26 12 13.01 - Liquid-Filled Medium Voltge Unit Substation Transformers.pdf

PDF 263 KB Posted

Attached to
Electrical Substation Replacement Project – Equipment Procurement Phase
Solicitation number
US.255952
Issued by
Lehigh County, Pennsylvania

About this file

This specification document outlines the technical requirements for liquid-filled, medium-voltage unit substation transformers for Lehigh County Authority's Electrical Substation Replacement Project – Equipment Procurement Phase, located in Allentown, Pennsylvania. The procurement covers three-phase substation distribution transformers rated between 300 and 12,000 kVA, with specific ratings designated for two substations: 2,300/2,576 kVA at 55/65°C for Substation #2 and 1,725/2,106 kVA at 55/75°C for Substation #4. Both units feature 12,470V high-voltage with 95 kV basic lightning impulse insulation level (BIL) and 480Y/277V low-voltage with 30 kV BIL, configured with delta-grounded wye connections and two ±2% split taps. Online sealed bids will be received through PennBid until 11:00 a.m. on Wednesday, October 28, 2026, with bids remaining open for 60 days from opening. Site visits are self-guided and can be scheduled with Charles Volk, P.E., Chief Capital Works Officer. Approved manufacturers include Eaton, ABB, Siemens, and Square D/Schneider Electric.

The specification mandates use of Envirotemp FR3 less-flammable dielectric fluid meeting National Electrical Code requirements, sealed tank construction rated for 7 psig without permanent distortion and 15 psig without rupturing, and vacuum-processed core and coil assemblies. Transformers must comply with multiple IEEE, NEMA, and Department of Energy standards, include all-copper windings, K-4 factor design, current transformers for relaying/metering, and be UL Listed and Classified per UL XPLH for installations on or inside buildings. Standard accessories include de-energized tap-changer, drain valve with sampling device, pressure relief device, lifting lugs, liquid level gauge, thermometer, pressure/vacuum gauge, and nitrogen blanket. Optional accessories specified include NEMA 4X stainless steel control box for SEL 2414 transformer monitoring and external SEL 787 protection relaying mounted at the 15 kV medium-voltage switchgear. Bid security of 10 percent of the bid total is required in the form of certified check, bank check, or bid bond. All bidding documents are available at no cost through PennBid, and Lehigh County Authority reserves the right to reject any and all bids and waive any defects or irregularities.

View the file

Other files

File Type Posted
26 11 16.11 - Secondary Unit Substations - Secondary Less Than 1000V.pdf PDF
9-Agreement of Surety Form Contract.pdf PDF
23-EJCDC - Payment Bond (C-620-2002).pdf PDF
1-LCA-ELECTRICAL SUBSTATION PROCUREMENT DWGS.pdf PDF
017716 – CONTRACT CLOSEOUT.pdf PDF
15-Affidavit of Non-Collusion.pdf PDF
21-EJCDC - Performance Bond (C-600-2002).pdf PDF
012977.02 - MEASUREMENT AND PAYMENT.pdf PDF
13-List of Proposed Subcontractors.pdf PDF
26 27 13.11 - Microprocessor-Based Metering Equipment.pdf PDF
017900.01 - VIDEO TRAINING PROGRAMS.pdf PDF
26 23 00.16 - Arc Resistant Metal Enclosed Drawout Switchgear LV.pdf PDF
27-PA Prevailing Wage Act Duties00810.pdf PDF
26 05 73.13 - Short Circuit Studies.pdf PDF
1-TITLE page.pdf PDF
26 13 26.11 - Metal Clad MV Arc Resistent Switchgear.pdf PDF
24-EJCDC - General Conditions (with Supplementary shown).pdf PDF
2-TOC.pdf PDF
011000.03 -SUMMARY OF THE WORK.pdf PDF
26 05 53 - Identification For Electrical Systems.pdf PDF
26 05 73.19 - Arc Flash Hazard Analysis.pdf PDF
26 43 13A - LV Surge Protective Devices For Electrical Distribution Systems.pdf PDF
19-EJCDC - Agreement Stipulated Price (C-520-2002).pdf PDF
5-EJCDC - Bid Form for Construction Contracts 00300 (003).pdf PDF
4-7-EJCDC - Bid Bond, Penal Sum Form (C-430-2002) Revised 10-30-2026.pdf PDF
11-Experience Questionnaire.pdf PDF
013300.0 - SUBMITTALS.pdf PDF
3-Addendum 1 LCA.pdf PDF
4-EJCDC - Instructions to Bidders (C-200-2002).pdf PDF
7-EJCDC - Bid Bond, Penal Sum Form (C-430-2002).pdf PDF
3-00010_Invitation to Bid.pdf PDF
26 05 73.16 - Coordination Studies.pdf PDF
17-CertAsToCorpPrincipal.pdf PDF
Show all 33

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Substation #2, #4 Procurement 7676 Industrial Blvd.

Allentown, PA 18106 September 15, 2026

26 12 13.01-1

SECTION 26 12 13.01

LIQUID-FILLED, MEDIUM-VOLTAGE UNIT SUBSTATION TRANSFORMERS

PART 1 GENERAL

1.01 SCOPE

A. This specification covers the electrical and mechanical characteristics of 300– 12,000 kVA three-phase substation type distribution transformers. Product is per Eaton’s catalog data CA202001EN.

B. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.

1.02 APPLICABLE STANDARDS

A. All characteristics, definitions, and terminology, except as specifically covered in this specification, shall be in accordance with the latest revision of the following IEEE®, Department of Energy, and NEMA® standards.

1. IEEE Std C57.12.00™-2015 – IEEE Standard for Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers

2. IEEE Std C57.12.28™-2014 – Sections 5.3, 5.4, 5.5 – Coating System Requirements

3. IEEE Std C57.12.36™- 2017 – IEEE Standard Requirements for Liquid- Immersed Distribution Substation Transformers

4. IEEE Std C57.12.70™-2011 – IEEE Standard for Terminal Markings and Connections for Distribution and Power Transformers

5. IEEE Std C57.12.90™-2010 – IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers and IEEE Guide for Short- Circuit Testing of Distribution and Power Transformers

6. IEEE Std C57.154™ -2012 – IEEE Standard for the Design, Testing, and Application of Liquid-Immersed Distribution, Power, and Regulating Transformers Using High-Temperature Insulation Systems and Operating at Elevated Temperatures

7. NEMA® TR 1-1993 (R2000) – Transformers, Regulators and Reactors, Table 0-2 Audible Sound Levels

8. 10 CFR Part 431 – Department of Energy–Energy Conservation Program:

Energy Conservation Standards for Distribution Transformers; Final Rule

9. IEEE Std 386™-2006 – IEEE Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600 V

PART 2 PRODUCTS

2.01 MANUFACTURERS

A. Eaton

Allentown, PA 18106 September 15, 2026

26 12 13.01-2

B. ABB

C. Siemens

D. Square D/Schneider Electric

2.02 RATINGS

A. The transformer shall be designed in accordance with this specification, and the base kVA rating shall be: 2300/2576 kVA, 55/65°C, KNAN/KNAF for Substation #2 and 1725/2106 kVA, 55/75°C, KNAN/KNAF for Substation #4.

