Revised_33_52_43_Amendment_0006.pdf

PDF 132 KB Posted

Attached to
C-17 Refueling Hydrant System Ramp Expansion Federal contract opportunity
Solicitation number
W91242-18-R-0002
Issued by
Department of the Army North Carolina Army National Guard

About this file

Revised 33 52 43 Amendment 0006

View the file

Other files for this federal contract opportunity

Other files attached to C-17 Refueling Hydrant System Ramp Expansion, newest first.
File Type Posted
Questions_and_Answers_96-101__W91242-18-R-0002.pdf PDF
Amendment_0007.pdf PDF
FJRP159073-CG103-Amendment_0007.pdf PDF
33_52_43.28_Amd03.pdf PDF
Questions_and_Answers_78-95__W91242-18-R-0002.pdf PDF
FJRP159073-A-601-Amendment_0006.pdf PDF
Revised_33_52_80_Amendment_0006.pdf PDF
Revised_09_96_00_Amendment_0006.pdf PDF
Revised_09_97_13.27_Amendment_0006.pdf PDF
FJRP159073-A-201-Amendment_0006.pdf PDF
Amendment_0005.pdf PDF
Amendment_0005_Revised_01_45_00.pdf PDF
FJRP159073-MS503-Amd03.pdf PDF
01_33_29_Amd03.pdf PDF
FJRP159073-M-603-Amd03.pdf PDF
FJRP159073-B-101-Amd03_(1).pdf PDF
31_32_11_Amd03.pdf PDF
FJRP159073-CU-223-Amd03.pdf PDF
FJRP159073-GC-002-Amd03.pdf PDF
EXIBIT_H_Proposal_Price_Schedule.pdf PDF
FJRP159073-GC-001-Amd03.pdf PDF
SpecTOC_Amd03.pdf PDF
33_52_80_Amd03.pdf PDF
Exhibit_D_Letter_of_Commitment.pdf PDF
FJRP159073-MS501-Amd03.pdf PDF
FJRP159073-EI-503-Amd03.pdf PDF
FJRP159073-CS-121-Amd03.pdf PDF
Exhibit_G_-_Subcontracting_Plan_Format.pdf PDF
33_52_43.11_Amd03.pdf PDF
FJRP159073-EI-602-Amd03.pdf PDF
FJRP159073-M-502-Amd03.pdf PDF
FJRP159073-E-703-Amd03.pdf PDF
Exhibit_C_Past_Performance_Questionnaire_Package.pdf PDF
FJRP159073-ES-401-Amd03_(1).pdf PDF
03_30_00_Amd03.pdf PDF
Exhibit_B_Subcontractor_Consent_Form.pdf PDF
FJRP159073-EI-501-Amd03.pdf PDF
Questions_and_Answers_1-17__W91242-18-R-0002.pdf PDF
Pre-proposal_Conference_Sign_in_sheet.pdf PDF
1.3_Drawings-CIVIL_1_of_4.pdf PDF
1.6_Drawings-CATHODIC_PROTECTION.pdf PDF
Exhibit_F_Small_Business_Participation_Format.pdf PDF
Exhibit_G_-_Subcontracting_Plan_Format.pdf PDF
1.1_Drawings-INDEX_SHEET_(1).pdf PDF
1._Drawings_-COVER_SHEET.pdf PDF
1.5_Drawings-ARCHITECTURE.pdf PDF
6_-_SAP_SINGLE_SOURCE_DETERMINATION,_1_PGS.pdf PDF
1.7_Drawings-MECHANICAL.pdf PDF
8_-_PRE-PROPOSAL_SITE_VISIT_INSTRUCTIONS.pdf PDF
1.9_Drawings-FIRE_DETECTION.pdf PDF
Show all 50

C-17 Refueling Hydrant System Ramp Expansion has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C-17 Type III Fuel System & Ramp Expansion FJRP159073

145th Airlift Wing, North Carolina Air National Guard

Section 33 52 43.13 Page 1

SECTION 33 52 43.13

AVIATION FUEL PIPING

02/10

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to in the text by basic designation only.

AMERICAN PETROLEUM INSTITUTE (API)

API RP 1110 (2013) Pressure Testing of Steel Pipelines for the Transportation of Gas, Petroleum Gas, Hazardous Liquids, Highly Volatile Liquids or

Carbon Dioxide

API RP 582 (2016) Welding Guidelines for the Chemical, Oil, and Gas Industries

API STD 600 (2015) Steel Gate Valves-Flanged and Butt-welding Ends, Bolted Bonnets

API STD 608 (2012) Metal Ball Valves - Flanged, Threaded, And Welding End

API Spec 5L (2012; ERTA 2015) Specification for Line Pipe

API Spec 6D (2014; Errata 1-2 2014; Errata 3-5 2015; ADD

1 2015) Specification for Pipeline Valves

API Std 594 (2010) Check Valves: Flanged, Lug, Wafer and

Butt-Welding

API Std 607 (2010) Testing of Valves: Fire Test for Soft-

Seated Quarter-Turn Valves

AMERICAN WELDING SOCIETY (AWS)

AWS A5.1 (2012) Specification for Carbon Steel

Electrodes for Shielded Metal Arc Welding

AWS A5.5 (2014) Specification for Low-Alloy Steel

Electrodes for Shielded Metal Arc Welding

AWS A5.9 (2012) Specification for Bare Stainless Steel

Welding Electrodes and Rods

ASME INTERNATIONAL (ASME)

ASME B1.1 (2003; R 2008) Unified Inch Screw Threads (UN and UNR Thread Form)

Section 33 52 43.13 Page 2

ASME B16.11 (2011) Forged Fittings, Socket-Welding and

Threaded

ASME B16.21 (2011) Nonmetallic Flat Gaskets for Pipe

Flanges

ASME B16.34 (2013) Valves - Flanged, Threaded and Welding

End

ASME B16.5 (2013) Pipe Flanges and Flanged Fittings:

NPS 1/2 Through NPS 24 Metric/Inch Standard

ASME B16.9 (2012) Standard for Factory-Made Wrought

Steel Buttwelding Fittings

ASME B18.2.1 (2012; Errata 2013) Square and Hex Bolts and

Screws (Inch Series)

ASME B18.2.2 (2015) Nuts for General Applications: Machine

Screw Nuts, Hex, Square, Hex Flange, and

Coupling Nuts (Inch Series)

ASME B31.1 (2016) Power Piping

ASME B31.3 (2014) Process Piping

ASME BPVC SEC IX (2010) BPVC Section IX-Welding and Brazing

Qualifications

ASME BPVC SEC VIII D1 (2015) BPVC Section VIII-Rules for

Construction of Pressure Vessels Division 1

ASTM INTERNATIONAL (ASTM)

