FJRP159073-M-401-Amd03.pdf

PDF 467 KB Posted

Attached to
C-17 Refueling Hydrant System Ramp Expansion
Solicitation number
W91242-18-R-0002
Issued by

View the file

Other files

File Type Posted
Questions_and_Answers_96-101__W91242-18-R-0002.pdf PDF
FJRP159073-CG104-Amendment_0007.pdf PDF
FJRP159073-CG103-Amendment_0007.pdf PDF
Amendment_0007.pdf PDF
33_52_43.28_Amd03.pdf PDF
Questions_and_Answers_78-95__W91242-18-R-0002.pdf PDF
Revised_33_52_80_Amendment_0006.pdf PDF
Revised_08_71_00_Amendment_0006.pdf PDF
Revised_33_52_43_Amendment_0006.pdf PDF
Revised_09_96_00_Amendment_0006.pdf PDF
Revised_09_97_13.27_Amendment_0006.pdf PDF
FJRP159073-A-201-Amendment_0006.pdf PDF
Revised_13_34_19_Amendment_0006.pdf PDF
W91242-18-R-0002_0006.pdf PDF
Revised_09_90_00_Amendment_0006.pdf PDF
FJRP159073-A-601-Amendment_0006.pdf PDF
Amendment_0005_Revised_01_45_00.pdf PDF
Amendment_0004_Section_0010_Price_Schedule.pdf PDF
Amendment_0005.pdf PDF
Questions_and_Answers_40-77__W91242-18-R-0002.pdf PDF
Revised_EXIBIT_H_Proposal_Price_Schedule_Amendment_0004.pdf PDF
Amendment_0004.pdf PDF
Questions_and_Answers_18-38__W91242-18-R-0002.pdf PDF
1._Drawings_-COVER_SHEET.pdf PDF
FJRP159073-M-002-Amd03.pdf PDF
FJRP159073-M-301-Amd03.pdf PDF
FJRP159073-GC-003-Amd03.pdf PDF
32_05_33_Amd03.pdf PDF
FJRP159073-EI-503-Amd03.pdf PDF
Exhibit_F_Small_Business_Participation_Format.pdf PDF
33_09_53_Amd03.pdf PDF
FJRP159073-MS502-Amd03.pdf PDF
FJRP159073-CS-121-Amd03.pdf PDF
FJRP159073-MS504-Amd03.pdf PDF
FJRP159073-M-512-Amd03_(1).pdf PDF
33_52_43.13_Amd03.pdf PDF
FJRP159073-EP-101-Amd03.pdf PDF
Exhibit_G_-_Subcontracting_Plan_Format.pdf PDF
33_52_43.11_Amd03.pdf PDF
FJRP159073-EI-602-Amd03.pdf PDF
FJRP159073-C-511-Amd03.pdf PDF
FJRP159073-M-003-Amd03.pdf PDF
FJRP159073-MD902-Amd03.pdf PDF
FJRP159073-MS503-Amd03.pdf PDF
FJRP159073-C-510-Amd03.pdf PDF
FJRP159073-CU-121-Amd03.pdf PDF
FJRP159073-CU-224-Amd03.pdf PDF
W91242-18-R-0002_0003.pdf PDF
FJRP159073-M-502-Amd03.pdf PDF
Amendment_0003_Exhibit_A_Performance_Relevancy_Questionnaire_Specialized_Experience.pdf PDF
Show 40 more

Latest 50 of 114 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

S c a l e

F o r

M i c r o f i l m i n g

I n c h e s

M i l l i m e t e r s date detailed checkeddesigned ofsheet sheets project contract rev.drawing file

NORTH CAROLINA AIR NATIONAL GUARD

DOUGLAS INTERNATIONAL AIRPORT

CHARLOTTE, NORTH CAROLINA

KANSAS CITY, MISSOURI

ENGINEERS ARCHITECTS & CONSULTANTS

Project No. - FJRP159073

C-17 TYPE III HYDRANT

REFUELING SYSTEM/

RAMP EXPANSION

94893

C O

P Y

R I G

H T

B U

R N

S

M c D

O N

N E

L L

E

N G

I N

E E

R I N

G

C

O M

P A

N Y

I N

C

D

2 3

C

4 5

A

B

C O

P Y

R I G

H T

ENLARGED PLAN -

PUMP SHELTER

M-401

FJRP159073-M-401.DWG

V.KEEBLE

B.COOVER R.PERUE

A1

ENLARGED PLAN - PUMP SHELTER

SCALE: 1/4"=1'-0"

N

GENERAL NOTES: THIS DRAWING ONLY

1. REFER TO DRAWINGS M-001 AND M-002 FOR

LEGENDS, ABBREVIATIONS AND GENERAL PROJECT

NOTES.

