26 05 53 - Identification For Electrical Systems.pdf
PDF 198 KB Posted
- Solicitation number
- US.255952
- Issued by
- Lehigh County, Pennsylvania
About this file
This specification document, Section 26 05 53 – Identification for Electrical Systems, is part of the Electrical Substation Replacement Project – Equipment Procurement Phase for the Lehigh County Authority in Pennsylvania. The specification establishes comprehensive requirements for electrical identification products and installation at Substation #2 and #4 located at 7676 Industrial Boulevard, Allentown, PA 18106. The project requires identification materials including labels, bands and tubes, tapes and stencils, tags, signs, cable ties, and miscellaneous identification products to comply with applicable standards including ASME A13.1, IEEE C2, NFPA 70, and ANSI Z535 series. Sealed bids will be received through the PennBid electronic bidding service until 11:00 a.m. on Wednesday, October 28, 2026, with public opening and reading immediately following. Pre-bid meetings will not be held; site visits are self-guided and may be scheduled by email with Charles Volk, P.E., Chief Capital Works Officer. All bidding documents are available at no cost through PennBid (www.PennBid.net). Bids must remain open for 60 days from the opening date, and each bid must be accompanied by bid security of 10 percent of the bid total in the form of a certified check, bank check, or bid bond.
The specification requires compliance with color-coding standards for various voltage levels (208/120-V, 240-V, and 480/277-V circuits), specific labeling requirements for raceways and cables at different voltage classifications, and installation procedures ensuring high visibility and accessibility of all identification materials. Products must meet performance requirements including thermal movement allowances for temperature changes from 120 degrees Fahrenheit ambient to 180 degrees Fahrenheit on material surfaces, and adhesive materials must comply with UL 969. Approved manufacturers for various product categories are listed with "or equal" alternatives permitted, including Brady Corporation, Panduit Corp., Ideal Industries, and others. Installation requirements specify placement at changes in direction, wall and floor penetrations, and maximum spacing intervals (50-foot intervals in straight runs, 25-foot intervals in congested areas). The specification includes detailed submittal requirements, including product data, samples, identification schedules, and delegated-design submittals for arc-flash hazard studies. The Lehigh County Authority reserves the right to reject any and all bids and waive any omissions, errors, or irregularities therein.
View the file
Other files
Show all 33
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Substation #2, #4 Procurement 7676 Industrial Blvd.
Allentown, PA 18106 September 15, 2026
26 05 53-1
SECTION 26 05 53
IDENTIFICATION FOR ELECTRICAL SYSTEMS
PART 1 GENERAL
1.01 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.02 SUMMARY
A. Section Includes:
1. Labels.
2. Bands and tubes.
3. Tapes and stencils.
4. Tags.
5. Signs.
6. Cable ties.
7. Miscellaneous identification products.
1.03 SUBMITTALS
A. Submittals for this section are subject to the re-evaluation fee identified in Article 4 of the General Conditions.
B. Manufacturer’s installation instructions shall be provided along with product data.
C. Submittals shall be provided in the order in which they are specified and tabbed (for combined submittals).
D. Product Data: For each type of product.
1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for electrical identification products.
E. Samples: For each type of label and sign to illustrate composition, size, colors, lettering style, mounting provisions, and graphic features of identification products.
F. Identification Schedule: For each piece of electrical equipment and electrical system components to be an index of nomenclature for electrical equipment and system components used in identification signs and labels. Use same designations indicated on Drawings.
Allentown, PA 18106 September 15, 2026
26 05 53-2
G. Delegated-Design Submittal: For arc-flash hazard study.
H. Submittals for this section are subject to the re-evaluation fee identified in Article 4 of the General Conditions.
PART 2 PRODUCTS
2.01 PERFORMANCE REQUIREMENTS
A. Comply with ASME A13.1 and IEEE C2.
B. Comply with NFPA 70.
C. Comply with 29 CFR 1910.144 and 29 CFR 1910.145.
D. Comply with ANSI Z535.4 for safety signs and labels.
E. Adhesive-attached labeling materials, including label stocks, laminating adhesives, and inks used by label printers, shall comply with UL 969.
F. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes.
1. Temperature Change: 120 deg F, ambient; 180 deg F, material surfaces .
2.02 COLOR AND LEGEND REQUIREMENTS
A. Raceways and Cables Carrying Circuits at 600 V or Less:
1. Black letters on an orange field.
2. Legend: Indicate voltage and system or service type.
B. Color-Coding for Phase- and Voltage-Level Identification, 600 V or Less: Use colors listed below for ungrounded service feeder and branch-circuit conductors.
1. Color shall be factory applied or field applied for sizes larger than No. 8 AWG if authorities having jurisdiction permit.
2. Colors for 208/120-V Circuits:
a. Phase A: Black.
b. Phase B: Red.
c. Phase C: Blue.
3. Colors for 240-V Circuits:
a. Phase A: Black.
b. Phase B: Red.
Allentown, PA 18106 September 15, 2026
26 05 53-3
4. Colors for 480/277-V Circuits:
a. Phase A: Brown.
b. Phase B: Orange.
c. Phase C: Yellow.
5. Color for Neutral: White or gray.
6. Color for Equipment Grounds: Bare copper Green Green with a yellow stripe.
7. Colors for Isolated Grounds: Green with two or more yellow stripes.
C. Raceways and Cables Carrying Circuits at More Than 600 V:
1. Black letters on an orange field.
2. Legend: "DANGER - CONCEALED HIGH VOLTAGE WIRING."
D. Warning Label Colors:
1. Identify system voltage with black letters on an orange/red background.
E. Warning labels and signs shall include, but are not limited to, the following legends:
1. Multiple Power Source Warning: "DANGER - ELECTRICAL SHOCK HAZARD -
EQUIPMENT HAS MULTIPLE POWER SOURCES."
2. Workspace Clearance Warning: "WARNING - OSHA REGULATION - AREA IN
FRONT OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 36
INCHES."
