.
DISPOSE OF DEBRIS LEGALLY. DO NOT BURN DEBRIS ON THE SITE. DO NOT ALLOW DEBRIS TO ENTER
SEWERS. DO NOT ALLOW PILED DEBRIS TO ENDANGER STRUCTURES, BLOCK EXISTS OR ROADWAYS.
COMBUSTIBLE WASTE WHICH COULD CREATE A FIRE HAZARD SHALL NOT BE PERMITTED TO ACCUMULATE
IN OR AROUND THE CONSTRUCTION SITE.
K. COORDINATE ALL WORK WITH ALL OTHER DISCIPLINES, INCLUDING, EXACT SIZE AND LOCATION OF ALL
ROOF AND FLOOR OPENINGS SHOWN ON ARCHITECTURAL DRAWINGS SHALL BE VERIFIED WITH THE
ASSOCIATED SUB-CONTRACTORS PRIOR TO CONSTRUCTION.
L. DO NOT SCALE DRAWINGS. DIMENSIONS SHALL GOVERN. ALL PLAN DIMENSIONS ARE TAKEN TO FINISH
FACE OF CONSTRUCTION.
M. ALL CONCEALED WOOD SHALL BE FIRE RETARDANT TREATED.
N. SEAL CONSTRUCTION TIGHT TO ALL PENETRATIONS AND APPLY SEALANT.
O. ALL PENETRATIONS THROUGH FIRE RATED CONSTRUCTION MUST BE FIRE SAFE'D IN ACCORDANCE WITH
THE SPECIFICATIONS. IF FLOOR OR RATED WALL PENETRATIONS CANNOT BE FIRESTOPPED AT THE END
OF THE WORK SHIFT DUE TO THE NEED TO PULL ADDITIONAL CABLES, TEMPORARY FIRESTOPPING
COMPOSED OF MINERAL WOOL SHOULD BE INSTALLED IN THE PENETRATION TO PROVIDE PROTECTION
AGAINST FIRE/SMOKE SPREAD THROUGH THE UNSEALED PENETRATION.
P. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING ALL EQUIPMENT INSTALLATION AND VERIFYING
ALL REQUIRED ROUGH OPENINGS, AND ROUGH-IN DIMENSIONS WITH THE EQUIPMENT MANUFACTURER, AND C.O.R. PRIOR TO CONSTRUCTION.
Q. REFER TO SHEET AE601 FOR SCHEDULES AND PARTITION TYPES.
N E W W O R K:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e V
A
E H
R M
/F F
E
C h ill ic o th e
E H
R M
C a m p u s rv t
/1
/2
:3
:1
P
M
GI000.9
COVER SHEET - VOL. 9
07/07/2023 PQ JF
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OHIO
BID DOCUMENTS - 100%
CAMPUS
CHILLICOTHE
VAMC
Approved: Veteran's Affairs Medical Center
No. Revisions: Date:
BID DOCUMENTS 07/07/2023
SHEET INDEX
ELECTRICAL
031-EP100 ELECTRICAL PLAN - GROUND FLOOR
031-EP101 ELECTRICAL PLAN - FIRST FLOOR
031-EP102 ELECTRICAL PLAN - SECOND FLOOR
035-EP100 ELECTRICAL PLAN - BASEMENT
035-EP101 ELECTRICAL PLAN - FIRST FLOOR
035-EP102 ELECTRICAL PLAN - SECOND FLOOR
035-EP103 ELECTRICAL PLAN - THIRD FLOOR
036-EP101 ELECTRICAL PLAN - FIRST FLOOR
060-EP101 ELECTRICAL PLAN - FIRST FLOOR
210-EP100 ELECTRICAL PLAN - BASEMENT
210-EP101 ELECTRICAL PLAN - FIRST FLOOR
210-EP102 ELECTRICAL PLAN - SECOND FLOOR
211-EP100 ELECTRICAL PLAN - BASEMENT
211-EP101 ELECTRICAL PLAN - FIRST FLOOR
211-EP102 ELECTRICAL PLAN - SECOND FLOOR
212-EP100 ELECTRICAL PLAN - BASEMENT FLOOR
212-EP101 ELECTRICAL PLAN - FIRST FLOOR
212-EP102 ELECTRICAL PLAN - SECOND FLOOR
247-EP101 ELECTRICAL PLAN - FIRST FLOOR
252-EP101 ELECTRICAL PLAN - FIRST FLOOR
259-EP102 ELECTRICAL PLAN - SECOND FLOOR
261-EP101 ELECTRICAL PLAN - FIRST FLOOR
EE500 ELECTRICAL DETAILS
E600.1 PANELBOARD SCHEDULES
E601.3 PANELBOARD SCHEDULES
E602.7 PANELBOARD SCHEDULES
E603.9 PANELBOARD SCHEDULES
E604.18 PANELBOARD SCHEDULES
E605.20 PANELBOARD SCHEDULES
E606.21 PANELBOARD SCHEDULES
E607.23 PANELBOARD SCHEDULES
E608.24 PANELBOARD SCHEDULES
E609.24 PANELBOARD SCHEDULES
E610.25 PANELBOARD SCHEDULES
E611.26 PANELBOARD SCHEDULES
E612.27 PANELBOARD SCHEDULES
E613.28 PANELBOARD SCHEDULES
E614.30 PANELBOARD SCHEDULES
E615.31 PANELBOARD SCHEDULES
E616.31 PANELBOARD SCHEDULES
E617.35 PANELBOARD SCHEDULES
E618.36 PANELBOARD SCHEDULES
E619.60 PANELBOARD SCHEDULES
E620.210 PANELBOARD SCHEDULES
E621.211 PANELBOARD SCHEDULES
E622.211 PANELBOARD SCHEDULES
E623.247 PANELBOARD SCHEDULES
E624.259 PANELBOARD SCHEDULES
E625.261 PANELBOARD SCHEDULES
E626.212 PANELBOARD SCHEDULES
VOLUME 9 OF 13
N.T.S.Scale:
CAMPUS MAP
N.T.S.Scale:
VICINITY MAP
SHEET INDEX
GENERAL
GI000.9 COVER SHEET - VOL. 9
UP
DN
UP
DN
UP
DN
DN
DN
DN
DN
UP
REF.
