1-LCA-ELECTRICAL SUBSTATION PROCUREMENT DWGS.pdf

PDF 3 MB Posted

Attached to
Electrical Substation Replacement Project – Equipment Procurement Phase
Solicitation number
US.255952
Issued by
Lehigh County, Pennsylvania

About this file

File Summary

This is a Scope of Work and Procurement Drawing Package for the Lehigh County Authority's Electrical Substation Replacement Project, specifically the equipment procurement phase for Substation #2 and Substation #4 located at the Authority's Pretreatment Plant in Allentown, Pennsylvania. The project involves procurement of electrical switchgear and related equipment for two substations, including 15kV class metal-clad switchgear assemblies, 600V class low-voltage switchgear, power transformers, protective relaying systems, and associated components. The work is limited to equipment procurement only and does not include installation or construction. Sealed bids will be received via PennBid until 11:00 a.m. on Wednesday, October 28, 2026, with public opening and reading to follow. Self-guided site visits may be scheduled by contacting Charles Volk, P.E., Chief Capital Works Officer, at charlesvolk@lehighcountyauthority.org. Bids shall remain open for 60 days from the opening date, and equipment delivery is specified as 650 calendar days from the date of agreement approval by the Comptroller, with an expedited delivery alternate available for additional cost.

Bid security of 10 percent of the total bid amount is required in the form of a certified check, bank check, or bid bond. All electrical equipment must be manufactured to comply with NEC, NEMA, IBC, ANSI, IEEE, and UL standards, and must be rated for the specified voltage classes, short-circuit ratings, and environmental conditions. The procurement documents require bidders to submit certified test reports, factory acceptance testing results, shop drawings, one-line diagrams, control wiring diagrams, and arc flash studies prior to fabrication and shipment. An Extended Warranty Alternate 1 is mandatory, with bidders required to provide separate line-item pricing for 12, 24, and 36-month extended warranties beyond the standard 24-month manufacturer warranty. All bidders must submit a Deviation List identifying any deviations from contract documents or compliance will be assumed. The Lehigh County Authority reserves the right to reject any and all bids and to waive any omissions, errors, or irregularities. Bidding documents are available at no cost through PennBid.

View the file

Other files

File Type Posted
26 11 16.11 - Secondary Unit Substations - Secondary Less Than 1000V.pdf PDF
26 12 13.01 - Liquid-Filled Medium Voltge Unit Substation Transformers.pdf PDF
9-Agreement of Surety Form Contract.pdf PDF
23-EJCDC - Payment Bond (C-620-2002).pdf PDF
017716 – CONTRACT CLOSEOUT.pdf PDF
15-Affidavit of Non-Collusion.pdf PDF
21-EJCDC - Performance Bond (C-600-2002).pdf PDF
012977.02 - MEASUREMENT AND PAYMENT.pdf PDF
13-List of Proposed Subcontractors.pdf PDF
26 27 13.11 - Microprocessor-Based Metering Equipment.pdf PDF
017900.01 - VIDEO TRAINING PROGRAMS.pdf PDF
26 23 00.16 - Arc Resistant Metal Enclosed Drawout Switchgear LV.pdf PDF
27-PA Prevailing Wage Act Duties00810.pdf PDF
26 05 73.13 - Short Circuit Studies.pdf PDF
1-TITLE page.pdf PDF
26 13 26.11 - Metal Clad MV Arc Resistent Switchgear.pdf PDF
24-EJCDC - General Conditions (with Supplementary shown).pdf PDF
2-TOC.pdf PDF
011000.03 -SUMMARY OF THE WORK.pdf PDF
26 05 53 - Identification For Electrical Systems.pdf PDF
26 05 73.19 - Arc Flash Hazard Analysis.pdf PDF
26 43 13A - LV Surge Protective Devices For Electrical Distribution Systems.pdf PDF
19-EJCDC - Agreement Stipulated Price (C-520-2002).pdf PDF
5-EJCDC - Bid Form for Construction Contracts 00300 (003).pdf PDF
4-7-EJCDC - Bid Bond, Penal Sum Form (C-430-2002) Revised 10-30-2026.pdf PDF
11-Experience Questionnaire.pdf PDF
013300.0 - SUBMITTALS.pdf PDF
3-Addendum 1 LCA.pdf PDF
4-EJCDC - Instructions to Bidders (C-200-2002).pdf PDF
7-EJCDC - Bid Bond, Penal Sum Form (C-430-2002).pdf PDF
3-00010_Invitation to Bid.pdf PDF
26 05 73.16 - Coordination Studies.pdf PDF
17-CertAsToCorpPrincipal.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES:

1. THIS IS A PROCUREMENT PROJECT ONLY AND THESE DRAWINGS SHALL NOT BE USED FOR

CONSTRUCTION.

2. ALL ELECTRICAL EQUIPMENT SHALL BE DESIGNED, MANUFACTURED, TESTED, FOR INSTALLATION IN ACCORDANCE WITH THE LATEST APPLICABLE EDITIONS OF NEC, NEMA, IBC, ANSI, IEEE, AND UL STANDARDS. MANUFACTURER OF THE 15kV CLASS SWITCHGEAR ASSEMBLY SHALL HIRE AN

APPROVED 3RD PARTY AGENCY ACCEPTED BY AHJ AND PROVIDE THE REQUIRED UL AND OR IBC

CERTIFICATION ON THE PRODUCT ACCORDING TO LOCAL/NATIONAL ADMINISTRATIVE CODE

REQUIREMENTS IF NECESSARY.

3. ALL EQUIPMENT SHALL BEAR UL LABEL OR BE LISTED BY A NATIONALLY RECOGNIZED TESTING

LABORATORY (NRTL) AS APPLICABLE.

4. WINNING BIDDER SHALL PROVIDE OWNER AND EOR WITH FULLY DIMENSIONED PLANS WITH

CONDUIT ENTRY LOCATIONS AND CLEARANCES PRIOR TO FABRICATION FOR APPROVAL.

5. ALL EQUIPMENT SHALL BE PROVIDED WITH MANUFACTURER'S STANDARD NAMEPLATES INDICATING VOLTAGE, CURRENT, SHORT-CIRCUIT RATING, AND MANUFACTURER'S DATA (PER ANSI C37.20.2 /

NEMA AS APPLICABLE).

6. EQUIPMENT SHALL BE SUITABLE FOR THE INSTALLATION ALTITUDE, AMBIENT TEMPERATURE

RANGE, AND ENVIRONMENTAL CONDITIONS SPECIFIED (OUTDOOR, NEMA 3/3R AND OR AS

APPLICABLE).

7. ALL EQUIPMENT SHALL MEET SEISMIC QUALIFICATION REQUIREMENTS PER IBC/ASCE 7 AND SITE-SPECIFIC SEISMIC DESIGN CATEGORY, WITH CERTIFICATION BY A LICENSED PROFESSIONAL

ENGINEER WHERE REQUIRED.

8. PROVIDE ARC-RESISTANT CONSTRUCTION WHERE INDICATED ON DRAWINGS/SCHEDULES, TESTED

PER IEEE C37.20.7.

9. ALL EQUIPMENT SHALL BE FACTORY TESTED IN ACCORDANCE WITH APPLICABLE ANSI/IEEE

STANDARDS; CERTIFIED TEST REPORTS SHALL BE SUBMITTED PRIOR TO SHIPMENT.

10. PROVIDE COMPLETE SUBMITTAL PACKAGE INCLUDING SHOP DRAWINGS, ONE-LINE DIAGRAMS, ELEVATION VIEWS, CONTROL WIRING DIAGRAMS, FACTORY TEST RESULTS, SHORT-CIRCUIT/COORDINATION STUDY INPUTS, AND O&M MANUALS FOR GEAR ASSOCIATED WITH

SUBSTATION #2 AND #4 AND OBTAIN APPROVAL PRIOR TO FABRICATION.

11. MANUFACTURER SHALL PROVIDE ARC FLASH HAZARD LABELS PER NFPA 70E BASED ON THE

PROJECT'S ARC FLASH STUDY PRIOR TO ENERGIZATION.

12. ALL EQUIPMENT SHALL BE NEW, CURRENT PRODUCTION, AND FROM A SINGLE MANUFACTURER PER

GEAR TYPE UNLESS OTHERWISE NOTED.

13. PROVIDE FACTORY-APPLIED ANSI 61 GRAY FINISH (OR MATCH EXISTING) UNLESS OTHERWISE

SPECIFIED.

14. ALL EQUIPMENT SHALL INCLUDE LIFTING PROVISIONS AND BE SUITABLE FOR RIGGING/TRANSPORT

WITHOUT DAMAGE; PROVIDE SHIPPING SPLITS AS REQUIRED FOR ACCESS.

15. PROVIDE EQUIPMENT GROUNDING PER NEC 250 AND UTILITY/AHJ REQUIREMENTS; GROUND BUS

SHALL BE CONTINUOUS THROUGH ALL SHIPPING SECTIONS.

16. COORDINATE SHORT-CIRCUIT AND COORDINATION STUDY WITH EQUIPMENT RATINGS PRIOR TO RELEASE FOR FABRICATION; ALL DEVICES SHALL BE RATED TO WITHSTAND THE AVAILABLE FAULT

CURRENT SHOWN ON THE ONE-LINE DIAGRAM.

17. DELIVERY OF ELECTRICAL EQUIPMENT SHALL BE 650 DAYS FROM THE DATE OF THE APPROVAL OF

THE AGREEMENT. ALL BIDDERS MUST PROVIDE A SEPARATE LINE ITEM FOR ALTERNATE 2 FOR

EXPEDITED DELIVERY OF THE EQUIPMENT AS SHOWN ON THE BID FORM.

18. WINNING BIDDER MUST SHIP AND DELIVER THE EQUIPMENT AND PRODUCT TO A DESIGNATED SITE/LOCATION AT LEHIGH COUNTY AUTHORITY'S PRETREATMENT PLANT AT THE ADDRESS IN THE

TITLE BLOCK. THE EQUIPMENT DELIVERY SHALL BE COORDINATED WITH THE INSTALLATION

CONTRACTOR (TBD BY THE AUTHORITY).