F. Equipment Identification Labels:
1. Black letters on a white field.
G. Nameplates:
1. General: Precision engrave letters and numbers with uniform margins, character size minimum 3/16 inch high.
a. Phenolic: Two color laminated engravers stock, 1/16 inch minimum thickness, machine engraved to expose inner core color (white).
b. Aluminum: Standard aluminum alloy plate stock, minimum .032 inches thick, engraved areas enamel filled or background enameled with natural aluminum engraved characters.
c. Materials for Outdoor Applications: As recommended by nameplate manufacturer to suit environmental conditions.
2.03 LABELS
A. Vinyl Wraparound Labels: Preprinted, flexible labels laminated with a clear, weather- and chemical-resistant coating and matching wraparound clear adhesive tape for securing label ends.
Allentown, PA 18106 September 15, 2026
26 05 53-4
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Brady Corporation.
b. Panduit Corp.
c. Seton Identification Products; a Brady Corporation company.
d. Or equal.
B. Snap-around Labels: Slit, pretensioned, flexible, preprinted, color-coded acrylic sleeves, with diameters sized to suit diameters and that stay in place by gripping action.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Brady Corporation.
b. Panduit Corp.
c. Seton Identification Products; a Brady Corporation company.
d. Or equal.
C. Self-Adhesive Wraparound Labels: Preprinted, Write-on, 3-mil- thick, polyester, vinyl flexible label with acrylic pressure-sensitive adhesive.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Brady Corporation.
b. Ideal Industries, Inc.
c. Thomas & Betts Corp.
d. Or equal.
2. Self-Lamination: Clear; UV-, weather- and chemical-resistant; self-laminating, protective shield over the legend. Labels sized such that the clear shield overlaps the entire printed legend.
3. Marker for Labels:
a. Permanent, waterproof, black ink marker recommended by tag manufacturer.
b. Machine-printed, permanent, waterproof, black ink recommended by printer manufacturer.
D. Self-Adhesive Labels: Polyester, Vinyl, thermal, transfer-printed, 3-mil- thick, multicolor, weather- and UV-resistant, pressure-sensitive adhesive labels, configured for intended use and location.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
Allentown, PA 18106 September 15, 2026
26 05 53-5
a. Brady Corporation.
b. Ideal Industries, Inc.
c. Thomas & Betts Corp.
d. Or equal.
2. Minimum Nominal Size:
a. 1-1/2 by 6 inches for raceway and conductors.
b. 3-1/2 by 5 inches for equipment.
c. As required by authorities having jurisdiction.
2.04 BANDS AND TUBES
A. Snap-around, Color-Coding Bands: Slit, pretensioned, flexible, solid-colored acrylic sleeves, 2 inches long, with diameters sized to suit diameters and that stay in place by gripping action.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Brady Corporation.
b. HellermannTyton.
c. Panduit Corp.
d. Or equal.
B. Heat-Shrink Preprinted Tubes: Flame-retardant polyolefin tubes with machine-printed identification labels, sized to suit diameter and shrunk to fit firmly. Full shrink recovery occurs at a maximum of 200 deg F. Comply with UL 224.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. 3M.
b. Brady Corporation.
c. Panduit Corp.
d. Or equal.
2.05 TAPES AND STENCILS
A. Marker Tapes: Vinyl or vinyl-cloth, self-adhesive wraparound type, with circuit identification legend machine printed by thermal transfer or equivalent process.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not
a. HellermannTyton.
Allentown, PA 18106 September 15, 2026
26 05 53-6
b. Ideal Industries, Inc.
c. Panduit Corp.
d. Or equal.
B. Self-Adhesive Vinyl Tape: Colored, heavy duty, waterproof, fade resistant; not less than 3 mils thick by 1 to 2 inches wide; compounded for outdoor use.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Brady Corporation.
b. Carlton Industries, LP.
c. emedco.
d. Or equal.
C. Tape and Stencil: 4-inch- wide black stripes on 10-inch centers placed diagonally over orange background and are 12 inches wide. Stop stripes at legends.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Brimar Industries, Inc.
b. HellermannTyton.
c. Seton Identification Products; a Brady Corporation company.
d. Or equal.
D. Floor Marking Tape: 2-inch- wide, 5-mil pressure-sensitive vinyl tape, with black and white, yellow and black stripes and clear vinyl overlay.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. 3M.
b. Carlton Industries, LP.
c. Seton Identification Products; a Brady Corporation company.
d. Or equal.
E. Underground-Line Warning Tape:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Brady Corporation.
b. Ideal Industries, Inc.
c. Seton Identification Products; a Brady Corporation company.
d. Or equal.
Allentown, PA 18106 September 15, 2026
26 05 53-7
2. Tape:
a. Recommended by manufacturer for the method of installation and suitable to identify and locate underground electrical and communications utility lines.
b. Printing on tape shall be permanent and shall not be damaged by burial operations.
c. Tape material and ink shall be chemically inert and not subject to degradation when exposed to acids, alkalis, and other destructive substances commonly found in soils.
3. Color and Printing:
a. Comply with ANSI Z535.1, ANSI Z535.2, ANSI Z535.3, ANSI Z535.4, and
ANSI Z535.5.
b. Inscriptions for Red-Colored Tapes: "ELECTRIC LINE, HIGH VOLTAGE".
c. Inscriptions for Orange-Colored Tapes: "TELEPHONE CABLE, CATV
CABLE, COMMUNICATIONS CABLE, OPTICAL FIBER CABLE".
4. Tape Type I:
a. Pigmented polyolefin, bright colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service.
b. Width: 3 inches.
c. Thickness: 4 mils.
d. Weight: 18.5 lb/1000 sq. ft..
e. Tensile according to ASTM D882: 30 lbf and 2500 psi.
5. Tape Type II:
a. Multilayer laminate, consisting of high-density polyethylene scrim coated with pigmented polyolefin; bright colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service.
b. Width: 3 inches.
c. Thickness: 12 mils.
d. Weight: 36.1 lb/1000 sq. ft..
e. Tensile according to ASTM D882: 400 lbf and 11,500 psi.