B. The transformer shall have a high voltage and the basic lightning impulse insulation level (BIL) of 12,470V and 95kV BIL.

C. The low voltage and the basic lightning impulse insulation level (BIL) shall be 480Y/277V and 30kV BIL.

Table 1

Transformer Ratings and Electrical Characteristics

Transformer

Basic Impulse Insulation Level –

BIL (kV)

Voltage Ratings (volts) Standard

Transformers

CLT/HDC

Transformers

Secondary Voltages 208Y/120 480Y/277 575Y/332 600Y/347 690Y/398 240 Delta 480 Delta 240 Delta with 120 Mid-Tap 480 Delta with 240 Mid-Tap

Allentown, PA 18106 September 15, 2026

26 12 13.01-3

Primary Voltages 2400 Delta 4160 Delta 4800 Delta 7200 Delta 12000 Delta 12470 Delta 13200 Delta 13800 Delta 14400 Delta 16340 Delta 34500 Delta 43800 Delta 4160GrdY/2400 8320GrdY/4800 12470GrdY/7200 13200GrdY/7620 13800GrdY/7970 22860GrdY/13200 23900GrdY/13800 24940GrdY/14400 34500GrdY/19920 43800GrdY/25300

D. The high voltage and low voltage connections of the transformer shall be (See checked option):

1. [] Delta - Wye:

a. For Delta - Wye configurations the low voltage neutral shall be a fully insulated X0 bushing. The low voltage shall lag the high voltage by 30°.

2. [X] Delta - Grounded Wye

a. For Delta - Grounded Wye configurations the low voltage neutral shall be a fully insulated X0 bushing with ground strap. The low voltage shall lag the high voltage by 30°.

3. [] Delta - Delta

a. For Delta - Delta configurations the transformer shall be provided without a neutral bushing. There shall be no phase shift between the high voltage and low voltage.

4. [] Grounded Wye - Wye

a. For Grounded Wye - Wye configurations the high voltage neutral shall be internally tied to the low voltage neutral and brought out as the H0X0 bushing. There shall be no phase shift between the high voltage and low voltage.

5. [] Wye - Grounded Wye

a. For Wye - Grounded Wye configurations the high voltage neutral shall be brought out as the Ho bushing on the high voltage side and the low voltage neutral shall be brought out as the X0 bushing with ground strap

Allentown, PA 18106 September 15, 2026

26 12 13.01-4 on the low voltage side. There shall be no phase shift between the high voltage and low voltage.

6. [] Wye - Delta

a. For Wye - Delta configurations the high voltage neutral shall be brought out as the Ho bushing on the high voltage side. The low voltage shall lag the high voltage by 30°.

E. The transformer shall be furnished with full capacity high-voltage taps. The tap-changer shall be clearly labeled to reflect that the transformer must be de-energized before operating the tap-changer as required in Section 4.3 of IEEE Std C57.12.34™-2009 standard. The tap-changer shall be operable on the higher voltage only for transformers with dual high voltages. The unit shall have one of the following tap configurations:

1. [] No Taps

2. [X] Two – 2 ½% taps above and below rated voltage (split taps)

3. [] Four – 2 ½% taps below rated voltage (four below)

4. [] NEMA taps (14400, 13800, 13200, 12470, 12540)

F. The dielectric coolant shall be listed less-flammable fluid meeting the requirements of National Electrical Code® Section 450-23 and the requirements of the National Electrical Safety Code® (IEEE Std C2™-2002 standard), Section 15. The dielectric coolant shall be non-toxic*, non-bioaccumulating and be readily and completely biodegradable per EPA OPPTS 835.3100. The base fluid shall be 100% derived from edible seed oils and food grade performance enhancing additives. The fluid shall not require genetically altered seeds for its base oil. The fluid shall result in zero mortality when tested on trout fry (Per OECD G.L. 203).

The fluid shall be certified to comply with the US EPA Environmental Technology Verification (ETV) requirements and tested for compatibility with transformer components. The fluid shall be Factory Mutual Approved®, UL® Classified Dielectric Medium (UL-EOUV) and UL® Classified Transformer Fluid (UL-EOVK), Envirotemp™ FR3™ fluid.

G. The transformer, filled with Envirotemp™ FR3™ fluid, shall have a (See checked option):

1. [] 65°C average winding temperature rise rating. The above winding temperature rise shall not exceed 65°C when loaded at base kVA rating.

2. [] 75°C average winding temperature rise rating. The above winding temperature rise shall not exceed 75°C when loaded at base kVA rating. This transformer is identified as a PEAK transformer.

3. [X] 55/65°C average winding temperature rise rating. The above winding temperature rise shall not exceed 55°C when loaded at base kVA rating. The transformer shall provide an additional 12% continuous operating capacity at the 65°C rating.

4. [] 65/75°C average winding temperature rise rating. The above winding temperature rise shall not exceed 65°C when loaded at base kVA rating. The transformer shall provide an additional 12% continuous operating capacity at the 75°C rating. This transformer is identified as a PEAK transformer.

Allentown, PA 18106 September 15, 2026

26 12 13.01-5

5. [] 55/75°C average winding temperature rise rating. The above winding temperature rise shall not exceed 55°C when loaded at base kVA rating. The transformer shall provide an additional 22% continuous operating capacity at the 75°C rating. This transformer is identified as a PEAK transformer.

H. The percent impedance voltage, as measured on the rated voltage connection, shall be per Table 5 of IEEE Std C57.12.36™-2007 standard.