AP
AP
2D/1V 6D
AP
AP
AP
AP
AP
AP
M H
W
W
2D/1V
2D/1V
2D/1V
2D /1
V
2D/1V
6D
AP
2D/1V
AP
2D/1V
AP
2D/1V 2D/1V
2D/1V
2D/1V 2D/1V 2D/1V
2D/1V
2D/1V2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
AP
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
AP
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
AP
AP
2D/1V
2D/1V
AP
2D/1V
2D/1V 2D/1V
2D/1V
AP
AP
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D /1
V
2D/1V
AP
AP
2D/1V
2D/1V2D/1V
2D/1V2D/1VAP
AP
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
APAP 2D/1V
2D /1
V
AP
2D/1V
AP
2D/1V
1D
2D/1V 2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V 2D /1
V
2D/1V
AP
AP
2D/1V
2D/1V
2D/1V2D/1V
AP
AP
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V2D/1V
2D/1V
2D/1V
1V1V
2D/1V
2D /1
V
2D /1
V
1V 2D/1V 1V
2D/1V
2D/1V2D/1V
2D/1V
2D/1V 2D/1V
2D/1V2D/1V
2D/1V 2D/1V
AP
2D/1V
AP
2D/1V2D/1V 1V 1V
2D/1V
1V 1V
2D/1V
AP
AP
AP
AP
2D/1V2D/1V
1V 2D/1V
2D /1
V
2D/1V
AP
AP2D/1V
2D/1V
AP
2D/1V2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
AP
2D/1V
AP
1V
2D /1
V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
AP
2D /1
V
2D/1V
1V
2D/1V
2D/1V
2D/1V
AP
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
AP
AP
1D
AP
2D/1V 2D/1V
2D/1V
2D/1V
1V 1V
AP
2D/1V
2D/1V
2D/1V 2D/1V1V
1V2D/1V
2D/1V
AP
2D/1V
AP
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V AP
2D/1V
2D /1
V
2D/1V
1V
2D/1V
2D/1V
AP
2D/1V
2D/1V
AP
2D/1V
2D/1V
2D/1V 2D/1V2D/1V
2D/1V
2D/1V
2D/1V
1V
AP
AP
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
CC
CC
CC
CC
E M
E
E M
E
(E)
(E)
K
AP
CC
EM
T
2D/1V
2D/1V 2D/1V1V
2D/1V
CC
E M
E M
EM
EM
E M
E M
EM
RX
DCEL
K
K
EM (E)
EM (E)
EM (E) AP
CC
E M
E M
E M
EM
T
2D/1V
CCD
C
E S
R X
K
EM
E M
EM
E M
E M
E M
031-EP100
031-EP100
031-EP100
031-EP100
ELECT. ROOM
G-500C
TR
G-500D
MAIN ELECT. ROOM
242G
TR
G-328
ELECT ROOM
G-217B
TELE CLOS
G-217A
TR
G-202
ELECT. ROOM
G-147
TELE CLOSET
G-132
ELECT. ROOM
G-122
ELECT. ROOM
G160G
(E) (B31) GB
(E) GA
(E) GIS
(E) (B31) GCRA
(E) (B31) EPBB
(E) PBA
(E) EPBA
(E) RBA
(E) RBB(E) BX
(E) BX2
(E) BR
(E) EBN
(E) 1F(E) 1G
(E) (B31) BW SEC
ODU-2
ODU-1
ODU-1
(B31) 1CR1A - 6,8
(B31) 1CR1A - 7,9
(E) (B31) EPBB - 12,14
ODU-1
(E) (B31) GCRA - 24,26
C1 C1
IDU-2TR
G-500D
Elect. Room
G-500C
(E) (B31) GEQ2
(E) (B31) GC
(E) (B31) GD
(E) (B31) 31PDP1
(E) (B31) GEQ2 - 42,44,46 (E) (B31)
GEQ2-43(E) (B31)
GEQ2-43
ODU-2
(E) (B31) GEQ2 - 45,47
(E) (B31) GD - 21,23,25
C1
C1
C1
C1
CT Power Equipment
G-345G
(E) (B31)
GEQ2-43
(E) (B31)
GEQ2-43
(E) (B31)
GEQ2-43
(E) (B31)
GEQ2-43
(E) (B31) GEQ2 - 48,50,52
(E) (B31) GD - 22,24,26
(E) (B31) GEQ2 - 49
(E) (B31) GEQ2 - 49
(E) (B31) GEQ2 - 49
(E) (B31) GEQ2 - 49
(E) (B31) GEQ2 - 49(E) (B31) GEQ2 - 49
IDU-2 9
ODU-2
(E) (B31) GEQ2 - 51,53
C1
C1
(E) (B31) BW SEC 2 - 17,19,21 (E) (B31) EPBB - 2,4,6