6. Tape Type ID:
a. Detectable three-layer laminate, consisting of a printed pigmented polyolefin film, a solid aluminum-foil core, and a clear protective film that allows inspection of the continuity of the conductive core; bright colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service.
b. Width: 3 inches.
c. Overall Thickness: 5 mils.
d. Foil Core Thickness: 0.35 mil.
e. Weight: 28 lb/1000 sq. ft..
f. Tensile according to ASTM D882: 70 lbf and 4600 psi.
Allentown, PA 18106 September 15, 2026
26 05 53-8
7. Tape Type IID:
a. Reinforced, detectable three-layer laminate, consisting of a printed pigmented woven scrim, a solid aluminum-foil core, and a clear protective film that allows inspection of the continuity of the conductive core; bright-colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service.
b. Width: 3 inches.
c. Overall Thickness: 8 mils.
d. Foil Core Thickness: 0.35 mil.
e. Weight: 34 lb/1000 sq. ft..
f. Tensile according to ASTM D882: 300 lbf and 12,500 psi.
F. Stenciled Legend: In nonfading, waterproof, black ink or paint. Minimum letter height shall be 1 inch.
2.06 TAGS
A. Metal Tags: Brass or aluminum, 2 by 2 by 0.05 inch, with stamped legend, punched for use with self-locking cable tie fastener.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Brady Corporation.
b. Carlton Industries, LP.
c. Seton Identification Products; a Brady Corporation company.
d. Or equal.
B. Nonmetallic Preprinted Tags: Polyethylene tags, 0.015 inch 0.023 inch thick, color-coded for phase and voltage level, with factory screened printed permanent designations;
punched for use with self-locking cable tie fastener.
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Brady Corporation.
b. Panduit Corp.
c. Seton Identification Products; a Brady Corporation company.
d. Or equal.
C. Write-on Tags:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not
Allentown, PA 18106 September 15, 2026
26 05 53-9
a. Brimar Industries, Inc.
b. Carlton Industries, LP.
c. Seton Identification Products; a Brady Corporation company.
d. Or equal.
2. Polyester Tags: 0.010 inch, 0.015 inch thick, with corrosion-resistant grommet and cable tie for attachment.
3. Marker for Tags:
a. Permanent, waterproof, black ink marker recommended by tag manufacturer.
b. Machine-printed, permanent, waterproof, black ink marker recommended by printer manufacturer.
2.07 SIGNS
A. Baked-Enamel Signs:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Carlton Industries, LP.
b. Champion America.
c. Marking Services, Inc.
d. Or equal.
2. Preprinted aluminum signs, high-intensity reflective, punched or drilled for fasteners, with colors, legend, and size required for application.
3. 1/4-inch grommets in corners for mounting.
4. Nominal Size: 7 by 10 inches.
B. Metal-Backed Butyrate Signs:
1. Weather-resistant, nonfading, preprinted, cellulose-acetate butyrate signs, with 0.0396-inch galvanized-steel backing, punched and drilled for fasteners, and with colors, legend, and size required for application.
2. 1/4-inch grommets in corners for mounting.
3. Nominal Size: 10 by 14 inches.
C. Laminated Acrylic or Melamine Plastic Signs:
1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
a. Brady Corporation.
b. Carlton Industries, LP.
c. Marking Services, Inc.
Allentown, PA 18106 September 15, 2026
26 05 53-10
d. Or equal.
2. Engraved legend.
3. Thickness:
a. For signs up to 20 sq. in., minimum 1/16 inch thick.
b. For signs larger than 20 sq. in., 1/8 inch thick.
c. Engraved legend with black letters on white face, white letters on a dark gray background.
d. Punched or drilled for mechanical fasteners with 1/4-inch grommets in corners for mounting Self-adhesive.
e. Framed with mitered acrylic molding and arranged for attachment at applicable equipment.
2.08 CABLE TIES
A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following:
1. HellermannTyton.
2. Ideal Industries, Inc.
3. Panduit Corp.
4. Or equal.
B. General-Purpose Cable Ties: Fungus inert, self-extinguishing, one piece, self-locking, and Type 6/6 nylon.
1. Minimum Width: 3/16 inch.
2. Tensile Strength at 73 Deg F according to ASTM D638: 12,000 psi.
3. Temperature Range: Minus 40 to plus 185 deg F.
4. Color: Black, except where used for color-coding.
C. UV-Stabilized Cable Ties: Fungus inert, designed for continuous exposure to exterior sunlight, self-extinguishing, one piece, self-locking, and Type 6/6 nylon.
1. Minimum Width: 3/16 inch.
2. Tensile Strength at 73 Deg F according to ASTM D638: 12,000 psi.
3. Temperature Range: Minus 40 to plus 185 deg F.
4. Color: Black.
D. Plenum-Rated Cable Ties: Self-extinguishing, UV stabilized, one piece, and self-locking.
1. Minimum Width: 3/16 inch.
2. Tensile Strength at 73 Deg F according to ASTM D638: 7000 psi.
3. UL 94 Flame Rating: 94V-0.
4. Temperature Range: Minus 50 to plus 284 deg F.
5. Color: Black.
Allentown, PA 18106 September 15, 2026
26 05 53-11
2.09 MISCELLANEOUS IDENTIFICATION PRODUCTS
A. Paint: Comply with requirements in painting Sections for paint materials and application requirements. Retain paint system applicable for surface material and location (exterior or interior).
B. Fasteners for Labels and Signs: Self-tapping, stainless-steel screws or stainless-steel machine screws with nuts and flat and lock washers.
PART 3 EXECUTION
3.01 PREPARATION
A. Self-Adhesive Identification Products: Before applying electrical identification products, clean substrates of substances that could impair bond, using materials and methods recommended by manufacturer of identification product.
3.02 INSTALLATION
A. Verify and coordinate identification names, abbreviations, colors, and other features with requirements in other Sections requiring identification applications, Drawings, Shop Drawings, manufacturer's wiring diagrams, and operation and maintenance manual. Use consistent designations throughout Project.