I. The transformer shall be cooled by the natural circulation of air over the tank surface

J. UL® Listing/Classification and FM® Approval (See checked option):

1. [] The transformer shall be UL® Listed (certifying compliance with IEEE® standards only) per UL® XPLH.

2. [X] The transformer shall be combination UL® Listed & Classified to comply with NEC® 450-23 listing restrictions for installations on, near, or inside of buildings per UL® XPLH.

3. [] The transformer shall be FM® Global (FM) Approved to comply with NEC® 450-23 listing restrictions for installations on, near, or inside of buildings.

2.03 CONSTRUCTION

A. The core and coil shall be vacuum processed to ensure maximum penetration of insulating fluid into the coil insulation system. While under vacuum, the windings will be energized to heat the coils and drive out moisture, and the transformer will be filled with preheated filtered degassed insulating fluid. The core shall be manufactured from burr-free, grain-oriented silicon steel and shall be precisely stacked to eliminate gaps in the corner joints. The coil shall be insulated with B-stage, epoxy coated, diamond pattern, insulating paper, which shall be thermally cured under pressure to ensure proper bonding of conductor and paper.

B. Panel type, removable radiators, complete with flanged shut off valves on the tank side shall be provided.

C. The tank must be welded using precision cut, cold-rolled steel plate and equipped with extra-heavy duty, welded-in-place lifting lugs and jacking provisions. The tank base must be designed to allow skidding or rolling in any direction.

D. The transformer shall be of sealed tank construction of sufficient strength to withstand a pressure of 7 psig without permanent distortion, and 15 psig without rupturing.

E. The tank shall include a pressure relief device as a means to relieve pressure in excess of pressure resulting from normal operation. The venting and sealing characteristics shall be as follows:

1. Cracking Pressure: 10 psig +/-2 psig

2. Resealing Pressure: 6-psig minimum

3. Zero leakage from reseal pressure to -8 psig

4. Flow at 15 psig: 50 SCFM minimum

F. The tank shall be cleaned with an alkaline cleaning agent to remove grease and oil. An iron phosphate coating shall then be chemically bonded to the metal to

Allentown, PA 18106 September 15, 2026

26 12 13.01-6 assure coating adhesion and retard corrosion. The tank shall be primed with an electrodeposited powder epoxy to provide a barrier against moisture, salt, and corrosives. The top-coat shall be a liquid polyurethane coating to seal and add ultraviolet protection. The tank coating shall meet all requirements in IEEE Std C57.12.28™-2014 standard.

G. The high voltage terminations shall each be enclosed with the following (Approved manufacturer shall select the appropriate arrangement such that alignment of switchgear is not compromised):

1. [X] Throat

a. A throat is used on a transformer with sidewall-mounted bushings for connecting the transformer with bus duct. It extends 8 inches above and below the centerline of the bushings.

2. [] Flange (required with high voltage air disconnect switch)

a. A flange is used on a transformer with sidewall mounted bushings for direct connection to metal clad switchgear and is required with the high voltage air disconnect switch option. The flange extends 8 inches above and 32 inches below the bushing centerline.

3. [X] Partial height, bottom entry air terminal chamber

a. The partial height bottom entry chamber extends approximately 24 inches below the centerline of the bushings and has a bottom removable plate that can accommodate cable glands or conduit hubs. The chamber shall include a hinged door with padlockable handle and a pentahead/hexhead bolt and a lift-off front panel.

4. [X] Partial height, top entry air terminal chamber

a. The partial height top entry air terminal chamber has a chimney with a removable cover that extends 24 inches above the bushing centerline and can be equipped with cable glands or conduit hubs.

Bus duct can be adapted to match the top of the chimney for bus termination. A hinged door with padlockable handle and a pentahead/hexhead bolt and a lift-off front panel.

5. [X] Full height, bottom entry cabinet

a. A full height bottom entry air terminal chamber is a weather-resistant metal enclosure around sidewall mounted bushings that extends downward to the transformer base level and upward approximately 10 inches above the bushing centerline. It is intended for underground feed and is provided with facilities for distribution arresters. A hinged door with padlockable handle and a pentahead/hexhead bolt and a lift-off front panel.

6. [X] Full height, top entry cabinet

a. A full height top entry air terminal chamber is a weather resistant metal enclosure around sidewall mounted bushings that extends downward to the transformer base level and upward approximately 24 inches above the centerline of the bushings. The chamber shall include a hinged door with padlockable handle and a hexhead bolt, and a lift-off front panel.

Allentown, PA 18106 September 15, 2026

26 12 13.01-7

H. The low voltage terminations shall each be enclosed with the following (See checked option, Approved manufacturer shall select the appropriate arrangement such that alignment of switchgear is not compromised):

1. [] Throat

a. A throat is used on a transformer with sidewall-mounted bushings for connecting the transformer with bus duct. It extends 8 inches above and below the centerline of the bushings.

2. [X] Flange

a. A flange is used on a transformer with sidewall mounted bushings for direct connection to metal clad switchgear and is required with the high voltage air disconnect switch option. The flange extends 8 inches above and 32 inches below the bushing centerline.

3. [] Partial height, bottom entry air terminal chamber

a. The partial height bottom entry chamber extends approximately 24 inches below the centerline of the bushings and has a bottom removable plate that can accommodate cable glands or conduit hubs. The chamber shall include a hinged door with padlockable handle and a pentahead/hexhead bolt and a lift-off front panel.

4. [] Partial height, top entry air terminal chamber

a. The partial height top entry air terminal chamber has a chimney with a removable cover that extends 24 inches above the bushing centerline and can be equipped with cable glands or conduit hubs. Bus duct can be adapted to match the top of the chimney for bus termination. A hinged door with padlockable handle and a pentahead/hexhead bolt and a lift-off front panel.

5. [] Full height, bottom entry cabinet

a. A full height bottom entry air terminal chamber is a weather-resistant metal enclosure around sidewall mounted bushings that extends downward to the transformer base level and upward approximately 10 inches above the bushing centerline. It is intended for underground feed and is provided with facilities for distribution arresters. A hinged door with padlockable handle and a pentahead/hexhead bolt and a lift-off front panel.

6. [] Full height, top entry cabinet

a. A full height top entry air terminal chamber is a weather resistant metal enclosure around sidewall mounted bushings that extends downward to the transformer base level and upward approximately 24 inches above the centerline of the bushings. The chamber shall include a hinged door with padlockable handle and a hexhead bolt, and a lift-off front panel.

