FUEL LINE
c
L FUEL LINE
c
L
18"
CLEAR
(MIN)
SIDEWALL CLEARANCE (8"
MIN)
O D
P
I P
E
S E
E
P
R O
F I L
E
D E
P T
H
V
A R
I E
S
SAND
EMBEDMENT
(SEE NOTE 1)
FUEL PIPE
PLASTIC WARNING
TAPE WITH FUEL LINE
NOTED
COMPACTED EARTH BACKFILL
TRENCH WALL
BRACED, SLOPED,
OR AS REQUIRED
FOR STABILITY (TYP)
PER OSHA
STANDARDS
FINISH GRADE
1. SEE SPECIFICATION SECTION 31 00 00 FOR FUEL PIPE SAND
BEDDING MATERIAL.
POURED CONCRETE BLOCKS
UNDISTURBED EARTH
BEARING AREA
PRESSURE PIPE
PLACE 1/2" PLYWOOD
BETWEEN CONCRETE
BLOCKING AND PLUG TO
PERMIT REMOVAL FOR FUTURE
EXTENSION OF WATER MAIN
1. PROVIDE CLEARANCE FOR BOLT REMOVAL WHEN PLACING CONCRETE.
2. THRUST BLOCKS SHALL BE 2,000 PSI CONCRETE.
3. BEARING AREAS ARE BASED ON 350 PSI PIPE TEST PRESSURE AND 2000 PSF SOIL BEARING PRESSURE. IF
LESS DENSE SOIL IS ENCOUNTERED, INCREASE BEARING AREA TO PREVENT MOVEMENT UNDER TEST OR
OPERATION PRESSURES.
N
O M
I N
A L
OPEN/SHUT
INDICATOR
P I P
E
D
E P
T H
V
A R
I E
S
8"Ø PIPE (TYP.)
PROVIDE CONNECTING
ADAPTORS AS REQUIRED
INVERT SEE UTILITY
PLANS AND PROFILE
SHEETS
POST INDICATOR GATE
VALVE (MECHANICAL
JOINT)
1. POST INDICATOR VALVES SHALL CONFORM TO NFPA 24.
2. PAINT POST INDICATOR VALVES YELLOW FOR CONTAINMENT
DRAINS.
PAVEMENT OR STRUCTURAL
SLAB
POST INDICATOR
WITH FRANGIBLE
LOCKING
MECHANISM
FINISH
GRADE
NOTE:
NOTES:
NOTES:
c
L
C1
TYPICAL FUEL PIPE TRENCH
A4
POST INDICATOR VALVE (PIV)
SCALE: NOT TO SCALE
A1
TYPICAL THRUST BLOCK
6" MIN
FLEXIBLE
MEMBRANE
LINER (FML)
STAINLESS STEEL
BATTEN BAR/FML
ANCHOR SYSTEM
SEE NOTE 2.
PREPARED SUBGRADE
GEOTEXTILE
6" GRANULAR BASE
4" FUEL RESISTANT
WATER STOP (IF CAST
WITH BOTTOM JOINT)
EPOXY COAT
INTERIOR OF
INLET
NOTES:
1. COAT WALLS AND FLOOR OF STRUCTURE WITH FIELD APPLIED COAL-TAR EPOXY (1-COAT OR
2-COAT SYSTEM), 15-MIL TOTAL MINIMUM THICKNESS, PER MANUFACTURER'S
RECOMMENDATIONS.
2. ATTACH FML TO TOP OF INLET USING CONTINUOUS BATTEN BARS. FML ANCHOR SYSTEM SHALL
CONFORM TO THE MANUFACTURER'S RECOMMENDATIONS.
3. LIGHT DUTY IRON OR GALVANIZED STEEL FRAME AND GRATE. MINIMUM SIZE SHALL BE 2'X2'.
4. INLET STRUCTURE SHALL BE A PRECAST CONCRETE STRUCTURE OF WATER-TIGHT
CONSTRUCTION. THE STRUCTURE CAN BE CAST IN-PLACE AT CONTRACTORS OPTION,
PROVIDED THE DESIGN IS SUBMITTED AND APPROVED.
5. MINIMUM WALL AND SLAB REINFORCING SHALL BE #6 @ 6" EW.
6. INSTALL PIPE SLEEVE PER DETAIL A1, DRAWING S-515. INSTALL SEGMENTED PIPE SEAL (ONE).
M
I N
GRATED TOP
SEE NOTE 3
C4
TYPICAL DIKE CONTAINMENT
DRAIN INLET
SEE NOTE 6
S c a l e
F o r
M i c r o f i l m i n g
I n c h e s
M i l l i m e t e r s date detailed checkeddesigned ofsheet sheets project contract rev.drawing file
NORTH CAROLINA AIR NATIONAL GUARD
DOUGLAS INTERNATIONAL AIRPORT
CHARLOTTE, NORTH CAROLINA
KANSAS CITY, MISSOURI
ENGINEERS ARCHITECTS & CONSULTANTS
Project No. - FJRP159073
C-17 TYPE III HYDRANT
REFUELING SYSTEM/
RAMP EXPANSION
94893
C O
P Y
R I G
H T
B U
R N
S
M c D
O N
N E
L L
E
N G
I N
E E
R I N
G
C
O M
P A
N Y
I N
C
D
2 3
C
4 5
A
B
AD
11/02/16 D.MUETING
A.DORMAN R.BARUTH
UTILITY DETAILS 3
C-511 0
FJRP159073-CU501.dwg
AD