B. Install identifying devices before installing acoustical ceilings and similar concealment.
C. Verify identity of each item before installing identification products.
D. Coordinate identification with Project Drawings, manufacturer's wiring diagrams, and operation and maintenance manual.
E. Apply identification devices to surfaces that require finish after completing finish work.
F. Install signs with approved legend to facilitate proper identification, operation, and maintenance of electrical systems and connected items.
G. System Identification for Raceways and Cables under 600 V: Identification shall completely encircle cable or conduit. Place identification of two-color markings in contact, side by side.
1. Secure tight to surface of conductor, cable, or raceway.
H. System Identification for Raceways and Cables over 600 V: Identification shall completely encircle cable or conduit. Place adjacent identification of two-color markings in contact, side by side.
1. Secure tight to surface of conductor, cable, or raceway.
Allentown, PA 18106 September 15, 2026
26 05 53-12
I. Auxiliary Electrical Systems Conductor Identification: Identify field-installed alarm, control, and signal connections.
J. Emergency Operating Instruction Signs: Install instruction signs with white legend on a red background with minimum 3/8-inch- high letters for emergency instructions at equipment used for power transfer, load shedding.
K. Elevated Components: Increase sizes of labels, signs, and letters to those appropriate for viewing from the floor.
L. Accessible Fittings for Raceways: Identify the covers of each junction and pull box of the following systems with the wiring system legend and system voltage. System legends shall be as follows:
1. "EMERGENCY POWER."
2. "POWER."
3. "UPS."
M. Vinyl Wraparound Labels:
1. Secure tight to surface of raceway or cable at a location with high visibility and accessibility.
2. Attach labels that are not self-adhesive type with clear vinyl tape, with adhesive appropriate to the location and substrate.
N. Snap-around Labels: Secure tight to surface at a location with high visibility and accessibility.
O. Self-Adhesive Wraparound Labels: Secure tight to surface at a location with high visibility and accessibility.
P. Self-Adhesive Labels:
1. On each item, install unique designation label that is consistent with wiring diagrams, schedules, and operation and maintenance manual.
2. Unless otherwise indicated, provide a single line of text with 1/2-inch- high letters on 1-1/2-inch- high label; where two lines of text are required, use labels 2 inches high.
Q. Snap-around Color-Coding Bands: Secure tight to surface at a location with high visibility and accessibility.
R. Heat-Shrink, Preprinted Tubes: Secure tight to surface at a location with high visibility and accessibility.
S. Marker Tapes: Secure tight to surface at a location with high visibility and accessibility.
T. Self-Adhesive Vinyl Tape: Secure tight to surface at a location with high visibility and accessibility.
Allentown, PA 18106 September 15, 2026
26 05 53-13
1. Field-Applied, Color-Coding Conductor Tape: Apply in half-lapped turns for a minimum distance of 6 inches where splices or taps are made. Apply last two turns of tape with no tension to prevent possible unwinding.
U. Tape and Stencil: Comply with requirements in painting Sections for surface preparation and paint application.
V. Floor Marking Tape: Apply stripes to finished surfaces following manufacturer's written instructions.
W. Underground Line Warning Tape:
1. During backfilling of trenches, install continuous underground-line warning tape directly above cable or raceway at 6 to 8 inches below finished grade. Use multiple tapes where width of multiple lines installed in a common trench or concrete envelope exceeds 16 inches overall.
2. Limit use of underground-line warning tape to direct-buried cables.
3. Install underground-line warning tape for direct-buried cables and cables in raceways.
X. Metal Tags:
1. Place in a location with high visibility and accessibility.
2. Secure using general-purpose UV-stabilized plenum-rated cable ties.
Y. Nonmetallic Preprinted Tags:
1. Place in a location with high visibility and accessibility.
2. Secure using general-purpose UV-stabilized plenum-rated cable ties.
Z. Write-on Tags:
1. Place in a location with high visibility and accessibility.
2. Secure using general-purpose UV-stabilized plenum-rated cable ties.
AA. Baked-Enamel Signs:
1. Attach signs that are not self-adhesive type with mechanical fasteners appropriate to the location and substrate.
2. Unless otherwise indicated, provide a single line of text with 1/2-inch- high letters on minimum 1-1/2-inch- high sign; where two lines of text are required, use signs minimum 2 inches high.
BB. Metal-Backed Butyrate Signs:
1. Attach signs that are not self-adhesive type with mechanical fasteners appropriate to the location and substrate.
2. Unless otherwise indicated, provide a single line of text with 1/2-inch- high letters on 1-1/2-inch- high sign; where two lines of text are required, use labels 2 inches high.
Allentown, PA 18106 September 15, 2026
26 05 53-14
CC. Laminated Acrylic or Melamine Plastic Signs:
1. Attach signs that are not self-adhesive type with mechanical fasteners appropriate to the location and substrate.
2. Unless otherwise indicated, provide a single line of text with 1/2-inch- high letters on 1-1/2-inch- high sign; where two lines of text are required, use labels 2 inches high.
DD. Cable Ties: General purpose, for attaching tags, except as listed below:
1. Outdoors: UV-stabilized nylon.
2. In Spaces Handling Environmental Air: Plenum rated.
3.03 IDENTIFICATION SCHEDULE
A. Install identification materials and devices at locations for most convenient viewing without interference with operation and maintenance of equipment. Install access doors or panels to provide view of identifying devices.
B. Identify conductors, cables, and terminals in enclosures and at junctions, terminals, pull points, and locations of high visibility. Identify by system and circuit designation.
C. Concealed Raceways, Duct Banks, More Than 600 V, within Buildings: Tape and stencil.
Stencil legend "DANGER - CONCEALED HIGH-VOLTAGE WIRING" with 3-inch- high, black letters on 20-inch centers.
1. Locate identification at changes in direction, at penetrations of walls and floors, and at 10-foot 30-foot maximum intervals.
D. Accessible Raceways, Armored and Metal-Clad Cables, More Than 600 V: Vinyl wraparound labels Snap-around labels Self-adhesive labels Snap-around color-coding bands for raceway and cables.
1. Locate identification at changes in direction, at penetrations of walls and floors, at 50-foot maximum intervals in straight runs, and at 25-foot maximum intervals in congested areas.