I. The tank shall be complete with an anodized aluminum laser engraved nameplate.

This nameplate shall meet IEEE Std C57.12.00™-2015 standard for Nameplate B.

J. High voltage bushings and terminals (See checked option):

1. [X] The transformer shall be provided with three (3) sidewall -mounted high voltage bushings plus a H0 neutral bushing for WYE connected transformers rated for full three-phase duty with a 2-hole spade or an eyebolt connector. The high voltage bushings shall be mounted in

Allentown, PA 18106 September 15, 2026

26 12 13.01-8 segment 2 or 4 of the transformer. Refer to the contract drawing for the exact side.

2. [] The transformer shall be provided with three (3) sidewall mounted high voltage bushings, 200 amp wells with inserts for dead front application and arranged for radial feed configuration. The high voltage bushings shall be mounted in segment 2 or 4 of the transformer.

3. [] The applicable bushing configuration shall be specified on the inquiry.

K. Low voltage bushings and terminals (See checked option):

1. [X] The low voltage bushings shall be sidewall mounted. For voltages less than 1000V bushings shall be molded epoxy with a 8-Hole NEMA® spade. Low voltage bushings above 1000 V and all cover-mounted bushings shall be electrical grade wet process porcelain. The low voltage bushings shall be located in the segment opposite of the specified high-voltage configuration.

2. [] The applicable bushing configuration (phasing) shall be specified on the inquiry.

L. Transformer Protections

1. The transformer protections including primary overvoltage and overcurrent protection shall be provided with externally mounted, SEL 787 which will be mounted at the 15kV MV Switchgear. SEL 2414 will be housed in a dedicated NEMA 3/4X Control box for Transformer Monitoring.

M. The following standard accessories shall be provided:

1. De-energized tap-changer

2. 1.0” upper fill plug with filter press connection

3. 1.0” drain valve with sampling device

4. Cover-mounted automatic pressure relief device

5. Welded cover with bolted manhole

6. Lifting lugs (4)

7. Liquid level gauge

8. Dial type thermometer

9. Pressure/vacuum gauge

10. SS ground pads (4)

11. Nitrogen blanket with purge valve

12. Touch-up paint (2 aerosol cans)

N. The following optional accessories shall be provided if specified (See checked option):

1. [] Copper low voltage bushings (standard with all-copper windings)

2. [] Bleeder valve

3. [X] NEMA® 4 control box (standard with fan package)

Allentown, PA 18106 September 15, 2026

26 12 13.01-9

4. [X] NEMA® 4X control box (stainless steel) For SEL 2414 Transformer Monitoring

5. [] NEMA® 7 control box (explosion proof)

6. [] Rapid pressure rise relay

7. [] Seal-in panel for rapid pressure rise relay

8. [] Forced air fan control package

9. [] Winding temperature indicator

10. [] Auxiliary contacts for liquid level gauge

11. [] Auxiliary contacts for dial type thermometer (standard with fan package)

12. [] Auxiliary contacts for pressure/vacuum gauge

13. [] Auxiliary contacts for pressure relief device

14. [] 1.0” globe-type upper fill valve

O. Special Features (See checked option):

1. The following special features may be provided if specified (See checked option):

2. [X] All copper windings

3. [] Primary air disconnect switch

a. [] 1200 A loadbreak rating (requires 1200 A copper bus bar)

b. [] Outer front door (covers viewing area and switch)

c. [] Key interlocks for interlocking switch with secondary

d. [] Porcelain bus insulators

e. [] Copper bus transition to transformer (required for 600 A and greater)

f. [] Auxiliary switch (remote indication of primary switch position)

g. [] Line-side bus (bottom entry only)

h. [] Thermostat for space heater

4. [] Vacuum Fault Interrupter, 600 A continuous, [12.5 kA] [16 kA (only at 15 kV)] RMS Interrupting

5. [] Dead front HV termination

a. [] Loop feed

b. [] Radial feed

6. [] Sectionalizing switch, 4-position T-blade, 600 A, make-before-break option

7. [] 304L stainless steel construction

a. [] Tank base

Allentown, PA 18106 September 15, 2026

26 12 13.01-10

b. [] Primary enclosure

c. [] Secondary enclosure

d. [] 100% 304L stainless steel construction

8. [] Cooling

a. [] Mild steel radiators

1) [] Welded

2) [] Removable

b. [] Stainless steel radiators

1) [] Welded

2) [] Removable

c. [] Galvanized steel radiators (removable and unpainted)

9. [X] K-4 factor transformer

10. [] Positive nitrogen pressure oil preservation system

11. [X] Current transformers for relaying/metering

12. [] Containment pan for indoor use for 100% fluid containment

13. [] Factory Mutual® (FM) approved transformer (for NEC® Code-listed installations on, near, or inside of buildings)

14. [X] UL® Listed and Classified transformer (for NEC® Code-listed installations on, near, or inside of buildings) per UL® XPLH

15. [] UL® Listed transformer (certifying compliance with IEEE® standards only) per UL® XPLH

2.04 FINISH PERFORMANCE REQUIREMENTS

A. The tank coating shall meet all requirements in IEEE Std C57.12.28™-2014 standard including:

1. Salt Spray

2. Crosshatch adhesion

3. Humidity

4. Impact

5. Oil resistance

6. Ultraviolet accelerated weathering

7. Abrasion resistance–taber abraser

PART 3 EXECUTION

3.01 PRODUCTION TESTING

A. All units shall be tested for the following:

Allentown, PA 18106 September 15, 2026

26 12 13.01-11

1. Ratio, polarity and phase relation tests using all tap settings

2. Winding resistance measurement tests

3. Insulation power factor

4. Full wave and reduced wave impulse test

5. Applied and Induced potential tests

6. No-Load losses at rated current

7. Total losses at rated current

8. Percent impedance at rated current

9. Excitation current (100% voltage) test

10. Leak test

B. Transformers shall conform to efficiency levels for liquid immersed distribution transformers, as specified in the Department of Energy ruling “10 CFR Part 431 Energy Conservation Program: Energy Conservation Standards for Distribution Transformers; Final Rule; April 18, 2013.” Manufacturer shall comply with the intent of all regulations set forth in noted ruling (commonly referred to as DOE 2016).

C. The manufacturer shall provide certification upon request for all design and other tests listed in IEEE Std C57.12.00™-2010 standard, including verification that the design has passed short circuit criteria per IEEE Std C57.12.00™-2010 and IEEE Std C57.12.90™-2010 standards.