IDU-2
ODU-2
(E) (B31) EPBB - 8,10
C1
C1
(E) (B31) GB (E) GA
(E) GIS (E) (B31) GCRA
(E) (B31) GB - 23,25,27
(E) (B31) GCRA - 29,31,33
(E) (B31) GCRA - 13 (E) (B31) GCRA - 13
(E) (B31) GCRA - 13
(E) (B31) GCRA - 13
(E) (B31) GCRA - 13
IDU-2
C1
C1
(E) (B31)
GCRA-15
(E) (B31)
GCRA-15
(E) (B31)
GCRA-15
(E) (B31)
GCRA-15
11 11
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:3
P
M
031-EP100
ELECTRICAL PLAN - GROUND
FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/16" = 1'-0"
BLDG 31 - OVERALL GROUND - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG - TR G500D - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 31 - TR G345G - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG - TR G202 / G204 - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG - TR G182B - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
2 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
3 CIRCUIT TO EXISTING EMERGENCY RECEPTACLE CIRCUIT IN THIS ROOM.
4 CIRCUIT NEW TR LIGHTING FIXTURES TO LOCAL LIGHTING CIRCUIT MAINTAINED DURING DEMOLITION.
5 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
6 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.
7 INSTALL NEW 8 DOOR SYMMETRY PACS PANEL CONTROLLER AND POWER SUPPLY.
8 CIRCUIT INDOOR UNIT TO ASSOCIATED CONDENSING UNIT LOCATED OUTSIDE, BEYOND OUTSIDE WALL OF BUILDING ON
GROUND LEVEL.
9 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
10 INSTALL NEW 120V 30A HEAVY DUTY NON-FUSED DISCONNECT AND FEED (2)#12, #12 GROUND, 3/4"C TO SPLIT SYSTEM
UNIT MOTOR.
11 CIRCUIT TO LOCAL RECEPTACLE CIRCUIT IN THIS ROOM.
No. Revisions: Date:
BID DOCUMENTS 07/07/2023
EM
EM
KF
AP
3D 1D
2D /1
V
3D 3D
CC
E M
E M
EM
EM
T
CC
D C
E S
R X
E M
EM
E M
K
EM
E M
E M
E M
031-EP101
031-EP101
(E) 1A
(E) E1A
(E) (B31) 1E
(E) (B31) R1A
C1
C1
(E) (B31) EPBB - 9,11,13
C1 C1
TR
F204
(E) (B31) 1A
(E) (B31) 1A - 19,21,23
(B31) 1CR1A
(B31) 1CR1A - 2 (B31) 1CR1A - 2
(B31) 1CR1A - 2(B31) 1CR1A - 2
(B31) 1CR1A - 2
(B31) 1CR1A - 1,3,5
(B31) 1CR1A - 4
(E) BUSBAR
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:4
P
M
031-EP101
ELECTRICAL PLAN - FIRST FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/16" = 1'-0"
BLDG 31 - OVERALL FIRST FLOOR - ELECTRICAL DEMOLITION PLAN
1/4" = 1'-0"
BLDG 31 - TR 1-210 - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 31 - TR 1-129 - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT NEW TR LIGHTING FIXTURES TO LOCAL LIGHTING CIRCUIT MAINTAINED DURING DEMOLITION.
2 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
3 PROVIDE (2) L21-30R RECEPTACLES. MOUNT ON TOP OF NEW DATA RACK.
4 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
5 INSTALL NEW 8 DOOR SYMMETRY PACS PANEL CONTROLLER AND POWER SUPPLY.
6 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.