ASTM A105 (2014) Standard Specification for Carbon

Steel Forgings for Piping Applications

ASTM A182 (2016) Standard Specification for Forged or

Rolled Alloy-Steel Pipe Flanges, Forged

Fittings, and Valves and Parts for High-

Temperature Service

ASTM A193 (2016) Standard Specification for Alloy-Steel and Stainless Steel Bolting Materials for

High-Temperature Service and Other Special

Purpose Applications

ASTM A194 (2016) Standard Specification for Carbon and

Alloy Steel Nuts for Bolts for High-Pressure or High-Temperature Service, or Both

ASTM A217 (2014) Standard Specification for Steel

Castings, Martensitic Stainless and Alloy, for Pressure-Containing Parts, Suitable for

High-Temperature Service

Section 33 52 43.13 Page 3

ASTM A234 (2013; E 2014) Standard Specification for

Piping Fittings of Wrought Carbon Steel and

Alloy Steel for Moderate and High Temperature

Service

ASTM A269 (2015a) Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service

ASTM A312 (2016) Standard Specification for Seamless, Welded, and Heavily Cold Worked Austenitic

Stainless Steel Pipes

ASTM A358 (2014a) Standard Specification for Electric-

Fusion-Welded Austenitic Chromium-Nickel

Stainless Steel Pipe for High-Temperature

Service and General Applications

ASTM A403 (2016) Standard Specification for Wrought

Austenitic Stainless Steel Piping Fittings

ASTM A436 (1984; R 2011) Standard Specification for

Austenitic Gray Iron Castings

ASTM A53 (2012) Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless

ASTM A961 (2014) Standard Specification for Common

Requirements for Steel Flanges, Forged

Fittings, Valves, and Parts for Piping

Applications

ASTM D229 (2013) Rigid Sheet and Plate Materials Used for Electrical Insulation

ASTM E94 (2004; R 2010) Radiographic Examination

ASTM F436 (2011) Hardened Steel Washers

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

IEEE C62.41 (1991; R 1995) Recommended Practice on Surge

Voltages in Low-Voltage AC Power Circuits

MANUFACTURERS STANDARDIZATION SOCIETY OF THE VALVE AND FITTINGS

INDUSTRY (MSS)

MSS SP-58 (1993; Reaffirmed 2010) Pipe Hangers and

Supports - Materials, Design and Manufacture, Selection, Application, and Installation

MSS SP-69 (2003; Notice 2012) Pipe Hangers and Supports

- Selection and Application (ANSI Approved

American National Standard)

NORTH ATLANTIC TREATY ORGANIZATION (NATO)

Section 33 52 43.13 Page 4

NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

NFPA 30 (2015) Flammable and Combustible Liquids Code

SOCIETY FOR PROTECTIVE COATINGS (SSPC)

SSPC SP 5 (2007) White Metal Blast Cleaning

SOCIETY OF AUTOMOTIVE ENGINEERS INTERNATIONAL (SAE)

SAE J514 (2012) Hydraulic Tube Fittings

U.S. DEPARTMENT OF DEFENSE (DOD)

MIL-A-25896 (1983; Rev E; Notice 1 1989; Notice 3 2003)

Adapter, Pressure Fuel Servicing, Nominal 2.5 inch diameter

MIL-PRF-13789 (1999; Rev E; Notice 1 2008) Strainers, Sediment: Pipeline, Basket Type

MIL-PRF-4556 (1998; Rev F; Am 1 1999; CANC Notice 1 2011)

Coating Kit, Epoxy, for Interior of Steel

Fuel Tanks

MIL-STD-161 (2005; Rev G; Notice 1 2010) Identification

Methods for Bulk Petroleum Products Systems

Including Hydrocarbon Missile Fuels

U.S. NAVAL SEA SYSTEMS COMMAND (NAVSEA)

NAVSEA T9074-AS-GIB-010/271 (1999; Notice 1) Requirements for

Nondestructive Testing Methods

1.2 ADMINISTRATIVE REQUIREMENTS

Design conditions shall be as specified in Section 33 52 43.11 AVIATION FUEL

MECHANICAL EQUIPMENT. Submit a copy of welding qualified procedures, where the procedures will be used, and a list of names and identification symbols of qualified welders and welding operators. Submit Operation and

Maintenance Manuals for the equipment items or systems listed under SD-10

Operation and Maintenance Data. Refer to Section 01 78 23.33 OPERATION AND

MAINTENANCE MANUALS FOR AVIATION FUEL SYSTEMS for the information to be submitted for various type of equipment and systems.

1.3 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00

SUBMITTAL PROCEDURES:

SD-03 Product Data

Carbon Steel Pipe; G

Section 33 52 43.13 Page 5

Interior Epoxy Coating for Carbon Steel Piping; G

Stainless Steel Pipe; G

Carbon Steel Fittings; G

Stainless Steel Fittings; G

Stainless Steel Control Tubing; G

Isolating Gasket Kits; G

Lightning Surge Arrester; G

Bolts and Nuts; G

Gaskets; G

Ball Valves; G

Plug (Double Block and Bleed) Valves; G

Electric Valve Actuator; G

Swing Check Valves; G

Silent Check Valves; G

Thermal Relief Valves; G

Sight Flow Indicators; G

Flexible Ball Joints; G

Pipe Sleeves; G

Strainers; G

Pipe Hangers and Supports; G

Fuel Sample Connection; G

Flanged Swivel Joints; G

Quick Disconnect Adapters; G

Quick Disconnect Couplers; G

Flexible Connectors; G

Surge Suppressor Tank and Valve; G

SD-05 Design Data

Welding Procedure Specification (WPS); G

SD-06 Test Reports

Section 33 52 43.13 Page 6

Acceptance Testing of Shop-Applied Internal Pipe Coating

Procedure Qualifications Records (PQR); G

Welder and Welding Operator Qualification Record (WQR); G

Factory Testing and Inspection Records; G

Pneumatic Test

Hydrostatic Test

Geometry Tool Reports; G

SD-07 Certificates

Welder and Welding Operator Certifications; G

Qualified Commercial or Testing Laboratory

Quality Assurance Plan

Fittings

Surge Suppressor Tank and Valve

Isolating Flange Gasket Kits

Survey Final Elevations

Pipeline Pigging Verification; G

SD-10 Operation and Maintenance Data

Isolating Gasket Kits

Ball Valves

Plug (Double Block and Bleed) Valves

Electric Valve Actuators

Swing Check Valves

Silent Check Valves

Thermal Relief Valves

Sight Flow Indicators

Fuel Sample Connection

Flexible Ball Joints

Flexible Connectors

Section 33 52 43.13 Page 7

Strainers

Surge Suppressor Tank and Valve

Isolating Flange Gasket Kits

Protective Coatings

1.4 QUALITY ASSURANCE

1.4.1 Welding Qualifications

Welding of fuel pipe joints shall comply with Section 33 52 90.00 20 WELDING

FOR POL SERVICE PIPING. Piping shall be welded in accordance with qualified procedures using performance-qualified welders and welding operators.