D. In the event of proposal bid evaluated with guaranteed losses due to a loss evaluation (see section 11.0), manufacturer shall conform to guaranteed average losses as specified in IEEE Std C57.12.00™-2010 standard. The no-load losses of a transformer shall not exceed the specified no-load losses by more than 10%, and the total losses of a transformer shall not exceed the specified total losses by more than 6%.

3.02 SHIPPING

A. The transformers shall be shipped from the Factory to the Transformers shall be loaded and unloaded with overhead cranes. No pallet shall be provided.

3.03 DATA WITH PROPOSAL

A. The following data shall be submitted with the proposal:

1. Core losses (when requested per Sections 3.01 D and 2.04 D).

2. Winding losses (when requested per Sections 3.01 D and 2.04 D).

3. Percent impedance

4. Typical bid drawing

B. The following checked data shall be submitted with the proposal:

1. [] Exciting Current @ 100% and 110% rated Voltage.

2. [X] Efficiencies must be provided at loading levels of 100%, 75%, 50%, and 25%.

Allentown, PA 18106 September 15, 2026

26 12 13.01-12

3. [] Percent regulation must be provided at 0.8 PF and 1.0 PF.

4.

3.04 DRAWINGS

A. The following will be provided by request after receipt of order:

1. [X] Construction drawings

2. [X] Record drawings

3. [X] Approval drawings

4. [X] CAD drawings

3.05 SERVICE

A. The manufacturer of the transformer shall have regional service centers located within 2 hours flight time of all contiguous 48 states. Service personnel shall be factory trained in commissioning and routine service of quoted transformers.

3.06 EXAMINATION

A. Examine liquid-filled, medium-voltage transformers upon delivery.

1. Upon delivery of transformers and prior to unloading, inspect equipment for any damage that may have occurred during shipment or storage.

2. Verify that tie rods and chains are undamaged and tight, and that all blocking and bracing is tight. Verify that there is no evidence of load shifting in transit, and that readings from transportation shock recorders, if equipped, are within manufacturer's recommendations.

3. Verify that there is no indication of external damage and no dents or scratches in doors and sill, tank walls, radiators and fins, or termination provisions.

4. Verify that there is no evidence of insulating-liquid leakage on transformer surfaces, at weld seams, on high- or low-voltage bushing parts, and at transformer base.

5. Transformers are factory sealed under vacuum and pressurized to prevent contamination of insulating liquid by contact with moisture or ambient air.

6. Verify that there is positive pressure or vacuum on the tank. Check the pressure gauge; it is required to read other than zero.

7. Compare transformers and accessories received with bill of materials to verify that shipment is complete. Verify that transformers and accessories conform with manufacturer's quotation and shop drawings. If shipment is incomplete or does not comply with Project requirements, notify manufacturer in writing immediately.

8. Verify presence of polychlorinated biphenyl content labeling.

9. Unload transformers carefully, observing all packing label warnings and handling instructions.

Allentown, PA 18106 September 15, 2026

26 12 13.01-13

10. Open termination compartment doors and inspect components for damage or displaced parts, loose or broken connections, cracked or chipped insulators, bent mounting flanges, dirt or foreign material, and water or moisture.

B. Handling:

1. Handle transformers carefully, in accordance with manufacturer recommendations, to avoid damage to enclosure, termination compartments, base, frame, tank, and internal components. Do not subject transformers to impact, jolting, jarring, or rough handling.

2. Protect transformer termination compartments against entrance of dust, rain, and snow.

3. Transport transformers upright, to avoid internal stresses on core and coil mounting assembly and to prevent trapping air in the windings. Do not tilt or tip transformers.

4. Verify that transformer weights are within rated capacity of handling equipment.

5. Use only manufacturer-recommended points for lifting, jacking, and pulling.

Use all lifting lugs when lifting transformers.

6. Use jacks only at corners of tank base plate.

7. Use nylon straps of same length to balance and distribute weight when handling transformers with a crane.

8. Use spreaders or a lifting beam to obtain a vertical lift and to protect transformer from straps bearing against enclosure. Lifting cable pull angles may not be greater than 15 degrees from vertical.

9. Exercise care not to damage tank base structure when handling transformer using skids or rollers. Use skids to distribute stresses over tank base when using rollers under large transformers.

C. Storage:

1. Store transformers in accordance with manufacturer's recommendations.

2. Transformers may be stored outdoors. If possible, store transformers at final installation locations on concrete pads. If dry concrete surfaces are unavailable, use pallets of adequate strength to protect transformers from direct contact with ground. Ensure transformer is level.

3. Ensure that transformer storage location is clean and protected from severe conditions. Protect transformers from dirt, water, contamination, and physical damage. Do not store transformers in presence of corrosive or explosive gases. Protect transformers from weather when stored for more than three months.

4. Store transformers with compartment doors closed.

5. Regularly inspect transformers while in storage and maintain documentation of storage conditions, noting any discrepancies or adverse conditions. Verify that an effective pressure seal is maintained using pressure gauges. Visually check for insulating-liquid leaks and rust spots.

Allentown, PA 18106 September 15, 2026

26 12 13.01-14

D. Examine areas and space conditions for compliance with requirements for liquid-filled, medium-voltage transformers and other conditions affecting performance of the Work.

E. Examine roughing-in of conduits and grounding systems to verify the following:

1. Wiring entries comply with layout requirements.

2. Entries are within conduit-entry tolerances specified by manufacturer, and no feeders will cross section barriers to reach load or line lugs.

F. Examine walls, floors, roofs, and concrete bases for suitable conditions for transformer installation.

G. Pre-Installation Checks:

1. Verify removal of any shipping bracing after placement.

2. Remove a sample of insulating liquid according to ASTM D923. Insulating-liquid values shall comply with NETA ATS, Table 100.4. Sample shall be tested for the following:

a. Dielectric Breakdown Voltage: ASTM D877 or ASTM D1816.

b. Acid Neutralization Number: ASTM D974.

c. Specific Gravity: ASTM D1298.

d. Interfacial Tension: ASTM D971.

e. Color: ASTM D1500.

f. Visual Condition: ASTM D1524.

g. Water in Insulating Liquids: ASTM D1533.

h. Power Factor or Dissipation Factor: ASTM D924.