19. THE VENDOR/MANUFACTURER REPRESENTATIVE SHALL ALLOW THE LEHIGH COUNTY AUTHORITY OR THE CONTRACTOR HIRED BY THE AUTHORITY TO PERFORM INSPECTION AT THE TIME OF THE DELIVERY OF THE EQUIPMENT AT SITE. VENDOR/MANUFACTURER NEEDS TO MAKE ARRANGEMENTS

FOR THE EQUIPMENT INSPECTION.

20. INCLUDE, SHIPPING AND LABOR COSTS IN THE PROCUREMENT BID.

21. THE WINNING VENDOR/MANUFACTURER SHALL PROVIDE SHOP DRAWINGS OF THE ELECTRICAL EQUIPMENT TO THE AHJ, EOR AND OWNER FOR REVIEW AND APPROVAL PRIOR TO FABRICATION. IF REQUIRED THE WINNING BIDDER SHALL HIRE A LICENSED ENGINEER AND FILE WITH THE AHJ TO

OBTAIN APPROVAL PRIOR TO FABRICATION.

22. WINNING BIDDER SHALL PROVIDE POWER SYSTEM STUDIES TO THE EOR INCLUDING, ARC FLASH

STUDIES AND ARC FLASH LABELS FOR THE EQUIPMENT.

23. INCLUDE FACTORY ACCEPTANCE TESTING IN THE PROCUREMENT BID.

24. ALL SWITCHGEAR SHALL BE INSTALLED ON A CONCRETE PAD ON GRADE, WITH ALL CONDUITS

ENTERING AND EXITING FROM THE BOTTOM OF THE SWITCHGEAR. INSTALLATION OF THE

CONCRETE PAD WILL BE A SEPARATE CONTRACT.

25. ALL BIDDERS ARE REQUIRED TO PROVIDE A LIST OF DEVIATIONS THAT THEY ARE TAKING FROM THE CONTRACT DOCUMENTS, IF NO LIST OF DEVIATIONS ARE PROVIDED IT WILL BE ASSUMED THAT THE

CONTRACTORS PROPOSED EQUIPMENT ARE IN COMPLIANCE WITH THE CONTRACT DOCUMENTS

AND INTENT.

26. EXTENDED WARRANTY ALTERNATE 1:

ALL BIDDERS MUST INCLUDE A SEPARATE LINE ITEM (ALTERNATE 1) FOR THE FOLLOWING

EXTENDED WARRANTY IN ADDITION TO THE STANDARD 24 MONTHS MANUFACTURER

WARRANTY.

a. 12 MONTHS

b. 24 MONTHS

c. 36 MONTHS

27. EQUIPMENT DELIVERY LEAD-TIME EXPEDITING ALTERNATE 2

ALL BIDDERS SHALL PROVIDE A SEPARATE LINE-ITEM PRICE AS AN ALTERNATE 2 FOR EXPEDITING THE MANUFACTURER'S STANDARD EQUIPMENT DELIVERY LEAD TIME. THE ALTERNATE PRICE SHALL REPRESENT THE ADDITIONAL COST REQUIRED TO REDUCE THE STANDARD DELIVERY LEAD TIME AND

EXPEDITE DELIVERY OF THE EQUIPMENT TO THE PROJECT SITE, THEREBY ALLOWING THE

EQUIPMENT TO BE DELIVERED EARLIER AND POTENTIALLY ALLOWING THE PROJECT TO ACHIEVE SUBSTANTIAL COMPLETION EARLIER THAN THE MAXIMUM 650-CALENDAR-DAY PERIOD SPECIFIED

BELOW.

THE BASE BID SHALL BE BASED ON THE MANUFACTURER'S/BIDDER'S STANDARD EQUIPMENT

DELIVERY LEAD TIME. THE EXPEDITED DELIVERY ALTERNATE SHALL IDENTIFY THE ADDITIONAL COST

AND THE CORRESPONDING REDUCTION IN DELIVERY TIME FROM THE STANDARD LEAD TIME.

UNDER NO CIRCUMSTANCES SHALL THE SUBSTANTIAL COMPLETION DATE EXCEED 650 CALENDAR

DAYS FROM THE DATE THE AGREEMENT IS APPROVED BY THE COMPTROLLER. ACCEPTANCE OF THE

EXPEDITING ALTERNATE MAY BE CONSIDERED BY THE OWNER TO FACILITATE AN EARLIER

SUBSTANTIAL COMPLETION DATE.

BIDDERS SHALL CLEARLY IDENTIFY THE FOLLOWING INFORMATION IN THEIR BID:

a. ADDITIONAL COST FOR EXPEDITING EQUIPMENT DELIVERY: $____________

b. NUMBER OF CALENDAR DAYS SAVED BY EXPEDITING: __________ DAYS

c. MANUFACTURER'S/BIDDER'S STANDARD EQUIPMENT DELIVERY LEAD TIME INCLUDED IN BASE BID:

__________ DAYS

THE STANDARD DELIVERY LEAD TIME IDENTIFIED ABOVE SHALL BE THE BASIS OF THE BIDDER'S ORIGINAL/BASE BID PRICE. THE EXPEDITED DELIVERY COST SHALL BE PROVIDED SEPARATELY AS AN

ALTERNATE/ADDITIVE COST AND SHALL NOT BE INCLUDED IN THE BASE BID.

THE OWNER RESERVES THE RIGHT TO ACCEPT OR REJECT THE EXPEDITING ALTERNATE.

12.47kV (15kV CLASS) SWITCHGEAR GENERAL NOTES:

1. METAL-CLAD SWITCHGEAR SHALL CONFORM TO IEEE C37.20.2 AND ANSI C37.06 FOR RATINGS, AND BE FACTORY

ASSEMBLED, WIRED, AND TESTED.

2. SWITCHGEAR SHALL BE RATED 15kV CLASS NOMINAL FOR UTILITY COMPANY'S 12.47kV SERVICE, 95kV BIL.

3. FOR BUS, SYMMETRICAL CURRENT INTERRUPTING RATING REFER TO ONE LINE DIAGRAM.

4. CIRCUIT BREAKERS SHALL BE VACUUM TYPE, DRAWOUT CONSTRUCTION, CONFORMING TO IEEE C37.04/C37.06/C37.09, WITH MECHANICAL AND ELECTRICAL INTERLOCKS TO PREVENT RACKING UNDER LOAD.

5. PROVIDE STORED-ENERGY (SPRING-CHARGED) OPERATING MECHANISMS WITH MANUAL AND ELECTRICAL

CHARGING, REMOTE CLOSE/TRIP CAPABILITY, AND ANTI-PUMP FEATURE.

6. PROVIDE PROTECTIVE RELAYING — MICROPROCESSOR-BASED MULTIFUNCTION RELAYS (PER INSTALLATION

DRAWINGS) WITH ETHERNET/FIBER COMMUNICATION PROTOCOL NEEDED BY THE AUTHORITY.

7. CURRENT TRANSFORMERS AND POTENTIAL/VOLTAGE TRANSFORMERS SHALL MEET IEEE C57.13 ACCURACY

CLASSES AS REQUIRED FOR METERING AND PROTECTION.

8. PROVIDE VIEWING WINDOWS OR EQUIVALENT MEANS TO VISUALLY VERIFY BREAKER DISCONNECTED POSITION

WITHOUT OPENING COMPARTMENT DOORS.

9. BUS BARS SHALL BE SILVER-PLATED COPPER, BRACED FOR THE SPECIFIED MOMENTARY/FAULT RATING;

PROVIDE HEAT-SHRINK OR EQUIVALENT INSULATION ON BUS CONNECTIONS.

10. PROVIDE SPACE HEATERS WITH THERMOSTAT CONTROL IN EACH VERTICAL SECTION TO PREVENT

CONDENSATION.

11. ALL MEDIUM VOLTAGE CABLE TERMINATIONS SHALL BE MADE WITH STRESS CONES/TERMINATIONS RATED FOR

THE SYSTEM VOLTAGE, INSTALLED PER MANUFACTURER'S INSTRUCTIONS.

12. PROVIDE CONTROL POWER TRANSFORMER(S) SIZED PER CONNECTED LOAD, FUSED PRIMARY AND SECONDARY, MOUNTED WITHIN SWITCHGEAR.

13. FACTORY TESTS SHALL INCLUDE PRODUCTION TESTS PER IEEE C37.20.2 (DIELECTRIC, MECHANICAL OPERATION, WIRING CONTINUITY); PROVIDE CERTIFIED TEST REPORTS.

MOTOR OPERATED

MOUNTED

NEUTRALN

LP

MTD

MCC

MO

MOTOR CONTROL CENTER

LIGHTING PANEL

SWITCHBOARD

TYPICAL

SWITCH

SURFACE

STANDARD

PANEL

POLE(S)

PULL BOX

RELOCATED

P

RGC

TYP

SUR

SWBD

SW

STD

RC

PNL

PB

N.C.

N.O.

REL

WEATHER PROOF

VOLT

WATT

V

WP

W

UOI

RIGID GALVANIZED CONDUIT

UNLESS OTHERWISE INDICATED

NORMALLY OPEN

REMOTE CONTROL

NORMALLY CLOSED

AUTH. HAVING JURISDICTION

CONDUIT

ARCHITECTURAL

AMPERE

ATS

C

AHJ

ARCH

AS

AFF/G

AF

A

AC

GROUND

GUARD

CIRCUIT BREAKER

DRAWING

CIRCUIT(S)

EXISTING TO REMAIN

G,GND

GR

DWG

CB

CKT(S)

E

ER

ERR

ISOLATED GROUND

JUNCTION BOXJB

IG

GFI GROUND FAULT INTERRUPTER

AUTOMATIC TRANSFER SWITCH

ABOVE FINISHED FLOOR/GRADE

SWITCH RATING IN AMPS

FUSE/FRAME RATING IN AMPS

ALTERNATING CURRENT

EXISTING TO BE REMOVED

EXISTING TO BE RELOCATED

EUH ELECTRIC UNIT HEATER

EF EXHAUST FAN

KILOWATT

KILOVOLT AMPERE

KW

KVA

SECTIONSECT

MAIN LUG ONLYMLO

POWERPWR

POWER PANELPP

KILOWATT HOURKWH

PORT PATCH PANELPPP

ABBREVIATIONS

SUMMARY OF WORK:

1. PROCUREMENT OF ELECTRICAL GEAR FOR SUBSTATION #2 AND #4.THIS CONTRACT

DOESN'T INCLUDE INSTALLATION OF ELECTRICAL EQUIPMENT AND GEAR. DESIGN FOR

CONSTRUCTION WILL BE PART OF A SEPARATE CONTRACT.