Procedures and welders shall be qualified in accordance with ASME BPVC SEC

IX. Welding procedures qualified by others, and welders and welding operators qualified by another employer, may be accepted as permitted by

ASME B31.1. The Contracting Officer shall be notified 24 hours in advance of tests, and the tests shall be performed at the work site if practicable.

Welders or welding operators shall apply their assigned symbols near each weld they make as a permanent record.

1.4.2 Qualifications of Welders

Welders and welding procedures shall be qualified in accordance with requirements of ASME B31.3. Submit for each pipe material and process a

Welding Procedure Specification (WPS), its corresponding Procedure

Qualifications Records (PQR), and the welder Performance Qualification (WPQ) for each welder and each specification. Submit on the forms contained within Appendix A of ASME BPVC SEC IX. All welding is to be performed in accordance with applicable requirements of API RP 582 and AWS WHB-2.9, Chapter 5 as it applies to stainless steel piping.

1.4.2.1 Weld Identification

Each qualified welder shall be assigned an identification symbol. All welds shall be permanently marked with the symbol of the individual who made the weld.

1.4.2.2 Defective Work

Welders found making defective welds shall be removed from the work or shall be required to be requalified in accordance with ASME B31.3.

PART 2 PRODUCTS

2.1 DESIGN CONDITIONS

Components shall be suitable for use with AFLP-3747 Jet A (F-24) turbine fuel with a specific gravity of 0.775 to 0.84, a viscosity 1.5 cSt at 100 degrees F, and a Reid Vapor Pressure 0.05 psia. Components shall be ASME

Class 150 (275 psi at 100 degrees F) unless otherwise noted. Components to be suitable for outdoor, unsheltered location, and to function normally in ambient temperatures between 0 and 100 degrees F.

Section 33 52 43.13 Page 8

2.2 MATERIALS AND EQUIPMENT

Pipe and fittings in contact with fuel shall be stainless steel, interior epoxy coated carbon steel, or carbon steel as indicated on the drawings. No zinc coated metals, brass, bronze or other copper bearing alloys shall be used in contact with the fuel. All carbon steel carrier piping, carbon steel secondary containment piping, and stainless steel underground piping shall have an exterior protective coating and shall be cathodically protected in accordance with Section 26 42 19.00 20 CATHODIC PROTECTION BY

IMPRESSED CURRENT. Identification of piping shall be in accordance with

MIL-STD-161G unless specified otherwise. Material for manual valves shall be as specified hereinafter.

2.2.1 Carbon Steel Piping

Subject each length of pipe to factory hydrostatic testing and ultrasonic testing in accordance with their respective pipe specification.

a. Piping 12-Inches and Larger: Seamless, ASTM A53 Grade B having a wall thickness of 0.375-inch.

b. Piping 2 1/2 through 10-Inches: Seamless, Schedule 40 API Spec 5L

Grade B or ASTM A53 Grade B.

c. Piping 2-Inches and Smaller: Seamless, Schedule 80 API Spec 5L Grade B or ASTM A53 Grade B.

d. Welding Electrodes (Factory Fabrication): E70XX low hydrogen electrodes conforming to AWS A5.1 or AWS A5.5.

e. Provide pipe with exterior coating systems in accordance with Section

33 52 80 LIQUID FUELS PIPELINE COATING SYSTEM and Section 09 97 13.27

EXTERIOR COATING OF STEEL STRUCTURES.

f. Provide pipe with factory applied interior epoxy coating system in accordance with MIL-PRF-4556, 6 to 8 mils dry film thickness.

Documentation of conditions during application shall be submitted to the Contracting Officer. Refer to 33 52 80 LIQUID FUELS PIPELINE

COATING SYSTEM for “SOURCE QUALITY CONTROL” and “FIELD QUALITY CONTROL” requirements for the coating system.

2.2.1.1 Interior Epoxy Coated Carbon Steel Piping

Before applying the epoxy coating, the inside of the pipe shall be sandblasted to "white" metal conforming with SSPC SP 5. If the pipe is not internally epoxy lined immediately after cleaning, a rust preventative coating shall be applied. The rust preventative shall be approved by the epoxy manufacturer. The ends of the pipe shall be masked or wiped back a minimum of one inch but not more than 1-1/2 inches.

2.2.1.2 Coat Testing

After the top coat has cured, the internal epoxy lining shall be tested electrically using an approved holiday detector and shall be free of holidays. The ends of the pipe shall then be capped. The shop doing the application shall have a minimum of five years of experience at applying internal epoxy coating. The application and holiday testing at the shop

Section 33 52 43.13 Page 9 shall be available for inspection at any time by the Contracting Officer.

The shop shall notify the Contracting Officer at least one week before the pipe and fittings will be cleaned and epoxy coated. Provide a certified technical representative of the epoxy manufacturer to make at least three separate inspection trips with at least one day in the shop per trip. Each trip report shall be submitted to the Contracting Officer. Pipe 2-1/2-inches and smaller shall not be interior coated.

2.2.2 Stainless Steel Piping

a. Piping 2-1/2 Inches and Larger:

(1) ASTM A358, Grade 304L, Class 1 or Class 3 with supplementary requirements of S1, S2 and S3, or ASTM A312 Type 304L, seamless

(only). Any agreements between the purchaser and the manufacturer or supplier as referenced in the applicable ASTM shall include the

Contracting Officer as a party to the agreement. All piping welds will receive 100 percent radiographic inspection, 100 percent liquid penetrant inspection, 100 percent visual inspection and all tests as required by the applicable ASTM Standard. Piping shall be provided with a nominal wall thickness as shown in Table A for ASTM

A358 with the deviation from the nominal wall thickness less than

0.01-inch. ASTM A312 seamless piping shall be provided with a minimum schedule 10S wall thickness.

(2) Pipe Ends: All Piping shall be provided with beveled ends per

Chapter V, ASME B31.3, and shall be shipped with the ends capped.

