Traction Power Substation Rehabilitation Program – Contract 5 Broad, Loudon, Park and Castor Substations Project
Solicitation number
RFP 26-00105-AJEB
Issued by
Philadelphia County, Philadelphia City, Pennsylvania

About this file

This is Addendum No. 7 to SEPTA's Sealed Bid No. 26-00105-AJEB for the Traction Power Substation Rehabilitation Program – Contract 5 covering Broad, Loudon, Park, and Castor Substations, issued August 5, 2026. The addendum maintains the proposal due date of August 12, 2026 by 11:00 AM and must be acknowledged on the Addendum Acknowledgement Sheet to avoid rejection of proposals. Key specification changes include removal of the Wayside Energy Storage Systems at Loudon and Park substations from contractor scope, as SEPTA will complete this work directly. Updated drawings are provided including revised DWG 7E-16563_28 and revised markups for Loudon substation 50% design documents. The addendum incorporates 32 questions and answers addressing specifications, drawings, contract terms, and technical requirements across electrical, communications, civil, structural, and safety disciplines.

Significant contractual modifications include removal of the 25% rolling withholding clause while maintaining standard 10% retainage, acceptance of mutual waiver of consequential damages except for gross negligence or willful misconduct, and addition of new Section XXXVI addressing tariff-related cost adjustments through good-faith negotiation. The addendum clarifies that Castor substation work can proceed independently of the other three substations, confirms SCADA server replacement at 1234 Market Street is not in contractor scope, establishes fiber optic installation limits at the first communications manhole with SEPTA completing connections beyond that point, and confirms ground grid work applies primarily to Castor substation with perimeter fencing connections. Minimum daily PPE requirements are specified as FR clothing rated minimum 8 Cal/Cat 2, FR safety vest, hard hat, safety glasses, and EH-rated work boots for all personnel in substation work zones. Approved DC breaker manufacturers are clarified to include Myers, NDC/Brush (supplied by Powell), and Balfour Beatty TPG (formerly IMPULSE). The addendum confirms that one rectifier transformer must remain operational during construction, the 4.8kV switchgear can be taken out of service with one auxiliary transformer remaining, and existing generators can be removed without temporary power provisions.

