26 27 13.11 - Microprocessor-Based Metering Equipment.pdf

PDF 124 KB Posted

Attached to
Electrical Substation Replacement Project – Equipment Procurement Phase
Solicitation number
US.255952
Issued by
Lehigh County, Pennsylvania

About this file

This is a specification document for microprocessor-based metering equipment (PQM) procurement for Substations #2 and #4 of the Lehigh County Authority's Electrical Substation Replacement Project, located at 7676 Industrial Boulevard, Allentown, Pennsylvania. The specification requires the provision of Power Quality Meters equivalent to the Eaton PXQ event analysis system, with bids to be submitted via PennBid electronic bidding service by 11:00 a.m. on Wednesday, October 28, 2026. Acceptable manufacturers include Eaton, ABB, Siemens, and Square D/Schneider Electric, provided products meet all specified ratings, features, and functions; other manufacturers' products may be considered if pre-approved by the engineer at least ten days prior to the bid date. Site visits are self-guided and can be scheduled via email with Charles Volk, P.E., Chief Capital Works Officer. Bids shall remain open for 60 days from the date of opening, and each bid must be accompanied by bid security equal to 10 percent of the bid total in the form of a certified check, bank check, or bid bond.

The specification details extensive technical requirements for the PQM, including safety certifications (UL 61010-1, EN 61010-1), accuracy standards (ANSI C12.20 Class 0.1, IEC/EN62053-22), and compliance with numerous IEC and IEEE standards for power quality and metering. The meter must support 24-48 Vdc control power inputs, four current inputs compatible with standard 5A or 1A instrument current transformers, voltage inputs ranging from 600V line-to-line to 150,000V with appropriate potential transformers, and advanced features including up to 32GB onboard memory, eight configurable event trigger types, dual RJ-45 Ethernet ports, and comprehensive cybersecurity protections including Trusted Platform Module integration and Role-Based Access Control. An optional 7-inch color touch screen display with IP 66 ingress protection and remote mounting capability up to 300 feet is available. The Lehigh County Authority reserves the right to reject any and all bids and to waive any omissions, errors, mistakes, defects, or irregularities in any bid.

View the file

Other files

File Type Posted
26 11 16.11 - Secondary Unit Substations - Secondary Less Than 1000V.pdf PDF
26 12 13.01 - Liquid-Filled Medium Voltge Unit Substation Transformers.pdf PDF
9-Agreement of Surety Form Contract.pdf PDF
23-EJCDC - Payment Bond (C-620-2002).pdf PDF
1-LCA-ELECTRICAL SUBSTATION PROCUREMENT DWGS.pdf PDF
017716 – CONTRACT CLOSEOUT.pdf PDF
15-Affidavit of Non-Collusion.pdf PDF
21-EJCDC - Performance Bond (C-600-2002).pdf PDF
012977.02 - MEASUREMENT AND PAYMENT.pdf PDF
13-List of Proposed Subcontractors.pdf PDF
017900.01 - VIDEO TRAINING PROGRAMS.pdf PDF
26 23 00.16 - Arc Resistant Metal Enclosed Drawout Switchgear LV.pdf PDF
27-PA Prevailing Wage Act Duties00810.pdf PDF
26 05 73.13 - Short Circuit Studies.pdf PDF
1-TITLE page.pdf PDF
26 13 26.11 - Metal Clad MV Arc Resistent Switchgear.pdf PDF
24-EJCDC - General Conditions (with Supplementary shown).pdf PDF
2-TOC.pdf PDF
011000.03 -SUMMARY OF THE WORK.pdf PDF
26 05 53 - Identification For Electrical Systems.pdf PDF
26 05 73.19 - Arc Flash Hazard Analysis.pdf PDF
26 43 13A - LV Surge Protective Devices For Electrical Distribution Systems.pdf PDF
19-EJCDC - Agreement Stipulated Price (C-520-2002).pdf PDF
5-EJCDC - Bid Form for Construction Contracts 00300 (003).pdf PDF
4-7-EJCDC - Bid Bond, Penal Sum Form (C-430-2002) Revised 10-30-2026.pdf PDF
11-Experience Questionnaire.pdf PDF
013300.0 - SUBMITTALS.pdf PDF
3-Addendum 1 LCA.pdf PDF
4-EJCDC - Instructions to Bidders (C-200-2002).pdf PDF
7-EJCDC - Bid Bond, Penal Sum Form (C-430-2002).pdf PDF
3-00010_Invitation to Bid.pdf PDF
26 05 73.16 - Coordination Studies.pdf PDF
17-CertAsToCorpPrincipal.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Substation #2, #4 Procurement 7676 Industrial Blvd.