(3) Seam and End Welds: All sections of the piping provided shall be accepted on the project site if the seam welds meet the requirements of the paragraph K341 of ASME B31.3 and Appendix 4 of

ASME BPVC SEC VIII D1. One hundred spots may be reinspected at the project site prior to installation and backfilling at the request of the Contracting Officer. End welds shall be properly aligned prior to welding per Chapter V of the ASME B31.3; welds found to be defective shall be repaired at no additional cost to the government. Observation by the Contracting Officer of the manufacturing and field procedures shall be allowed under this contract.

(4) Welders Qualifications: Piping shall be welded in accordance with qualified procedures using performance qualified welders and welding operators. Welding procedures qualified by another employer may be accepted as permitted by ASME B31.1. The

Contracting Officer shall be notified 24 hours in advance of tests and the tests shall be performed at the work site if practical.

The welder or welding operator shall apply his assigned symbol near each weld he makes as a permanent record.

(5) Factory Testing and Inspection Records: Per Table K341.3.2 of

Chapter IX of ASME B31.3, visual, radiographic and liquid penetrant tests shall be performed for each section of piping provided as all sections are subjected to cyclic conditions. All testing and inspections records shall be submitted to the Contracting Officer and shall indicate the pipe mark and installed location of each piping section on the project site. Observation by the Contracting

Officer of the manufacturers and the fields testing and inspection

Section 33 52 43.13 Page 10 procedures shall be allowed under this contract. Pipe certification along with pipe markings shall be submitted before the pipe arrives on the job site.

(6) Qualifications of Welding Inspectors for Stainless Steel Piping:

Submit the qualifications of all the testing personnel that will perform all field tests as requested by the Contracting Officer.

The qualifications of all personnel on the job site that will perform welding inspection shall be submitted for approval. These inspectors shall meet the qualifications as defined in Chapter VI of the ASME B31.3, and use the methods as defined in Table K341.3.2 of the ASME B31.3.

(7) Provide a qualified inspector in accordance with Chapter VI of ASME

B31.3 to act as the owner's inspector (for the Government) at the pipe manufacturer's facility in addition to the manufacturer's inspector.

(8) Submit Quality Assurance Plan for the welding, inspecting and testing of the welded seam pipe.

TABLE A

Nominal Pipe Size Nominal (Average) Pile

O.D.

Wall Thickness(tn)

16 inches 16.000 inches 0.312 inch

14 inches 14.000 inches 0.312 inch

12 inches 12.750 inches 0.250 inch

10 inches 10.750 inches 0.250 inch

8 inches 8.625 inches 0.250 inch

6 inches 6.625 inches 0.219 inch

4 inches 4.500 inches 0.219 inch

2.5 inches 2.875 inches 0.156 inch

b. Piping 2-inches and Smaller: Schedule 80 ASTM A312 seamless Type 304L for threaded piping and schedule 40 (unless otherwise indicated) ASTM

A312 seamless Type 304L for welded piping.

c. Stainless Steel Control Tubing: Seamless, fully annealed tubing conforming to ASTM A269, Grade TP316, Rockwell hardness B80 or less.

Wall thickness for 1/2-inch tubing to be 0.049 inch.

d. Welding Electrodes (Factory Fabrication): E308L conforming to AWS

A5.9.

Section 33 52 43.13 Page 11

e. Provide buried stainless steel pipe with coating systems in accordance with Section 33 52 80 LIQUID FUELS PIPELINE COATING SYSTEM. Do not provide with an interior epoxy coating system.

2.2.3 Protective Coatings for Aboveground Piping

Provide coating of aboveground piping, piping in pits, pipe supports, filter separators, and miscellaneous metal and equipment in accordance with Section

09 97 13.27 EXTERIOR COATING OF STEEL STRUCTURES. Color of finish coat shall be white. Do not paint stainless steel or aluminum surfaces.

2.2.4 Protective Coatings for Buried Steel Piping

Provide carbon steel carrier piping, carbon steel secondary containment piping, and stainless steel (underground only) piping pipe with coating system in accordance with Section 33 52 80 LIQUID FUELS PIPELINE COATING

SYSTEM.

2.2.5 Fittings

2.2.5.1 General

Welding ells, caps, tees, reducers, etc., shall be of materials compatible for welding to the pipe line in which they are installed, and wall thickness, pressure and temperature ratings of the fittings shall be not less than the adjoining pipe line. Unless otherwise required by the conditions of installation, all elbows shall be the long radius type. Miter joints are not acceptable. Make odd angle offsets with pipe bends or elbows cut to the proper angle. Butt weld fittings shall be factory-made wrought fittings manufactured by forging or shaping. Fabricated fittings will not be permitted. Welding branch fittings shall be insert type suitable for radiographic inspections specified herein.

2.2.5.2 Carbon Steel Fittings

a. Fittings 2.5 Inches and Larger: Butt weld, conforming to ASTM A234, grade WPB and ASME B16.9 of the same wall thickness as the adjoining pipe. All welds shall be radiographically examined throughout the entire length of each weld. Each fitting shall be subjected to the

Supplementary Requirements S3 and S4, Liquid Penetration examination and Magnetic-Particle Examination. Detectable flaws will not be accepted in the supplementary examinations. Fittings shall be identified to relate them to their respective radiograph. Elbows located between the pig launcher and the receiver, shall have a radius three times the pipe diameter. Tees with branches 6 inches and larger, located between the pig launcher and pig receiver, shall have guide bars as detailed on the drawings.

b. Fittings 2 Inches and Smaller. Forged (socket welded or if indicated on drawings, threaded), 3,000-pound W.O.G., conforming to ASTM A105, Grade 2 and ASME B16.11. Threaded fittings shall only be used for above grade applications. Underground and in pits low point drain pipe and high point vent pipe shall be butt welded.

c. Flanges: Flanges 2.5 inches and larger shall be 150 pound weld neck, forged flanges conforming to ASTM A105, and ASME B16.5. Flanges 2 inches and smaller shall be 150 pound socket weld, forged flanges

Section 33 52 43.13 Page 12 conforming to ASTM A105, and ASME B16.5. Flanges to be 1/16-inch raised face with phonographic finish, except where required otherwise to match equipment furnished. Match flange face to valves or equipment furnished. Flange face shall be machined to match valves or equipment furnished. Use of spacing rings or gaskets discs are not allowed.

Flanges shall be subjected to the Supplementary Requirements S56, Liquid Penetrant Examination as outlined in ASTM A961. Detectable flaws will not be accepted.

d. Interior Epoxy Coating System shall be applied to the fittings as specified in paragraph "Carbon Steel Piping."