E. Accessible Raceways and Metal-Clad Cables, 600 V or Less, for Service, Feeder, and Branch Circuits, More Than 30 A and 120 V to Ground: Identify with self-adhesive raceway labels vinyl tape applied in bands.
1. Locate identification at changes in direction, at penetrations of walls and floors, at 50-foot maximum intervals in straight runs, and at 25-foot maximum intervals in congested areas.
F. Accessible Fittings for Raceways and Cables within Buildings: Identify the covers of each junction and pull box of the following systems with self-adhesive labels containing the wiring system legend and system voltage. System legends shall be as follows:
Allentown, PA 18106 September 15, 2026
26 05 53-15
1. "EMERGENCY POWER."
2. "POWER."
3. "UPS."
G. Power-Circuit Conductor Identification, 600 V or Less: For conductors in vaults, pull and junction boxes, manholes, and handholes, use vinyl wraparound labels self-adhesive wraparound labels snap-around labels snap-around color-coding bands self-adhesive vinyl tape to identify the phase.
1. Locate identification at changes in direction, at penetrations of walls and floors, at 50-foot maximum intervals in straight runs, and at 25-foot maximum intervals in congested areas.
H. Power-Circuit Conductor Identification, More Than 600 V: For conductors in vaults, pull and junction boxes, manholes, and handholes, use write-on tags nonmetallic preprinted tags colored and marked to indicate phase, and a separate tag with the circuit designation.
I. Control-Circuit Conductor Identification: For conductors and cables in pull and junction boxes, manholes, and handholes, use write-on tags self-adhesive labels with the conductor or cable designation, origin, and destination.
J. Control-Circuit Conductor Termination Identification: For identification at terminations, provide heat-shrink preprinted tubes self-adhesive labels with the conductor designation.
K. Conductors to Be Extended in the Future: Attach write-on tags marker tape to conductors and list source.
L. Auxiliary Electrical Systems Conductor Identification: Marker tape Self-adhesive vinyl tape that is uniform and consistent with system used by manufacturer for factory-installed connections.
1. Identify conductors, cables, and terminals in enclosures and at junctions, terminals, and pull points. Identify by system and circuit designation.
M. Locations of Underground Lines: Underground-line warning tape for power, lighting, communication, and control wiring and optical-fiber cable.
N. Concealed Raceways and Duct Banks, More Than 600 V, within Buildings: Apply floor marking tape to the following finished surfaces:
1. Floor surface directly above conduits running beneath and within 12 inches of a floor that is in contact with earth or is framed above unexcavated space.
2. Wall surfaces directly external to raceways concealed within wall.
3. Accessible surfaces of concrete envelope around raceways in vertical shafts, exposed in the building, or concealed above suspended ceilings.
O. Workspace Indication: Apply floor marking tape or tape and stencil to finished surfaces.
Show working clearances in the direction of access to live parts. Workspace shall comply
Allentown, PA 18106 September 15, 2026
26 05 53-16 with NFPA 70 and 29 CFR 1926.403 unless otherwise indicated. Do not install at flush-mounted panelboards and similar equipment in finished spaces.
P. Instructional Signs: Self-adhesive labels, including the color code for grounded and ungrounded conductors.
Q. Warning Labels for Indoor Cabinets, Boxes, and Enclosures for Power and Lighting: Self-adhesive labels Baked-enamel warning signs Metal-backed, butyrate warning signs.
1. Apply to exterior of door, cover, or other access.
2. For equipment with multiple power or control sources, apply to door or cover of equipment, including, but not limited to, the following:
a. Power-transfer switches.
b. Controls with external control power connections.
R. Arc Flash Warning Labeling: Self-adhesive labels.
S. Operating Instruction Signs: Self-adhesive labels Baked-enamel warning signs Metal-backed, butyrate warning signs Laminated acrylic or melamine plastic signs.
T. Emergency Operating Instruction Signs: Self-adhesive labels Baked-enamel warning signs Metal-backed, butyrate warning signs Laminated acrylic or melamine plastic signs with white legend on a red background with minimum 3/8-inch- high letters for emergency instructions at equipment used for power transfer load shedding.
U. Equipment Identification Labels:
1. Indoor Equipment: Self-adhesive label Baked-enamel signs Metal-backed butyrate signs Laminated acrylic or melamine plastic sign.
2. Outdoor Equipment: Laminated acrylic or melamine sign Stenciled legend 4 inches high.
3. Equipment to Be Labeled:
a. Panelboards: Typewritten directory of circuits in the location provided by panelboard manufacturer. Panelboard identification shall be in the form of a self-adhesive, engraved, engraved, laminated acrylic or melamine label.
b. Enclosures and electrical cabinets.
c. Access doors and panels for concealed electrical items.
d. Switchgear.
e. Switchboards.
f. Transformers: Label that includes tag designation indicated on Drawings for the transformer, feeder, and panelboards or equipment supplied by the secondary.
g. Substations.
h. Emergency system boxes and enclosures.
i. Motor-control centers.
j. Enclosed switches.
k. Enclosed circuit breakers.
l. Enclosed controllers.
Allentown, PA 18106 September 15, 2026
26 05 53-17
m. Variable-speed controllers.
n. Push-button stations.
o. Power-transfer equipment.
p. Contactors.
q. Remote-controlled switches, dimmer modules, and control devices.
r. Battery-inverter units.
s. Battery racks.
t. Power-generating units.
u. Monitoring and control equipment.
v. UPS equipment.
w. Other equipment.