View the file

Other files

File Type Posted
Addendum-10-Contract-5-Substations-Step-1-8-25-26.pdf PDF
Addendum-9-Contract-5-Substations-Step-1-8-20-26.pdf PDF
Addendum-8-Contract-5-Substations-Step-1-8-10-26.pdf PDF
Addendum-7-DWG-7E-16563_28_color_a.pdf PDF
Addendum-7-REV1-Markups-11x17_SEPTA_CONTRACT-5_50_LOUDON.pdf PDF
Addendum-6-Contract-5-Substations-Step-1-7-6-26.pdf PDF
Managing-Asbestos-In-Place-Addendum-5.pdf PDF
SEPTA-Environmental-Report-combined-Addendum-5.pdf PDF
Broad-Roof-Replacement-100-DWG_Set-Addendum-5.pdf PDF
Management-of-Lead-Paint-in-SEPTA-Construction-Projects-Document-3001-Addendum-5.pdf PDF
Orange-Blue-Green-line-emerg.-lght-single-line-diag.-Addendum-5.pdf PDF
Park-Peco-Info-Addendum-5.pdf PDF
Market-PECO-fault-duty-letters-dc-TPSS-Addendum-5.pdf PDF
Broad-Peco-Info-Addendum-5.pdf PDF
Tentative-Layout-of-WESS-Equipment-in-Park-TPSS_22-Jan-2018-Addendum-5.pdf PDF
Loudon-WESS-Details-REV3_signed-171108-Addendum-5.pdf PDF
PECO-fault-duty-letters-dc-TPSS-Addendum-5.pdf PDF
Addendum-5-Contract-5-Substations-Step-1-6-25-26.pdf PDF
SEPTA-Station-20-Sansom-Points-List-Addendum-5.pdf PDF
3004-ACM-Handling-Program-2023-Addendum-5.pdf PDF
DWG-7E-16563_28_color_a-Addendum-5.pdf PDF
Pre-Qualification-Meeting_-RFQ_-26-00105-AJEB-Substation-attendance-report-6-10-26.pdf PDF
Addendum-3-Contract-5-Substations-Step-1-6-10-26.pdf PDF
SIte-Visit-Attendance-Meeting-Power-Substation-Contract-5-6-11-26.pdf PDF
Addendum-4-Contract-5-Substations-Step-1-6-15-26.pdf PDF
Site-Visit-Attendance-Meeting-Substation-Contract-5-6-12-26.pdf PDF
Addendum-2-Contract-5-Substations-Step-1-6-4-26.pdf PDF
22x34-Loudon-Contract-5-Drawings-Addendum-3.pdf PDF
22x34-Broad-Street-Contract-5-Drawings-Addendum-3.pdf PDF
Attachment-2-11x17_SEPTA_CONTRACT-5_MARKET_50_BROAD-PARK-LOUDON-CASTOR-DRAWINGS-SET-3.pdf PDF
22x34-Castor-Contract-5-Drawings-Addendum-3.pdf PDF
Attachment-2-11x17_SEPTA_CONTRACT-5_MARKET_50_BROAD-PARK-LOUDON-CASTOR-DRAWINGS-SET-2.pdf PDF
Attachment-2-11x17_SEPTA_CONTRACT-5_MARKET_50_BROAD-PARK-LOUDON-CASTOR-DRAWINGS-SET-1.pdf PDF
22x34-General-Notes-Contract-5-Drawings-Addendum-3.pdf PDF
Addendum-1-Contract-5-Substations-Step-1-6-3-26.pdf PDF
22x34-Park-Contract-5-Drawings-Addendum-3.pdf PDF
JAL192590415-Substation-Rehab-Contract-5-Step-1.pdf PDF
ATTACHMENT-3-Form-330.pdf PDF
ATTACHMENT-2-SEPTA_CONTRACT-5_MARKET_50_BROAD-PARK-LOUDON-CASTOR-Drawings-SET-3.pdf PDF
JAL192590415-Invitation-to-Propose-2-Step-Process-Traction-Substation.pdf PDF
ATTACHMENT-4-Addendum-Acknowledgement-1.pdf PDF
ATTACHMENT-2-SEPTA_CONTRACT-5_MARKET_50_BROAD-PARK-LOUDON-CASTOR-Drawings-SET-1.pdf PDF
ATTACHMENT-1-SEPTA-Contract-5-Substations-50-Specifications.pdf PDF
Exhibit-FEDERAL-CONSTRUCTION-CONTRACT-STEP-2-CONTRACT-5-SUBSTATIONS.pdf PDF
ATTACHMENT-2-SEPTA_CONTRACT-5_MARKET_50_BROAD-PARK-LOUDON-CASTOR-Drawings-SET-2-1.pdf PDF
Show all 45

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

August 5, 2026

Dear Sir/Madam:

Attached is Addendum No. 7 for SEPTA's Sealed Bid No. 26-00105-AJEB Traction Power Substation Rehabilitation Program – Contract 5 Broad, Loudon, Park and Castor Substations Project. The Proposal Due Date remains unchanged on Wednesday, August 12, 2026 by 11AM.

Any inquiries regarding this bid must be directed to Justin Benante of the Procurement and Supply Chain Management Department at (215) 580-7022.

Sincerely, Justin Benante

Justin Benante Sr. Contract Administrator Procurement & Supply Chain Management Dept.

Addendum #7 August 5, 2026

SEALED BID No. 26-00105-AJEB

Traction Power Substation Rehabilitation Program – Contract 5 Broad, Loudon, Park and Castor Substations Project

ADDENDUM No. 7 To All Bidders:

The following constitutes Addendum No. 7 to SEPTA's Sealed Bid No. 26-00105-AJEB Traction Power Substation Rehabilitation Program – Contract 5 Broad, Loudon, Park and Castor Substations Project. Addendum No. 7 must be acknowledged by inserting the date on the Addenda Response form. Failure to do so may render a bidder's proposal as non-responsive. Addendum No. 7 must be acknowledged by inserting the date of the Addendum within Attachment 4: ADDENDUM ACKNOWLEDGEMENT SHEET of the Bid Package. Failure to do so may render a bidder's proposal as non-responsive.