NOTE - NOT ALL THE ABBREVIATIONS MAY BE USED

SHEET LIST TABLE

DWG. SHEET TITLE CONTRACT

SHEET #

E001.00 ELECTRICAL SYMBOLS, GENERAL NOTES & ABBREVIATIONS 1

E002.00 ELECTRICAL SITE PLAN - DEMOLITION 2

E003.00 ELECTRICAL SITE PLAN - INSTALLATION 3

E008.00 ELECTRICAL POWER SINGLE LINE DIAGRAM - DEMOLITION 8

E009.00 ELECTRICAL POWER SINGLE LINE DIAGRAM - SUBSTATION #2 9

E010.00 ELECTRICAL POWER SINGLE LINE DIAGRAM - SUBSTATION #4

SHEET#1 10

E011.00 ELECTRICAL POWER SINGLE LINE DIAGRAM - SUBSTATION #4

SHEET#2 11

7E007.00 ELECTRICAL SUBSTATION#4 PART PLAN - INSTALLATION

6E006.00 ELECTRICAL SUBSTATION#4 PART PLAN - DEMOLITION

5E005.00 ELECTRICAL SUBSTATION#2 PART PLAN - INSTALLATION

4E004.00 ELECTRICAL SUBSTATION#2 PART PLAN - DEMOLITION

480V (600V CLASS) SWITCHGEAR GENERAL NOTES:

1. LOW-VOLTAGE SWITCHGEAR/SWITCHBOARDS SHALL CONFORM TO UL 1558 AND ANSI C37.20.

2. EQUIPMENT SHALL BE RATED 600V, 4000A BUS, 65kA SCCR FULLY RATED (OR AS INDICATED ON ONE LINE

DIAGRAM.

3. POWER CIRCUIT BREAKERS SHALL CONFORM TO UL 1066 AND SHALL BE DRAWOUT TYPE FOR USE IN UL 1558

SWITCHGEAR.

4. PROVIDE GROUND FAULT PROTECTION PER NEC 230.95 FOR SERVICES 1000A AND ABOVE AT 480Y/277V, AS

APPLICABLE.

5. BUS BRACING SHALL MEET OR EXCEED THE CALCULATED AVAILABLE FAULT CURRENT AT THE POINT OF

INSTALLATION, PER THE PROJECT SHORT-CIRCUIT STUDY.

6. PROVIDE COPPER BUS FULLY RATED (NON-TAPERED) THROUGHOUT UNLESS SPECIFICALLY NOTED

OTHERWISE.

7. PROVIDE 100% RATED MAIN BREAKER(S) WHERE CONTINUOUS LOADING EXCEEDS 80% OF FRAME RATING, PER NEC 215.2/230.90.

8. PROVIDE SURGE PROTECTIVE DEVICE (SPD) AT SERVICE ENTRANCE EQUIPMENT PER UL 1449 LISTED.

9. PROVIDE FACTORY-INSTALLED METERING (MULTIFUNCTION POWER METER) AT MAIN/TIE SECTIONS AS

SCHEDULED, WITH COMMUNICATION CAPABILITY AS SPECIFIED.

10. ALL EQUIPMENT SHALL BE PROVIDED WITH HINGED, GASKETED DOORS WITH QUARTER-TURN OR BOLTED

LATCHES AS SPECIFIED, AND NEMA 3/3R RATING PER INSTALLATION ENVIRONMENT.

11. FACTORY TESTS SHALL INCLUDE DIELECTRIC WITHSTAND, MECHANICAL OPERATION, AND CONTROL WIRING/CONTINUITY CHECKS PER UL 1558/845; PROVIDE CERTIFIED TEST REPORTS PRIOR TO SHIPMENT.

12. PROVIDE ELECTRICAL INTERLOCKING SCHEME BETWEEN MAIN-TIE-MAIN BREAKERS TO PREVENT

INADVERTENT PARALLELING OF SOURCES.

13. PROVIDE CONTROL POWER TRANSFORMER(S) SIZED PER CONNECTED LOAD, FUSED PRIMARY AND

SECONDARY, MOUNTED WITHIN SWITCHGEAR.

UTILITY COMPANY DATA:

1. THE FACILITY IS FED FROM TWO FEEDERS - FEEDER A AND B.

2. 12.47KV UTILITY FEEDER 1 (BUS A):

SHORT-CIRCUIT BOX

NODE - 2594844.216_455463.749

FAULT TYPE LG LL LLG LLL

AMPERE ---> 3564 3618 4037 4178

MVA ------> 27 81 90 93

THEVENIN RTH XTH R0TH X0TH

OHMS ------> 0.4256 1.7314 0.8920 2.5604

PU ---------> 0.2737 1.1134 0.5737 1.6465

IMPEDANCE R X RATIO X/R TOTAL

POSITIVE 0.2737 1.1134 4.07 3.454

NEGATIVE 0.2737 1.1134 4.07

ZERO 0.5737 1.6465 2.87

FEEDER PHASE DISTANCE

14701 ABC 0.98

3. 12.47KV UTILITY FEEDER 2 (BUS B):

SHORT-CIRCUIT BOX

SWITCH - 59500S45533-3

FAULT TYPE LG LL LLG LLL

AMPERE ---> 4550 4263 4971 5016

MVA ------> 34 95 111 112

THEVENIN RTH XTH R0TH X0TH

OHMS ------> 0.1526 1.4770 0.4446 1.8424

PU ---------> 0.0981 0.9498 0.2859 1.1848

IMPEDANCE R X RATIO X TOTAL/R TOTAL

POSITIVE 0.0981 0.9498 9.68 6.393

NEGATIVE 0.0981 0.9498 9.68

ZERO 0.2859 1.1848 4.14

FEEDER PHASE DISTANCE

14704 ABC 0.79

GROUND ROD AND OR CONNECTION TO GROUND

DESCRIPTIONSYMBOL

DUPLEX THREE WIRE GROUNDED WEATHER PROOF RECEPTACLE, 20A,

125V. (NEMA 5-20R) WITH "GFI" GROUND FAULT INTERRUPTER

WALL/STANCHION MOUNTED AT 18" A.F.F. U.O.I.

GFI

POWER TRANSFORMER / DISTRIBUTION TRANSFORMER

- INDICATES "DELTA" CONNECTED COPPER WINDINGS.

- INDICATES "GROUNDED WYE" CONNECTED COPPER WINDINGS.

- INDICATES kVA RATING.

- INDICATES PRIMARY AND SECONDARY VOLTAGE.

- INDICATES IMPEDANCE PERCENTAGE.

100kVA 480/277V 1.2Z

POWER SYMBOL LIST

SEL-751

SEL-787

SEL-2414

1200A

ET, LSIG

100A/5A

METERING

DRAWOUT TYPE 600V CLASS CIRCUIT BREAKER. "ET" INDICATES

ELECTRONIC TRIP. "LSIG" INDICATES LONG, SHORT, INSTANTENEOUS AND

GROUND CURRENT DETECTION.

INSTRUMENT CURRENT TRANSFORMER, 100/5A INDICATES CT RATIO.

15 kV CLASS MEDIUM VOLTAGE DRAWOUT TYPE CIRCUIT BREAKER. "1200A"

INDICATES CIRCUIT BREAKER AMPERE RATING.

4' HIGH 8" DIAMETER BOLLARD

TOUCH SCREEN TYPE SEL-751 FEEDER PROTECTION RELAY BY

SCHWEITZER ENGINEERING LABORATORIES. NUMBERING INDICATES ANSI

DEVICE NUMBER. PROVIDE CONFORMAL COATING.

TOUCH SCREEN TYPE SEL-787 TWO TERMINAL TRANS. PROTECTION RELAY

BY SCHWEITZER ENGINEERING LABORATORIES. NUMBERING INDICATES

ANSI DEVICE NUMBER. PROVIDE PROVIDE CONFORMAL COATING.

TOUCH SCREEN TYPE SEL2414 TRANSFORMER AUTOMATION, MONITORING

AND CONTROLLER BY SCHWEITZER ENGINEERING LABORATORIES.PROVIDE

CONFORMAL COATING.

PLC FOR AUTOMATIC MAIN-TIE-MAIN CONTROLLER WITH TOUCH SCREEN

AND ELECTRICAL INTERLOCKS BY EATON OR APPROVED EQUAL.

JUNCTION BOX, SIZE IS REQUIRED.J

GROUND ROD AND TEST PIT

MTM-PLC

EATON PXQ-ST2-1A1 OR APPROVED EQUAL OUTDOOR METER INSTALLED IN

600V CLASS SWITCHGEAR.

50,51

50,51

Δ

Y

100KVA

460/277 1.2Z

HMI HUMAN MACHINE INTERFACE IN NEMA 3/3R ENCLOSURE.

LIGHTINGLTG

TIE CIRCUIT BREAKERTCB

Y

CONTROL POWER TRANSFORMER 480 TO 120V

DRAW OUT TYPE VOLTAGE TRANSFORMER

VT

CPT

SPD

SWITCHGEAR INTEGRATED SURGE PROTECTIVE DEVICE WITH SURGE

COUNTER BY EATON OR APPROVED EQUAL.