2. REFER TO SECTIONS FOR CLARITY OF STACKED

PIPING.

3. EXTEND FBE COATING A MINIMUM OF 6 INCHES

ABOVE GRADE

4. REFER TO SECTION C1 ON M-302 FOR STACKED

PIPE.

5. ALL LARGE BORE MANUAL VALVES LOCATED 72

INCHES OR HIGHER ABOVE FINISHED FLOOR SHALL

BE PROVIDED WITH CHAIN OPERATORS.

6. NOT USED.

7. SMALL BORE PIPING IS SHOWN SCHEMATICALLY.

REFER TO P&ID FOR SIZES. REFER TO THE

APPROPRIATE DETAIL ON M-511 TO M-514.

8. REFER TO S-551 TO S-555 FOR PIPE SUPPORT

DETAILS.

INDICATES BID OPTION 3

8" DBB W/ LIMIT

SWITCH (TYP OF 6)

12" CS 12" CS

FP-3

900 GPM

API 610

10" CS

10" CS

10" CS

FSI-3

900 GPM

10" ISSUE

VENTURI

SURGE ARRESTOR

TANK (TYP OF 2)

S

U C

T I O

N

T

O

T

K

FP-2

900 GPM

API 610

FP-1

900 GPM

API 610

FCV-3

FSI-2

900 GPM

FSI-1

900 GPM

FSR-2

900 GPM

FSR-1

900 GPM

FROM EXISTING TRUCK

OFFLOAD (NOTE 3) FOR

CONTINUATION ON

CU228

6" SUPPLY TO HHT

CHECKOUT STAND

(NOTE 3)

T

O

T

K

T

O

T

K

PS-2

PS-2C

PS-2

PS-2

PS-2

10" DBB PLUG

VALVE (TYP OF 3)

PS-8

PS-4

PS-4CPS-4

10" CS

10" CS

6" CS

6" BALL VALVE

(TYP OF 3)

NOTE 5

6" BALL VALVE

(TYP OF 3)

(NOTE 5)

6" DBB

PLUG VALVE

8" MOV

BALL VALVE

8" DBB PLUG

VALVE

6" DBB

PLUG VALVE

PS-2

PS-2

PS-2

8" BALL VALVE

NOTE 5

6" BALL VALVE

(NOTE 5) (TYP OF 2)

8" BALL

VALVE

(NOTE 5)

8" BALL VALVE

(NOTE 5)

8" BALL VALVE

(NOTE 5)

RETURN FROM HHT

CHECKOUT STAND

(NOTE 3)

8" CS

8" CS

AG

UG

AG

UG

PS-2

10"X6" FOT

REDUCER

(TYP OF3)

8" CS

6" BALL

VALVE

6" BASKET

STRAINER

8" CS

8"X6"

REDUCER

(TYP OF 2)

FSCV-4

FSCV-5

FSCV-1

FSCV-2

FSCV-3

FCV-1

FCV-2

FLOW SWITCH

(TYP OF 3)

D/FV-1

SEE NOTE 4

8" BALL

VALVE

P S

C

P S

C

P S

C

PS-2

PS-7 PS-7

PS-2C

6" CS

C

S

6" CS6" CS

C

S

6" CS

6" CS

C

S

C

S

PS-7

PS-7

PS-2

PS-6

PS-2C

PS-2

PS-2

PS-5

PS-2

PS-5

PS-2

MAV

PG

PG

TRV

PRESSURE

TRANSMITTER

ASSEMBLY

(FP-1 ONLY)

MAV

PG

PG

TRV

MAV

PG

PG

TRV

TRV

TRV

MAV

MAV

MAV

PG

PG

PG

MAV

TRV

TRV

TRV

TRVTRV

TRV

TRV

KEYED NOTES: THIS DRAWING ONLY

IF BID OPTION IS SELECTED DO NOT PROVIDE

FLANGES AS INDICATED.

THE HINGE FOR FILTER SEPARATOR SHALL OPEN

AS INDICATED.