Questions and Answers issued with this Addendum No. 7 are hereby incorporated by reference and made part of the Terms and Conditions of this project.

A. General

1. N/A

B. Specifications,

1. SEPTA will soon be removing the Wayside Energy Storage Systems at the Loudon and Park substations. This is no longer the contractor's responsibility.

C. Drawings & Attachments

1. Please see attached Addendum 7- DWG 7E-16563_28_color_a

2. Please see attached Addendum 7 -REV1 Markups 11x17_SEPTA_CONTRACT 5_50%_LOUDON

D. Ques t ions & Answers

1. Please see attached document for questions and answers.

ADDENDUM 7 - QUESTIONS & ANSWERS

Reference Question Response

4 Spec 01010.1.02.N

Specification section 01010.1.02.N lists a table (01010-1) of reference documents that were obtained or developed in conjunction with the contract documents. It does not appear that these reference documents have been provided with the bid documents.

All documents listed in specification 01010.1.01.N have been uploaded and are available to bidders.

https://wwww.septa.org/procurement/bids/traction-power-substation-rehabilitation-program-contract-5-broad-loudon-park-and-castor-substations-project/

Louden Substation Drawing pages 109 thru 116 need to be revised/corrected. Many Communications are labeled Mechanical

Documents will be updated with amendment. Will cloud over the text with revisions

Specification section 01060 Part 2.06 states that all contractors and subcontractors must receive SEPTA’s ESMS training. Please provide details of this training requirement.

Yes, all contractors need this training found here (online training):https://wwww.septa.org/procureme nt/

1. Specification section 01061.4.01.C states that SEPTA may withhold a rolling 25% of the contract value until all SSC items are satisfied. We ask that this withholding be removed as SEPTA withholds up to 10% of the contract value in retainage to ensure all contract requirements are satisfied. This language shall be removed from the specification.

Contractor requests inclusion of a mutual waiver of consequential damages.

Accepted:

MUTUAL WAIVER OF CONSEQUENTIAL

DAMAGES

Except for gross negligence or willful misconduct, neither SEPTA or the Contractor (including its parent company, affiliates, subsidiaries, subcontractors, agents, employees, officers, directors, assignees, and vendors) will be liable to the other for any special, consequential, indirect, punitive, exemplary, or incidental damages of any kind arising out of or related to the performance or non performance of the Contract, and regardless of whether such losses, damages, or liability arises from the breach of contract or warranty, tort (including negligence), strict liability, or otherwise.

Section VIII Part G Contractor requests striking “consequential damages”.

Accepted – Strike “consequential damages” from Section VIII (G).

Section VIII Part G Contractor requests an indemnity provision that limits Contractor’s obligation to the extent of its negligence for personal injury or for damage to real property.) Rejected.

Section XI Part C - Contractor seeks equitable adjustment in Contract Sum and Contract Time in the event of a delay caused by SEPTA. Contractor requests inclusion of equitable adjustment language in the Contract for this Project

If the Contractor is unreasonably delayed by the negligence of SEPTA, its agents or representatives, or another contractor for whom SEPTA is responsible, the Contractor shall be entitled to an equitable adjustment in the Contract Sum and Contract Time in accordance with the Time Impact Analysis language in Section XI C 4 of the contract."

Section XI Part D - Contractor seeks equitable adjustment in the event the Work is suspended by SEPTA. Contractor requests inclusion of equitable adjustment language in the Contract for this Project.

Accepted. Incorporate the following in Section XI, Part D :

If the duration of suspended Work is for an unreasonable period of time, an adjustment will be made to the Contract Sum in accordance with the Time Impact Analysis language in Section XI C 4 of the contract for any increase in the cost of performance (including profit) caused by such Suspension and this Contract shall be modified accordingly in writing

Section XX - Contractor requests inclusion of the Parties’ ability to attend non-binding mediation in the Contract for this

Project.