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL

SYMBOLS,

GENERAL NOTES

& ABBREVIATIONS

E001.00

PROCUREMENT BID 09/15/26

X

X

X

X

X

X

X

X

X

X

X

X

X

XXX

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X X

X X

X X

X X

X

X

X X X X X X X X X X X X X X X X X X X X X X X X X

X

X

X

X

X X

X X

X X

X X

X

X

SCALE:

ELECTRICAL SITE PLAN - DEMOLITION1

E002 1" = 40'-0"

EXISTING SUBSTATION #2 TO BE REMOVED AFTER

NEW SUBSTATION #2 IS INSTALLED.

EXISTING SUBSTATION #4 TO BE REMOVED

AFTER NEW SUBSTATION #4 IS INSTALLED.

ER

ER

NOTES:

1. THIS DRAWING IS NOT FOR CONSTRUCTION.

2. THIS DRAWING IS ONLY TO CONVEY THE INTENT OF THE PROCUREMENT

OF ELECTRICAL GEAR FOR SUBSTATION #2 AND #4.

3. DEMOLITION OF SUBSTATION #2 AND #4 WILL BE CARRIED OUT AS A PART

OF A SEPARATE CONTRACT, ONCE THE PROCUREMENT AND THE

INSTALLATION OF THE NEW ELECTRICAL SWITCHGEAR AT SUBSTATION #2

AND SUBSTATION #4 IS COMPLETED.

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL SITE

PLAN -

DEMOLITION

E002.00

PROPOSED POSSIBLE LOCATION

OF NEW SUBSTATION #4.

REFER TO E007.00.

PROPOSED POSSIBLE LOCATION

OF NEW SUBSTATION #2. REFER

TO E005.00.

X

X

X

X

X

X

X

X

X

X

X

X

X

XXX

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X X

X X

X X

X X

X X

X

X

X X X X X X X X X X X X X X X X X X X X X X X X X

X

X

X

X

X X

X X

X X

X X

X

SCALE:

ELECTRICAL SITE PLAN - INSTALLATION1

E003 1" = 40'-0"

X

EXISTING FEEDER MANHOLES

FOR SUBSTATION #4

EXISTING SUBSTATION #2 TO BE REMOVED

AFTER NEW SUBSTATION #2 IS INSTALLED.

EXISTING SUBSTATION #4 TO BE REMOVED AFTER

NEW SUBSTATION #4 IS INSTALLED.

ER

ER

ER

NOTES:

1. THIS DRAWING IS NOT FOR CONSTRUCTION.

2. THIS DRAWING IS ONLY TO CONVEY THE INTENT OF THE PROCUREMENT

OF ELECTRICAL GEAR FOR SUBSTATION #2 AND #4.

3. DEMOLITION OF SUBSTATION #2 AND #4 WILL BE CARRIED OUT AS A PART

OF A SEPARATE CONTRACT, ONCE THE PROCUREMENT AND THE

INSTALLATION OF THE NEW ELECTRICAL SWITCHGEAR AT SUBSTATION #2

AND SUBSTATION #4 IS COMPLETED.

EXISTING MAIN MV GEAR TO REMAIN.

FUSES TO BE REPLACED AS PER ONE-LINE

DIAGRAM IN A FUTURE CONTRACT.

E

EXISTING FEEDER MANHOLES

FOR SUBSTATION #2

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL SITE

PLAN -

INSTALLATION

E003.00

SCALE:

ELECTRICAL SUBSTATION#2 PART PLAN - DEMOLITION1

E004 1/8" = 1'-0"

EXISTING SUBSTATION #2 TO BE

REMOVED AFTER NEW

SUBSTATION #2 IS INSTALLED.

ER

NOTES:

1. THIS DRAWING IS NOT FOR CONSTRUCTION.

2. THIS DRAWING IS ONLY TO CONVEY THE INTENT OF THE PROCUREMENT

OF ELECTRICAL GEAR FOR SUBSTATION #2.

3. DEMOLITION OF SUBSTATION #2 WILL BE CARRIED OUT AS A PART OF A

SEPARATE CONTRACT, ONCE THE PROCUREMENT AND THE

INSTALLATION OF THE NEW ELECTRICAL SWITCHGEAR AT SUBSTATION #2

IS COMPLETED.

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL

SUBSTATION#2

PART PLAN -

DEMOLITION

E004.00

ELECTRICAL SUBSTATION#2 PART PLAN - INSTALLATION1

E005 3/8" = 1'-0"

MEDIUM

VOLTAGE

BREAKER

MVS-2A

TR

AN

SI

TI

O N

SE

C

TI

O

N

TRANSFORMER

T2-A

MEDIUM

VOLTAGE

BREAKER

MVS-2B

4000A COPPER

FLEXIBLE BRAIDED

BUS 600V CLASS

4000A COPPER

FLEXIBLE BRAIDED

BUS 600V CLASS

1 2 3 4 5 6 7

3'

8'

2'

6'-2" 2'

2' 3'-10" 3'-10" 2'-6" 3'-10" 3'-10" 2'

2' 2'

3'

8'

5'-4"

5'-7"

7'-6"

8" CONCRETE PAD

2 2

INSTALLATION PLAN KEY NOTES:

1. 2.3/2.576 MVA LIQUID FILLED KNAN/KNAF 55/75°C RISE, Z=6.6% SUBSTATION TYPE OUTDOOR STEP-DOWN CU

TRANSFORMER (12.47kV) Δ-Y (480/277V) Dyn1, K-4, TRANSFORMER T2-A AND T2-B. PROVIDE SEL787 IN MVS-2A/B ENCLOSURE FOR TRANSFORMER PROTECTION AND SEL 2414 FOR TRANSFORMER MONITORING.TRANSFORMER COLOR SHALL BE ANSI 61.WINNING BIDDER MUST COORDINATE WITH SEL TO INTEGRATE SEL RELAYS IN 15kV

CLASS MV GEAR. GAUGES SHALL BE INSTALLED AT EYE LEVEL.

2. 15kV CLASS, METAL CLAD SWITCHGEAR WITH 15KV CLASS 1200A MV CIRCUIT BREAKER. FEEDER CONDUIT TO ENTER MV GEAR FROM BOTTOM, OUTGOING CABLES SHALL RUN TO AIR TERMINAL CHAMBER/THROAT. WINNING BIDDER MUST COORDINATE WITH SEL TO INTEGRATE SEL RELAYS IN 15kV CLASS MV GEAR.

3. FULL/PARTIAL HEIGHT AIR TERMINAL CHAMBER OR THROAT TYPE TRANSITION SECTION FOR 15kV CLASS HV SIDE OF TRANSFORMER. CABLES TO BE USED FOR CONNECTION FROM MV LOAD SIDE TO TRANSFORMER HV

SIDE.

4. FLANGE TYPE TRANSITION SECTION FOR 600V CLASS LV SIDE OF TRANSFORMER TO LV SWITCHGEAR. COPPER FLEXIBLE BRAIDED BUS TO BE USED FOR CONNECTION FROM TRANSFORMER SECONDARY TO LV SWITCHGEAR.

5. WINNING BIDDER TO COORDINATE WITH SEL, PROCURE THEIR RELAYS AND INTEGRATE ON NEW METAL CLAD/TRANSFORMER/LV SWITCHGEAR. ALL SEL RELAYS SHALL HAVE TOUCH SCREENS. SEL 2414 SHALL BE HOUSED IN A DEDICATED NEMA 4X CONTROL BOX. FOR SEL 751 WINNING BIDDER SHALL PROCURE LIGHT AND PRESSURE SENSORS FROM SEL AND INTEGRATE IT ON THEIR SWITCHGEAR FOR ARC FLASH DETECTION AND

PROTECTION.

6. TRANSITION SECTION OF LV SWITCHGEAR

7. MAIN CIRCUIT BREAKERS, SPD'S, CPT METERING AND CONTROLS

8. BREAKERS AND LSIG ELECTRONIC TRIP UNITS. REFER TO ONE LINE DIAGRAM FOR FOR OUTGOING CIRCUIT

BREAKERS.

9. TIE CIRCUIT BREAKER, ASSOCIATED HMI, PLC AND ELECTRICAL INTERLOCK CONTROLS. THIS TIE-BREAKER WILL

BE NORMALLY OPEN.

10. PROVIDE WEATHER PROOF LOCK BOX FOR MAINTENANCE RECEPTACLE.

11. HMI IN NEMA 3/3R ENCLOSURE

NOTES:

1. DRAWING IS ONLY FOR THE PURPOSE OF EQUIPMENT PROCUREMENT AND IS NOT FOR CONSTRUCTION.

2. DIMENSIONS INDICATED ARE FOR EATON'S FAMILY OF EQUIPMENT FOR THE PURPOSE OF BIDDING. THE WINNING BIDDER MUST SUBMIT DIMENSIONS SCALED SHOP DRAWINGS AND A COORDINATED PLAN FOR EOR'S

REVIEW AND FINAL APPROVAL.

3. FOR SYMBOL LIST, GENERAL NOTES AND ABBREVIATIONS REFER TO DWGS E001.00.

4. ALL EQUIPMENT SHALL BE PROVIDED WITH GROUND BUS AND LUGS FOR CONNECTION TO GROUNDING

RING/RODS.

5. FOR RATINGS OF EQUIPMENT REFER TO ONE LINE DIAGRAM / KEY NOTES.

6. PROVIDE DIMENSIONED PART PLAN DRAWINGS OF EQUIPMENT REFLECTING ACTUAL INSTAL TO THE EOR FOR

REVIEW AND APPROVAL.

7. PROVIDE O&M MANUALS AND EQUIPMENT WARRANTY DOCUMENTATION TO OWNER.

8. SWITCHGEAR SHALL BE FACTORY-ASSEMBLED, TESTED, AND UL-LISTED (OR THIRD-PARTY CERTIFIED) FOR THE SPECIFIED VOLTAGE CLASS, BIL RATING, AND SHORT-CIRCUIT RATING AS INDICATED ON THE ONE-LINE

DIAGRAM.

9. PROVIDE ARC-RESISTANT CONSTRUCTION WHERE INDICATED, TESTED PER IEEE C37.20.7.

10. ALL SWITCHGEAR SHALL BE PROVIDED WITH A MANUFACTURER'S NAMEPLATE INDICATING RATED VOLTAGE, CURRENT, BIL, AND SHORT-CIRCUIT RATING.