H. Proceed with installation only after unsatisfactory conditions have been corrected.

3.07 INSTALLATION

A. Install transformers on cast-in-place concrete equipment base(s).

B. Transformer shall be installed level and plumb and shall tilt less than 1.5 degrees while energized.

C. Maintain minimum clearances and workspace at equipment according to manufacturer's written instructions and NFPA 70.

3.08 CONNECTIONS

A. At Interior Locations: For grounding to grounding electrodes, use bare copper cable not smaller than No. 4/0 AWG. Bond surge arrester and neutrals directly to transformer enclosure and then to grounding electrode system with bare copper conductors. Keep leads as short as practicable, with no kinks or sharp bends.

Allentown, PA 18106 September 15, 2026

26 12 13.01-15

Make joints in grounding conductors and loops by exothermic weld or compression connector.

B. At Exterior Locations:

1. For counterpoise, use tinned bare copper cable not smaller than No. 4/0 AWG, buried not less than 30 inches below grade interconnecting grounding electrodes. Bond surge arrester and neutrals directly to transformer enclosure and then to grounding electrode system with bare copper conductors. Keep lead lengths as short as practicable, with no kinks or sharp bends.

2. Fence and equipment connections shall not be smaller than No. 4 AWG.

Ground fence at each gate post and corner post and at intervals not exceeding 10 feet Bond each gate section to fence post using 1/8 by 1 inch [tinned ]flexible braided copper strap and clamps.

3. Make joints in grounding conductors and loops by exothermic weld or compression connector.

C. Terminate all grounding and bonding conductors on a common equipment grounding terminal on transformer enclosure. Install supplemental terminal bars, lugs, and bonding jumpers as required to accommodate number of conductors for termination.

D. Complete transformer tank grounding and lightning arrester connections prior to making any other electrical connections.

E. Maintain air clearances between energized live parts and between live parts and ground for exposed connections in accordance with manufacturer recommendations.

F. Bundle associated phase, neutral, and equipment grounding conductors together within transformer enclosure. Arrange conductors such that there is not excessive strain that could cause loose connections. Allow adequate slack for expansion and contraction of conductors.

3.09 KEY INTERLOCK PROCEDURE

A. Remove padlock securing low-voltage compartment door handle.

B. Release pentahead bolts.

C. Obtain key from key interlock provided on the pad mounted high voltage switch and fuse assembly serving the transformer. (High voltage switch must be in the open position before the key can be removed).

D. Insert key into key interlock on transformer low-voltage compartment door and release key interlock.

E. Operate door handle to unlatch and open low-voltage compartment door.

Allentown, PA 18106 September 15, 2026

26 12 13.01-16

F. Release internal locking device that allows high-voltage compartment door to be opened.

3.10 SIGNS AND LABELS

A. Install warning signs as required to comply with 29 CFR 1910.269.

3.11 FIELD QUALITY CONTROL

I. Testing Agency: Engage a qualified testing agency to perform tests and inspections.

J. Manufacturer's Field Service: Engage a Company Service Advisor to test and inspect components, assemblies, and equipment installations, including connections.

K. Perform the following tests and inspections with the assistance of a Company Service Advisor:

1. General Field-Testing Requirements:

a. NFPA 70B reference in first subparagraph below contains requirements for qualifications of test operators and test equipment.

b. Comply with provisions of NFPA 70B, Ch. "Testing and Test Methods."

c. Perform each visual and mechanical inspection and electrical test.

Certify compliance with test parameters.

d. After installing transformer but before primary is energized, verify that grounding system at substation is tested at specified value or less.

e. After installing transformer and after electrical circuitry has been energized, test for compliance with requirements.

f. Visual and Mechanical Inspection:

1) Verify equipment nameplate data complies with Contract Documents.

2) Inspect bolted electrical connections for high resistance using one of the following two methods:

a) Use a low-resistance ohmmeter to compare bolted connection resistance values to values of similar connections. Investigate values that deviate from those of similar bolted connections by more than 50 percent of lowest value.

Allentown, PA 18106 September 15, 2026

26 12 13.01-17

b) Verify tightness of accessible bolted electrical connections by calibrated torque-wrench method according to manufacturer's published data or NETA ATS, Table 100.12. Bolt-torque levels shall be according to manufacturer's published data. In absence of manufacturer's published data, use NETA ATS, Table 100.12.

g. Remove and replace malfunctioning units and retest.

h. Prepare test and inspection reports. Record as-left set points of all adjustable devices.

2. Medium-Voltage Surge Arrester Field Tests:

a. Visual and Mechanical Inspection:

1) Inspect physical and mechanical condition.

2) Inspect anchorage, alignment, grounding, and clearances.

3) Verify arresters are clean.

4) Verify that ground lead on each device is individually attached to a ground bus or ground electrode.

5) Verify that stroke counter is correctly mounted and electrically connected if applicable. Record stroke counter reading.

b. Electrical Test:

1) Perform an insulation-resistance test on each arrester, phase terminal-to-ground. Apply voltage according to manufacturer's published data. In the absence of manufacturer's published data, comply with NETA ATS, Table 100.1. Replace units that fail to comply with recommended minimum insulation resistance listed in that table.

2) Perform a watts-loss test. Evaluate watts-loss values by comparison with similar units and test equipment manufacturer's published data.

3. Liquid-Filled Transformer Field Tests:

a. Visual and Mechanical Inspection:

1) Test dew point of tank gases if applicable.

2) Inspect anchorage, alignment, and grounding.

3) Verify bushings are clean.

Allentown, PA 18106 September 15, 2026

26 12 13.01-18

4) Verify that alarm, control, and trip settings on temperature and level indicators are set and operate within manufacturer's recommended settings.

5) Verify that cooling fans and pumps operate correctly and have appropriate overcurrent protection.

6) Verify that liquid level in tanks and bushings is within manufacturer's published tolerances.

7) Perform specific inspections and mechanical tests recommended by manufacturer.

8) Verify presence of transformer surge arresters and that their ratings are as specified.

9) Verify that as-left tap connections are as specified.

10) Verify presence of surge arresters and that their ratings are as specified.

b. Electrical Tests:

1) Perform insulation-resistance tests winding-to-winding and each winding-to-ground. Apply voltage according to manufacturer's published data. In the absence of manufacturer's published data, comply with NETA ATS, Table 100.5. Calculate polarization index; the value of the index shall not be less than 1.0.

2) Perform power-factor or dissipation-factor tests on all windings according to test equipment manufacturer's published data.