2.2.5.3 Stainless-Steel Fittings

a. Fittings 2.5 Inches and Larger: Butt weld stainless steel conforming to ASTM A403, Class WP, Type 304L, seamless, and ASME B16.9 of the same minimum wall thickness as the adjoining pipe. Welded fittings shall be tested and inspected the same as the welded seam pipe and meet the same requirements as for the pipe. Elbows located between the pig launcher and the receiver, shall have a radius three times the pipe diameter.

Tees with branches 6 inches and larger, located between the pig launcher and pig receiver, shall have guide bars as detailed on the drawings.

b. Fittings 2 Inches and Smaller: Forged Type 304 or 304L (socket welded or if indicated on drawings, threaded), 3,000-pound W.O.G. conforming to ASTM A182 and ASME B16.11. Threaded fittings shall only be used for above grade applications. Underground and in pits low point drain pipe and high point vent pipe shall be butt welded.

c. Unions. Conforming to ASTM A312, Grade 304 or 316.

d. Flanges. Flanges 2.5 inches or larger shall be 150 pound weld neck, forged Type 304 stainless-steel flanges conforming to ASTM A182 and

ASME B16.5, except flanges that are to be connected to the fueling pumps shall be 300 pound. Flanges 2 inches and smaller shall be 150 pound socket weld, forged Type 304 stainless-steel flanges conforming to ASTM A182 and ASME B16.5. Flanges to be 1/16-inch raised-face with phonographic finish, except where required otherwise to match equipment furnished. Match flange face to valves or equipment furnished.

Flanges shall be subjected to the Supplementary Requirements S56, Liquid Penetrant Examination as outlined in ASTM A961.

e. Stainless-Steel Tube Fittings. Flareless, 316 stainless-steel fittings conforming to SAE J514.

2.2.5.4 Isolating Gasket Kits (Insulating) for Flanges

Provide ASTM D229 electrical insulating material of 1,000 ohms minimum resistance; material shall be resistant to the effects of aviation hydrocarbon fuels. Provide full face insulating gaskets between flanges.

Provide full surface 0.03 inch thick wall thickness, spiral-wound mylar insulating sleeves between the bolts and the holes in flanges; bolts may have reduced shanks of a diameter not less than the diameter at the root of threads. Provide 0.125-inch thick high-strength phenolic insulating washers next to flanges and provide flat circular stainless steel washers over insulating washers and under bolt heads and nuts. Provide bolts 0.5 inch

Section 33 52 43.13 Page 13 longer than standard length to compensate for the thicker insulating gaskets and the washers under bolt heads and nuts. Exterior above grade flanges separated by electrically isolating gasket kits shall be provided with weatherproof lightning surge arrester devices. The surge arrester shall bolt across flanges separated by insulating gasket kits per detail on contract drawings. The arrestor shall have the following features:

a. Weatherproof NEMA 4 enclosure.

b. Bidirectional and bipolar protection.

c. Constructed of solid state components, no lights, fuses or relays and used without required maintenance or replacement.

d. Withstand unlimited number of surges at 50,000 Amperes.

e. Maximum clamping voltage of 700 Volts based on a IEEE C62.41 8x20 microsecond wave form at 50,000 Amperes peak measured at the device terminals (zero lead length).

f. A UL listed arrester for installation in Class 1, Division 2, Group D, hazardous areas.

Install the mounting bracket and leads on the flange side of the bolt insulating sleeve and washer, and size in accordance with this schedule:

Line Size Bolt Size

2 inch 5/8 inch

2.5 inch 5/8 inch

3 inch 5/8 inch

4 inch 5/8 inch

6 inch 3/4 inch

8 inch 3/4 inch

10 inch 7/8 inch

12 inch 7/8 inch

14 inch 1 inch

16 inch 1 inch

Note: Make allowance for the 1/32-inch thickness of the insulating sleeve around the bolts when sizing the mounting lugs.

Section 33 52 43.13 Page 14

2.2.6 Bolts and Nuts

Bolts and nuts for pipe flanges, flanged fittings, valves and accessories shall conform to ASME B18.2.1 and ASME B18.2.2, except as otherwise specified. Bolts shall be of sufficient length to obtain full bearing on the nuts and shall project no more than three full threads beyond the nuts with the bolts tightened to the required torque. Bolts shall be regular hexagonal bolts conforming to ASME B18.2.1 with material conforming to ASTM

A193, Class 2, Grade B8, stainless steel, when connections are made where a stainless steel flange is involved, and Grade B7 when only carbon steel flanges are involved. Bolts shall be threaded in accordance with ASME B1.1, Class 2A fit, Coarse Thread Series, for sizes one inch and smaller and

Eight-Pitch Thread Series for sizes larger than one inch. Nuts shall conform to ASME B18.2.2, hexagonal, heavy series with material conforming to

ASTM A194, Grade 8, stainless steel for stainless steel bolts, and Grade 7 for carbon steel bolts. Nuts shall be threaded in accordance with ASME

B1.1, Class 2B fit, Coarse Thread Series for sizes one inch and smaller and

Eight-Pitch Thread Series for sizes larger than one inch. Provide washers under bolt heads and nuts. Use carbon steel washers conforming to ASTM F436

Type 1 (carbon steel), flat circular for carbon steel bolts. Stainless steel washer dimensioned in accordance with ASTM A436 flat circular, use material the same as the bolt. Use torque wrenches to tighten all flange bolts to the torque recommended by the gasket manufacturer. Tight in the pattern recommended by the gasket manufacturer. Use anti-seize compound on stainless steel bolts.

2.2.7 Gaskets

ASME B16.21, composition ring, using a Buna-N, polytetrafluoroethylene

(PTFE), or a protein and glycerin binder, 0.1250 inch thick. Gaskets shall be resistant to the effects of aviation hydrocarbon fuels and manufactured of fire-resistant materials. Full-face gaskets shall be used for flat-face flanged joints. Ring gaskets shall be used for raised-face flanged joints.

Gaskets shall be of one piece factory cut.

2.2.8 Relief and Drain System Piping

Pressure relief valve discharge lines and drain lines to the product recovery tank shall be as indicated.

2.2.9 Field Applied Protective Coatings

The field joints and fittings of all underground piping shall be coated as specified in Section 33 52 80 LIQUID FUELS PIPELINE COATING SYSTEM.

2.2.10 Threaded Joints

Threaded joints, if indicated on the drawings, shall be made tight with manufacturer recommended PTFE tape or a mixture of graphite and oil, inert filler and oil, or with a graphite compound, applied with a brush to the male threads. Not more than three threads shall show on made up joints.

Threaded joints, mechanical couplings and flanges will not be permitted in buried piping. Threaded joints shall not get welded.

2.2.11 Welded Joints

Welded joints in steel pipe shall be as specified in Part 3.