11. EQUIPMENT ENCLOSURES SHALL BE RATED NEMA 3R (OR AS SPECIFIED) FOR OUTDOOR INSTALLATION.

12. PROVIDE SURGE/LIGHTNING ARRESTERS AT EQUIPMENT AS INDICATED, COORDINATED WITH INSULATION

COORDINATION STUDY.

13. ALL EQUIPMENT SHALL HAVE PERMANENT, ENGRAVED PHENOLIC NAMEPLATES IDENTIFYING SOURCE, VOLTAGE, AND EQUIPMENT DESIGNATION, PER ONE-LINE DIAGRAM.

14. PROVIDE ARC-FLASH WARNING LABELS ON ALL EQUIPMENT PER NFPA 70E, BASED ON PROJECT-SPECIFIC

ARC-FLASH HAZARD ANALYSIS.

15. PROVIDE HIGH-VOLTAGE WARNING SIGNAGE AT SWITCHGEAR ENCLOSURES AND FENCE PERIMETER PER

NESC/OSHA REQUIREMENTS.

16. EQUIPMENT LABELING SHALL MATCH ONE-LINE DIAGRAM DESIGNATIONS EXACTLY.

17. CPT SHALL BE SIZED TO POWER ALL SEL RELAYS, REMOTE OPERATORS, (2) MAINTENANCE RECEPTACLES AND

OTHER 120V LOADS.

18. WINNING BIDDER MUST TAKE RESPONSIBILITY FOR THE ALIGNMENT OF MV AND LV GEAR WITH TRANSFORMER

PRIMARY AND SECONDARY BUSHINGS AND ASSOCIATED ACCESSORIES.

SEL-751

SEL-787

SEL-2414

SEL-751

SEL-787

GROUND ROD 5/8" X 10' /TEST POINT (TYP)

#4/0 AWG BARE GROUND CONDUCTOR BELOW

GRADE (TYP)

CONCRETE

WALKWAY

TR

AN

SI

TI

O N

SE

C

TI

O

N

TR

AN

SI

TI

O N

SE

C

TI

O

N

CONCRETE WALL

CONCRETE WALL / METAL STRUCTURE TO

BE DESIGNED AFTER PROCUREMENT

PHASE

BOLLARDS. (TYP)

3 3

TR

AN

SI

TI

O N

SE

C

TI

O

N

GROUND BAR

6 67 8 789

8'

62'-1"

22'-7"

TRANSFORMER

T2-B

6'-2"

SEL-2414

6'

6'

GFI

GFI

METERING

H M

I

6 7 8 9 LV GEAR SHALL BE NEMA 3R NON-WALK IN OUTDOOR RATED UL 1558 EATON MAGNUM PXR OR APPROVED EQUAL.

SPD

METERING

SPD

MTM-PLC

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL

SUBSTATION#2

PART PLAN -

INSTALLATION

E005.00

ELECTRICAL SUBSTATION#4 PART PLAN - DEMOLITION1

E006 1/8" = 1'-0"

EXISTING SUBSTATION #4 TO BE REMOVED AFTER NEW

SUBSTATION #4 IS INSTALLED.

ER

NOTES:

1. THIS DRAWING IS NOT FOR CONSTRUCTION.

2. THIS DRAWING IS ONLY TO CONVEY THE INTENT OF THE PROCUREMENT

OF ELECTRICAL GEAR FOR SUBSTATION #4.

3. DEMOLITION OF SUBSTATION #4 WILL BE CARRIED OUT AS A PART OF A

SEPARATE CONTRACT, ONCE THE PROCUREMENT AND THE

INSTALLATION OF THE NEW ELECTRICAL SWITCHGEAR AT SUBSTATION #4

IS COMPLETED.

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL

SUBSTATION#4

PART PLAN -

DEMOLITION

E006.00

TRANSFORMER

T4-B

MEDIUM

VOLTAGE

BREAKER

MVS-4B

4000A COPPER FLEXIBLE

BRAIDED BUS 600V

CLASS

TRANSFORMER

T4-A

MEDIUM

VOLTAGE

BREAKER

MVS-4A

4000A COPPER FLEXIBLE

BRAIDED BUS 600V CLASS

2' 5'-10"

5'

2'

2' 3'-10" 3'-10" 2'-6" 3'-10" 3'-10" 2'

2' 5'-10" 2'

CONCRETE

WALKWAY

NOTES:

1. DRAWING IS ONLY FOR THE PURPOSE OF PROCUREMENT AND NOT FOR CONSTRUCTION.

2. DIMENSIONS INDICATED ARE FOR EATON'S FAMILY OF EQUIPMENT FOR THE PURPOSE OF BIDDING. THE WINNING BIDDER MUST SUBMIT DIMENSIONS SCALED SHOP DRAWINGS AND A COORDINATED PLAN FOR EOR'S

REVIEW AND FINAL APPROVAL.

3. FOR SYMBOL LIST, GENERAL NOTES AND ABBREVIATIONS REFER TO DWGS E001.00.

4. ALL EQUIPMENT SHALL BE PROVIDED WITH GROUND BUS AND LUGS FOR CONNECTION TO GROUNDING

RING/RODS.

5. FOR RATINGS OF EQUIPMENT REFER TO ONE LINE DIAGRAM / KEY NOTES.

6. PROVIDE DIMENSIONED PART PLAN DRAWINGS OF EQUIPMENT REFLECTING ACTUAL INSTAL TO THE EOR FOR

REVIEW AND APPROVAL.

7. PROVIDE O&M MANUALS AND EQUIPMENT WARRANTY DOCUMENTATION TO OWNER.

8. SWITCHGEAR SHALL BE FACTORY-ASSEMBLED, TESTED, AND UL-LISTED (OR THIRD-PARTY CERTIFIED) FOR THE SPECIFIED VOLTAGE CLASS, BIL RATING, AND SHORT-CIRCUIT RATING AS INDICATED ON THE ONE-LINE

DIAGRAM.

9. PROVIDE ARC-RESISTANT CONSTRUCTION WHERE INDICATED, TESTED PER IEEE C37.20.7.

10. ALL SWITCHGEAR SHALL BE PROVIDED WITH A MANUFACTURER'S NAMEPLATE INDICATING RATED VOLTAGE, CURRENT, BIL, AND SHORT-CIRCUIT RATING.

11. EQUIPMENT ENCLOSURES SHALL BE RATED NEMA 3R (OR AS SPECIFIED) FOR OUTDOOR INSTALLATION.

12. PROVIDE SURGE/LIGHTNING ARRESTERS AT EQUIPMENT AS INDICATED, COORDINATED WITH INSULATION

COORDINATION STUDY.

13. ALL EQUIPMENT SHALL HAVE PERMANENT, ENGRAVED PHENOLIC NAMEPLATES IDENTIFYING SOURCE, VOLTAGE, AND EQUIPMENT DESIGNATION, PER ONE-LINE DIAGRAM.

14. PROVIDE ARC-FLASH WARNING LABELS ON ALL EQUIPMENT PER NFPA 70E, BASED ON PROJECT-SPECIFIC

ARC-FLASH HAZARD ANALYSIS.

15. PROVIDE HIGH-VOLTAGE WARNING SIGNAGE AT SWITCHGEAR ENCLOSURES AND FENCE PERIMETER PER

NESC/OSHA REQUIREMENTS.

16. EQUIPMENT LABELING SHALL MATCH ONE-LINE DIAGRAM DESIGNATIONS EXACTLY.

17. CPT SHALL BE SIZED TO POWER ALL SEL RELAYS, REMOTE OPERATORS, (2) MAINTENANCE RECEPTACLES AND

OTHER 120V LOADS.

18. WINNING BIDDER MUST TAKE RESPONSIBILITY FOR THE ALIGNMENT OF MV AND LV GEAR WITH TRANSFORMER

PRIMARY AND SECONDARY BUSHINGS AND ASSOCIATED ACCESSORIES.

22'-7" TR

AN

SI

TI

O N

SE

C

TI

O

N

TR

AN

SI

TI

O N

SE

C

TI

O

N

TR

AN

SI

TI

O N

SE

C

TI

O

N

TR

AN

SI

TI

O N

SE

C

TI

O

N

GROUND ROD 5/8" X 10' /TEST POINT (TYP)

8" CONCRETE PAD

BOLLARDS. (TYP)

8'

3'

8' 8'

3'

1 2 3 4 5 6 7

6 67 8 7895

5'-7"

3 4

4 3

7'-6"

#4/0 AWG BARE GROUND CONDUCTOR BELOW

GRADE (TYP)

CONCRETE WALL

CONCRETE WALL / METAL STRUCTURE TO

BE DESIGNED AFTER PROCUREMENT

PHASE

SCALE:

ELECTRICAL SUBSTATION #4 PART PLAN - INSTALLATION1

E007 3/8" = 1'-0"

INSTALLATION PLAN KEY NOTES:

1. 1.725/2.106 MVA LIQUID FILLED KNAN/KNAF 55/75°C RISE, Z=5.75% SUBSTATION TYPE OUTDOOR STEP-DOWN CU

TRANSFORMER (12.47kV) Δ-Y (480/277V) Dyn1, K-4, TRANSFORMER T4-A AND T4-B. PROVIDE SEL787 IN MVS-4A/B ENCLOSURE FOR TRANSFORMER PROTECTION AND SEL 2414 FOR TRANSFORMER MONITORING. TRANSFORMER COLOR SHALL BE ANSI 61.WINNING BIDDER MUST COORDINATE WITH SEL TO INTEGRATE SEL RELAYS IN 15kV

CLASS MV GEAR. GAUGES SHALL BE INSTALLED AT EYE LEVEL.

2. 15kV CLASS, METAL CLAD SWITCHGEAR WITH 15KV CLASS 1200A MV CIRCUIT BREAKER. FEEDER CONDUIT TO ENTER MV GEAR FROM BOTTOM, OUTGOING CABLES SHALL RUN TO AIR TERMINAL CHAMBER/THROAT. WINNING BIDDER MUST COORDINATE WITH SEL TO INTEGRATE SEL RELAYS IN 15kV CLASS MV GEAR.