Incorporate the following: Non-Binding Mediation. If the PARTIES fail to achieve resolution after an initial appeal, and no later than thirty (30) days after such failure, either party may file a demand for non-binding mediation in accordance with contract section .

Section XXVII - Contractor requests inclusion of Contractor’s right to suspend and/or terminate due to non-payment in the

Contract for this Project.

Rejected.

The contractor requests that a provision be added to the contract that allows the SEPTA to compensate the contractor for costs that are materially increased by the implementation of tariffs on, or in connection with the work. While the project is strictly Buy America the imposition of tariffs potentially affects the pricing of subcomponents to American made products. These tariffs can adversely and unfairly affect the cost and availability of American made products after pricing proposals have been submitted and contracts signed.

Tariff section XXXVI. TARIFFS has been added to the contract: If Contractor’s costs in the performance of its duties under this Agreement are materially increased by the implementation of material tariffs on, or in connection with the Work performed under Agreement, pricing and fees may be escalated accordingly, after consultation and agreement with SEPTA, to compensate Contractor for such increased costs. As such, the parties agree to meet and negotiate in good faith to determine any appropriate and reasonable adjustments to pricing to compensate Contractor for such costs. Prior to any such meeting, Contractor shall provide all relevant information, invoices and documentation to support its claim of increased tariffs, including but not limited to, the actual amount and date of tariff imposed and the percentage of such tariff directly related to the Work, country of origin of the product or goods and any other documentation supporting or related to the claim of additional costs resulting from tariffs.

Drawings set 1- G 108/ Spec

Please confirm that the restriction to rehabilitate one substation at a time only applies to Loudon, Park, and Broad, and that work at Castor TPSS can occur in parallel with any of the other 3 substations, as it feeds a separate system.

As per note 4 on Drawing G-108: The rehabilitation of Castor TPSS can be done independently of the rehabilitaton of the other TPSS's.

Drawings set 2- TP 110

Please verify the below allowable outage requirements, based on TP-110, (Typ to all TPSSs):

a- One Rectifier transformer must remain in service and is able to carry the subsation's TP load.

b- The 4.8KV switchgear can be taken out of service without the need for temporary power, as long as one of the two auxiliary transformers is in service.

c- the existing Generator and its rectifier can be taken out of service without the need for temporary power.

d- The wayside energy storage systems is currently not in operations, and does not require any temporary provision during construction.

Please verify the below allowable outage requirements, based on TP-110, (Typ to all TPSSs):

a- One Rectifier transformer must remain in service and is able to carry the subsation's TP load.Correct.

Replace one TRU at a time, the second TRU must remain in service.

b- The 4.8KV switchgear can be taken out of service without the need for temporary power, as long as one of the two auxiliary transformers is in service. Correct.

c- the existing Generator and its rectifier can be taken out of service without the need for temporary power.

Correct d- The wayside energy storage systems is currently not in operations, and does not require any temporary provision during construction. Correct. Provide DC breaker and reconnect to the existing WESS equipment enclosure.

Drawings set 1- TP 106

TP 106, note 3, states: "Refer to SEPTA work order 30206 drawing 7E-16564 for the 4800V single line diagram". Please provide this drawing, or clarify details on the loads being fed from the 4.8kv switchgear, at all locations; currently, only the auxiliary transformer is called out. Confirm that the scope of work of this project for the 4800V is restricted to the 4800V switchgear and does not include replacement of the 4800V feeders (existing feeders will be reterminated to the new 4800V switchgear).

Note 3 in TP106 calls out Drawing 7E-16563 and not 7E-16564. Drawing 7E-16563 shall be provided by SEPTA. As per Final SLD - drawing TP-109 Note 2, Contractor shall replace 4800V cables and load break connectors out up to first manhole outside of TPSS.