Allentown, PA 18106 September 15, 2026

26 27 13.11-1

SECTION 26 27 13.11

MICROPROCESSOR-BASED METERING EQUIPMENT

PART 1 GENERAL

1.01 RELATED DOCUMENTS

A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Eaton products

B. ABB

C. Siemens

D. Square d/Schneider Electric

The listing of specific manufacturers above does not imply acceptance of their products that do not meet the specified ratings, features and functions. Manufacturers listed above are not relieved from meeting these specifications in their entirety. Products in compliance with the specification and manufactured by others not named will be considered only if pre-approved by the Engineer ten (10) days prior to bid date.

2.02 MICROPROCESSOR-BASED METERING EQUIPMENT

A. Where indicated on the drawings, provide a microprocessor-based line of Power Quality Meter(s), designated (PQM), equal to Eaton PXQ event analysis system.

1. A complete PQM combination meter base and/or display shall have the following minimum listings and/or certifications:

a. Safety: UL 61010-1, EN 61010-1.

b. Accuracy: ANSI C12.20 Class 0.1, IEC/EN62053-22 0.1 for revenue meters.

c. EMC: FCC Part 15 Subpart B Class B immunity, EN55011 and EN55032 Class B, ICES-003 Class B

d. IEC Standards: 61000-4, and 61326-1.

e. Environmental: RoHS (EU 2015/863)

f. Power Quality/Metering:

1) IEC 61000-4-30 Class A

2) IEC 61000-4-15

Allentown, PA 18106 September 15, 2026

26 27 13.11-2

3) IEC 61000-4-7

4) IEC 61557-12 (PMD)

5) IEC 62586-1

6) IEC 62586-2

7) IEEE 1453 - Flicker

2. The PQM shall comply with the following standards for accuracy:

a. Active energy (Wh): IEC 62053-22 Class 0.1 S, ANSI C12.20 2015 Class 0.1

b. Reactive energy (VARh): IEC 62053–24 Class 1

c. Active power (P): IEC 61557-12 Class 0.1

d. Reactive power (QV): IEC 61557-12 Class 1

e. Apparent power (SV): IEC 61557-12 Class 0.2

f. Apparent energy (EapV): IEC 61557–12 Class 0.2

g. Current (I): IEC 61557-12 Class 0.1

h. Voltage (U): IEC 61557-12 Class 0.1

3. The PQM shall accept standard 24-48 Vdc (50VA max load) control power inputs.

a. The PQM shall support use of external ride-through module (e.g. CliQ II Buffer Module DRB-24V040ABN or similar). The PQM shall support up to 15 seconds of ride-through.

b. Upon loss of control power, the PQM real time clock shall receive backup power from an off-the-shelf coin-cell battery (e.g. CR1632) that is replaceable in the field.

4. The PQM shall support mounting configuration either by using a DIN Rail or integral to optional display with mounting bracket.

5. The PQM shall support four current inputs with calculated residuals (selectable Neutral or Ground). Current inputs for each channel shall be compatible with standard 5A or 1A instrument current transformers.

a. The analog current inputs shall be captured with True RMS sampling at 1024 samples per cycle.

b. Overload withstand capability shall be a minimum of 500A for 1 second, non-repeating.

c. Input current range shall be 0.025 to 20 amperes. (ANSI C12.20 Class 20)

6. Voltage inputs for each channel shall allow for connection into circuits with the following parameters:

a. Input range of 600V L-L, 400V L-N direct connected (no PTs required).

b. PT primary input of 120 volts to 150,000 volts.