7 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
2D/1V
46" MH
2D/1V
2D/1V
1V
1V
2D /1
V
CC
E M
E M
E M
EM
EM
E M
K
ES
DC
RX
E M
T
031-EP102
(E) (B31) 2W
(E) (B31) E2W (E) (B31) 2E SEC 2
5 6
C1 C1
C1C1
TR-1
2-207A-1
(E) (B31) 2E SEC 2 - 36,38,40
IDU-1
IDU-1
(B31) 1CR1A - 10,12,14
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:5
P
M
031-EP102
ELECTRICAL PLAN - SECOND
FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/8" = 1'-0"
BLDG 31 - OVERALL SECOND FLOOR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 31 - TR 2-207A - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT NEW TR LIGHTING FIXTURES TO LOCAL LIGHTING CIRCUIT MAINTAINED DURING DEMOLITION.
2 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
3 PROVIDE (2) L21-30R RECEPTACLES. MOUNT ON TOP OF NEW DATA RACK.
4 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
5 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.
6 INSTALL NEW 8 DOOR SYMMETRY PACS PANEL CONTROLLER AND POWER SUPPLY.
7 CIRCUIT INDOOR UNIT TO ASSOCIATED CONDENSING UNIT LOCATED OUTSIDE, BEYOND OUTSIDE WALL OF BUILDING ON
GROUND LEVEL.
AP
AP
1D 3D 2D/1V3D 3D
2D/1V
2D/1V
1D
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V2D/1V
AP
3D3D
3D2D/1V3D
3D
2D/1V
2D/1V 3D
3D
3D
2D/1V
3D 3D2D/1V 3D
AP
AP
AP
AP
AP
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
W
2D/1V
2D/1V
2D/1V
2D/1V 2V
AP
AP
AP
AP
W 2D/1V
W
3D 3D
3D
3D 3D 3D
2D/1V 2D/1V
AP
AP
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V2D/1V
2D/1V
AP
AP
AP
3D3D3D3D
2D /1
V 2D
/1 V
2D /1
V
2D /1
V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
3D
3D
2D/1V
CC
EM (E)
E M
E M
CC
E M
E M
E M
K
ESDC
RX
035-EP100
(E) (B35) NB (E) (B35) ENB
ODU-2 ODU-2 ODU-2
(B35) E1N-2 - 19,21
(B35) E1N-2 - 20,22
(B35) E1N-2 - 23,25
C1
C1
C1
(B35) 1N-2 - 2,4,6 (B35) E1N-2 - 12,14,16
IDU-2 5
(B35) E1N-2 - 15,17
(B35) E1N-2-18
(B35) E1N-2-18
(B35) E1N-2-18
ODU-2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:0
P
M
035-EP100
ELECTRICAL PLAN - BASEMENT
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
3/32" = 1'-0"
BLDG 35 - OVERALL BASEMENT - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 35 - TR BC102 - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT TO EXISTING EMERGENCY RECEPTACLE CIRCUIT IN THIS ROOM.
2 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
3 INSTALL NEW 120V 30A HEAVY DUTY NON-FUSED DISCONNECT AND FEED (2)#12, #12 GROUND, 3/4"C TO SPLIT SYSTEM
UNIT MOTOR.
4 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.
5 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
D W
EM
EM
2D/1V
CC
K
E M
EM
E M
035-EP101
C1
C1
(B35) E1N-2
TR
1A109
(B35) E1N-2 - 1,3,5(B35) 1N-2 - 1,3,5
(B35) 1N-2
(B35) E1N-2-10
(B35) E1N-2-10 IDU-2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:0
P
M
035-EP101
ELECTRICAL PLAN - FIRST FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
3/32" = 1'-0"
BLDG 35 - OVERALL FIRST FLOOR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 35 - TR 1A109 - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT TO EXISTING EMERGENCY RECEPTACLE CIRCUIT IN THIS ROOM.
2 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
3 CIRCUIT INDOOR UNIT TO ASSOCIATED CONDENSING UNIT LOCATED OUTSIDE, BEYOND OUTSIDE WALL OF BUILDING ON
GROUND LEVEL.
D W
R E
F
EM
2D/1V
2D/1V
K
E M
EM
E M E
M
035-EP102
C1
C1
(B35) E1N-2 - 7
(B35) E1N-2 - 7
(B35) E1N-2 - 7
(B35) E1N-2 - 2,4,6(B35) 1N-2 - 7,9,11
IDU-2
(B35) E1N-2-10
(B35) E1N-2-10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:1
P
M
035-EP102
ELECTRICAL PLAN - SECOND
FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
3/32" = 1'-0"
BLDG 35 - OVERALL SECOND FLOOR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 35 - TR 2A109 - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
2 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
3 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
EM
CC
K
E M
EM
EM
E M
E M
035-EP103
C1
C1
(B35) E1N-2 - 8
(B35) E1N-2 - 8
(B35) E1N-2 - 8
(B35) E1N-2 - 8
(B35) E1N-2 - 9,11,13(B35) 1N-2 - 8,10,12
IDU-2
TR
3A109
(B35) E1N-2-10
(B35) E1N-2-10
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:2
P
M
035-EP103
ELECTRICAL PLAN - THIRD FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
3/32" = 1'-0"
BLDG 35 - OVERALL THIRD FLOOR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 35 - TR 3A109 - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
2 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
3 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
036-EP101
(E) (B36) LP
(E) (B36) LP - 37
(E) (B36) LP - 37
(E) (B36) LP - 39
(E) (B36) LP - 41
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:3
P
M
036-EP101
ELECTRICAL PLAN - FIRST FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/8" = 1'-0"
BLDG 36 - TR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 36 - TR B36B - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