Drawings set 1- COM 103 and COM 107

Regarding the fiber connection from the Substation to the OTN, please confirm that the scope of this project for Loudon, Park and Broad is limited to installing a Fiber cable from the first existing Comms manhole to the new interface panel in the substation, via existing ductbank/conduits. Please confirm that all work beyond the first manhole will be completed by SEPTA forces.

Confirmed. The Contractor's scope is limited to installing the fiber optic cable from the first existing communications manhole to the new interface panel within the substation using the existing ductbank/conduit system. The final fiber connection to the SEPTA OTN network, including all work beyond the first existing communications manhole, will be completed by SEPTA forces.

Drawings set 3- COM 403

For Castor substation, please confirm that the Fiber connection (including ductbank and conduit) from the substation (interface panel) to the OTN node is by SEPTA forces, and the DB's scope is limited to the connections inside the substation. If that is not the case, please clarify where the fiber demarcation point is to be assumed, as it does not appear that Castor currently has a connection to the

SEPTA OTN.

The Contractor shall install the fiber optic cable from the fiber demarcation point to the new interface panel within the substation. The location of the fiber demarcation point shall be coordinated with SEPTA in the field.

Specification 01010-7, section 17-t

The summary of work states: "Ground grid with ground buses and connections to the equipment and perimeter fencing.

Install new ground grid and associated conductors to supplement and/or replace the existing ground grid and all equipment connections" Please clarify this scope at the contract drawings do not show the location of the existing ground grid (rods, conductors, etc), nor does it show a new proposed ground grid design, and this will present significant site work. The DB suggests maintaining the existing grid and replacing the grounding conductors/buses within the substation building.

DB suggest to provide new substation's perimeter ground bus with all new connections to new equipment. Ground grid outside of the substation apply to Castor Substation which have outside transformer and fence.

Specification 01010-6, section 16-d

The summary of work states: Existing servers A, B and C located at 1234 Market Street to be replaced prior to any new RTU installation for this Contract."

Please confirm that SCADA servers replacement is by SEPTA forces/others. If server replacement/migration is expected as part of this contract's scope please provide detailed contract drawings/specifications related to this work.

SCADA Server A,B,&C replacement at 1234 Market are not in the scope of this contract. As stated in Spec 01010-6.16d -Contractor must provide labor and equipment for the required testing to verify proper communication with the servers located at 1234 Market St and all locations that are intregal to SEPTA SCADA systems . Please also refer to G107 Note 18 for Scada Requirements

Specification 16344

Please confirm if the DC Short circuit field test and train start tests will be required to verify DC feeder relay settings, or if existing settings will be provided by SEPTA to be used by the DB instead.

Refer to specification 16344 3.01.C Coordinate settings with SEPTA. Existing settings can be used as a starting setting and adjusted as necessary.

C202 Does existing topographical survey include enough detail to design curb ramp to RC-67M?

The topographic information shown in the contract documents is considered appropriate for the current 50% design level and is sufficient to identify the limits, layout, and feasibility of the proposed curb ramp improvements. Final curb ramp design, including determination of exact grades, elevations, transitions, and compliance with Standard RC

67M and applicable ADA requirements, will be completed during final design based on field verification and site conditions. The contractor/designer shall verify existing conditions and develop the final curb ramp geometry necessary to achieve compliance with the governing standards.

C200, Notes 1-3 Will signed and sealed survey drawings be provided listing coordinate systems, utility sources, and property information?

No additional signed and sealed survey drawings are anticipated to be provided. The horizontal and vertical datums are identified on Sheet C200. Utility and property information shown in the contract documents is provided for reference and planning purposes. As noted on Sheet C200, utility locations are approximate and shall be field verified as necessary, and property line information is approximate and provided for information only. The Contractor shall be responsible for verifying existing site conditions and obtaining any additional survey, utility, property, or other supporting information required to complete the final design and construction activities.

S101, Tank

Is any information available related to size, specific contents, and exact location of the tank? The exact size and contents of tank will need to be verified in the field once the Contract is awarded.