Maximum winding insulation power-factor/dissipation-factor values shall be according to manufacturer's published data. In the absence of manufacturer's published data, comply with NETA ATS, Table 100.3.

3) Measure core insulation resistance at 500-V dc if the core is insulated and the core ground strap is removable. Core insulation-resistance values shall not be less than 1 megohm at 500-V dc.

4) Perform a power-factor or dissipation-factor tip-up test on windings greater than 2.5 kV.

5) Perform turns-ratio tests at tap positions. Turns-ratio test results shall not deviate by more than one-half percent from either adjacent coils or calculated ratio. If test fails, replace transformer.

Allentown, PA 18106 September 15, 2026

26 12 13.01-19

6) Perform an excitation-current test on each phase. The typical excitation-current test data pattern for a three-legged core transformer is two similar current readings and one lower current reading. Investigate and correct if test shows a different pattern.

7) Measure resistance of each winding at each tap connection, and record temperature-corrected winding-resistance values in Operations and Maintenance Manual.

8) Perform an applied-voltage test on high- and low-voltage windings-to-ground.

9) Verify correct secondary voltage, phase-to-phase and phase-to-neutral, after energization and prior to loading.

10) Remove a sample of insulating liquid according to ASTM D923, and perform dissolved-gas analysis according to IEEE C57.104 or ASTM D3612.

3.12 FOLLOW-UP SERVICE

A. Voltage Monitoring and Adjusting: After Substantial Completion, if requested by Director’s Representative, but not more than six months after Final Acceptance, perform the following voltage monitoring:

1. During a period of normal load cycles as evaluated by Director’s

Representative, perform seven days of three-phase voltage recording at the outgoing section of each transformer. Use voltmeters with calibration traceable to the National Institute of Science and Technology standards and with a chart speed of not less than 1 inch per hour. Voltage unbalance greater than 1 percent between phases, or deviation of any phase voltage from the nominal value by more than plus or minus 5 percent during test period, is unacceptable.

2. Corrective Action: If test results are unacceptable, perform the following corrective action, as appropriate:

a. Adjust transformer taps.

b. Prepare written request for voltage adjustment by electric utility.

3. Retests: Repeat monitoring, after corrective action is performed, until satisfactory results are obtained.

4. Report:

a. Prepare a written report covering monitoring performed and corrective action taken.

Allentown, PA 18106 September 15, 2026

26 12 13.01-20

B. Infrared Inspection: Perform survey during periods of maximum possible loading.

Remove all necessary covers prior to inspection.

1. After Substantial Completion, but not more than 60 days after Final

Acceptance, perform infrared inspection of transformer's electrical power connections.

2. Instrument: Inspect distribution systems with imaging equipment capable of detecting a minimum temperature difference of 1 deg C at 30 deg C.

3. Record of Infrared Inspection: Prepare a certified report that identifies testing technician and equipment used, and lists results as follows:

a. Description of equipment to be tested.

b. Discrepancies.

c. Temperature difference between area of concern and reference area.

d. Probable cause of temperature difference.

e. Areas inspected. Identify inaccessible and unobservable areas and equipment.

f. Identify load conditions at time of inspection.

g. Provide photographs and thermograms of deficient area.

4. Act on inspection results according to recommendations of NETA ATS, Table 100.18. Correct possible and probable deficiencies as soon as Director’s Representative's operations permit. Retest until deficiencies are corrected.