2 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
3 PROVIDE (2) 120V-30A (L5-30) RECEPTACLES MOUNTED ON WALL BEHIND TE.
(E)
46"
(E) (B60) EB
(E) (B60) EB - 28
(E) (B60) EB - 28
2 (E) (B60) EB - 30
(E) (B60) EB - 31
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:3
P
M
060-EP101
ELECTRICAL PLAN - FIRST FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/4" = 1'-0"
BLDG 60 - OVERALL FIRST FLOOR - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
2 PROVIDE (2) 120V-30A (L5-30) RECEPTACLES MOUNTED ON WALL BEHIND TE.
S C
S C
S C
S C
2D/1V
2D/1V
2D/1V 2D /1
V
2D /1
V
AP
AP
2D/1V
2D/1V
AP
AP
2D/1V
2D /1
V
2D/1V
2D/1V
AP
1D
AP
AP
AP
AP
AP
1D
2D/1V
APAP
AP
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
AP
AP
AP
AP
AP
AP
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
AP
AP
46" MH2D/1V
2D/1V
2D/1V 2D/1V 2D/1V
2D/1V
2D/1V
AP AP
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
AP
AP
AP
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V2D/1V
2D/1V2D/1V
AP
AP
AP
CC
E M
E M
CC
K
ES
RX
DC
E M
EM
E M
EM
EM
210-EP100
(E) (B210) NGB
(E)(B210) 210
EDP1
(E) LSG
(E) (B210) EGB
ODU-2 ODU-2
ODU-1 ODU-1
(E) (B210) EGB - 18,20
(E) (B210) EGB - 29,31
(E) (B210) EGB - 33,35
(E) (B210) EGB - 34,36
(E) (B210) EGB - 37,39 (E) (B210) EGB - 38,40
C1
C1
(E) (B210) EGB - 25
(E) (B210) EGB - 25
(E) (B210) EGB - 25
(E) (B210) EGB - 25
(E) (B210) EGB - 28,30,32
(E) (B210) NGB - 38,40,42
TR
G023
IDU-1
IDU-1
(E) (B210)
EGB-27
(E) (B210)
EGB-27
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:4
P
M
210-EP100
ELECTRICAL PLAN - BASEMENT
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
3/32" = 1'-0"
BLDG 210 - OVERALL BASEMENT - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 210 - TR G023 - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
2 PROVIDE (2) L21-30R RECEPTACLES. MOUNT ON TOP OF NEW DATA RACK.
3 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
4 INSTALL NEW 120V 30A HEAVY DUTY NON-FUSED DISCONNECT AND FEED (2)#12, #12 GROUND, 3/4"C TO SPLIT SYSTEM
UNIT MOTOR.
5 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
CC
K
DC
RX
ES
E M
E M
EM
E M
EM
EM
EM
210-EP101
(E) (B210) E1A
(E) N1A
(E) N1B
(E) (B210) E1B
(E) N1G
(E) (B210) N1D
(E) N1C
(E) LS1
C1
C1
(E) (B210) E1B - 23
(E) (B210) E1B - 23
(E) (B210) E1B - 23
(E) (B210) E1B - 23
(E) (B210) E1B - 23
(E) (B210) E1B - 35,37,39
(E) (B210) E1B - 23
(E) (B210) N1D - 22,24,26
IDU-2 7
(E) (B210) E1B-24
(E) (B210) E1B-24
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:0
P
M
210-EP101
ELECTRICAL PLAN - FIRST FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
3/32" = 1'-0"
BLDG 210 - OVERALL FIRST FLOOR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 210 - TR 102B - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT NEW TR LIGHTING FIXTURES TO LOCAL LIGHTING CIRCUIT MAINTAINED DURING DEMOLITION.
2 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
3 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
4 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
5 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.
6 INSTALL NEW 8 DOOR SYMMETRY PACS PANEL CONTROLLER AND POWER SUPPLY.
7 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
CC
DCES
RX
K
EM
EM
E M
EM
E M
EM
OS
210-EP102
(E) (B210) E2B
(E) 210-N2D
(E) (B210) N2G (E) N2C
C1
C1
(E) (B210) E2B - 23
(E) (B210) E2B - 23
(E) (B210) E2B - 32,34,36
(E) (B210) E2B - 23
(E) (B210) E2B - 23
(E) (B210) E2B - 23
(E) (B210) N2G - 7,9,11
IDU-2 6
(E) (B210) E2B-26
(E) (B210) E2B-26
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:1
P
M
210-EP102
ELECTRICAL PLAN - SECOND
FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
3/32" = 1'-0"
BLDG 210 - OVERALL SECOND FLOOR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 210 - TR 202B - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
2 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
3 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
4 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.