Allentown, PA 18106 September 15, 2026

26 27 13.11-3

c. The analog voltage input shall be captured with True RMS sampling at 1024 samples per cycle.

7. The PQM shall provide the following sampling and capture capabilities:

a. Third-Order Butterworth A/D technology, sampling at 1024 samples per cycle for input voltages and currents

b. Sag/Swell and Waveform recording:

1) Up to (60 cycles of waveform shall be recorded at 512 samples per cycle, including 30 cycles of pre-trigger and post-trigger data) stored as COMTRADE format.

2) Multiple back-to-back sag sequences such as a distribution recloser shall be recorded with COMTRADE waveform capture for each recloser operation

3) Up to [2 minutes (1 min pre-trigger and 1 min post-trigger)] of RMS captured and stored as COMTRADE file.

4) Waveforms and RMS shall be available in non-volatile memory and retrievable via secure file transfer protocol (SFTP) in COMTRADE file format over the Ethernet network. COMTRADE waveforms shall be available for the entire waveform duration of (60 cycles at 512 samples per cycle.)

5) Timestamps shall be (+/- 0.1 ms) resolution or better while utilizing

PTP.

c. Triggered Event Capture:

1) The PQM shall have a quantity of eight (8) types of configurable event triggers consisting of 1) Out of limits, 2) Demand overload, 3) ITIC sag/swell, 4) SEMI-F47, 5) Sub-cycle disturbance transient (20 microsecond transient), 6) Rapid Voltage Change, and 7) Harmonic out of limits.

2) When a trigger occurs, actions shall include Capturing Waveform, Capturing metered parameters, and ability to send by email and/or activate a digital output.

3) Setpoint learning for out-of-limits event triggers.

4) Pre-configured ITIC and SEMI-F47 triggers.

8. The PQM shall have up to 32GB of onboard memory

a. At least 3 years of energy data shall be retained at 15-minute intervals

9. The PQM shall have provision for field-installable 10MHz transient capture capability.

B. The PQM shall be capable of monitoring, displaying, and communicating the following true rms minimum information where applicable. The PQM shall be suitable for installation in single phase, two or three wire systems or in three phase, three or four wire systems

1. AC current (amperes) in A, B and C phase, 3-phase average, and Neutral (N) and/or Ground (G).

a. PQM shall support measured fourth CT and calculated residuals.

Allentown, PA 18106 September 15, 2026

26 27 13.11-4

b. User shall have the option of choosing between either calculated Neutral or calculated Ground.

c. The 5 ampere current inputs shall withstand 40 amperes continuous and 500 amperes for 1 second, non-repeating. Current transformer ratios shall be selectable from 5:5 up to 20000:5.

2. AC voltage (volts) for A-B, B-C and C-A, phase average, A-N, B-N and C-N, average phase to N, and N to G. Capable of metering up to 600 volt L-L without external Potential Transformers (PTs) and up to 150 kV with appropriate PTs.

3. Real Power (Watts), Reactive Power (vars), Apparent Power (VA), for each phase and system. Forward/Reverse indication shall be provided.

4. Accumulated and conditional measurement for Real Energy (kWH), Reactive Energy (kVARh), Apparent Energy (kVAh) for the system. Forward/Reverse and Net difference readings shall be provided.

5. Frequency (Hz)

6. Demand values including present (last complete interval) and peak for System Current (Amperes). Coincident demand readings for kVA and kW.

