J
J
J
J
OUTLET VALVE LIMIT SWITCHES
PRODUCT RETURN PUMP
MOUNT ON WATER
DRAW-OFF SYSTEM
PIPE SUPPORTS.
WITHDRAW LINE
STRIPPING LINE
TO HANDHOLES,
SEE DRAWING ES401.
S
1. THE ENTIRE VOLUME WITHIN THE VAULT AT THE PRODUCT RECOVERY TANK SHALL BE CONSIDERED A
CLASS I, DIVISION 1, GROUP D HAZARDOUS LOCATION. ALSO THE VOLUME WITHIN A 5 FOOT RADIUS
FROM THE TOP OF THE TANK VENT SHALL BE CONSIDERED A CLASS I, DIVISION 1, GROUP D
HAZARDOUS LOCATION.
2. STUB CONDUIT UP NEXT TO CANOPY COLUMN,INSTALL SEAL-OFF AT 18" A.G., AND ROUTE CONDUIT UP
COLUMN TO CANOPY ROOF FOR CANOPY LIGHTING.
3. NEMA 3R, 480V, 3-POLE, MANUAL MOTOR STARTER WITH INTEGRAL OVERLOADS, HAND SWITCH, AND
PILOT LIGHT TO INDICATE RUNNING STATUS. MOUNT STARTER TO CANOPY COLUMN.
TO
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - FJRP159073
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
94893
C O
P Y
R I G
H T
B U
R N
S
M c D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
D
2 3
C
4 5
A
B
ES502
94893ES502.DWG
TANK DETAILS
A. FANGMAN
NOVEMBER 2016 J. LITTLE
S. LACY
A1
PRODUCT RECOVERY TANK ELECTRICAL PLAN VIEW
SCALE: NOT TO SCALE
NEW ALARMS AND
SENSORS TO BE
ACCESSIBLE FROM
STAIRS
1. SEE TANK DRAWINGS FOR EXACT LOCATION OF TANK EQUIPMENT.
2. WELD CONDUIT SUPPORT STRUCTURES (UNISTRUT OR EQUAL) TO TANK WALL. DO NOT WELD UNISTRUT DIRECTLY
TO TANK SHELL. USE THREADED ARC STUDS OR EQUIVALENT TO INCLUDE THREADED COUPLERS OF THE SAME
MATERIAL AS THE MATERIAL OF THE TANK SHELL.
3. SEE ES051 FOR HAZARDOUS AREA LOCATIONS.
4. IN TANK CONTAINMENT AREA ALL CONDUIT SHALL BE ROUTED ALONG PIPING OR CONTAINMENT WALL WITH
CONDUIT SUPPORT STRUCTURES. CONDUIT SHALL NOT BE ROUTED BELOW GRADE.
A3
STORAGE TANK ELECTRICAL ELEVATION
SCALE: NOT TO SCALE
INLET VALVE
LIMIT SWITCHES
J
J
FTP-1 WITH HEATER
AND MOTOR WINDING
TEMPERATURE SWITCH
OVERFILL
PREVENTION
VALVE
ATG
WATER LEVEL SWITCH
PRODUCT LEVEL SWITCHES
WDP-1
IC.ATG.Tx, PB-32
CONTINUE TO STILLWELL
FOR ATG SYSTEM
DETAIL A1, ES504
HIGH LEVEL CONTROL
VALVE SOLENOID
HIGH LEVEL CONTROL
VALVE LIMIT SWITCH
CLOSED
3/4"C: C.MCC.Tx.JY
3/4"C: C.PCP.Tx.ZS4
3/4"C: C.PCP.Tx.ZS1
JY
ZSC
ZSZS
ZS
ZS
ZS
ZS
LSLL
LSL
LSHH
LSH
1"C: (PA-22 - TANK 1) (PA-28 - TANK 2) (PA-34 - TANK 3)
1"C: C.PCP.Tx.ZS2, C.PCP.Tx.ZS3
1"C: C.PCP.Tx.L (I.S.)
1"C: IC.ATG.Tx
10' X 3/4" GALVANIZED
STEEL GND ROD (TYP)
#4/0 TW CU
GND CABLE
LSH
LSH
LSM
LSL
LSHH
J
M
M
UT
ZSC
FS
J
M
TSH
1"C: C.MCC.PRT.L3 (I.S.)
1"C: C.MCC.PRT.L1, C.MCC.PRT.L2 (I.S.)
1"C: IC.ATG.PRT (I.S.)
1"C: C.PCP.PRT.ZSC
1"C: C.MCC.FTP.TS,
C.MCC.FTP.H
1"C: C.MCC.FTP.FS
SEE A1 ON ES401 FOR
CONTINUATION
NOTES:
SEE NOTE 2
x = 1 FOR TANK 1 x = 2 FOR TANK 2 x = 3 FOR TANK 3
(TYP.)
ME
XE
TO HANDHOLES,
SEE DRAWING ES401
1"C: IC.ATG.PRT.LD (I.S.)
1"C:
PA-16
1"C: PB-40
J
IC.ATG.UIx
UI
TANK SIDE INDICATOR
(COORDINATE FINAL
PLACEMENT WITH ANG
PERSONNEL)
J
ME
J
1"C: P.MCC.FTP1
NOTES:
LEVEL SWITCH
TO BOLTED
CONNTECTION
AT TANK STAIRS
J
LOW SUCTION VALVE LIMIT SWITCHES
MANUAL MOTOR
STARTER
(SEE NOTE 3)
S.EHH1.PRT;
S.CHH5.PRT
SEAL-OFFS. AS REQUIRED.
(SEE DETAIL B3/ES052)