5 INSTALL NEW 8 DOOR SYMMETRY PACS PANEL CONTROLLER AND POWER SUPPLY.
6 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
1V 1V
1V 1V
1V 1V
1V 1V
1V 1V
2D/1V
2D/1V
2D/1V2D/1V 2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
1D
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
W W
2D/1V
2D/1V
W
46" MH2D/1V
46" MH
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V 2D/1V
2D/1V
2D/1V2D/1V
2D/1V
W
1D
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V2D/1V
2D/1V
2D/1V
2D/1V
2D/1V 2D/1V 2D/1V
2D/1V 2D/1V
2D/1V 2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
1V
46"
2D/1V
2D/1V
E M
K
E M
EM
EM
E M
K
(E)
E M
(E
EM
E M
EM
211-EP100
211-EP100
ODU-2
ODU-2
ODU-2
ODU-2
ODU-1 ODU-1 ODU-2
Elect. Room
G009
Mechanical
G028
(E) (B211) EGB
(E) (B211) EGB - 27,29
(E) (B211) EGB - 31,33
(E) (B211) EGB - 32,34
(E) (B211) EGB - 35,37
(E) (B211) E1A - 33,35
(E) (B211) E1A - 34,36
(E) (B211) E1D - 33,35
(E) (B211) NGB
C1
C1
(E) SYMMETRY
PACS
CONTROLLER
(E) (B211) EGB - 36,38,40
(E) (B211) NGB - 31,33,35
IDU-2 8
C1
C1
IDU-2
(E) (B211) EGB - 17,19,21 (E) (B211) NGB - 25,27,29
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:3
P
M
211-EP100
ELECTRICAL PLAN - BASEMENT
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
3/32" = 1'-0"
BLDG 211 - OVERALL BASEMENT - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 211 - TR G007 - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 211 - TR G018 - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
2 CIRCUIT NEW TR LIGHTING FIXTURES TO LOCAL LIGHTING CIRCUIT MAINTAINED DURING DEMOLITION.
3 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
4 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
5 CIRCUIT TO EXISTING EMERGENCY RECEPTACLE CIRCUIT IN THIS ROOM.
6 PROVIDE (2) L21-30R RECEPTACLES. MOUNT ON TOP OF NEW DATA RACK.
7 INSTALL NEW 120V 30A HEAVY DUTY NON-FUSED DISCONNECT AND FEED (2)#12, #12 GROUND, 3/4"C TO SPLIT SYSTEM
UNIT MOTOR.
8 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
E M
EM K
DC
RX
ES
E M
E M
EM
T
F
AP
46" MH2D/1VW
RX
K
DCES
EM
EM
E M
EM
EM
F
211-EP101
211-EP101
(E) (B211) E1A
(E) N1A
(E) N1B
(E) 211-N1H
(E) (B211) N1G
(E) (B211) E1D
(E) (B211) N1C
(B211) N1D
(E) (B211) E1B
C1
C1
(E) (B211) E1D - 25
(E) (B211) E1D - 25
(E) (B211) E1D - 25
(E) (B211) E1D - 25
(E) (B211) E1D - 38,40,42
(E) (B211) N1G - 46,48,50
3 5
(E) (B211) E1D - 25
(E) (B211) E1B-21
(E) (B211) E1B-21
2 3
(E) (B211) E1B - 19
(E) (B211) E1B - 19 (E) (B211) E1B - 19
(E) (B211) E1B - 19
(E) (B211) E1B - 20,22,24
(E) (B211) N1C - 43,45,47
C1
C1
IDU-2
(E) (B211) E1B-21
(E) (B211) E1B-21
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:5
P
M
211-EP101
ELECTRICAL PLAN - FIRST FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
3/32" = 1'-0"
BLDG 211 - OVERALL FIRST FLOOR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 211 - TR 189B - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 211 - TR 108B - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
2 PROVIDE (2) L21-30R RECEPTACLES. MOUNT ON TOP OF NEW DATA RACK.
3 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
4 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.