Section 33 52 43.13 Page 15

2.3 MANUAL VALVES

All portions of a valve coming in contact with fuel in stainless-steel pipe lines or epoxy lined carbon steel pipe lines shall be of noncorrosive material. Valves in stainless steel pipe lines or epoxy lined carbon steel pipe lines shall be Type 304 or Type 316 stainless steel or carbon steel internally plated with chromium or nickel or internally electroless nickel plated. Valves in unlined carbon steel pipelines shall have carbon steel body. Stem and trim shall be stainless steel for all valves. Manually operated valves 6 inches and larger shall be worm-gear operated and valves smaller than 6 inches shall be lever operated or handwheel operated. Valves smaller than 2 inches shall have lever-type handles. Valves installed more than 8 feet above finished floor shall have chain operators and a position indicators visible from ground level. Sprocket wheel for chain operator shall be aluminum. Valves in the isolation pits in fuel piping between the pig launchers and the pig receivers shall be full bore, piggable, double block and bleed type.

2.3.1 Ball Valves

Ball valves shall be fire tested and qualified in accordance with the requirements of API Std 607 and API STD 608. Ball valves shall be nonlubricated valves that operate from fully open to fully closed with 90 degree rotation of the ball. Valves 2 inches and larger shall conform to applicable construction and dimension requirements of API Spec 6D, ANSI

Class 150 and shall have flanged ends. Valves smaller than 2 inches shall be ANSI class 150 valves with one piece bodies with flanged ends, unless noted otherwise. The balls in valves 10 inches full port and 12 inch regular port and larger shall have trunnion type support bearings. Except as otherwise specified, reduced port or full port valves may be provided at the Contractor's option. Balls shall be solid, not hollow cavity.

2.3.1.1 Materials

Ball shall be stainless steel. Ball valves shall have tetrafluoroethylene

(TFE) or fluoroelastetomer (FKM), commonly referred to as Viton seats, body seals and stem seals. Valves 4 inches and smaller shall have a locking mechanism.

2.3.2 Plug (Double Block and Bleed) Valves

API Spec 6D, Type III, ANSI Class 150, non-lubricated, resilient, double seated, trunnion mounted, tapered lift plug capable of two-way shutoff.

Valve shall have tapered plug of steel or ductile iron with chrome or nickel plating and plug supported on upper and lower trunnions. Sealing slips shall be steel or ductile iron, with Viton seals which are held in place by dovetail connections. Valve design shall permit sealing slips to be replaced from the bottom with the valve mounted in the piping. Valves shall operate from fully open to fully closed by rotation of the handwheel to lift and turn the plug. Valves shall have weatherproof operators with mechanical position indicators. Indicator shaft shall be stainless steel. Minimum bore size shall be not less than 65 percent of the internal cross sectional area of a pipe of the same nominal diameter unless bore height of plug equals the nominal pipe diameter and manufacturer can show equal or better flow characteristics of the reduced bore size design. Valves indicated as

Section 33 52 43.13 Page 16

Full Bore (FB) shall be piggable. Full port plug valves in distribution piping shall be provided with a 1-inch flanged body drain.

2.3.2.1 General

Valves in the operating tank suction and fill lines and the valves at the six valve manifold in the pump shelter in the tank fill lines shall be provided with a factory-installed limit switch that is actuated by the valve closure, as indicated. Each switch shall have one double pole double throw contacts or four single pole, double throw contracts, two for open, two for closed, and shall be watertight and U.L. listed for Class I, Division 1, Group D hazardous areas.

2.3.2.2 Valve Operation

Rotation of the handwheel toward open shall lift the plug without wiping the seals and retract the sealing slips so that during rotation of the plug clearance is maintained between the sealing slips and the valve body.

Rotation of the handwheel toward closed shall lower the plug after the sealing slips are aligned with the valve body and force the sealing slips against the valve body for positive closure. When valve is closed, the slips shall form a secondary fire-safe metal-to-metal seat on both sides of the resilient seal. Plug valves located in Isolation Valve Pits or vaults shall be provided with handwheel extensions.

2.3.2.3 Relief Valves

ANSI Class 150. Provide plug valves with automatic thermal relief valves to relieve the pressure build up in the internal body cavity when the plug valve is closed. Relief valves shall open at 25 psi differential pressure and shall discharge to the throat of, and to the upstream side, of the plug valve.

2.3.2.4 Bleed Valves

ANSI Class 150, stainless steel body valve. Provide manually operated bleed valves that can be opened to verify that the plug valves are not leaking when in the closed position.

2.3.3 ELECTRIC VALVE ACTUATORS

The actuator, controls and accessories shall be the responsibility of the valve-actuator supplier for sizing, assembly, certification, field-testing and any adjustments necessary to operate the valve as specified. The electric valve actuator shall include as an integral unit the electric motor, actuator unit gearing, limit switch gearing, position limit switches, torque switches, drive bushing or stem nut, declutch lever, wiring terminals for power, remote control,indication connections and handwheel. The electrically actuated plug valve or ball valve shall be set to open and close completely in 30 to 60 seconds against a differential pressure of 275

PSIG. The actuator settings of torque and limit contacts shall be adjustable. The valve actuator shall be suitable for mounting in a vertical or horizontal position and be rated for 30 starts per hour. The valve actuator shall be capable of functioning in an ambient environment temperature ranging from -32 to 158 degrees F. Provide where indicated on the drawings.

Section 33 52 43.13 Page 17

a. The electrical enclosure shall be specifically approved by UL or

Factory Mutual for installation in Class I, Division 1, Group D locations.

b. The electric motor shall be specifically designed for valve actuator service and shall be totally enclosed, non-ventilated construction.

The motor shall be capable of complete operation at plus or minus 10 percent of specified voltage. Motor insulation shall be a minimum NEMA

Class F. The motor shall be a removable subassembly to allow for motor or gear ratio changes as dictated by system operational requirements.