7. Power Factor

a. Displacement based on phase angle

b. Apparent power factor based on Watts to Total VA including harmonics

8. Current Total Harmonic Distortion (THD) in A, B and C phase and N, expressed in both Amps and percent, including the following components:

a. Total

b. Even

c. Odd

d. Interharmonic frequencies

9. Current Total Demand Distortion (TDD) for A, B and C phase and N, expressed in percent, including the following components:

a. Even

b. Odd

c. Interharmonic frequencies

10. Voltage THD for Line to Line and Line to Neutral voltages, including the following components:

a. Total (expressed in volts and percentage)

b. Even

c. Odd

d. Interharmonic frequencies

11. K-Factor (sum of the squares of harmonic currents times the square of their harmonic numbers).

Allentown, PA 18106 September 15, 2026

26 27 13.11-5

12. Crest Factor (ratio of peak current to rms current).

13. Graphical ITIC curve (formerly CBEMA) and SEMI-F47 curve data

14. Flicker data compliant with IEC 61000-4-15 and IEEE 1453

C. The PQM shall provide advanced analysis at the edge with the following features onboard the device. Features shall be browser accessible and shall not require any additional software external to the PQM:

1. Automatic PQ analysis

a. Statistical Gauge of electrical parameters based on sigma deviations from normal

b. Single summary value for power quality health (e.g. Power Quality Health Index)

c. Events grouped into sequences

d. Sags and Swells automatically categorized by severity based on industry standards and reported graphically

2. Graphical trended data

a. 5-minute interval with averaging of data

b. Interactive multichannel trends with dual plotting of current and voltage to view both graphs simultaneously.

c. Graphical views exportable as PDF or PNG. Data exportable as CSV.

d. Zero configuration required to set up historical trends. All metered and derived parameters (except individual harmonics) are automatically logged.

e. Min/max analysis for each metered parameter based on 200ms calculations

f. Linkage between historical trend data and corresponding event, providing 1-click navigation between the two.

3. Graphical energy and demand comparisons

a. Comparison of energy and demand for current period vs prior period

b. Comparison of energy and demand for any two days, weeks, or months

c. Comparison graphics exportable as PNG or PDF for reporting

4. Advanced harmonics analysis

a. Calculation of individual harmonic magnitudes and phase angle for each phase voltage and current through the 85th harmonic.

b. Harmonic trending for up to 50 selected harmonics

c. Configurable out of limits alarming for individual harmonic trends

D. PQM shall have onboard digital Input/Output (I/O):

1. Eight (8) digital inputs – externally supplied 24 Vdc or internal (isolated) 24 Vdc supply.

Allentown, PA 18106 September 15, 2026

26 27 13.11-6

a. Inputs shall be interrupt driven, allowing for up to +/- 1ms resolution of digital events time stamps when utilizing local NTP server (or +/- 0.1ms resolution when utilizing PTP).

b. Inputs shall support status reporting, with configurable state for active or inactive.

c. Inputs shall support demand synchronization.

d. Inputs shall support pulses for WAGES applications. Pulses shall be scalable for unit conversion and support labeling for units. PQM shall maintain interval-by-interval pulse recordings and provide usage graph.

Graphics shall be exportable as PDF or PNG for reporting.

e. Inputs shall support energy accumulation

2. Two (2) solid state outputs – form C continuous NO and NC Bidirectional FET, 80 mA maximum continuous, 24 Vdc +/- 20%.

a. Outputs shall support programmable Boolean logic.

b. Outputs shall be controllable via triggered events

E. The PQM shall be provided with multiple communications ports and protocols, including the following capabilities:

1. Dual RJ-45 10/100/1GbE base-T Ethernet ports or 10/100/1000 BASE-T

2. USB micro for device configuration via local web server

3. Secure HTTPS HTML web pages

4. Secure file transfer protocol (SFTP)

5. Modbus TCP

6. BACnet/IP

7. Authenticated SMTP (Simple Mail Transfer Protocol) for email support

8. SNMP (Simple Network Management Protocol) MIB support

9. NTP (Network Time Protocol) support

10. PTP (Precision Time Protocol) support

11. IPv4 or IPv6

F. The PQM shall provide the following Cybersecurity protections:

1. Integrated Trusted Platform Module (TPM) to provide hardware-based cryptographic security

2. Secure firmware update through use of digitally signed firmware.

3. Advanced access management with:

a. Individual accounts by user

b. Local Role Based Access Control (RBAC), configurable timeouts, configurable password-expirations and complexity rules, configurable user-roles. PQM shall support up to 50 local users.