3. FULL/PARTIAL HEIGHT AIR TERMINAL CHAMBER OR THROAT TYPE TRANSITION SECTION FOR 15kV CLASS HV SIDE OF TRANSFORMER. CABLES TO BE USED FOR CONNECTION FROM MV LOAD SIDE TO TRANSFORMER HV

SIDE.

4. FLANGE TYPE TRANSITION SECTION FOR 600V CLASS LV SIDE OF TRANSFORMER TO LV SWITCHGEAR. COPPER FLEXIBLE BRAIDED BUS TO BE USED FOR CONNECTION FROM TRANSFORMER SECONDARY TO LV SWITCHGEAR.

5. WINNING BIDDER TO COORDINATE WITH SEL, PROCURE THEIR RELAYS AND INTEGRATE ON NEW METAL CLAD/TRANSFORMER/LV SWITCHGEAR. ALL SEL RELAYS SHALL HAVE TOUCH SCREENS. SEL 2414 SHALL BE HOUSED IN A DEDICATED NEMA 4X CONTROL BOX. FOR SEL 751 WINNING BIDDER SHALL PROCURE LIGHT AND PRESSURE SENSORS FROM SEL AND INTEGRATE IT ON THEIR SWITCHGEAR FOR ARC FLASH DETECTION AND

PROTECTION.

6. TRANSITION SECTION OF LV SWITCHGEAR

7. MAIN CIRCUIT BREAKER, SPD's, CPT METERING AND CONTROLS.

8. BREAKERS AND LSIG ELECTRONIC TRIP UNITS. REFER TO ONE LINE DIAGRAM FOR FOR OUTGOING CIRCUIT

BREAKERS.

9. TIE CIRCUIT BREAKER, ASSOCIATED HMI, PLC AND ELECTRICAL INTERLOCK CONTROLS. THIS TIE-BREAKER WILL

BE NORMALLY OPEN.

10. PROVIDE WEATHER PROOF LOCK BOX FOR MAINTENANCE RECEPTACLE

11. HMI IN NEMA 3/3R ENCLOSURE

61'-4"

GROUND BAR

6'

6'

GFI

GFI

H M

I

6 7 8 9 LV GEAR SHALL BE NEMA 3R NON-WALK IN OUTDOOR RATED UL 1558 EATON MAGNUM PXR OR APPROVED EQUAL.

SEL-751

SEL-787

SEL-751

SEL-787

SEL-2414

SEL-2414

METERING

SPD

METERING

SPD

MTM-PLC

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL

SUBSTATION#4

PART PLAN -

INSTALLATION

E007.00

ELECTRICAL POWER SINGLE LINE DIAGRAM - DEMOLITION1

E008 NTS

EXISTING SUBSTATION #2 TO BE REMOVED AFTER NEW

SUBSTATION #2 IS INSTALLED

ER

EXISTING 15kV CLASS

FEEDERS TO REMAIN

EXISTING LV FEEDERS TO

REMAIN

ER

EXISTING 15kV CLASS

FEEDERS TO REMAIN

EXISTING LV

FEEDERS TO

REMAIN

EEEEEEEEEEEE

E E

E E

EXISTING SUBSTATION #4 LV SWITCHGEAR, FEEDER AND

BRANCH CIRCUITS TO REMAIN.

NOT IN CONTRACT.

EXISTING SUBSTATION #2 LV

SWITCHGEAR, FEEDER AND

BRANCH CIRCUITS TO REMAIN.

E

E

E

EXISTING TO REMAIN.

NOT IN CONTRACT.

EEEEE

NOTES:

1. THIS DRAWING IS NOT FOR CONSTRUCTION.

2. THIS DRAWING IS ONLY TO CONVEY THE INTENT OF THE PROCUREMENT OF

ELECTRICAL GEAR FOR SUBSTATION #2 AND #4.

3. DEMOLITION OF SUBSTATION #2 AND #4 WILL BE CARRIED OUT AS A PART

OF A SEPARATE CONTRACT, ONCE THE PROCUREMENT AND THE

INSTALLATION OF THE NEW ELECTRICAL SWITCHGEAR AT SUBSTATION #2

AND SUBSTATION #4 IS COMPLETED.

KEYED NOTES:

1. REPLACE EXISTING EXPULSION TYPE FUSE WITH NEW EXPULSION TYPE

FUSE. REFER TO NEW DRAWINGS.

2. EXISTING SUBSTATION TO BE REMOVED AFTER NEW SUBSTATION IS

INSTALLED1 1 1 1

E

E

E

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL

POWER SINGLE

LINE DIAGRAM -

DEMOLITION

E008.00

ELECTRICAL POWER SINGLE LINE DIAGRAM - SUBSTATION #21

E009 NTS

KEYED NOTES:

1. PROVIDE ADDITIONAL CPT'S IF NEEDED FOR SWITCHGEAR HEATING.

2. PROVIDE MV/LV CIRCUIT BREAKER REMOTE OPERATOR. REMOTE OPERATOR SHALL

BE POWERED FROM THE LV BUS CPT AFTER SS#2-MCB-A/B.

3. TRIP/CLOSE/BREAKER STATUS AND BREAKER MONITORING.

4. PROVIDE ELECTRICAL INTERLOCKS BETWEEN MAIN-TIE-MAIN BREAKER AND FEEDER

#1 AND FEEDER #2 LV BREAKERS AS NEEDED. FOR MAIN-TIE-MAIN SEQUENCE OF

OPERATION REFER TO SPECIFICATION 26 23 00.13.

EXISTING TO REMAIN.

NOT IN CONTRACT.

TO SUBSTATION #4 REFER TO

DRAWING E010

(3) LIGHTNING ARRESTERS, 15kV MCOV.

PROVIDE SURGE EVENT COUNTER

#2/0G, 15kV CLASS CABLE

FOR EACH ARRESTER

1200A

Δ

SEL-787

SEL-2414

MVS-2A

ET, LSIG

METERING4000A/5A

2.3/2.576 MVA LIQUID FILLED KNAN/KNAF 55/65°C RISE, Z=6.6%

SUBSTATION TYPE OUTDOOR STEP-DOWN CU TRANSFORMER

(12.47kV) Δ-Y (480/277V) Dyn1, K-4, TRANSFORMER T2-A. PROVIDE

SEL787 IN MVS-2A ENCLOSURE FOR TRANSFORMER PROTECTION

AND SEL 2414 FOR TRANSFORMER MONITORING.TRANSFORMER

COLOR SHALL BE ANSI 61.WINNING BIDDER MUST COORDINATE

WITH SEL TO INTEGRATE SEL RELAYS IN 15kV CLASS MV GEAR.

150A/5A

4000A/5A

POWER XPERT METER PXQ-ST2-1A1 OR APPROVED EQUAL

CPT-480 TO 120V

4000AF

3100AT

EXISTING TO REMAIN.

NOT IN CONTRACT.

ET, LSIG ET, LSIG ET, LSIG ET, LSIG ET, LSIG ET, LSIG

ET, LSIG

SPARE

TO SUBSTATION #4 REFER TO

DRAWING E010

NEW CABLES & FROM EXISTING MANHOLE TO NEW MVS-2A/B

3#250MCM+1#2/0G IN 5"C.

PART OF FUTURE CONTRACT. NOT IN THIS CONTRACT.

INSTALL NEW CABLES FROM MAIN

SWITCHGEAR TO MANHOLE IN EXISTING

CONDUIT.

3#250MCM+1#2/0G IN EXISTING CONDUIT.

PART OF FUTURE CONTRACT. NOT IN

THIS CONTRACT.

T2-A

INTERCEPT EXISTING CABLES AND

EXTEND TO NEW BREAKERS. PROVIDE

SIMILAR MATCHING NEW CABLES,

CONDUITS, ACCESSORIES AND

FITTINGS TO MAKE THE EXTENSION.

480V, 3 PHASE, 4W + G

SS#2-BUS-2, 4000A BUS

SCCR 65kA, 600V CLASS

480V, 3 PHASE, 4W + G

SS#2-BUS-1, 4000A BUS

SCCR 65kA, 600V CLASS

4000AF

3100AT 1600AF

1200AT

SPARE

1600AF

1200AT

MCC-OGB

1600AF

1200AT

MCC-SPBB

1600AF

1200AT

MCC-OGA

1600AF

1200AT

MCC-SPBAMCC-OGC

600AF

300AT

MTM-PLC

PLC FOR AUTOMATIC MAIN-TIE-MAIN

CONTROLLER WITH ELECTRICAL

INTERLOCKS BY EATON OR APPROVED

EQUAL FOR TCB#2

SPD

150A/5A

SS#2-

MCB-A

POWER TO GFI MAINTENANCE RECEPTACLE

120V CONTROL POWER FROM CPT FOR METERING

ET, LSIG 400AF

400AT

SPARE

(3) LIGHTNING ARRESTERS, 15kV MCOV.

PROVIDE SURGE EVENT COUNTER

#2/0G, 15kV CLASS CABLE

FOR EACH ARRESTER

Δ SEL-2414

MVS-2B

ET, LSIG

METERING4000A/5A

2.3/2.576 MVA LIQUID FILLED KNAN/KNAF 55/65°C RISE, Z=6.6%

SUBSTATION TYPE OUTDOOR STEP-DOWN CU TRANSFORMER

(12.47kV) Δ-Y (480/277V) Dyn1, K-4, TRANSFORMER T2-B.

PROVIDE SEL787 IN MVS-2B ENCLOSURE FOR TRANSFORMER

PROTECTION AND SEL 2414 FOR TRANSFORMER

MONITORING.TRANSFORMER COLOR SHALL BE ANSI

61.WINNING BIDDER MUST COORDINATE WITH SEL TO

INTEGRATE SEL RELAYS IN 15kV CLASS MV GEAR.