S101, Tank

Is soil export expected as part of this project? If so, has an estimated volume been determined from the 50% drawings? Any soil work will be determined during final design once the Contract is awarded.

Specifications 16344, 2.07

The specification identifies the following approved DC breaker manufacturers:

1.Myers
2.NDC/Brush (supplied by Powell)
3.Balfour

We are not aware of any DC breakers currently manufactured by Balfour for the U.S. traction power market, however, Secheron does provide the specified breakers rated up to 8,000 A and is currently used by SEPTA. Please review and revise the specification, as necessary, to reflect current market availability and approved suppliers.

Balfour Beatty TPG - (formerly IMPULSE) located in Goldsboro, N. Carolina and manufactures power equipment including rectifiers and EMC DC breakers up to 10000A. These DC breakers are approved for NYC Transit.

https://www.balfourbeattyus.com/teams/total-power-group. Phone: 919-432-1470

RFQ Evaluation Criteria - Part 4 Subsection Item 4

Part 4 Subsection 1 item 4 states that a form 330 is to be completed and submitted with the proposal. Is the Form 330 intended only for the Engineer / Architect to complete for submission or should it be utilized for the key contractors as well? Is it expected for each major team participant to each submit a Form 330 or is one Form 330 to be submitted that encompasses the entire team?

This form is required to be submitted for each member team participating with this project.

Form 330 is located on the SEPTA website.

could you please confirm what documentation is required at the time of bid/proposal submission? For example, is the Joint Venture’s Tax ID required at bid time, or can it be provided after award? Additionally, are there any other mandatory JV-related documents or certifications that must be included with the initial submission?

Proposers must submit their RFQ Technical Proposal addressing the specific elements of the Evaluation Criteria as stated in Section 1, Part 4

FR Vest will be required for PPE

I am currently reviewing the project specifications for Section 06610 – Glass Fiber and Resin Fabrications.

However, I am unable to locate the clear detail drawings for the fiberglass grating in the documents provided. Could you please provide the complete detail drawings for these items, or direct us to the relevant drawing sheets? These details are required for us to accurately review the scope and prepare our quotation.

The existing fiberglass panel system at Loudon TPSS could not be removed or fully disassembled during the field investigation without causing damage to the installation. As such, the condition of the panels, attachment system, gaskets, sealants, and supporting components could not be verified. The Contractor shall be responsible for evaluating the existing panel system during final design and prior to construction to determine its suitability for continued service. If the existing panels are found to be in acceptable condition, they may remain in place, with replacement of gaskets, sealants, and associated hardware as necessary to restore and maintain a weather-tight and watertight building envelope. If the Contractor determines that replacement of some or all of the panels is required, the replacement system shall comply with the requirements of Specification Section 06610 and shall match the existing installation's functional, durability, fire-resistance, weather-resistance, and aesthetic characteristics. No replacement panel details are currently shown because reuse of the existing fiberglass panels may be feasible pending the Contractor's evaluation and verification of existing conditions

Minimum Daily PPE: FR clothing, FR safety vest, hard hat, safety glasses, and EH-rated work boots are mandatory for all personnel within the substation work zone unless otherwise approved by the Site Safety Manager. FR clothing ratings should be based on SEPTA's existing minimum requirements for FR clothing worn by our substation workers. Minimum 8 Cal /Cat 2.

All personnel entering or working within substations containing exposed energized equipment, open switchgear, or areas where electrical hazards may be present shall wear the following minimum PPE at all times: Flame-Resistant (FR) clothing meeting applicable arc flash and electrical safety requirements. FR-rated high-visibility safety vest or FR outerwear. ANSI-approved hard hat. Safety glasses with side shields meeting ANSI Z87.1 requirements.

EH-rated safety footwear with non-conductive soles and protective toe protection

Addendum-7-Contract-5-Substations-Step-1-8-5-26
ADDENDUM No. 7
B. Specifications,
C. Drawings & Attachments
D. Questions & Answers
Addendum 7 Questions-Answers-8-5-26 Traction Power Substations