Allentown, PA 18106 September 15, 2026

26 27 13.11-7

c. LDAP support to utilize an organization’s existing user credentials via Active Directory authentication. PQM shall support virtually unlimited users via Active Directory

4. Advanced password management for 6 to 64 characters, including customizable special character requirement, password expiration, and configurable lock-out period

5. Security and access logs providing history of access attempts, configuration changes and other security actions

6. Secure protocols including SFTP, HTTPS

7. Ability to enable/disable communication protocols or specific ports

8. Secure field password recovery procedure shall be possible with physical access to the device. Removal of installed PQM shall not be required to recover access.

9. Tested in UL-accredited lab environment

10. Adheres to IEC 62443-4-1 and UL 2900 certified secure product development lifecycle

G. PQM shall support a local display that provides access to metered, trend and waveform information in both numeric and graphical visual formats.

1. PQM shall be display agnostic and support “bring your own display” (BYOD).

PQM shall be compatible with third-party web-enabled screens and be capable of

a. Acknowledging events and alarms

b. Showing graphical ITIC analysis, waveform and event sequence RMS view, dual plotting of historical trends, energy and demand comparison, event analysis calendar, advanced harmonics analysis and Sag Source Analysis.

c. Secure authentication, supporting:

1) Advanced password management for 6 to 64 characters, including customizable special character requirement, password expiration, and configurable lock-out period

2) Active Directory authentication

d. Providing support for configuration of the PQM, including:

1) Ability to edit system configuration as an administrative user

2) Ability to add new users or manage existing users

3) Ability to connect to Active Directory

4) View of Access Attempts in Session Log

5) Ability to disable or protocols as an administrative user

6) Ability to set or edit triggers

7) Ability to configure email reporting

Allentown, PA 18106 September 15, 2026

26 27 13.11-8

2. Optional graphical display shall utilize a 7-inch color touch screen interface to easily navigate the meter in front of the installation. The display shall be web based and provide the following features:

a. 7-inch backlight color LED remote capacitive touchscreen display with 1024 x 600 pixels.

b. Conformity to the following:

1) EN60068-2-6

2) EN60068-2-27

3) Humidity EN60068-2-30

c. Ingress protection IP 66 or better

d. Backlight life 50,000 hrs or greater with a brightness of 500 cd/m²

e. Capable of being mounted to the Meter base unit with optional mounting bracket or remote mounting of display up to 300 ft away.

f. Support for intuitive multi-touch functionality permitting user to pinch, zoom, scroll and swipe.

g. Shielded Ethernet CAT5e/CAT6e as physical media to communicate with the PQM Processor located in the assembly either directly or via an Ethernet switch.