150A/5A

POWER XPERT METER PXQ-ST2-1A1 OR APPROVED EQUAL

CPT-480 TO 120V

4000AF

3100AT

T2-B

SPD

120V CONTROL POWER FROM CPT FOR SEL 751,787,2414

SS#2-

MCB-B

POWER TO GFI MAINTENANCE RECEPTACLE

120V CONTROL POWER FROM CPT FOR METERING

150E 150E

INSTALL NEW CABLES FROM MAIN

SWITCHGEAR TO MANHOLE IN EXISTING

CONDUIT.

3#250MCM+1#2/0G IN EXISTING CONDUIT.

PART OF FUTURE CONTRACT. NOT IN

THIS CONTRACT.

REPLACE EXISTING 100A

EXPULSION TYPE FUSE WITH

150A EXPULSION TYPE FUSE.

PART OF FUTURE CONTRACT.

NOT IN THIS CONTRACT.

REPLACE EXISTING 100A

EXPULSION TYPE FUSE WITH

150A EXPULSION TYPE FUSE.

PART OF FUTURE CONTRACT.

NOT IN THIS CONTRACT.

120V CONTROL POWER FROM

CPT FOR MAIN-TIE-MAIN PLC

1 1

2.3/2.576MVA

12.47kV/480V 5.75Z

2.3/2.576MVA

12.47kV/480V 5.75Z

NOTES:

1. FOR UTILITY COMPANY DATA, SYMBOLS GENERAL NOTES AND ABBREVIATIONS REFER TO

DRAWING E001.00

2. BASIS OF DESIGN FOR OUTDOOR 15kV CLASS ELECTRICAL MEDIUM VOLTAGE SWITCHGEAR

AND BREAKERS IS EATON OR APPROVED EQUAL.

3. BASIS OF DESIGN FOR SUBSTATION TYPE 12.47kV TO 480V TRANSFORMERS IS EATON

TRANSFORMERS OR APPROVED EQUAL.

4. ALL EQUIPMENT MUST BE PROVIDED FROM A SINGLE MANUFACTURER.

5. ALL LV EQUIPMENT SHALL BE RATED FOR SCCR OF 65kA. ALL LV BREAKERS SHALL BE RATED FOR 65 kAIC.

6. PROVIDE CIRCUIT BREAKER REMOTE MOTOR OPERATOR FOR ALL 15kV CLASS BREAKERS.

PROVIDE CIRCUIT BREAKER REMOTE MOTOR OPERATOR FOR 480V CIRCUIT BREAKERS

MARKED "MO".

7. ALL CIRCUIT BREAKERS, FUSE DISCONNECT SWITCHES ARE THREE (3) POLE U.O.I.

8. FUSE RATING/CIRCUIT BREAKER FRAME RATINGS IN AMPS ARE DENOTED BY THE LETTERS

"AF", SWITCH RATING IN AMPS ARE DENOTED BY THE LETTERS "AS" AND "AT" DENOTES TRIP

RATING IN AMPS.

9. INCOMING MV CABLES/CONDUITS ARE BOTTOM ENTRY, OUTGOING LV CABLES/CONDUIT ARE

BOTTOM EXIT.

10. COORDINATE SPECIFICS OF INCOMING SERVICE FROM THE NEAREST MANHOLE IN THE FIELD.

11. SPD SHALL BE INTEGRALLY MOUNTED IN THE LV BOARD BY THE SAME MANUFACTURER AS

THE SWITCHBOARD. SPD SHALL BE SERVICE ENTRANCE TYPE AND MUST INCLUDE A SURGE

COUNTER.

12. MANUFACTURERS SELECTION OF PRIMARY TYPE OF FUSE SHALL ENSURE COORDINATION

WITH SUBSTATION #2 AND #4. IF MIS-COORDINATION IS IDENTIFIED THE MANUFACTURER

SHALL REPLACE THE FUSE THAT WILL PROPERLY COORDINATE AT NO ADDITIONAL COST.

13. WINNING BIDDER SHALL PROVIDE POWER SYSTEM STUDIES TO THE EOR INCLUDING, ARC

FLASH STUDIES AND ARC FLASH LABELS.

14. INCLUDE FACTORY ACCEPTANCE TESTING IN THE PROCUREMENT BID.

E

TCB#2

N.O.

WORK TO BE DONE IN A FUTURE

CONTRACT

25kAIC

SEL-751

100A/5A

50,51,50PAF

E

1200A

SEL-787

150A/5A

325kAIC

SEL-751

100A/5A

50,51,50PAF

ET, LSIG 400AF

400AT

SPARE

Y Y

(3)VT-480/120V

4000A/5A

TO SEL-787 TO SEL-787

3 3

49,50N/G,51, 52A/B,87

49,50N/G,51, 52A/B,87

HMI

ETHERNET TO SEL-751,787,2414,PQ METER,

MAIN -TIE-MAIN CONTROLLER AND SPD's

ASSOCIATED WITH SUBSTATION #2.

TO SCADA IN MAIN OFFICE VIA

ETHERNET/FIBER.

4 4

MO MO

MO MO

2 2

MO

27,47

1 1

27,47

(3)VT-480/120V

120V CONTROL POWER FROM CPT FOR SEL 751,787,2414

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL

POWER SINGLE

LINE DIAGRAM -

SUBSTATION #2

E009.00

ELECTRICAL POWER SINGLE LINE DIAGRAM - SUBSTATION #4 SHEET#11

E010 NTS

TO SUBSTATION #2 REFER TO

DRAWING E009

ET, LSIG ET, LSIG ET, LSIG ET, LSIG ET, LSIG ET, LSIG ET, LSIG ET, LSIG ET, LSIG ET, LSIG ET, LSIG ET, LSIG

480V, 3 PHASE, 4W + G

SS#4-BUS 2, 3000A BUS

SCCR 65kA, 600V CLASS

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

REFER TO E011 FOR

CONTINUATION

800AF

600AT

800AF

600AT

800AF

600AT

800AF

600AT

800AF

600AT

800AF

600AT

800AF

600AT

800AF

600AT

800AF

600AT

800AF

600AT

800AF

600AT

800AF

600AT

INTERCEPT EXISTING CABLES AND EXTEND TO

NEW BREAKERS. PROVIDE SIMILAR MATCHING

NEW CABLES, CONDUITS, ACCESSORIES AND

FITTINGS TO MAKE THE EXTENSION.

2 SETS OF

(3#500MCM+1#4/0G)

IN 2-4"C

2 SETS OF

(3#500MCM+

1#4/0G) IN 2-4"C

2 SETS OF

(3#600MCM+1#4/0G)

IN 2-4"C

2 SETS OF

(3#600MCM+1#4/0G)

IN 2-4"C

2 SETS OF

(3#600MCM+1#4/0G)

IN 2-4"C

2 SETS OF

(3#600MCM+1#4/0G)

IN 2-4"C

2 SETS OF

(3#600MCM+1#4/0G)

IN 2-4"C

2 SETS OF

(3#600MCM+1#4/0G)

IN 2-4"C

2 SETS OF

(3#600MCM+1#4/0G)

IN 2-4"C

2 SETS OF

(3#600MCM+1#4/0G)

IN 2-4"C

2 SETS OF

(3#600MCM+1#4/0G)

IN 2-4"C

2 SETS OF

(3#600MCM+1#4/0G)

IN 2-4"C

MCC-FEB-A MCC-DCBA PP-OBA MCC-MBA MCC-PCA MCC-HWA MCC-HWB MCC-PCB MCC-MBB PP-OBB MCC-DCBB MCC-FEB-B

TO SUBSTATION #2 REFER TO

DRAWING E009

480V, 3 PHASE, 4W + G

SS#4-BUS 1, 3000A BUS

SCCR 65kA, 600V CLASS

MTM-PLC

#2/0G, 15kV CLASS CABLE

FOR EACH ARRESTER

1200A

SEL-751

Δ

SEL-787

SEL-2414

MVS-4A

ET, LSIG

METERING

100A/5A

3000A/5A

1.725/2.106 MVA LIQUID FILLED KNAN/KNAF 55/75°C RISE,

Z=5.75% SUBSTATION TYPE OUTDOOR STEP-DOWN CU

TRANSFORMER (12.47kV) Δ-Y (480/277V) Dyn1, K-4, TRANSFORMER T4-A. PROVIDE SEL787 IN MVS-2A

ENCLOSURE FOR TRANSFORMER PROTECTION AND SEL 2414

FOR TRANSFORMER MONITORING.TRANSFORMER COLOR

SHALL BE ANSI 61.WINNING BIDDER MUST COORDINATE WITH

SEL TO INTEGRATE SEL RELAYS IN 15kV CLASS MV GEAR.

150A/5A

3000A/5A

POWER XPERT METER PXQ-ST2-1A1 OR APPROVED EQUAL

CPT-480 TO 120V

3000AF

2600AT

T4-A

50,51,50PAF

150A/5A

120V CONTROL POWER FROM CPT FOR SEL 751,787,2414SS#4-

MCB-A

POWER TO GFI MAINTENANCE RECEPTACLE

120V CONTROL POWER FROM CPT FOR METERING

#2/0G, 15kV CLASS CABLE

FOR EACH ARRESTER

Δ SEL-2414

MVS-4B

ET, LSIG

METERING3000A/5A

1.725/2.106 MVA LIQUID FILLED KNAN/KNAF 55/75°C RISE,

Z=5.75% SUBSTATION TYPE OUTDOOR STEP-DOWN CU

TRANSFORMER (12.47kV) Δ-Y (480/277V) Dyn1, K-4, TRANSFORMER T4-B. PROVIDE SEL787 IN MVS-4B ENCLOSURE

FOR TRANSFORMER PROTECTION AND SEL 2414 FOR

TRANSFORMER MONITORING.TRANSFORMER COLOR SHALL

BE ANSI 61.WINNING BIDDER MUST COORDINATE WITH SEL TO

INTEGRATE SEL RELAYS IN 15kV CLASS MV GEAR.

150A/5A

3000A/5A

POWER XPERT METER PXQ-ST2-1A1

OR APPROVED EQUAL

CPT-480 TO 120V

3000AF

2600AT

T4-B

120V CONTROL POWER FROM

CPT FOR SEL 751,787,2414

SS#4-

MCB-B

POWER TO GFI

MAINTENANCE RECEPTACLE

120V CONTROL POWER

FROM CPT FOR METERING

SPD SPD

PLC FOR AUTOMATIC MAIN-TIE-MAIN

CONTROLLER WITH ELECTRICAL INTERLOCKS

BY EATON OR APPROVED EQUAL FOR TCB#4.

120V CONTROL POWER FROM

CPT FOR MAIN-TIE-MAIN PLC

ET, LSIG

3000AF

2600AT

125E 125E

REPLACE EXISTING 75A EXPULSION TYPE

FUSE WITH 125A EXPULSION TYPE FUSE.

PART OF FUTURE CONTRACT. NOT IN THIS

CONTRACT.

REPLACE EXISTING 75A EXPULSION TYPE

FUSE WITH 125A EXPULSION TYPE FUSE.

PART OF FUTURE CONTRACT. NOT IN THIS

CONTRACT.

NEW CABLES & FROM EXISTING MANHOLE TO NEW MVS-4A/B

3#250MCM+1#2/0G IN 5"C.

PART OF FUTURE CONTRACT. NOT IN THIS CONTRACT.

INSTALL NEW CABLES FROM MAIN

SWITCHGEAR TO MANHOLE IN EXISTING

CONDUIT.

3#250MCM+1#2/0G IN EXISTING CONDUIT.

PART OF FUTURE CONTRACT. NOT IN

THIS CONTRACT.

INSTALL NEW CABLES FROM MAIN

SWITCHGEAR TO MANHOLE IN EXISTING

CONDUIT.

3#250MCM+1#2/0G IN EXISTING CONDUIT.

PART OF FUTURE CONTRACT. NOT IN THIS

CONTRACT.

NOTES:

1. FOR UTILITY COMPANY DATA, SYMBOLS GENERAL NOTES AND

ABBREVIATIONS REFER TO DRAWING E001.00

2. BASIS OF DESIGN FOR OUTDOOR 15kV CLASS ELECTRICAL MEDIUM

VOLTAGE SWITCHGEAR AND BREAKERS IS EATON OR APPROVED

EQUAL.

3. BASIS OF DESIGN FOR SUBSTATION TYPE 12.47kV TO 480V

TRANSFORMERS IS EATON TRANSFORMERS OR APPROVED EQUAL.

4. ALL EQUIPMENT MUST BE PROVIDED FROM A SINGLE

MANUFACTURER.

5. ALL LV EQUIPMENT SHALL BE RATED FOR SCCR OF 65kA. ALL LV BREAKERS SHALL BE RATED FOR 65kAIC.

6. PROVIDE CIRCUIT BREAKER REMOTE MOTOR OPERATOR FOR ALL

15kV CLASS BREAKERS. PROVIDE CIRCUIT BREAKER REMOTE

MOTOR OPERATOR FOR 480V CIRCUIT BREAKERS MARKED "MO".

7. ALL CIRCUIT BREAKERS, FUSE DISCONNECT SWITCHES ARE THREE

(3) POLE U.O.I.

8. FUSE RATING/CIRCUIT BREAKER FRAME RATINGS IN AMPS ARE

DENOTED BY THE LETTERS "AF", SWITCH RATING IN AMPS ARE

DENOTED BY THE LETTERS "AS" AND "AT" DENOTES TRIP RATING IN

AMPS.

9. INCOMING MV CABLES/CONDUITS ARE BOTTOM ENTRY, OUTGOING

LV CABLES/CONDUIT ARE BOTTOM EXIT.

10. COORDINATE SPECIFICS OF INCOMING SERVICE FROM THE

NEAREST MANHOLE IN THE FIELD.

11. SPD SHALL BE INTEGRALLY MOUNTED IN THE LV BOARD BY THE

SAME MANUFACTURER AS THE SWITCHBOARD. SPD SHALL BE

SERVICE ENTRANCE TYPE AND MUST INCLUDE A SURGE COUNTER.

12. MANUFACTURERS SELECTION OF PRIMARY TYPE OF FUSE SHALL

ENSURE COORDINATION WITH SUBSTATION #2 AND #4. IF

MIS-COORDINATION IS IDENTIFIED THE MANUFACTURER SHALL

REPLACE THE FUSE THAT WILL PROPERLY COORDINATE AT NO

ADDITIONAL COST.

13. WINNING BIDDER SHALL PROVIDE POWER SYSTEM STUDIES TO THE

EOR INCLUDING, ARC FLASH STUDIES AND ARC FLASH LABELS.

14. INCLUDE FACTORY ACCEPTANCE TESTING IN THE PROCUREMENT

BID.

KEYED NOTES:

1. PROVIDE ADDITIONAL CPT'S IF NEEDED FOR SWITCHGEAR HEATING.

2. PROVIDE MV/LV CIRCUIT BREAKER REMOTE OPERATOR. REMOTE OPERATOR SHALL BE POWERED FROM THE

LV BUS CPT AFTER SS#4-MCB-A/B.

3. TRIP/CLOSE/BREAKER STATUS AND BREAKER MONITORING.

4. PROVIDE ELECTRICAL INTERLOCKS BETWEEN MAIN-TIE-MAIN BREAKER AND FEEDER #1 AND FEEDER #2 LV BREAKERS AS NEEDED. FOR MAIN-TIE-MAIN SEQUENCE OF OPERATION REFER TO SPECIFICATION 26 23 00.13.

1 1

1.725/2.106MVA

12.47kV/480V 5.75Z

1.725/2.106MVA

12.47kV/480V 5.75Z

E E E E E E E E E E E E

TCB#4

N.O.

HMI

ETHERNET TO SEL-751,787,2414, PQ METER,

MAIN -TIE-MAIN CONTROLLER AND SPD'S

ASSOCIATED WITH SUBSTATION #4.

WORK TO BE DONE IN A

FUTURE CONTRACT

5225kAIC

Y Y

EXISTING TO REMAIN.

NOT IN CONTRACT.

E

1200A

SEL-751

SEL-787

100A/5A

50,51,50PAF

150A/5A

35225kAIC 3

TO SEL-787 TO SEL-787

3 3

49,50N/G,51, 52A/B,87

49,50N/G,51, 52A/B,87

TO SCADA IN MAIN OFFICE VIA

ETHERNET/FIBER.

4 4

ET, LSIG 400AF

400AT

SPARE

ET, LSIG 400AF

400AT

SPARE

MO MO

MO MO

MO

27,47

1 1

27,47

(3)VT-480/120V (3)VT-480/120V

(3) LIGHTNING ARRESTERS, 15kV MCOV.

PROVIDE SURGE EVENT COUNTER

(3) LIGHTNING ARRESTERS, 15kV MCOV.

PROVIDE SURGE EVENT COUNTER

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL

POWER SINGLE

LINE DIAGRAM -

SUBSTATION #4

SHEET#1

E010.00

EXISTING TO REMAIN.

NOT IN CONTRACT.

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

REFER TO E010 FOR

CONTINUATION

SCALE:

ELECTRICAL POWER SINGLE LINE DIAGRAM - SUBSTATION #4 SHEET#21

E011 NTS

E

E E E E E E E E E E E E

NOTES:

1. THIS DRAWING IS NOT FOR CONSTRUCTION.

2. THIS DRAWING IS ONLY TO CONVEY THE INTENT OF THE THE

PROCUREMENT OF ELECTRICAL GEAR FOR SUBSTATION #4.

3. DEMOLITION OF SUBSTATION #4 WILL BE CARRIED OUT AS A PART OF A

SEPARATE CONTRACT, ONCE THE PROCUREMENT AND THE

INSTALLATION OF THE NEW ELECTRICAL SWITCHGEAR AT SUBSTATION #4

IS COMPLETED.

REVISIONS

NO. REVISION DATE

DRAWN/DESIGN BY CHECKED BY

PREPARED FOR

GPI PROJECT/CONTRACT NO.:

ISSUED FOR PERMIT REVIEW ONLY. THESE DRAWINGS ARE

IN SUBSTANTIAL CONFORMANCE WITH THE BUILDING CODE.

Construction Inspection

Engineering Design Planning

2 Executive Boulevard, Suite 202 Suffern, NY 10901

Greenman-Pedersen, Inc.

845.368.4050 GPINET.COM

MNY-2600015.00

1053 SPRUCE ROAD

ALLENTOWN, PA

IN

DU

ST

RI

AL

B

LV

D, AL

LE

NT

O

W N, P A

LE

HI

G H

CO

UN

TY

A

UT

HO

RI

TY

EL

EC

TR

IC

AL

S

UB

ST

AT

IO

N #2

A

ND

#4 P

RO

CU

RE

M

EN

T

NOT FOR CONSTRUCTION. FOR EQUIPMENT PROCUREMENT ONLY.

DK SH

ELECTRICAL

POWER SINGLE

LINE DIAGRAM -

SUBSTATION #4

SHEET#2

E011.00

Sheets and Views
E002.00 ELECTRICAL SITE PLAN - DEMOLITION
E003.00 ELECTRICAL SITE PLAN - INSTALLATION
E004.00 ELECTRICAL SUBSTATION#2 PART PLAN - DEMOLITION
E005.00 ELECTRICAL SUBSTATION#2 PART PLAN - INSTALLATION
E006.00 ELECTRICAL SUBSTATION#4 PART PLAN - DEMOLITION
E007.00 ELECTRICAL SUBSTATION#4 PART PLAN - INSTALLATION
E008.00 ELECTRICAL POWER SINGLE LINE DIAGRAM - DEMOLITION
E009.00 ELECTRICAL POWER SINGLE LINE DIAGRAM - SUBSTATION #2
E010.00 ELECTRICAL POWER SINGLE LINE DIAGRAM - SUBSTATION #4 SHEET#1
E011.00 ELECTRICAL POWER SINGLE LINE DIAGRAM - SUBSTATION #4 SHEET#2

File details come from the government source that posted it. Updated .