5 INSTALL NEW 8 DOOR SYMMETRY PACS PANEL CONTROLLER AND POWER SUPPLY.
6 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
EM
E M
E M
K
DC
ES
RX
E M
T
1V
EM
EM
E M
E M
K
DC ES
RX
EM
EM
F
211-EP102
211-EP102
(E) E2A
(E) N2A
(E) N2B
(E) 211-N2H
(E) 211-N2G
(E) (B211) E2D
(E) 211-LS2
(E) 211-N2D
(E) (B211) N2C
(E) (B211) E2B
12 34
C1 C1
(E) (B211) E2B - 20
(E) (B211) E2B - 20
(E) (B211) E2B - 20
(E) (B211) E2B - 37,39,41
(E) (B211) N2C - 43,45,47
(E) (B211) E2B - 20
(E) (B211) E2B - 20
(E) (B211) E2B-22
(E) (B211) E2B-22
IDU-2
C1
C1
(E) (B211) E2B - 21
(E) (B211) E2B - 21
(E) (B211) E2B - 21
(E) (B211) E2B - 21
(E) (B211) E2B - 21
(E) (B211) E2B - 38,40,42(E) (B211) N2C - 37,39,41
IDU-2
(E) (B211) E2B-22
(E) (B211) E2B-22
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:1
P
M
211-EP102
ELECTRICAL PLAN - SECOND
FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
3/32" = 1'-0"
BLDG 211 - OVERALL SECOND FLOOR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 211 - TR 289B - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 211 - TR 208B - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
2 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
3 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.
4 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
5 INSTALL NEW 8 DOOR SYMMETRY PACS PANEL CONTROLLER AND POWER SUPPLY.
6 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
(E
(E)
2D/1V
W
CC
E M
EM
E M
EM
K
DC
ES
RX
E M
212-EP100
(E) 212-E
SYMMETRY PACS
CONTROLLER
C1 C1TR
15A
ODU-2 ODU-2
(E) (B212) EM-2 - 13,15,17
(E) (B212) C - 38,40,42
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:2
P
M
212-EP100
ELECTRICAL PLAN - BASEMENT
FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/8" = 1'-0"
BLDG 212 - OVERALL BASEMENT - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 212 - TR 15A - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
2 INSTALL NEW 120V 30A HEAVY DUTY NON-FUSED DISCONNECT AND FEED (2)#12, #12 GROUND, 3/4"C TO SPLIT SYSTEM
UNIT MOTOR.
3 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.
4 CIRCUIT TO EXISTING EMERGENCY RECEPTACLE CIRCUIT IN THIS ROOM.
5 INSTALL NEW 8 DOOR SYMMETRY PACS PANEL CONTROLLER AND POWER SUPPLY.
6 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
7 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
REF.
CC
EM
E M
E M
E
ME
M
212-EP101
(E) (B212) E
(E) (B212) EQ
(E) (B212) EM-2
(E) (B212) B
C1 C1
IDU-2
(E) (B212) EM-2 - 7,9,11
(E) (B212) E - 3,5,7
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:2
P
M
212-EP101
ELECTRICAL PLAN - FIRST FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/8" = 1'-0"
BLDG 212 - OVERALL FIRST FLOOR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 212 - TR 125 - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 PROVIDE (2) L21-30R RECEPTACLES. MOUNT ON TOP OF NEW DATA RACK.
2 CIRCUIT NEW RECEPTACLES TO EMERGENCY PANEL.
3 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
EM
EM
E M
CR
CC
212-EP102
(E) (B212) F
(E) (B212) C
C1
C1
(E)
(E) BUSBAR
IDU-2
(E) (B212) EM-2 - 8,10,12(E) (B212) F - 38,40,42
STAIRS STAIRS
TR LOCATION
KEY PLAN
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:3
P
M
212-EP102
ELECTRICAL PLAN - SECOND
FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/8" = 1'-0"
BLDG 212 - OVERALL SECOND FLOOR - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
2 CIRCUIT NEW TR LIGHTING FIXTURES TO LOCAL LIGHTING CIRCUIT MAINTAINED DURING DEMOLITION.
3 CIRCUIT INDOOR UNIT TO ASSOCIATED CONDENSING UNIT LOCATED OUTSIDE, BEYOND OUTSIDE WALL OF BUILDING ON
GROUND LEVEL.
4 CIRCUIT TO EXISTING EMERGENCY RECEPTACLE CIRCUIT IN THIS ROOM.
1/4" = 1'-0"
BLDG 212 - TR 225 - NEW WORK PLAN
D W
CC
(E)
OS
46"
46"
247-EP101
(E) (B247) L1
(E) L2
(E) (B247) L1
(E) (B247) L1 - 28 (E) (B247) L1 - 28
2(E) (B247) L1 - 27
(E) (B247) L3 - 35
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:4
P
M
247-EP101
ELECTRICAL PLAN - FIRST FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/8" = 1'-0"
BLDG 247 - TR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 247 - TR 109 - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
2 PROVIDE (2) 120V-30A (L5-30) RECEPTACLES MOUNTED ON WALL BEHIND TE.
AP
AP
AP
2D/1V
2D/1V 2D/1V
2D/1V 3D/1V
2D/1V
2D/1V
AP
2D/1V
CC
46"
(E)
(E) (B252) B (E) (B252) A
(E) (B252) B - 5(E) (B252) B - 5
(E) (B252) B - 6
(E) (B252) B - 7
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:4
P
M
252-EP101
ELECTRICAL PLAN - FIRST FLOOR
07/07/2023 JB IA
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/4" = 1'-0"
BLDG 252 - OVERALL FIRST FLOOR - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