PART 1 GENERAL
1.01 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
part 2 products
2.01 manufacturers
A. Eaton products
B. ABB
C. Siemens
D. Square d/Schneider Electric
2.02 microprocessor-based metering equipment
A. Where indicated on the drawings, provide a microprocessor-based line of Power Quality Meter(s), designated (PQM), equal to Eaton PXQ event analysis system.
1. A complete PQM combination meter base and/or display shall have the following minimum listings and/or certifications:
a. Safety: UL 61010-1, EN 61010-1.
b. Accuracy: ANSI C12.20 Class 0.1, IEC/EN62053-22 0.1 for revenue meters.
c. EMC: FCC Part 15 Subpart B Class B immunity, EN55011 and EN55032 Class B, ICES-003 Class B
d. IEC Standards: 61000-4, and 61326-1.
e. Environmental: RoHS (EU 2015/863)
f. Power Quality/Metering:
1) IEC 61000-4-30 Class A
2) IEC 61000-4-15
3) IEC 61000-4-7
4) IEC 61557-12 (PMD)
5) IEC 62586-1
6) IEC 62586-2
7) IEEE 1453 - Flicker
2. The PQM shall comply with the following standards for accuracy:
a. Active energy (Wh): IEC 62053-22 Class 0.1 S, ANSI C12.20 2015 Class 0.1
b. Reactive energy (VARh): IEC 62053–24 Class 1
c. Active power (P): IEC 61557-12 Class 0.1
d. Reactive power (QV): IEC 61557-12 Class 1
e. Apparent power (SV): IEC 61557-12 Class 0.2
f. Apparent energy (EapV): IEC 61557–12 Class 0.2
g. Current (I): IEC 61557-12 Class 0.1
h. Voltage (U): IEC 61557-12 Class 0.1
3. The PQM shall accept standard 24-48 Vdc (50VA max load) control power inputs.
a. The PQM shall support use of external ride-through module (e.g. CliQ II Buffer Module DRB-24V040ABN or similar). The PQM shall support up to 15 seconds of ride-through.
b. Upon loss of control power, the PQM real time clock shall receive backup power from an off-the-shelf coin-cell battery (e.g. CR1632) that is replaceable in the field.
4. The PQM shall support mounting configuration either by using a DIN Rail or integral to optional display with mounting bracket.
5. The PQM shall support four current inputs with calculated residuals (selectable Neutral or Ground). Current inputs for each channel shall be compatible with standard 5A or 1A instrument current transformers.
a. The analog current inputs shall be captured with True RMS sampling at 1024 samples per cycle.
b. Overload withstand capability shall be a minimum of 500A for 1 second, non-repeating.
c. Input current range shall be 0.025 to 20 amperes. (ANSI C12.20 Class 20)
6. Voltage inputs for each channel shall allow for connection into circuits with the following parameters:
a. Input range of 600V L-L, 400V L-N direct connected (no PTs required).
b. PT primary input of 120 volts to 150,000 volts.
c. The analog voltage input shall be captured with True RMS sampling at 1024 samples per cycle.
7. The PQM shall provide the following sampling and capture capabilities:
a. Third-Order Butterworth A/D technology, sampling at 1024 samples per cycle for input voltages and currents
b. Sag/Swell and Waveform recording:
1) Up to (60 cycles of waveform shall be recorded at 512 samples per cycle, including 30 cycles of pre-trigger and post-trigger data) stored as COMTRADE format.
2) Multiple back-to-back sag sequences such as a distribution recloser shall be recorded with COMTRADE waveform capture for each recloser operation
3) Up to [2 minutes (1 min pre-trigger and 1 min post-trigger)] of RMS captured and stored as COMTRADE file.
4) Waveforms and RMS shall be available in non-volatile memory and retrievable via secure file transfer protocol (SFTP) in COMTRADE file format over the Ethernet network. COMTRADE waveforms shall be available for the entire waveform duration of (60 cy...
5) Timestamps shall be (+/- 0.1 ms) resolution or better while utilizing PTP.
c. Triggered Event Capture:
1) The PQM shall have a quantity of eight (8) types of configurable event triggers consisting of 1) Out of limits, 2) Demand overload, 3) ITIC sag/swell, 4) SEMI-F47, 5) Sub-cycle disturbance transient (20 microsecond transient), 6) Rapid Voltage Chan...
2) When a trigger occurs, actions shall include Capturing Waveform, Capturing metered parameters, and ability to send by email and/or activate a digital output.
3) Setpoint learning for out-of-limits event triggers.
4) Pre-configured ITIC and SEMI-F47 triggers.
8. The PQM shall have up to 32GB of onboard memory
a. At least 3 years of energy data shall be retained at 15-minute intervals