The motor shall be equipped with an embedded thermostat to protect against motor overload and also be equipped with space heaters. It shall de-energize when encountering a jammed valve.

c. The reversing starter, control transformer and local controls shall be integral with the valve actuator and suitably housed to prevent breathing or condensation buildup. The electromechanical starter shall be suitable for 30 starts per hour. The windings shall have short circuit and overload protection. A transformer, if needed, shall be provided to supply all internal circuits with 24 VDC or 110 VAC may be used for remote controls.

d. The actuator gearing shall be totally enclosed in an oil-filled or grease-filled gearcase. Standard gear oil or grease shall be used to lubricate the gearcase.

e. The actuator shall integrally contain local controls for Open, Close and Stop and a local/remote three position selector switch: Local

Control Only, Off, and Remote Control plus Local Stop Only. A metallic handwheel shall be provided for emergency operation. The handwheel drive must be mechanically independent of the motor drive. The remote control capability shall be to open and close. Rim pull to operate valve manually shall not exceed 80 pounds.

f. Position limit switches shall be functional regardless of main power failure or manual operation. Four contacts shall be provided with each selectable as normally open or normally closed. The contacts shall be rated at 5A, 120 VAC, 30 VDC.

g. Each valve actuator shall be connected to a PLC supplied by "others".

h. The actuator shall have a local display of position even when power has been lost.

i. The actuator shall be supplied with a start-up kit comprising installation instruction, electrical wiring diagram and spare cover screws and seals.

j. The actuator must be performance tested and a test certificate shall be supplied at no extra charge. The test should simulate a typical valve load with current, voltage, and speed measured.

2.3.4 Swing Check Valves

Swing check valves shall conform to applicable requirements of API Spec 6D, regular type, ANSI Class 150 with flanged end connections. Check valves shall conform to API STD 600 and be swing type with material as previously

Section 33 52 43.13 Page 18 indicated herein. Discs and seating rings shall be renewable without removing the valve from the line. The disc shall be guided and controlled to contact the entire seating surface.

2.3.5 Silent Check Valves

Spring assisted, wafer/lug pattern, butterfly check with FKM or PTFE seat ring, designed to prevent flow reversal slamming of valve, dual plate, and shall conform to ASME B16.34, API Std 594, except face to face dimensions may deviate from standard. Valves shall be suitable for installation in any orientation. Valve body and trim material shall be as previously indicated herein.

2.4 THERMAL RELIEF VALVES

Relief valves shall be the fully enclosed, spring loaded, angle pattern, single port, hydraulically operated type with plain caps, and shall be labeled in accordance with ASME BPVC SEC VIII D1. Valve stems shall be fully guided between the closed and fully opened positions. The valves shall be factory-set to open as indicated on the drawings. Operating pressure shall be adjustable by means of an enclosed adjusting screw. The valves shall have a minimum capacity of 20 GPM at 10 percent overpressure.

Valves shall have a replaceable seat. Relief valves that do not relieve to a zone of atmospheric pressure or tank must be a balanced type relief or regulator valve.

2.4.1 Valve Materials

Valves shall have carbon steel bodies and bonnets with stainless steel springs and trim. Valves shall be Class 150 flanged end connections.

2.4.2 Sight Flow Indicators

Sight flow indicators shall be ASME Class 150 and shall have flanged end connections. Sight flow indicators shall consist of a housing containing a rotating propeller that is visible through a glass observation port. The housing shall be stainless steel when installed in stainless steel lines and carbon steel when installed in carbon steel lines. The glass in the indicator shall also meet the Class 150 rating.

2.4.3 Safety Relief Valve

ASME BPVC SEC VIII D1 - (2010) BPVC Section VIII-Rules for Construction of

Pressure Vessels Division 1

2.4.4 SAFETY RELIEF VALVES

Safety relief valves shall be fully enclosed, spring loaded, angle pattern, single port, hydraulically operated type with plan caps. Valves shall meet the requirements of ASME BPVC SEC VIII D1 and API Std 526. Valve stems shall be fully guided between the closed and fully opened positions. Valve seats shall provide a double seal with a metal-to-metal seat in addition to an oring soft seat. End connections shall be ASME B16.5, 150 lb class raised face flanges.

2.4.4.1 Materials of Construction

Section 33 52 43.13 Page 19

Valve bodies and bonnets shall be ASTM A217, Grade WCC carbon steel unless otherwise noted. Trim and internals shall be 316 stainless steel. Oring soft seat shall be Viton SRV-8 value body and bonnet shall be 316 stainless steel.

2.4.4.2 Specific Requirements

Valve manufacturer shall verify sizing of the valve provided in accordance with API Std 520 and the design conditions. Sizing shall include 10 percent overpressure at the given relief flow. Initial sizes and design conditions are given in the following table.

Valve

Number

Set

Pressure

(PSI)

Relief Flow

(GPM)

Inlet/Outlet

Size

(Nominal)

API Orifice

Size

Location

SRV-1 35 10 1" by 2" D PRP-1

(Tank 1)

SRV-2 35 10 1" by 2" D PRP-2

(Tank 2)

SRV-3 35 10 1" by 2" D PRP-3

(Tank 3)

SRV-4 30 10 1" by 2" D WDP-1

(PRT)

Note 1: SRV-1 through SRV-3 are only required if positive displacement pumps are selected for the product saver tank return.

2.5 PIPING ACCESSORIES

2.5.1 Flexible Ball Joints

Flexible ball joints shall be carbon steel with electroless nickel-plating to a minimum of 3 mils thickness, capable of 360-degree rotation plus 15-degree angular flex movement, ASME B16.5, Class 150 flanged end connections.

Provide pressure molded composition gaskets designed for continuous operation temperature of 275 degrees F. Joints shall be designed for minimum working pressure of ANSI Class 150. Injectable packing will not be allowed.

2.5.2 Pipe Sleeves

Pipe sleeves shall be installed where indicated and at all points where the piping passes through concrete construction. Such sleeves shall be of sufficient inside diameter to provide a minimum clear distance between the pipe and the sleeve of 1/2 inch. Sleeves through concrete pits or slabs shall be standard weight carbon steel pipe with a protective coating. Each sleeve shall extend through the respective pit wall or slab and shall be provided with a Buna-N casing seal. Sleeves where piping passes under roads or piping indicated to be double walled shall be standard weight carbon steel pipe with a protective coating as previously specified. Alignment of the sleeve and piping shall be such that the pipe is accurately centered within the sleeve by a nonconductive centering element. The sleeve shall be securely anchored to prevent dislocation. Closure of space between the pipe and the pipe sleeve shall be by means of a mechanically adjustable segmented elastomeric seal. The seal shall be installed so as to be flush.

Section 33 52 43.13 Page 20

2.5.3 Strainers

2.5.3.1 Basket Type

Strainer shall be in compliance with MIL-PRF-13789, except as specified otherwise. Strainer end connections shall be designed in accordance with

ASME B16.5, Class 150. Strainer body material shall be the same as the material specified for manual valves. Strainers shall have removable baskets of 60 mesh wire screen with larger wire mesh reinforcement; wire shall be stainless steel, Type 316. Pressure drop for clean strainer shall not exceed 3 psig at maximum design flow rate. The ratio of net effective strainer area to the area of the connecting pipe shall be not less than three to one. Each strainer shall be provided with a suitable drain at the bottom, equipped with a ball valve. The strainer shall be equipped with a direct-reading, piston type differential pressure gauge that measures the differential pressure across the basket. The gauge shall consist of a spring-supported, corrosion resistant piston moving inside a glass cylinder, with high pressure applied on top of the piston and low pressure applied below it. Under a differential pressure of 30 PSI, leakage past the piston shall not exceed 120 drops per minute. The cylinder shall have stainless steel and flanges with FKM O-ring seals. The high pressure inlet of the gauge shall have a 10-micron pleated paper filter and the low pressure connection shall have a fine mesh stainless steel strainer. The gauge shall have an operating pressure of 300 PSI. Differential pressure range of the gauge through approximately 3 inches of piston movement shall be 0-30 PSI with an accuracy of + 0.5 PSI, calibrated linearly with one PSI scale graduations. High and low pressure connections shall be 1/4 inch NPT female with a stainless-steel bar stock valve at each connection. Construction of the gauge shall be such that a 3-valve manifold is not necessary. If only one bar stock valve is closed, the gauge shall not be damaged by up to 300

PSI differential pressure in either direction. A pressure gauge shall be attached to the differential pressure gauge to indicate the high pressure and have a range of 300 psi.

2.5.3.2 Cone Type (Temporary)

Strainer shall be stainless steel type 304 or 316, 100 mesh screen with the ratio of net open area of strainer to the area of the connecting pipe shall be not less than three to one at the pump suction, and 5/32-inch perforations and suitable for bi-directional flow at the inlet to the hydrant pit control valves.

2.5.4 Pipe Hangers and Supports

2.5.4.1 General

Pipe hangers and supports shall conform to MSS SP-58. Supports shall be provided at the indicated locations. Support channels for drain lines shall be epoxy coated on all surfaces or hot-dip galvanized after the channels are cut to length. Coated supports shall be coated with fusion bonded epoxy resin applied by the fluidized bed method. Thickness of the coating shall be not less than 10 mils. Surface preparation and coating application shall be in accordance with the epoxy manufacturer's instructions. The coating shall be pinhole free when tested with a low voltage holiday detector set at no more than 100 times the mil thickness of the coating. All pinholes shall be marked, repaired and retested to ensure a pinhole free film. The coating

Section 33 52 43.13 Page 21 material shall be a 100 percent solids, thermosetting, fusion-bonded, dry powder epoxy resin. The manufacturer shall certify that the material is suitable for fluidized bed application and that it is approved by the

Environmental Protection Agency. A PTFE pad shall be installed between the pipe and the u-bolt.

2.5.4.2 Adjustable Pipe Supports

Adjustable pipe supports shall consist of a cast iron saddle and a threaded nipple connected to a carbon steel pipe by means of a special reducer conforming to MSS SP-69. The supports shall be provided with PTFE insulation strips.

2.5.4.3 Low Friction Supports

Low friction supports shall be self-lubricating antifriction element composed of reinforced PTFE. Units shall be factory designed and manufactured.

2.5.4.4 Concrete and Grout

Concrete and grout for anchors and supports shall comply with SECTION 03 30

00 CAST-IN-PLACE CONCRETE.

2.5.5 Sample Connections

a. Sample connections shall be factory assembled units specifically designed for obtaining representative samples from fuel pipelines.

Each connection shall include a 1/4-inch sampling probe where the probe faces upstream, ball valve and 1/4-inch quick disconnect coupling with dust plug, all assembled into a unit that is suitable for installation in a pipe nipple. The sampling probe shall extend not less than one inch into the fuel pipe. All materials in the sample connections shall be stainless steel or aluminum.

b. Furnish two sampling hose assemblies to the Contracting Officer at the project site. Each assembly shall consist of a 6-foot length of 1/4-inch clear plastic tubing with internal bonding/grounding wire. One end of the tubing will contain a male connector that actuates flow when inserted into the quick disconnect coupler. Each end of the bonding/grounding wire shall be equipped with clips for attaching to the pipe and metal sample container.

2.5.6 Flanged Swivel Joints

Flanged swivel joints shall be stainless steel, single plane, capable of rotating 360 degrees. Welded swivel joints and welding of swivel joints to the pipe and/or elbow is not permitted. Swivel joints shall be of the non-lubricated, maintenance free type with nonlubricated bearings and no lubricating fitting. Swivel joint shall be flanged at the end connecting to the piping system and threaded (female NPT) at the end connecting to the fuel hose. No leakage shall be permitted under positive or negative pressure conditions. No leakage shall be permitted under high or low temperature conditions. Welding of swivel joint to six-bolt flange connector is permitted. The swivel joints shall be warranted for three years against leakage. There must be electrical continuity from one flange to the other without the use of ground straps. The electrical continuity

Section 33 52 43.13 Page 22 from one flange to another (without the use of ground straps) shall be less than 1000 ohms. Each swivel joint shall have at least two ball bearings and one roller bearing and two seals.

2.5.7 Monitoring Points

At the following locations, provide half-inch pipe, flanged ball valve, and blind flange for future test equipment connections:

a. On the filter separator discharge header in the pumphouse.

b. At the Hydrant Hose Truck Checkout, inlet to Hydrant Valve.

c. At the inlet to the Back Pressure Control Valve in the Pumphouse.

d. At both sides of the isolation valve in all the isolation valve pits.

2.5.8 Quick Disconnect Adapters

Provide a male cam-and-groove style adapter of stainless steel aluminum.

Process connection shall be flanged or threaded. Provide with a dust cap and Buna-N seal.

2.5.9 Quick Disconnect Couplers

Provide a female cam-and-groove style coupler of stainless steel aluminum.

Process connection shall be flanged or threaded. Provide with a dust plug and Buna-N seal.

2.5.10 Nozzle Adapter (SPR)

Adapter shall be a nominal 2-1/2 inches with self-closing valve in accordance with MIL-A-25896. Adapter shall have a 4-inch flange mounting and vacuum tight, locking dust cap using the SPR lugs.

2.6 FLEXIBLE CONNECTORS

Flexible hoses for fueling pumps shall have ANSI Class 300 flanges to mate to the pump and Class 150 to connect to the system flanges of stainless steel construction conforming to ASME B16.5. Flexible hoses shall be of stainless steel flexible metal hose consisting of an inner corrugated stainless steel tube with stainless steel braid cover. All components to be suitable for not less than 275 psig. Length and application of flexible hoses shall be per manufacturer's written recommendations.

2.7 AUTOMATIC AIR VENT

Unit shall have one-inch connections and automatically vent air under pressure, and prevent a vacuum when pressure drops below a positive pressure.