END OF SECTION 260553
| PART 1 GENERAL |
| 1.01 RELATED DOCUMENTS |
| A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. |
| 1.02 SUMMARY |
| A. Section Includes: |
| 1. Labels. |
| 2. Bands and tubes. |
| 3. Tapes and stencils. |
| 4. Tags. |
| 5. Signs. |
| 6. Cable ties. |
| 7. Miscellaneous identification products. |
| 1.03 SUBMITTALS |
| A. Submittals for this section are subject to the re-evaluation fee identified in Article 4 of the General Conditions. |
| B. Manufacturer’s installation instructions shall be provided along with product data. |
| C. Submittals shall be provided in the order in which they are specified and tabbed (for combined submittals). |
| D. Product Data: For each type of product. |
| 1. Include construction details, material descriptions, dimensions of individual components and profiles, and finishes for electrical identification products. |
| E. Samples: For each type of label and sign to illustrate composition, size, colors, lettering style, mounting provisions, and graphic features of identification products. |
| F. Identification Schedule: For each piece of electrical equipment and electrical system components to be an index of nomenclature for electrical equipment and system components used in identification signs and labels. Use same designations indicated ... |
| G. Delegated-Design Submittal: For arc-flash hazard study. |
| H. Submittals for this section are subject to the re-evaluation fee identified in Article 4 of the General Conditions. |
| PART 2 PRODUCTS |
| 2.01 PERFORMANCE REQUIREMENTS |
| A. Comply with ASME A13.1 and IEEE C2. |
| B. Comply with NFPA 70. |
| C. Comply with 29 CFR 1910.144 and 29 CFR 1910.145. |
| D. Comply with ANSI Z535.4 for safety signs and labels. |
| E. Adhesive-attached labeling materials, including label stocks, laminating adhesives, and inks used by label printers, shall comply with UL 969. |
| F. Thermal Movements: Allow for thermal movements from ambient and surface temperature changes. |
| 1. Temperature Change: 120 deg F, ambient; 180 deg F, material surfaces . |
| 2.02 COLOR AND LEGEND REQUIREMENTS |
| A. Raceways and Cables Carrying Circuits at 600 V or Less: |
| 1. Black letters on an orange field. |
| 2. Legend: Indicate voltage and system or service type. |
| B. Color-Coding for Phase- and Voltage-Level Identification, 600 V or Less: Use colors listed below for ungrounded service feeder and branch-circuit conductors. |
| 1. Color shall be factory applied or field applied for sizes larger than No. 8 AWG if authorities having jurisdiction permit. |
| 2. Colors for 208/120-V Circuits: |
| a. Phase A: Black. |
| b. Phase B: Red. |
| c. Phase C: Blue. |
| 3. Colors for 240-V Circuits: |
| a. Phase A: Black. |
| b. Phase B: Red. |
| 4. Colors for 480/277-V Circuits: |
| a. Phase A: Brown. |
| b. Phase B: Orange. |
| c. Phase C: Yellow. |
| 5. Color for Neutral: White or gray. |
| 6. Color for Equipment Grounds: Bare copper Green Green with a yellow stripe. |
| 7. Colors for Isolated Grounds: Green with two or more yellow stripes. |
| C. Raceways and Cables Carrying Circuits at More Than 600 V: |
| 1. Black letters on an orange field. |
| 2. Legend: "DANGER - CONCEALED HIGH VOLTAGE WIRING." |
| D. Warning Label Colors: |
| 1. Identify system voltage with black letters on an orange/red background. |
| E. Warning labels and signs shall include, but are not limited to, the following legends: |
| 1. Multiple Power Source Warning: "DANGER - ELECTRICAL SHOCK HAZARD - EQUIPMENT HAS MULTIPLE POWER SOURCES." |
| 2. Workspace Clearance Warning: "WARNING - OSHA REGULATION - AREA IN FRONT OF ELECTRICAL EQUIPMENT MUST BE KEPT CLEAR FOR 36 INCHES." |
| F. Equipment Identification Labels: |
| 1. Black letters on a white field. |
| G. Nameplates: |
| 1. General: Precision engrave letters and numbers with uniform margins, character size minimum 3/16 inch high. |
| a. Phenolic: Two color laminated engravers stock, 1/16 inch minimum thickness, machine engraved to expose inner core color (white). |
| b. Aluminum: Standard aluminum alloy plate stock, minimum .032 inches thick, engraved areas enamel filled or background enameled with natural aluminum engraved characters. |
| c. Materials for Outdoor Applications: As recommended by nameplate manufacturer to suit environmental conditions. |
| 2.03 LABELS |
| A. Vinyl Wraparound Labels: Preprinted, flexible labels laminated with a clear, weather- and chemical-resistant coating and matching wraparound clear adhesive tape for securing label ends. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brady Corporation. |
| b. Panduit Corp. |
| c. Seton Identification Products; a Brady Corporation company. |
| d. Or equal. |
| B. Snap-around Labels: Slit, pretensioned, flexible, preprinted, color-coded acrylic sleeves, with diameters sized to suit diameters and that stay in place by gripping action. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brady Corporation. |
| b. Panduit Corp. |
| c. Seton Identification Products; a Brady Corporation company. |
| d. Or equal. |
| C. Self-Adhesive Wraparound Labels: Preprinted, Write-on, 3-mil- thick, polyester, vinyl flexible label with acrylic pressure-sensitive adhesive. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brady Corporation. |
| b. Ideal Industries, Inc. |