FROM FILTER SEPARATOR DRAIN.

FROM FILTER SEPARATOR PRESSURE SAFETY

VALVE.

TO FILTER SEPARATOR (SLOW FILL).

2" STAINLESS STEEL CARRIER PIPE WITH 4"

CONTAINMENT PIPE WITH EXTERIOR FBE

COATING. ASTM A139, 10 GAUGE SPIRAL WELDED

STEEL. INSTALL PER MANUFACTURERS

RECOMMENDATIONS. DOUBLE WALL PIPE END

SEAL SHALL BE A SEGMENTED ELASTOMERIC

SEAL. MINIMUM TOP OF PIPE SHALL BE 3'-0"

BELOW GRADE. SLOPE THE UNDERGROUND LINE

TOWARDS THE PRODUCT RECOVERY TANK WITH

NO HIGH POINTS AND THE LOW POINT BEING

LOCATED IN THE PRODUCT RECOVERY TANK

VAULT. COORDINATE ELEVATIONS WITH

ELECTRICAL DUCT BANK.

2" CARBON STEEL CARRIER PIPE WITH 4"

CONTAINMENT PIPE WITH EXTERIOR FBE

COATING. ASTM A139, 10 GAUGE SPIRAL WELDED

STEEL. INSTALL PER MANUFACTURERS

RECOMMENDATIONS. DOUBLE WALL PIPE END

SEAL SHALL BE A SEGMENTED ELASTOMERIC

SEAL. MINIMUM TOP OF PIPE SHALL BE 3'-0"

BELOW GRADE. SLOPE THE UNDERGROUND LINE

TOWARDS THE PRODUCT RECOVERY TANK WITH

NO HIGH POINTS AND THE LOW POINT BEING

LOCATED IN THE PRODUCT RECOVERY TANK

VAULT. COORDINATE ELEVATIONS WITH

ELECTRICAL DUCT BANK.

2" SS TO PRT

℄ELEVATION NOT TO

EXCEED 12" ABOVE TOP

OF SLAB

PCV-1

(TYP OF 5)

(TYP OF 5)

(TYP OF 5)

2" SS

2" SS

2" SS

DAY

TANK

MAV

MAV

MAV

MAV

MAV

PG

PG

2" MOV

BALL VALVE

TRV

TRV

PS-2

PRESSURE

INDICATING

TRANSMITTER

10" CS

HYDRANT

RETURN

10" CS

HYDRANT

ISSUE

2" CS LEAK DETECTION

EQUALIZATION LINE

SEE CONT. ON

SHEET M-103

2" SS DRAIN/

TRV LINE

PS-1

2" SS DRAIN/

TRV LINE

M A

T C

H L

I N

E

S

E E

C O

N T

I N

U A

T I O

N

O

N

M

2" CS FROM PRT

FOR CONTINUATION

SEE CU227

FOR CONTINUATION

SEE CU227

SCALE IN FEET

0 2' 4' 8'

NOVEMBER 2016

F

R O

M

P

S T

2" SS SLOW FILL

TRV

MAV

2" SS TO PRT

℄ELEVATION NOT TO

EXCEED 12" ABOVE TOP

OF SLAB

MAV

2" CS

S

AutoCAD SHX Text

DATE

AutoCAD SHX Text

REV.

AutoCAD SHX Text

DESCRIPTION

AutoCAD SHX Text

INIT

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text 10/13/17

AutoCAD SHX Text

B-3 FINAL SUBMITTAL

AutoCAD SHX Text

AutoCAD SHX Text 02/07/18

AutoCAD SHX Text

AMENDMENT 0003

AutoCAD SHX Text

AutoCAD SHX Text

BC

AutoCAD SHX Text A1

AutoCAD SHX Text M-302

AutoCAD SHX Text C1

AutoCAD SHX Text M-301

AutoCAD SHX Text A1

AutoCAD SHX Text M-301

AutoCAD SHX Text C1

AutoCAD SHX Text M-302

AutoCAD SHX Text C1

AutoCAD SHX Text M-303

AutoCAD SHX Text

IF

AutoCAD SHX Text

IF

AutoCAD SHX Text

IF

AutoCAD SHX Text

IF

AutoCAD SHX Text

IF

AutoCAD SHX Text

IF

AutoCAD SHX Text

BC

2018-02-07T15:16:12-0600
Coover, Bra

File details come from the government source that posted it.