9. The PQM shall have provision for field-installable 10MHz transient capture capability.

B. The PQM shall be capable of monitoring, displaying, and communicating the following true rms minimum information where applicable. The PQM shall be suitable for installation in single phase, two or three wire systems or in three phase, three or fou...
1. AC current (amperes) in A, B and C phase, 3-phase average, and Neutral (N) and/or Ground (G).
a. PQM shall support measured fourth CT and calculated residuals.
b. User shall have the option of choosing between either calculated Neutral or calculated Ground.
c. The 5 ampere current inputs shall withstand 40 amperes continuous and 500 amperes for 1 second, non-repeating. Current transformer ratios shall be selectable from 5:5 up to 20000:5.
2. AC voltage (volts) for A-B, B-C and C-A, phase average, A-N, B-N and C-N, average phase to N, and N to G. Capable of metering up to 600 volt L-L without external Potential Transformers (PTs) and up to 150 kV with appropriate PTs.
3. Real Power (Watts), Reactive Power (vars), Apparent Power (VA), for each phase and system. Forward/Reverse indication shall be provided.
4. Accumulated and conditional measurement for Real Energy (kWH), Reactive Energy (kVARh), Apparent Energy (kVAh) for the system. Forward/Reverse and Net difference readings shall be provided.
5. Frequency (Hz)
6. Demand values including present (last complete interval) and peak for System Current (Amperes). Coincident demand readings for kVA and kW.
7. Power Factor
a. Displacement based on phase angle
b. Apparent power factor based on Watts to Total VA including harmonics
8. Current Total Harmonic Distortion (THD) in A, B and C phase and N, expressed in both Amps and percent, including the following components:
a. Total
b. Even
c. Odd
d. Interharmonic frequencies
9. Current Total Demand Distortion (TDD) for A, B and C phase and N, expressed in percent, including the following components:
a. Even
b. Odd
c. Interharmonic frequencies
10. Voltage THD for Line to Line and Line to Neutral voltages, including the following components:
a. Total (expressed in volts and percentage)
b. Even
c. Odd
d. Interharmonic frequencies
11. K-Factor (sum of the squares of harmonic currents times the square of their harmonic numbers).
12. Crest Factor (ratio of peak current to rms current).
13. Graphical ITIC curve (formerly CBEMA) and SEMI-F47 curve data
14. Flicker data compliant with IEC 61000-4-15 and IEEE 1453
C. The PQM shall provide advanced analysis at the edge with the following features onboard the device. Features shall be browser accessible and shall not require any additional software external to the PQM:
1. Automatic PQ analysis
a. Statistical Gauge of electrical parameters based on sigma deviations from normal
b. Single summary value for power quality health (e.g. Power Quality Health Index)
c. Events grouped into sequences
d. Sags and Swells automatically categorized by severity based on industry standards and reported graphically
2. Graphical trended data
a. 5-minute interval with averaging of data
b. Interactive multichannel trends with dual plotting of current and voltage to view both graphs simultaneously.
c. Graphical views exportable as PDF or PNG. Data exportable as CSV.
d. Zero configuration required to set up historical trends. All metered and derived parameters (except individual harmonics) are automatically logged.
e. Min/max analysis for each metered parameter based on 200ms calculations
f. Linkage between historical trend data and corresponding event, providing 1-click navigation between the two.
3. Graphical energy and demand comparisons
a. Comparison of energy and demand for current period vs prior period
b. Comparison of energy and demand for any two days, weeks, or months
c. Comparison graphics exportable as PNG or PDF for reporting
4. Advanced harmonics analysis
a. Calculation of individual harmonic magnitudes and phase angle for each phase voltage and current through the 85th harmonic.
b. Harmonic trending for up to 50 selected harmonics
c. Configurable out of limits alarming for individual harmonic trends
D. PQM shall have onboard digital Input/Output (I/O):
1. Eight (8) digital inputs – externally supplied 24 Vdc or internal (isolated) 24 Vdc supply.
a. Inputs shall be interrupt driven, allowing for up to +/- 1ms resolution of digital events time stamps when utilizing local NTP server (or +/- 0.1ms resolution when utilizing PTP).
b. Inputs shall support status reporting, with configurable state for active or inactive.
c. Inputs shall support demand synchronization.
d. Inputs shall support pulses for WAGES applications. Pulses shall be scalable for unit conversion and support labeling for units. PQM shall maintain interval-by-interval pulse recordings and provide usage graph. Graphics shall be exportable as PDF...
e. Inputs shall support energy accumulation
2. Two (2) solid state outputs – form C continuous NO and NC Bidirectional FET, 80 mA maximum continuous, 24 Vdc +/- 20%.
a. Outputs shall support programmable Boolean logic.
b. Outputs shall be controllable via triggered events
E. The PQM shall be provided with multiple communications ports and protocols, including the following capabilities:
1. Dual RJ-45 10/100/1GbE base-T Ethernet ports or 10/100/1000 BASE-T
2. USB micro for device configuration via local web server
3. Secure HTTPS HTML web pages
4. Secure file transfer protocol (SFTP)
5. Modbus TCP
6. BACnet/IP
7. Authenticated SMTP (Simple Mail Transfer Protocol) for email support
8. SNMP (Simple Network Management Protocol) MIB support
9. NTP (Network Time Protocol) support
10. PTP (Precision Time Protocol) support
11. IPv4 or IPv6
F. The PQM shall provide the following Cybersecurity protections:
1. Integrated Trusted Platform Module (TPM) to provide hardware-based cryptographic security
2. Secure firmware update through use of digitally signed firmware.
3. Advanced access management with:
a. Individual accounts by user
b. Local Role Based Access Control (RBAC), configurable timeouts, configurable password-expirations and complexity rules, configurable user-roles. PQM shall support up to 50 local users.
c. LDAP support to utilize an organization’s existing user credentials via Active Directory authentication. PQM shall support virtually unlimited users via Active Directory
4. Advanced password management for 6 to 64 characters, including customizable special character requirement, password expiration, and configurable lock-out period
5. Security and access logs providing history of access attempts, configuration changes and other security actions
6. Secure protocols including SFTP, HTTPS
7. Ability to enable/disable communication protocols or specific ports
8. Secure field password recovery procedure shall be possible with physical access to the device. Removal of installed PQM shall not be required to recover access.
9. Tested in UL-accredited lab environment
10. Adheres to IEC 62443-4-1 and UL 2900 certified secure product development lifecycle
G. PQM shall support a local display that provides access to metered, trend and waveform information in both numeric and graphical visual formats.
1. PQM shall be display agnostic and support “bring your own display” (BYOD). PQM shall be compatible with third-party web-enabled screens and be capable of
a. Acknowledging events and alarms
b. Showing graphical ITIC analysis, waveform and event sequence RMS view, dual plotting of historical trends, energy and demand comparison, event analysis calendar, advanced harmonics analysis and Sag Source Analysis.
c. Secure authentication, supporting:
1) Advanced password management for 6 to 64 characters, including customizable special character requirement, password expiration, and configurable lock-out period
2) Active Directory authentication
d. Providing support for configuration of the PQM, including:
1) Ability to edit system configuration as an administrative user
2) Ability to add new users or manage existing users
3) Ability to connect to Active Directory
4) View of Access Attempts in Session Log
5) Ability to disable or protocols as an administrative user
6) Ability to set or edit triggers
7) Ability to configure email reporting
2. Optional graphical display shall utilize a 7-inch color touch screen interface to easily navigate the meter in front of the installation. The display shall be web based and provide the following features:
a. 7-inch backlight color LED remote capacitive touchscreen display with 1024 x 600 pixels.
b. Conformity to the following:
1) EN60068-2-6
2) EN60068-2-27
3) Humidity EN60068-2-30
c. Ingress protection IP 66 or better
d. Backlight life 50,000 hrs or greater with a brightness of 500 cd/m²
e. Capable of being mounted to the Meter base unit with optional mounting bracket or remote mounting of display up to 300 ft away.
f. Support for intuitive multi-touch functionality permitting user to pinch, zoom, scroll and swipe.
g. Shielded Ethernet CAT5e/CAT6e as physical media to communicate with the PQM Processor located in the assembly either directly or via an Ethernet switch.

File details come from the government source that posted it. Updated .