| c. Thomas & Betts Corp. |
| d. Or equal. |
| 2. Self-Lamination: Clear; UV-, weather- and chemical-resistant; self-laminating, protective shield over the legend. Labels sized such that the clear shield overlaps the entire printed legend. |
| 3. Marker for Labels: |
| a. Permanent, waterproof, black ink marker recommended by tag manufacturer. |
| b. Machine-printed, permanent, waterproof, black ink recommended by printer manufacturer. |
| D. Self-Adhesive Labels: Polyester, Vinyl, thermal, transfer-printed, 3-mil- thick, multicolor, weather- and UV-resistant, pressure-sensitive adhesive labels, configured for intended use and location. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brady Corporation. |
| b. Ideal Industries, Inc. |
| c. Thomas & Betts Corp. |
| d. Or equal. |
| 2. Minimum Nominal Size: |
| a. 1-1/2 by 6 inches for raceway and conductors. |
| b. 3-1/2 by 5 inches for equipment. |
| c. As required by authorities having jurisdiction. |
| 2.04 BANDS AND TUBES |
| A. Snap-around, Color-Coding Bands: Slit, pretensioned, flexible, solid-colored acrylic sleeves, 2 inches long, with diameters sized to suit diameters and that stay in place by gripping action. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brady Corporation. |
| b. HellermannTyton. |
| c. Panduit Corp. |
| d. Or equal. |
| B. Heat-Shrink Preprinted Tubes: Flame-retardant polyolefin tubes with machine-printed identification labels, sized to suit diameter and shrunk to fit firmly. Full shrink recovery occurs at a maximum of 200 deg F. Comply with UL 224. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. 3M. |
| b. Brady Corporation. |
| c. Panduit Corp. |
| d. Or equal. |
| 2.05 TAPES AND STENCILS |
| A. Marker Tapes: Vinyl or vinyl-cloth, self-adhesive wraparound type, with circuit identification legend machine printed by thermal transfer or equivalent process. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. HellermannTyton. |
| b. Ideal Industries, Inc. |
| c. Panduit Corp. |
| d. Or equal. |
| B. Self-Adhesive Vinyl Tape: Colored, heavy duty, waterproof, fade resistant; not less than 3 mils thick by 1 to 2 inches wide; compounded for outdoor use. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brady Corporation. |
| b. Carlton Industries, LP. |
| c. emedco. |
| d. Or equal. |
| C. Tape and Stencil: 4-inch- wide black stripes on 10-inch centers placed diagonally over orange background and are 12 inches wide. Stop stripes at legends. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brimar Industries, Inc. |
| b. HellermannTyton. |
| c. Seton Identification Products; a Brady Corporation company. |
| d. Or equal. |
| D. Floor Marking Tape: 2-inch- wide, 5-mil pressure-sensitive vinyl tape, with black and white, yellow and black stripes and clear vinyl overlay. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. 3M. |
| b. Carlton Industries, LP. |
| c. Seton Identification Products; a Brady Corporation company. |
| d. Or equal. |
| E. Underground-Line Warning Tape: |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brady Corporation. |
| b. Ideal Industries, Inc. |
| c. Seton Identification Products; a Brady Corporation company. |
| d. Or equal. |
| 2. Tape: |
| a. Recommended by manufacturer for the method of installation and suitable to identify and locate underground electrical and communications utility lines. |
| b. Printing on tape shall be permanent and shall not be damaged by burial operations. |
| c. Tape material and ink shall be chemically inert and not subject to degradation when exposed to acids, alkalis, and other destructive substances commonly found in soils. |
| 3. Color and Printing: |
| a. Comply with ANSI Z535.1, ANSI Z535.2, ANSI Z535.3, ANSI Z535.4, and ANSI Z535.5. |
| b. Inscriptions for Red-Colored Tapes: "ELECTRIC LINE, HIGH VOLTAGE". |
| c. Inscriptions for Orange-Colored Tapes: "TELEPHONE CABLE, CATV CABLE, COMMUNICATIONS CABLE, OPTICAL FIBER CABLE". |
| 4. Tape Type I: |
| a. Pigmented polyolefin, bright colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service. |
| b. Width: 3 inches. |
| c. Thickness: 4 mils. |
| d. Weight: 18.5 lb/1000 sq. ft.. |
| e. Tensile according to ASTM D882: 30 lbf and 2500 psi. |
| 5. Tape Type II: |
| a. Multilayer laminate, consisting of high-density polyethylene scrim coated with pigmented polyolefin; bright colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service. |
| b. Width: 3 inches. |
| c. Thickness: 12 mils. |
| d. Weight: 36.1 lb/1000 sq. ft.. |
| e. Tensile according to ASTM D882: 400 lbf and 11,500 psi. |
| 6. Tape Type ID: |
| a. Detectable three-layer laminate, consisting of a printed pigmented polyolefin film, a solid aluminum-foil core, and a clear protective film that allows inspection of the continuity of the conductive core; bright colored, continuous-printed on one s... |
| b. Width: 3 inches. |
| c. Overall Thickness: 5 mils. |
| d. Foil Core Thickness: 0.35 mil. |
| e. Weight: 28 lb/1000 sq. ft.. |
| f. Tensile according to ASTM D882: 70 lbf and 4600 psi. |
| 7. Tape Type IID: |
| a. Reinforced, detectable three-layer laminate, consisting of a printed pigmented woven scrim, a solid aluminum-foil core, and a clear protective film that allows inspection of the continuity of the conductive core; bright-colored, continuous-printed ... |