2 PROVIDE (2) 120V-30A (L5-30) RECEPTACLES MOUNTED ON WALL BEHIND TE.
2D/1V 2D/1V
2D/1V
AP
2D/1V
2D/1V
46" MH2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
2D/1V
AP
AP
CC
E M
EM
R X
D C
E S
K
E M
AP
46" MH2D/1V 2D/1V
2D/1V
SYMMETRY PACS
CONTROLLER
C1 C1
(E) (B259) B - 5,7,9
(E) (B259) B - 11,13,15
IDU-2
(E) (B259) B
(E) 45 XFMR
(E) 45 XFMR
(E) A(E) P(E) H
ODU-2
(E) (B259) B - 2,4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:5
P
M
259-EP102
ELECTRICAL PLAN - SECOND
FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/4" = 1'-0"
BLDG 259 - OVERALL SECOND FLOOR - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 INSTALL NEW KEY PAD / CARD READER, DOOR CONTACT, ELECTRIC STRIKE, AND MOTION SENSOR TO DOOR.
2 INSTALL NEW 120V 30A HEAVY DUTY NON-FUSED DISCONNECT AND FEED (2)#12, #12 GROUND, 3/4"C TO SPLIT SYSTEM
UNIT MOTOR.
3 INSTALL NEW 8 DOOR SYMMETRY PACS PANEL CONTROLLER AND POWER SUPPLY.
4 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
5 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
6 CIRCUIT NEW TR LIGHTING FIXTURES TO LOCAL LIGHTING CIRCUIT MAINTAINED DURING DEMOLITION.
7 CIRCUIT INDOOR CASSETTE UNIT TO OUTDOOR CONDENSER. PROVIDE DISCONNECT SWITCH MOUNTED UP HIGH NEXT
TO CASSETTE UNIT.
8 CIRCUIT TO LOCAL EMERGENCY RECEPTACLE CIRCUIT
1/8" = 1'-0"
BLDG 259 - OVERALL FIRST FLOOR - ELECTRICAL NEW WORK PLAN
No. Revisions: Date:
BID DOCUMENTS 07/07/2023
1/8" = 1'-0"
BLDG 259 - OVERALL ROOF PLAN - ELECTRICAL NEW WORK PLAN
UP
AP
22D/1V
2D/1V
AP
2V
1V1D/1V
CC
2D/1V
CC
OS
(E)
(E)
(E)
(E)
K
RX
ESDC
E M
E M
261-EP101
(E) (B261) 20:1
208 VOLT (E) (B261) 48:1
480 VOLT
ODU-2
(E) (B261) 20:1 208 VOLT - 2,4
20:3 208 VOLT
(E) SYMMETRY
PACS
CONTROLLER
(E) PACS POWER
SUPPLY
(E) PACS POWER
SUPPLY
(E) SYMMETRY
PACS
CONTROLLER
GROUNDING BUS
BAR
(E) (B261) 20:1 208 VOLT - 5,7,9
C2
C2
IDU-2
(E) (B261) 20:1 208 VOLT - 11,13,15
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
A u to d e s k D o c s /C h ill ic o th e
V A
E
H R
M /F
F E
C h ill ic o th e
E H
R M
M
E P rv t
/9 /2
:4
:0
P
M
261-EP101
ELECTRICAL PLAN - FIRST FLOOR
07/07/2023 JB CLG
EHRM INFRASTRUCTURE
UPGRADES
538-21-701
CHILLICOTHE, OH
BID DOCUMENTS
CHILLICOTHE
VAMC
Approved: Owner
1/8" = 1'-0"
BLDG 261 - OVERALL FIRST FLOOR - ELECTRICAL NEW WORK PLAN
1/4" = 1'-0"
BLDG 261 - TR 103 - ELECTRICAL NEW WORK PLAN
D R A W I N G N O T E S :
1 CIRCUIT NEW TR LIGHTING FIXTURES TO LOCAL LIGHTING CIRCUIT MAINTAINED DURING DEMOLITION.
2 INSTALL NEW BUSBAR GROUNDING ELECTRODE. (TGB) THE BONDING CONDUCTOR SHALL BE COPPER, STRANDED OR SOLID IN CONDUIT AND SHALL BE RUN IN AS STRAIGHT A LINE AS PRACTICABLE. (1/0 CU). THE BONDING CONDUCTOR SHALL BE CONNECTED TO THE INTERSYSTEM BONDING TERMINATION. (1/0 CU). IF NO INTERSYSTEM BONDING TERMINATION EXISTS, CONNECT TO THE GROUNDED INTERIOR METAL WATER PIPING SYSTEM, WITHIN 1.5 M (5 FT) FROM
ITS POINT OF ENTRANCE TO THE BUILDING.
3 CIRCUIT TO EXISTING EMERGENCY RECEPTACLE CIRCUIT IN THIS ROOM.
4 PROVIDE (2) L21-20R RECEPTACLES. MOUNT ABOVE DATA RACK ON SIDE OF CABLE TRAY.
5 CIRCUIT INDOOR…