part 1 general
1.01 Scope
A. This specification covers the electrical and mechanical characteristics of 300–12,000 kVA three-phase substation type distribution transformers. Product is per Eaton’s catalog data CA202001EN.
B. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.02 Applicable Standards
A. All characteristics, definitions, and terminology, except as specifically covered in this specification, shall be in accordance with the latest revision of the following IEEE®, Department of Energy, and NEMA® standards.
1. IEEE Std C57.12.00™-2015 – IEEE Standard for Standard General Requirements for Liquid-Immersed Distribution, Power, and Regulating Transformers
2. IEEE Std C57.12.28™-2014 – Sections 5.3, 5.4, 5.5 – Coating System Requirements
3. IEEE Std C57.12.36™- 2017 – IEEE Standard Requirements for Liquid-Immersed Distribution Substation Transformers
4. IEEE Std C57.12.70™-2011 – IEEE Standard for Terminal Markings and Connections for Distribution and Power Transformers
5. IEEE Std C57.12.90™-2010 – IEEE Standard Test Code for Liquid-Immersed Distribution, Power, and Regulating Transformers and IEEE Guide for Short-Circuit Testing of Distribution and Power Transformers
6. IEEE Std C57.154™ -2012 – IEEE Standard for the Design, Testing, and Application of Liquid-Immersed Distribution, Power, and Regulating Transformers Using High-Temperature Insulation Systems and Operating at Elevated Temperatures
7. NEMA® TR 1-1993 (R2000) – Transformers, Regulators and Reactors, Table 0-2 Audible Sound Levels
8. 10 CFR Part 431 – Department of Energy–Energy Conservation Program: Energy Conservation Standards for Distribution Transformers; Final Rule
9. IEEE Std 386™-2006 – IEEE Standard for Separable Insulated Connector Systems for Power Distribution Systems Above 600 V
part 2 Products
2.01 Manufacturers
A. Eaton
B. ABB
C. Siemens
D. Square D/Schneider Electric
2.02 ratings
A. The transformer shall be designed in accordance with this specification, and the base kVA rating shall be: 2300/2576 kVA, 55/65 C, KNAN/KNAF for Substation #2 and 1725/2106 kVA, 55/75 C, KNAN/KNAF for Substation #4.
B. The transformer shall have a high voltage and the basic lightning impulse insulation level (BIL) of 12,470V and 95kV BIL.
C. The low voltage and the basic lightning impulse insulation level (BIL) shall be 480Y/277V and 30kV BIL.
D. The high voltage and low voltage connections of the transformer shall be (See checked option):
1. [] Delta - Wye:
a. For Delta - Wye configurations the low voltage neutral shall be a fully insulated X0 bushing. The low voltage shall lag the high voltage by 30 .
2. [X] Delta - Grounded Wye
a. For Delta - Grounded Wye configurations the low voltage neutral shall be a fully insulated X0 bushing with ground strap. The low voltage shall lag the high voltage by 30 .
3. [] Delta - Delta
a. For Delta - Delta configurations the transformer shall be provided without a neutral bushing. There shall be no phase shift between the high voltage and low voltage.
4. [] Grounded Wye - Wye
a. For Grounded Wye - Wye configurations the high voltage neutral shall be internally tied to the low voltage neutral and brought out as the H0X0 bushing. There shall be no phase shift between the high voltage and low voltage.
5. [] Wye - Grounded Wye
a. For Wye - Grounded Wye configurations the high voltage neutral shall be brought out as the Ho bushing on the high voltage side and the low voltage neutral shall be brought out as the X0 bushing with ground strap on the low voltage side. There shall...
6. [] Wye - Delta
a. For Wye - Delta configurations the high voltage neutral shall be brought out as the Ho bushing on the high voltage side. The low voltage shall lag the high voltage by 30 .
E. The transformer shall be furnished with full capacity high-voltage taps. The tap-changer shall be clearly labeled to reflect that the transformer must be de-energized before operating the tap-changer as required in Section 4.3 of IEEE Std C57.12.3...
1. [] No Taps
2. [X] Two – 2 ½% taps above and below rated voltage (split taps)
3. [] Four – 2 ½% taps below rated voltage (four below)
4. [] NEMA taps (14400, 13800, 13200, 12470, 12540)
F. The dielectric coolant shall be listed less-flammable fluid meeting the requirements of National Electrical Code® Section 450-23 and the requirements of the National Electrical Safety Code® (IEEE Std C2™-2002 standard), Section 15. The dielectric ...
G. The transformer, filled with Envirotemp™ FR3™ fluid, shall have a (See checked option):
1. [] 65 C average winding temperature rise rating. The above winding temperature rise shall not exceed 65 C when loaded at base kVA rating.
2. [] 75 C average winding temperature rise rating. The above winding temperature rise shall not exceed 75 C when loaded at base kVA rating. This transformer is identified as a PEAK transformer.
3. [X] 55/65 C average winding temperature rise rating. The above winding temperature rise shall not exceed 55 C when loaded at base kVA rating. The transformer shall provide an additional 12% continuous operating capacity at the 65 C rating.
4. [] 65/75 C average winding temperature rise rating. The above winding temperature rise shall not exceed 65 C when loaded at base kVA rating. The transformer shall provide an additional 12% continuous operating capacity at the 75 C rating. This tr...
5. [] 55/75 C average winding temperature rise rating. The above winding temperature rise shall not exceed 55 C when loaded at base kVA rating. The transformer shall provide an additional 22% continuous operating capacity at the 75 C rating. This tr...
H. The percent impedance voltage, as measured on the rated voltage connection, shall be per Table 5 of IEEE Std C57.12.36™-2007 standard.
I. The transformer shall be cooled by the natural circulation of air over the tank surface
J. UL® Listing/Classification and FM® Approval (See checked option):
1. [] The transformer shall be UL® Listed (certifying compliance with IEEE® standards only) per UL® XPLH.
2. [X] The transformer shall be combination UL® Listed & Classified to comply with NEC® 450-23 listing restrictions for installations on, near, or inside of buildings per UL® XPLH.
3. [] The transformer shall be FM® Global (FM) Approved to comply with NEC® 450-23 listing restrictions for installations on, near, or inside of buildings.
2.03 Construction
A. The core and coil shall be vacuum processed to ensure maximum penetration of insulating fluid into the coil insulation system. While under vacuum, the windings will be energized to heat the coils and drive out moisture, and the transformer will be ...
B. Panel type, removable radiators, complete with flanged shut off valves on the tank side shall be provided.
C. The tank must be welded using precision cut, cold-rolled steel plate and equipped with extra-heavy duty, welded-in-place lifting lugs and jacking provisions. The tank base must be designed to allow skidding or rolling in any direction.
D. The transformer shall be of sealed tank construction of sufficient strength to withstand a pressure of 7 psig without permanent distortion, and 15 psig without rupturing.
E. The tank shall include a pressure relief device as a means to relieve pressure in excess of pressure resulting from normal operation. The venting and sealing characteristics shall be as follows:
1. Cracking Pressure: 10 psig +/-2 psig
2. Resealing Pressure: 6-psig minimum
3. Zero leakage from reseal pressure to -8 psig
4. Flow at 15 psig: 50 SCFM minimum
F. The tank shall be cleaned with an alkaline cleaning agent to remove grease and oil. An iron phosphate coating shall then be chemically bonded to the metal to assure coating adhesion and retard corrosion. The tank shall be primed with an electrode...
G. The high voltage terminations shall each be enclosed with the following (Approved manufacturer shall select the appropriate arrangement such that alignment of switchgear is not compromised):
1. [X] Throat
a. A throat is used on a transformer with sidewall-mounted bushings for connecting the transformer with bus duct. It extends 8 inches above and below the centerline of the bushings.
2. [] Flange (required with high voltage air disconnect switch)
a. A flange is used on a transformer with sidewall mounted bushings for direct connection to metal clad switchgear and is required with the high voltage air disconnect switch option. The flange extends 8 inches above and 32 inches below the bushing c...
3. [X] Partial height, bottom entry air terminal chamber
a. The partial height bottom entry chamber extends approximately 24 inches below the centerline of the bushings and has a bottom removable plate that can accommodate cable glands or conduit hubs. The chamber shall include a hinged door with padlockabl...
4. [X] Partial height, top entry air terminal chamber
a. The partial height top entry air terminal chamber has a chimney with a removable cover that extends 24 inches above the bushing centerline and can be equipped with cable glands or conduit hubs. Bus duct can be adapted to match the top of the chimn...
5. [X] Full height, bottom entry cabinet
a. A full height bottom entry air terminal chamber is a weather-resistant metal enclosure around sidewall mounted bushings that extends downward to the transformer base level and upward approximately 10 inches above the bushing centerline. It is inte...
6. [X] Full height, top entry cabinet
a. A full height top entry air terminal chamber is a weather resistant metal enclosure around sidewall mounted bushings that extends downward to the transformer base level and upward approximately 24 inches above the centerline of the bushings. The ch...
H. The low voltage terminations shall each be enclosed with the following (See checked option, Approved manufacturer shall select the appropriate arrangement such that alignment of switchgear is not compromised):
1. [] Throat
a. A throat is used on a transformer with sidewall-mounted bushings for connecting the transformer with bus duct. It extends 8 inches above and below the centerline of the bushings.
2. [X] Flange