| b. Width: 3 inches. |
| c. Overall Thickness: 8 mils. |
| d. Foil Core Thickness: 0.35 mil. |
| e. Weight: 34 lb/1000 sq. ft.. |
| f. Tensile according to ASTM D882: 300 lbf and 12,500 psi. |
F. Stenciled Legend: In nonfading, waterproof, black ink or paint. Minimum letter height shall be 1 inch.
| 2.06 TAGS |
| A. Metal Tags: Brass or aluminum, 2 by 2 by 0.05 inch, with stamped legend, punched for use with self-locking cable tie fastener. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brady Corporation. |
| b. Carlton Industries, LP. |
| c. Seton Identification Products; a Brady Corporation company. |
| d. Or equal. |
| B. Nonmetallic Preprinted Tags: Polyethylene tags, 0.015 inch 0.023 inch thick, color-coded for phase and voltage level, with factory screened printed permanent designations; punched for use with self-locking cable tie fastener. |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brady Corporation. |
| b. Panduit Corp. |
| c. Seton Identification Products; a Brady Corporation company. |
| d. Or equal. |
| C. Write-on Tags: |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brimar Industries, Inc. |
| b. Carlton Industries, LP. |
| c. Seton Identification Products; a Brady Corporation company. |
| d. Or equal. |
| 2. Polyester Tags: 0.010 inch, 0.015 inch thick, with corrosion-resistant grommet and cable tie for attachment. |
| 3. Marker for Tags: |
| a. Permanent, waterproof, black ink marker recommended by tag manufacturer. |
| b. Machine-printed, permanent, waterproof, black ink marker recommended by printer manufacturer. |
| 2.07 SIGNS |
| A. Baked-Enamel Signs: |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Carlton Industries, LP. |
| b. Champion America. |
| c. Marking Services, Inc. |
| d. Or equal. |
| 2. Preprinted aluminum signs, high-intensity reflective, punched or drilled for fasteners, with colors, legend, and size required for application. |
| 3. 1/4-inch grommets in corners for mounting. |
| 4. Nominal Size: 7 by 10 inches. |
| B. Metal-Backed Butyrate Signs: |
| 1. Weather-resistant, nonfading, preprinted, cellulose-acetate butyrate signs, with 0.0396-inch galvanized-steel backing, punched and drilled for fasteners, and with colors, legend, and size required for application. |
| 2. 1/4-inch grommets in corners for mounting. |
| 3. Nominal Size: 10 by 14 inches. |
| C. Laminated Acrylic or Melamine Plastic Signs: |
| 1. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| a. Brady Corporation. |
| b. Carlton Industries, LP. |
| c. Marking Services, Inc. |
| d. Or equal. |
| 2. Engraved legend. |
| 3. Thickness: |
| a. For signs up to 20 sq. in., minimum 1/16 inch thick. |
| b. For signs larger than 20 sq. in., 1/8 inch thick. |
| c. Engraved legend with black letters on white face, white letters on a dark gray background. |
| d. Punched or drilled for mechanical fasteners with 1/4-inch grommets in corners for mounting Self-adhesive. |
| e. Framed with mitered acrylic molding and arranged for attachment at applicable equipment. |
| 2.08 CABLE TIES |
| A. Manufacturers: Subject to compliance with requirements, available manufacturers offering products that may be incorporated into the Work include, but are not limited to the following: |
| 1. HellermannTyton. |
| 2. Ideal Industries, Inc. |
| 3. Panduit Corp. |
| 4. Or equal. |
| B. General-Purpose Cable Ties: Fungus inert, self-extinguishing, one piece, self-locking, and Type 6/6 nylon. |
| 1. Minimum Width: 3/16 inch. |
| 2. Tensile Strength at 73 Deg F according to ASTM D638: 12,000 psi. |
| 3. Temperature Range: Minus 40 to plus 185 deg F. |
| 4. Color: Black, except where used for color-coding. |
| C. UV-Stabilized Cable Ties: Fungus inert, designed for continuous exposure to exterior sunlight, self-extinguishing, one piece, self-locking, and Type 6/6 nylon. |
| 1. Minimum Width: 3/16 inch. |
| 2. Tensile Strength at 73 Deg F according to ASTM D638: 12,000 psi. |
| 3. Temperature Range: Minus 40 to plus 185 deg F. |
| 4. Color: Black. |
| D. Plenum-Rated Cable Ties: Self-extinguishing, UV stabilized, one piece, and self-locking. |
| 1. Minimum Width: 3/16 inch. |
| 2. Tensile Strength at 73 Deg F according to ASTM D638: 7000 psi. |
| 3. UL 94 Flame Rating: 94V-0. |
| 4. Temperature Range: Minus 50 to plus 284 deg F. |
| 5. Color: Black. |
| 2.09 MISCELLANEOUS IDENTIFICATION PRODUCTS |
| A. Paint: Comply with requirements in painting Sections for paint materials and application requirements. Retain paint system applicable for surface material and location (exterior or interior). |
| B. Fasteners for Labels and Signs: Self-tapping, stainless-steel screws or stainless-steel machine screws with nuts and flat and lock washers. |
| PART 3 EXECUTION |
| 3.01 PREPARATION |
| A. Self-Adhesive Identification Products: Before applying electrical identification products, clean substrates of substances that could impair bond, using materials and methods recommended by manufacturer of identification product. |
| 3.02 INSTALLATION |
| A. Verify and coordinate identification names, abbreviations, colors, and other features with requirements in other Sections requiring identification applications, Drawings, Shop Drawings, manufacturer's wiring diagrams, and operation and maintenance ... |
| B. Install identifying devices before installing acoustical ceilings and similar concealment. |
| C. Verify identity of each item before installing identification products. |
| D. Coordinate identification with Project Drawings, manufacturer's wiring diagrams, and operation and maintenance manual. |
| E. Apply identification devices to surfaces that require finish after completing finish work. |
| F. Install signs with approved legend to facilitate proper identification, operation, and maintenance of electrical systems and connected items. |
| G. System Identification for Raceways and Cables under 600 V: Identification shall completely encircle cable or conduit. Place identification of two-color markings in contact, side by side. |
| 1. Secure tight to surface of conductor, cable, or raceway. |
| H. System Identification for Raceways and Cables over 600 V: Identification shall completely encircle cable or conduit. Place adjacent identification of two-color markings in contact, side by side. |
| 1. Secure tight to surface of conductor, cable, or raceway. |
| I. Auxiliary Electrical Systems Conductor Identification: Identify field-installed alarm, control, and signal connections. |
| J. Emergency Operating Instruction Signs: Install instruction signs with white legend on a red background with minimum 3/8-inch- high letters for emergency instructions at equipment used for power transfer, load shedding. |
| K. Elevated Components: Increase sizes of labels, signs, and letters to those appropriate for viewing from the floor. |
| L. Accessible Fittings for Raceways: Identify the covers of each junction and pull box of the following systems with the wiring system legend and system voltage. System legends shall be as follows: |
| 1. "EMERGENCY POWER." |
| 2. "POWER." |
| 3. "UPS." |
| M. Vinyl Wraparound Labels: |
| 1. Secure tight to surface of raceway or cable at a location with high visibility and accessibility. |
| 2. Attach labels that are not self-adhesive type with clear vinyl tape, with adhesive appropriate to the location and substrate. |
| N. Snap-around Labels: Secure tight to surface at a location with high visibility and accessibility. |
| O. Self-Adhesive Wraparound Labels: Secure tight to surface at a location with high visibility and accessibility. |
| P. Self-Adhesive Labels: |
| 1. On each item, install unique designation label that is consistent with wiring diagrams, schedules, and operation and maintenance manual. |
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .