These are construction documents for the renovation of Building 9A at Carl Vinson VA Medical Center in Dublin, Georgia (Project 557-21-703). The documents include plumbing and electrical design sheets, abbreviations, general notes, legends, and demolition plans prepared by SPEES Design Build as the Architect/Engineer of Record. The project is titled "Renovate Building 9A for EHRM Administrative Space" and is issued as Construction Documents dated June 14, 2024.
The plumbing sheets (P-103 West and P-104 East) detail Level 1 plumbing installations including cold water (CW), hot water (HW), sanitary (SAN), and vent (V) piping for multiple rooms such as restrooms, break rooms, mechanical spaces, and testing areas. Key plumbing specifications require sanitary lines sloped at 1/4" per foot minimum, DWV cast iron materials, and cleanouts per IPC standards. Electrical sheets include lighting and power demolition plans (ED101-ED103) and special systems demolition requirements, indicating equipment to be salvaged or removed, including fire alarm systems, telecommunications infrastructure, wireless access points, and data cabling. The electrical legends (E-002) establish standard symbols for power distribution, lighting, fire alarm, security access, telecommunications, and nurse call systems. General notes specify that all work must comply with applicable plumbing and electrical codes, contractors must coordinate with other trades, existing circuits must remain energized until work completion, and abandoned wiring must be completely removed. The documents are fully sprinklered and indicate coordination is required between multiple building systems during the EHRM administrative space renovation.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DETAIL AREA
PROJECT
NORTH
TRUE NORTH
(DASHED)
2120191817
1 2 3 4 5 6 7
P-528
P-103 (TYP 4)
P-418 (TYP 4)
FD-C (TYP 4)
M A
T C
H L
IN
E
M A
T C
H L
IN
E
1/2" CW, 2" SS FROM
BELOW AND 1/2" HW &
1-1/2" V DN TO SINK
IV TESTING
CHANGE MGMT
USER
STAFF BREAK
CORRIDOR
CR11-9
MECHANICAL
ELECTRICAL
CLOSET
STORAGE
RESTROOM
RESTROOM
RESTROOM
RESTROOM
WAITING ALCOVE
1/2" 2" SS UP FROM
BELOW TO BOTTLE
FILLER. 1-1/2" VENT DN
2" V
2" V
2" V TIE INTO
EXISTING VTR
(E) 3" W UP AND
DN
(E) 1-1/2" SAN
UP
S S
SS
S S
(E) 3"SAN UP
TIE 2" V INTO
(E) 2"V UP
(E) 4"SAN UP,
INSULATE
STERILIZER
DRAINS
CO
(E) 2"V UP
(E) 2"V UP
(E) 3"SAN
UP
(E) 4"SAN UP
CO
(E) 4" SAN
(E) 4" SAN
(E) 4" SAN
DN
1" CW, HW/HWR
LINES
RELOCATED
INTO WALL
1-1/2" V TIE
INTO (E) VTR
1/2" HWR
1" HW
3/4" HW
(TYP. 2)
(TYP. 2)
2" V TIE INTO
EXISTING VTR
1/2" HWR DN
P-608
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:3
:4
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /M
E C
H B
L D
G
A
.r v t
P-103
PLUMBING - WEST
009A
MGH/JW NBH
CONSTRUCTION
DOCUMENTS
06/14/2024
557-21-703
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
Revisions: Date:
3/16" = 1'-0"
LEVEL 1 - PLUMBING - WEST
PROJECT
NORTH
TRUE NORTH
(DASHED)
GENERAL NOTES
1. DRAWINGS ARE DIAGRAMMATICAL TO ENSURE LEGIBILITY AND CLEANLINESS.
CONTRACTOR SHALL CONFIRM DIMENSIONS AND EQUIPMENT FIT AS NEEDED FOR
COMPLETE INSTALL
2. ALL WORK SHALL BE COMPLY WITH PLUMBING CODE RECOGNIZED BY AUTHORITY
HAVING JURISDICTION
3. SLOPE ALL SANITARY SEWER LINES @ 1/4" PER FOOT UNLESS APPROVED BY
AUTHORITY HAVING JURISDICTION . LINES EQUAL TO OR GREATER THAN 4" MAY BE
SLOPED AT 1/8" UPON APPROVAL AND IN ACCORDANCE WITH IPC
4. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER RECOMMENDATION
UNLESS OTHERWISE DIRECTED
5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.
6. SANITARY PIPING SHALL BE DWV CAST IRON. USE APPROPRIATE FITTINGS AS
INDICATED IN IPC.
7. PROVIDE CLEANOUTS AS SHOWN ON DRAWINGS, LINES FROM MAIN PIPE LONGER
THAN 5 FT UNLESS EXEMPT IN UPC, MAINS OVER 100 FT IN HORIZONTAL LENGTH, OR
CHANGE IN DIRECTION GREATER THAN 135 DEGREES
KEYNOTES
KEY PLAN
1 1/2" CW & 2" SS FROM BELOW, 1-1/4"HW DN TO WITHIN 24" FROM LAV CONNECTION
AND BACK UP IN WALL, AND 1-1/2 V DN. SEE 2/P-001 FOR MORE DETAILS.
1/2" CW & 2" SS FROM BELOW, 1"HW DN TO WITHIN 24" FROM LAV CONNECTION AND
BACK UP IN WALL, AND 1-1/2 V DN. SEE 2/P-001 FOR MORE DETAILS. .
1/2" CW & 2" SS FROM BELOW, 3/4"HW DN TO WITHIN 24" FROM LAV CONNECTION AND
THEN 3/4" ROUTED TO SINK ON ADJACENT WALL, AND 1-1/2 V DN. SEE 3/P-001 FOR
MORE DETAILS.
1/2" CW & 2" SS FROM BELOW, 1/2"HWR UP, AND 1-1/2 V DN. SEE 3/P-001 FOR MORE
DETAILS.
1-1/2" CW, 3"SAN FROM BELOW TO WC.
(E) 1-1/2" CW UP/DN
(E) 4" W UP/DN
(E) 1-1/2" HW UP/DN
2" V DN WALL TO FD
6/14/2024 73 OF 102
DETAIL AREA
PROJECT
NORTH
TRUE NORTH
(DASHED)
32 5831302928272625
9 10 11 12 13 14 15 16 60 61 62 63 64
M A
T C
H L
IN
E
M A
T C
H L
IN
E
FD-C
1/2" CW FROM
BELWO AND 1/2"
HW FROM ABOVE
CORRIDOR
CR11-9
IV SUPPORT
IV TESTING
STG
103A
HAC
MECHANICAL
TR
CORRIDOR
CR11-9
(E) 3"
CW
UP
P502
2" DN WALL
(TYP.2)
3/4"
HW&
1" CW
3/4" HWR
3/4" HWR DN
4" SAN DN
3" SAN
(E) 3/4"
HW UP
(E) 1"
CW UP
3" SAN
DN
3" SAN DN
1-1/4"
CW DN
SS
SS
SS
SS
(E) 2"V UP
(E) 4" SAN UP
(E) 2" SAN UP (E) 2"V UP
(E) 4" SAN UP
(E) 1-1/2" V UP
(E) 2"V UP
(E) 1-1/2" V UP
(E) 3" SAN UP
(E) 4" SAN
(E) 2"V UP
(E) 4" SAN DOWN
(E) 3" SAN UP
(E) 1-1/2" V UP
(E) 2"V UP
(E) 4" SAN UP
(E) 4" SAN UP (E) 3" SAN UP
(E) 2"V UP
(E) 2"
SAN UP
(TYP.3)
(E) 3" SAN UP
(E) 2" V UP
(E) 2" SAN
UP
(E) 4"SAN UP
(E) 3" SAN UP
CO
3/4" HWR&
3/4" CW
(E)1" HW
UP
4" SAN
DN
ELECTRICAL
ROOM
(E) 4" SAN UP
1-1/4"
HWR DN
CIRCUIT
SETTER
(TYP.3)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:3
:4
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /M
E C
H B
L D
G
A
.r v t
P-104
PLUMBING - EAST
009A
MGH/JW NBH
CONSTRUCTION
DOCUMENTS
06/14/2024
557-21-703
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
GENERAL NOTES
1. DRAWINGS ARE DIAGRAMMATICAL TO ENSURE LEGIBILITY AND CLEANLINESS.
CONTRACTOR SHALL CONFIRM DIMENSIONS AND EQUIPMENT FIT AS NEEDED FOR
COMPLETE INSTALL
2. ALL WORK SHALL BE COMPLY WITH PLUMBING CODE RECOGNIZED BY AUTHORITY
HAVING JURISDICTION
3. SLOPE ALL SANITARY SEWER LINES @ 1/4" PER FOOT UNLESS APPROVED BY
AUTHORITY HAVING JURISDICTION . LINES EQUAL TO OR GREATER THAN 4" MAY BE
SLOPED AT 1/8" UPON APPROVAL AND IN ACCORDANCE WITH IPC
4. INSTALL EQUIPMENT IN ACCORDANCE WITH MANUFACTURER RECOMMENDATION
UNLESS OTHERWISE DIRECTED
5. COORDINATE EXACT LOCATION OF PIPING WITH OTHER TRADES.
6. SANITARY PIPING SHALL BE DWV CAST IRON. USE APPROPRIATE FITTINGS AS
INDICATED IN IPC.
7. PROVIDE CLEANOUTS AS SHOWN ON DRAWINGS, LINES FROM MAIN PIPE LONGER
THAN 5 FT UNLESS EXEMPT IN UPC, MAINS OVER 100 FT IN HORIZONTAL LENGTH, OR
CHANGE IN DIRECTION GREATER THAN 135 DEGREES
KEY PLAN
PROJECT
NORTH
TRUE NORTH
(DASHED)
3/16" = 1'-0"
LEVEL 1 - PLUMBING - EAST
Revisions: Date:
6/14/2024 74 OF 102
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:5
:2
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /V
A D
U
G E
N S
H E
E T
S
E L
S
D B
.r v t
E-001
ABBREVIATIONS, GENERAL
NOTES, AND SHEET INDEX -
JPB/WNM BCL
CONSTRUCTION
DOCUMENT
06/14/2024
557-21-703RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA
1PH SINGLE-PHASE
1P SINGLE POLE
2/C TWO-CONDUCTOR
3/C THREE-CONDUCTOR
3PH THREE-PHASE
4/C FOUR-CONDUCTOR
4W FOUR-WIRE
A/C AIR CONDITIONING UNIT
A/E ARCHITECT/ENGINEER
AAP ALARM ANNUNCIATOR PANEL
AC ALTERNATING CURRENT OR ARMORED CABLE
ACC ACCESSIBLE
ADDL ADDITIONAL
ADJ ADJACENT, ADJOINING
AF AMPERE FRAME OR AMP FUSE
AFC ABOVE FINISHED COUNTER, AUTOMATIC
FREQUENCY CONTROL, OR AVAILABLE
FAULT CURRENT
AFCI ARC-FAULT CURRENT INTERRUPTER
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
Ah AMPERE HOUR
AHJ AUTHORITY HAVING JURISDICTION
AIC AMPERE INTERRUPTING CAPACITY
ALT ALTERNATE
AMB AMBIENT
AMP AMPERE
ARCH ARCHITECT
ASC AMPS SHORT CIRCUIT
AT AMPERE TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AV AUDIO VISUAL
BAT BATTERY
BD BOARD
BFF BELOW FINISH FLOOR
BLDG BUILDING
BRKR BREAKER
BYP BY PASS
C CONDUIT
CAB CABINET
CALC CALCULATE
CAP CAPACITY
CAT CATALOG
CATV COMMUNITY ANTENNA TELEVISION
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR FURNISHED
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/
OWNER INSTALLED
CFE CONTRACTOR FURNISHED EQUIPMENT
CHW CHILLED WATER
CHWP CHILLED WATER PUMP
CKT CIRCUIT
C/B CIRCUIT BREAKER
CL CONNECTOR LIGHTING
CLF CURRENT LIMITING FUSE
CLG CEILING
CO CONDUIT ONLY
COAX COAX CABLE
COMM COMMUNICATION
COMPT COMPARTMENT
CONC CONCRETE
CONT CONTINUE
CONTR CONTRACTOR
COORD COORDINATE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
CUR CURRENT
dB DECIBEL
DC DIRECT CURRENT
DCP DIMMER CONTROL PANEL
DDC DIRECT DIGITAL CONTROLS
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLITION
DIAG DIAGRAM
DISC DISCONNECT
DP DISTRIBUTION PANEL
DMR SW DIMMER SWITCH
DPDT DOUBLE POLE, DOUBLE THROW
DPST DOUBLE POLE, SINGLE THROW
DRSW DOOR SWITCH
DS DISCONNECT SWITCH
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EL ELEVATION OR EXISTING TO BE RELOCATED
ELEC ELECTRIC OR ELECTRICAL
ELEV ELEVATOR
EMER/EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMT ELECTRICAL METALLIC TUBING
EN EXISTING IN NEW LOCATION
ENCL ENCLOSURE
EPO EMERGENCY POWER OFF
EPRF EXPLOSION PROOF
ER EXISTING TO REMAIN
ESMT EASEMENT
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WATER HEATER
EXIST(E) EXISTING
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCIO FURNISHED BY CONTRACTOR,
INSTALLED BY OWNER
FOIC FURNISHED BY OWNER,
INSTALLED BY CONTRACTOR
FIXT FIXTURE
FLA FULL LOAD AMPS
FLUOR FLUORESCENT
FP FIRE PROTECTION
FT FEET OR FOOT
FU SW FUSED SWITCH
FVNR FULL VOLTAGE NON-REVERSING
FVR FULL VOLTAGE REVERSING
G ELECTRICAL GROUND
GEN GENERATOR
GFCI GROUND FAULT
CIRCUIT INTERRUPTER
GFP GROUND FAULT PROTECTION
GND GROUND
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HZ HERTZ
IG ISOLATED GROUND
IESNA ILLUMINATION ENGINEERING
SOCIETY OF NORTH AMERICA
IMC INTERMEDIATE METAL CONDUIT
INCAND INCANDESCENT
IR INFRARED
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAh KILOVOLT AMPERE PER HOUR kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR kWhM KILOWATT HOUR METER
LCP LIGHTING CONTROL PANEL
LED LIGHT EMITTING DIODE
LF LINEAR FEET (FOOT)
LP LIGHT POLE
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTG PNL LIGHTING PANEL
LTNG LIGHTNING
LV LOW VOLTAGE
MAX MAXIMUM
MC METAL-CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MH MANHOLE
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
MLO MAIN LUGS ONLY
MS MOTOR STARTER
MT MOUNT
MTD MOUNTED
MTG MOUNTING
MTS MANUAL TRANSFER SWITCH
MV MEDIUM VOLTAGE
MVA MEGAVOLT-AMPERE
MW MEGAWATT
NA NOT APPLICABLE
NAC NOTIFICATION APPLIANCE CABINET
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS ASSOCIATION
NEUT, N NEUTRAL
NFC NOT FOR CONSTRUCTION
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
OS OCCUPANCY SENSOR
P POLE
PB PULL BOX
PEC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PIV POST INDICATOR VALVE
PF POWER FACTOR
PH PHASE
PNL PANEL
PS POWER SUPPLY
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (PLASTIC)
PWR POWER
R EXISTING TO BE REMOVED
RCP REFLECTED CEILING PLAN
REC RECESSED
RECPT RECEPTACLE
RM ROOM
RMC RIGID METAL CONDUIT
RMS ROOT MEAN SQUARE
REQD REQUIRED
SAC SMALL APPLIANCE CIRCUIT
SCC SHORT CIRCUIT CAPACITY
SD SMOKE DETECTOR
SF SQUARE FOOT (FEET)
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SM SMART METER
SPD SURGE PROTECTIVE DEVICE
SPEC SPECIFICATION
SPST SINGLE POLE, SINGLE THROW
SURF SURFACE
SW SWITCH
SWBD OR SB SWITCHBOARD
SWGR OR SG SWITCHGEAR
TEL TELEPHONE
TR TAMPER RESISTANT
TV TELEVISION
TYP TYPICAL
UFD UNDERFLOOR DUCT
UGND UNDERGROUND
UL UNDERWRITERS LABORATORY
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER
SUPPLY
UTIL UTILITY
V VOLT
VA VOLT AMPERE
VAR VOLT AMPERE REACTIVE
VFD VARIABLE FREQUENCY DRIVE
VOLT VOLTAGE
W WATT/WEATHERPROOF
(WHILE IN USE)
WH WATER HEATER
WP/W WEATHERPROOF
XFER TRANSFER
XFMR TRANSFORMER
1. THESE "GENERAL NOTES" SHALL APPLY TO ALL DRAWINGS WITHIN THIS DRAWING SET. "SHEET NOTES" APPLY TO ONLY THE SHEETS ON WHICH
THEY OCCUR. "KEYNOTES" APPLY ONLY WHERE CALLED OUT.
2. IF THE SPECIFICATIONS OR DRAWINGS CONFLICT WITH EACH OTHER THE MORE STRINGENT CRITERIA/SCOPE OF WORK SHALL BE REQUIRED.
3. BLACKENED OR BOLDED EQUIPMENT INDICATES THE EQUIPMENT SHALL BE PROVIDED AND INSTALLED BY THE CONTRACTOR. ITEMS NOT DIRECTLY FURNISHED BY THE CONTRACTOR SHALL HAVE A DESIGNATION SUCH AS OFCI (OWNER FURNISHED CONTRACTOR INSTALLED), OFOI
(OWNER FURNISHED OWNER INSTALLED), OR NIC (NOT IN CONTRACT). GRAY OR GRAY-SCALED EQUIPMENT SHALL BE ASSUMED TO BE EXISTING
OR SHOWN FOR EQUIPMENT LOCATION COORDINATION.
4. EXISTING CIRCUITS ASSOCIATED WITH THE PROJECT AREA OF WORK ARE TO BE DE-ENERGIZED DURING CONSTRUCTION.
5. ALL ELECTRICAL WORK SHALL BE COMPLETED WITH ALL PROXIMATE ELECTRICAL CIRCUITS DE-ENERGIZED (i.e. A NEW BREAKER OR CIRCUIT CANNOT BE ADDED TO A PANEL UNLESS THE PANEL IS COMPLETELY DE-ENERGIZED), OR THE CONTRACTOR MUST COMPLY WITH NFPA 70E FOR WORK ON ENERGIZED SERVICE. THE VA WILL DETERMINE IF THE ELECTRICAL SERVICE CAN BE SHUT DOWN OR IT WILL HAVE TO BE WORKED HOT DEPENDING ON THE CRITICALITY OF THE AREA BEING AFFECTED. IF THE WORK MUST BE DONE WITH THE SERVICE LIVE, THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL REQUIRED PROTECTIVE TOOLS, EQUIPMENT, AND CLOTHING, AND MUST FOLLOW THE JOB SPECIFIC WORK PLAN PREPARED BY THE CONTRACTOR AND APPROVED BY THE VA. WORK THAT REQUIRES SHUTTING DOWN ELECTRICAL SERVICE MAY HAVE TO
BE ACCOMPLISHED DURING OTHER THAN NORMAL DUTY HOURS.
6. PROVIDE RACEWAYS AND CONDUCTORS/CABLING FROM LUMINAIRES TO THEIR CORRESPONDING CONTROL DEVICES AS INDICATED ON PLANS.
7. LUMINAIRE INSTALLATIONS AND LAYOUTS SHALL BE COORDINATED WITH ALL OBSTACLES, EQUIPMENT AND ARCHITECTURAL FEATURES.
8. WHERE NOT SPECIFICALLY INDICATED ON DRAWINGS, BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG MINIMUM FOR RUNS EQUAL TO OR LESS THAN 65 FEET AND 10 AWG MINIMUM FOR RUNS GREATER THAN 65 FEET. RACEWAYS AND CONDUCTORS SHALL BE SIZED AND QUANTIFIED TO SERVE AND CONTROL APPLICABLE EQUIPMENT WITH VOLTAGE DROP NO GREATER THAN THREE PERCENT. INDIVIDUAL CIRCUITS SHALL NOT
SHARE NEUTRAL CONDUCTORS.
9. MINIMUM CONDUIT SIZE SHALL BE 1” FOR EXTERIOR AND UNDERGROUND CONDUIT. MINIMUM CONDUIT SIZE SHALL BE 3/4” FOR INTERIOR CONDUIT.
ADDITIONAL CONDUCTORS FOR UNSWITCHED HOT CONDUCTOR TO LUMINAIRES WITH EMERGENCY BATTERY POWERED BACKUP UNITS OR TRANSFER DEVICES SHALL BE PROVIDED. ALL CONDUIT SHALL BE CONCEALED. THE ABOVE COMMENTS SHALL BE ADHERED TO UNLESS
OTHERWISE NOTED ON THE DRAWINGS.
10. EMERGENCY LIGHTING OR EQUIPMENT CIRCUITS SHALL BE ROUTED INDEPENDENT FROM OTHER CIRCUIT TYPES; ENSURE NEC 700.10
REQUIREMENTS ARE MET.
11. PROVIDE ALL CONDUIT AND WIRE FOR ALL CIRCUITS INDICATED AND/OR NOTED ON THE DRAWINGS AND/OR SPECIFICATIONS. ALL AUXILIARY OR REQUIRED APPURTENANCES FOR PROVIDED EQUIPMENT SHALL BE PROVIDED WITH ALL CONNECTIONS AS REQUIRED.
12. ALL EQUIPMENT AND DEVICES INCLUDING, BUT NOT LIMITED TO, ELECTRICAL DISTRIBUTION EQUIPMENT, RECEPTACLES, DATA OUTLETS, AND SPECIAL SYSTEM DEVICES, SHALL HAVE THEIR EXACT LOCATION COORDINATED WITH ARCHITECTURAL DRAWINGS AND ALL TRADES PRIOR TO
COMMENCING WORK.
13. COORDINATE WITH LIGHTING MANUFACTURER FOR ALL LIGHTING CONTROL EQUIPMENT AND APPURTENANCES; PROVIDE ANY ADDITIONAL SENSORS TO PROVIDE FULL COVERAGE OF THE SPACE AS REQUIRED. ALL CONDUIT, WIRE, POWER SUPPLIES, AND APPURTENANCES REQUIRED FOR THE LIGHTING CONTROL SYSTEM SHALL BE PROVIDED TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL SYSTEM.
14. ALL EXTERIOR MOUNTED RECEPTACLES AND LUMINAIRE INSTALLATIONS SHALL COORDINATE EXACT LOCATIONS WITH ARCHITECTURAL SHEETS.
ADDITIONALLY, WHERE MASONRY IS USED, SMOOTH BLOCK SHALL BE UTILIZED TO PROVIDE A PROPER MOUNTING SURFACE TO ALL EQUIPMENT;
RECEPTACLES SHALL BE INSTALLED FLUSH AND THE DEVICE LEVEL TO SURROUNDING SURFACE.
15. ALL CONDUIT/SLEEVE FLOOR AND WALL PENETRATIONS SHALL BE SEALED WITH FIRE RATED ASSEMBLIES, CAULKING, AND APPURTENANCES.
ELECTRICAL BOXES LOCATED IN FIRE RATED WALLS SHALL BE RATED FOR USE IN FIRE RATED WALLS.
16. ALL EQUIPMENT AND INSTALLATION METHODS SHALL BE LISTED AND LABELED PER NEC, UL LISTED, OR REVIEWED EQUAL.
17. FOR ALL EQUIPMENT, COORDINATE WITH ALL TRADES (ARCHITECTURAL, MECHANICAL, PLUMBING, ETC) FOR ELECTRICAL REQUIREMENTS AND
INSTALLATION LOCATIONS PRIOR TO INSTALLATION.
18. ALL LOW-VOLTAGE SYSTEM CABLING NOT RAN IN CONDUIT TO WALL MOUNTED DEVICE SHALL HAVE A MINIMUM 1"C ROUTED FROM DEVICE THROUGH WALL INTO THE ACCESSIBLE CEILING SPACE; CABLING SHALL NOT BE ROUTED IN WALLS OR IN AN INACCESSIBLE LOCATION WITHOUT
CONDUIT.
19. GFCI RECEPTACLES SHALL BE PROVIDED WITHIN 6’ OF A SINK/OR WATER SOURCE, WITHIN DAMP ROOMS, OR WHEN MOUNTED
OUTDOORS/EXTERIOR TO THE BUILDING.
20. NO STRUCTURAL MEMBERS SHALL BE CUT, DRILLED, OR NOTCHED WITHOUT PRIOR WRITTEN CONSENT FROM THE STRUCTURAL ENGINEER OR
ARCHITECT.
21. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED CEILING PLAN.
22. LIGHTING FIXTURES WITH MORE THAN TWO LAMPS SHALL HAVE TWO OUTER LAMPS CONTROLLED WITH ONE SWITCH AND INNER LAMP(S)
CONTROLLED BY A SECOND SWITCH.
23. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR SIZED PER NEC TABLE 250.122. ALL WIRING IS BASED ON Cu COPPER PER NEC TABLE
310.15(B)(16), USING 75°C AMPACITIES FOR FEEDERS.
24. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE DIVIDERS
BETWEEN DEVICES.
25. FOR EXISTING EQUIPMENT, SUCH AS LIGHTING FIXTURES, WIRING DEVICES, CONDUITS, ETC., SHOWN ON PLANS TO BE REMOVED, COMPLETELY CUT/CAP CONDUITS AT THE AREA OF WORK PERIMETER AND REMOVE CONDUIT WITHIN THE WORK AREA, DISCONNECT WIRING AT THE OVERCURRENT PROTECTIVE DEVICE AND REMOVE WIRING COMPLETELY FROM THE ABANDONED CONDUITS.
26. DISCONNECT ALL ABANDONED WIRING OF ALL TYPES AT THE OVERCURRENT PROTECTIVE DEVICE. COMPLETELY REMOVE ALL ABANDONED
WIRING.
27. MAINTAIN AND RESTORE, IF INTERRUPTED, ALL CONDUITS AND CONDUCTORS PASSING THROUGH RENOVATED AREAS AND SERVICING
UNDISTURBED AREAS.
28. EVERY DEVICE SHALL BE LABELED WITH PANEL NUMBER AND CIRCUIT NUMBER, BLACK LETTERING ON YELLOW FOR NORMAL POWER, AND BLACK
LETTERING ON RED FOR EMERGENCY POWER.
29. NO MC CABLE TO BE USED EXCEPT FOR LIGHTING FIXTURES FACTORY WIRED WITH IT.
30. WHERE FLEXIBLE CONDUIT IS PROVIDED TO BE USED, CONDUIT SHALL BE FLEXIBLE METAL CONDUIT.
31. ALL TELECOMMUNICATIONS SYSTEMS ARE DESIGNED IN ACCORDANCE WITH THE BICSI TDMM LATEST EDITION. ALL CONTRACTOR PERSONNEL WORKING ON THIS PROJECT SHALL BE TRAINED AND CERTIFIED BY THE MANUFACTURER OF THOSE PRODUCTS AND SHALL SUPPLY AS PART OF
THE SUBMITTAL PROCESS THOSE CERTIFICATIONS PRIOR TO THE START OF ANY WORK.
32. ALL CONDUIT, SLEEVES, AND PATHWAYS SHALL BE FREE OF DEBRIS OR BLOCKAGES. ALL FIELD CUT RAW EDGES SHALL BE DEBURRED BY THE INSTALLING CONTRACTOR. ALL CONDUITS THAT FEED CATEGORY 6A CABLE TO A WORK AREA OUTLET (WAO) BOX SHALL HAVE A PLASTIC
BUSHING PLACED ON THE END OF THE CONDUIT.
33. ALL TERMINATIONS, CONNECTING BLOCKS, PATCH PANELS, RACKS, GROUND BARS, AND ASSOCIATED COMMUNICATIONS EQUIPMENT SHALL BE LABELED AND RECORDED BY THE CONTRACTOR. AS BUILT DOCUMENTS SHALL BE COMPILED BY THE CONTRACTOR AND FURNISHED TO THE ENGINEER AT THE END OF THE PROJECT INDICATING THE LOCATION OF ALL INSTALLED COMPONENTS AND THE LABELING OF THOSE
COMPONENTS.
34. THE INSTALLATION OF ALL COMMUNICATIONS PATHWAYS, SLEEVES, AND CABLE TRAYS SHALL BE LAID OUT BY THE CONTRACTOR AND SUBMITTED TO THE ENGINEER FOR APPROVAL PRIOR TO ANY WORK. DRAWINGS SHALL SHOW PROPOSED ROUTES THAT WILL NOT CONFLICT
WITH OTHER TRADES SUCH AS HVAC, ELECTRICAL, AND ARCHITECTURAL.
35. CONTRACTOR SHALL PROVIDE, INSTALL, AND TERMINATE HORIZONTAL CAT6A CABLING FROM EACH WAO TO ITS RESPECTIVE TR, UNLESS
OTHERWISE NOTED.
36. UNLESS OTHERWISE INDICATED, ALL EXISTING CAMERAS AND ACCESS CONTROL PANELS SHALL BE RE-CABLED WITH (1) CAT 6A CABLE EACH.
S H E E T I N D E XG E N E R A L N O T E SA B B R E V I A T I O N S
E-001 - ABBREVIATIONS, GENERAL NOTES, AND SHEET INDEX
E-002 - ELECTRICAL LEGENDS
ED101 - BLDG 09A - LEVEL 01 - LIGHTING DEMOLITION PLAN - PHASE 1
ED102 - BLDG 09A - LEVEL 01 - POWER DEMOLITION PLAN - PHASE 1
ED103 - BLDG 09A - LEVEL 01 - SPECIAL SYSTEMS DEMOLITION PLAN - PHASE 1
EL101 - BLDG 09A - LEVEL 01 - LIGHTING PLAN - PHASE 1
EL102 - BLDG 09A - LEVEL 01 - LIGHTING PLAN - PHASE 2
EP100 - BLDG 03, 09A, AND 11 - LEVEL 00 - POWER PLAN - PHASE 1
EP101 - BLDG 09A - LEVEL 01 - POWER PLAN - PHASE 1
EP102 - BLDG 09A - LEVEL 01 - POWER PLAN - PHASE 2
ET101 - BLDG 09A - LEVEL 01 - SPECIAL SYSTEMS PLAN - PHASE 1
ET102 - BLDG 09A - LEVEL 01 - SPECIAL SYSTEMS PLAN - PHASE 2
EF101 - BLDG 09A - LEVEL 01 - FIRE ALARM SYSTEMS PLAN - PHASE 1
EF102 - BLDG 09A - LEVEL 01 - FIRE ALARM SYSTEMS PLAN - PHASE 2
E-401 - ENLARGED TR ROOM 100 ELECTRICAL PLANS
E-402 - ENLARGED TR ROOM 100 TELECOMMUNICATIONS PLANS
E-501 - ELECTRICAL DETAILS
E-502 - ELECTRICAL DETAILS
E-503 - ELECTRICAL DETAILS
E-504 - ELECTRICAL DETAILS
E-505 - ELECTRICAL DETAILS
E-506 - ELECTRICAL DETAILS
EP601 - ONE-LINE DIAGRAM - EMERGENCY POWER
EP602 - ONE-LINE DIAGRAM - NORMAL POWER
ET601 - FIBER RISER AND TELECOMMUNICATIONS BONDING DIAGRAM
E-701 - ELECTRICAL SCHEDULES
E-702 - ELECTRICAL SCHEDULES
E-703 - ELECTRICAL SCHEDULES
Revisions: Date:
CONSTRUCTION
DOCUMENTS
SECTION
SECTION LETTER
SHEET WHERE
SECTION IS TAKEN
FROM
SECTION LETTER
SHEET WHERE
SECTION IS TAKEN
FROM
DETAIL NUMBER
SHEET ON WHICH
DETAIL APPEARS
DETAIL AREA
SCALE CONDUIT & WIRE TAG
(REFER TO CONDUIT
AND WIRE SCHEDULE)
XX FAULT CURRENT TAG
(3 PH, SYM AMPS)
1 KEY NOTE
FIGURE OR PHOTO
DETAIL NUMBER
IF PHOTO, ARROW
DENOTES DIRECTION
TAKEN
SHEET WHERE DETAIL
IS TAKEN FROM
DETAIL/PLAN
DETAIL/PLAN NUMBER
XXXX
XXX
XXX
A
XXX
A
XXX
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:5
:2
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /V
A D
U
G E
N S
H E
E T
S
E L
S
D B
.r v t
E-002
ELECTRICAL LEGENDS
JPB/WNM BCL
CONSTRUCTION
DOCUMENT
06/14/2024
557-21-703RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA
G E N E R A L S Y M B O L
D I V 2 6 - L E G E N D D I V 2 7 - L E G E N D D I V 2 8 - L E G E N D
G
SWITCH, MULTIPOSITION
SWITCH, SINGLE BREAK
FUSE WITH RATING
NORMALLY CLOSED RELAY CONTACT
NORMALLY OPEN RELAY CONTACT
CIRCUIT BREAKER
DRAWOUT AIR CIRCUIT BREAKER
MOTOR, SINGLE-PHASE
MOTOR, THREE-PHASE
DELTA CONNECTION
TRANSFORMER
WYE CONNECTION
EARTH GROUND
JUNCTION BOX
PULL BOX
GENERATOR, POWER
BATTERY
CAPACITOR
RELAY; NUMBER INDICATES RELAY TYPE
50 = INSTANTANEOUS OVER CURRENT OR RATE-OF-RISE
51 = AC-TIME OVER CURRENT
67 = AC-DIRECTIONAL OVER CURRENT
86 = LOCKING OUT
DISCONNECT SWITCH, FUSED
DISCONNECT SWITCH, UNFUSED
STARTER, COMBINATION WITH DISCONNECT SWITCH
STARTER OR MOTOR CONTROLLER
METER
AMMETER
VOLTMETER
WATTMETER
WATT-HOUR METER
TRANSFORMER, PLAN
MOTOR
LADDER CABLE TRAY
PANELBOARD, FLUSH MOUNTED
PANELBOARD, SURFACE MOUNTED
RECEPTACLE, DUPLEX, 20A, 125V
RECEPTACLE, DUPLEX ON EMERGENCY POWER, 20A, 125V
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER, 20A, 125V
RECEPTACLE, QUADRUPLEX, 20A, 125V
RECEPTACLE, SINGLE, 20A, 125V
RECEPTACLE, SINGLE WITH SWITCH
RECEPTACLE, SPECIAL PURPOSE; SHADED
INDICATES EMERGENCY POWER
A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.
B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.
C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.
D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.
E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.
F = 208V, 30A, 3 PHASE, 4-POLE, 5W, NEMA L21-30R.
G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.
H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.
RECEPTACLE, SWITCHED DUPLEX
DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,
GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE
CORD (CENTER LINE OF OUTLET: 6'-6" [1981mm] AFF. MINIMUM).
ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm]
CENTERS OR AS DESIGNATED ON DRAWINGS), MTD
3'-6" [1067mm] AFF OR AS INDICATED.
F = FUSED SWITCH K = KEY OPERATED
L = LOCK LM= LOW VOLTAGE MASTER
M = MANUAL MOTOR STARTING MC= MOMENTARY CONTACT
MP= MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT
(THERMAL TYPE)
PB= PUSH BUTTON STATION RC= REMOTE CONTROL
WP= WEATHER PROOF X = EXPLOSION PROOF
SWITCH, CEILING MOUNTED PULL
SWITCH (# SUBSCRIPT AS INDICATED BELOW):
BLANK = SINGLE POLE 2 = DOUBLE POLE
3 = THREE-WAY 4 = FOUR-WAY
D = DIMMER K = KEY OPERATED
LV= LOW VOLTAGE P = WITH PILOT LIGHT
LM= LOW VOLTAGE MASTER RC= REMOTE CONTROL
PB= PUSH BUTTON STATION WP= WEATHER PROOF
T = TIMER OPERATED Mo= OCCUPANCY SENSOR
LIGHTING, ONE HEAD EMERGENCY BATTERY POWER
LIGHTING, TWO HEAD EMERGENCY BATTERY POWER
LIGHTING, THREE HEAD EMERGENCY BATTERY POWER
EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL ARROWS AND
FACES AS SHOWN
EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL ARROWS AND
FACES AS SHOWN
POWER
LIGHTING
x = LUMINAIRE SWITCH ZONE (ANY LOWER CASE LETTER APPLIES)
AUDIO DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BELL C-CHIME H-HORN K-KLAXON
L-LISTEN-IN M-MICROPHONE S-SOUNDER S-SPEAKER Z-BUZZER
BI-STATIC BEAM SENSOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
I-INFRARED M-MICROWAVE
F=FUNCTION
RX-RECEIVE TX-TRANSMIT
BIOMETRICS ACCESS CONTROL DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
F-FINGER PRINT H-HAND GEOMETRY I-EYE IRIS
R-EYE RETINA V-VOICE
CARD ACCESS READER; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BARCODE F-ELEVATOR FLOOR CALL H-ELEVATOR HALLCALL
M-MAG STRIP P-PROXIMITY S-SMART CARD
T-TOKEN
CARD READER WITH KEYPAD; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
CARD READER WITH TIME AND ATTENDANCE; LETTER INDICATES ASFOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH
H-HIDDEN M-MULLIONP-PEDESTAL R-RACK
S-SURFACE W-WALLCENTRAL PROCESSING UNIT
CONTROL PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
B-BURGLAR D-DOOR F-FIRE P-PERIMETER
ELECTRONIC LOCK; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
D-DEADBOLT H-HYBRID L-LATCH SET M-MAGNETIC S-STRIKE
EXIT DEVICE; LETTER INDICATES AS FOLLOWS:
T=TECHNOLOGY/TYPE
D-DELAYED EGRESS E-ELECTRIFIED M-MECHANICAL X-HIGH SECURITY
FIBER OPTIC MODULE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
R-RECEIVERT-TRANSCEIVER TX-TRANSMITTER
FIELD PANEL; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-ALARM C-CARD READER
GLASS BREAKAGE SENSOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
A-AUDIO S-SHOCK
INTERCOM; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
T=TECHNOLOGY/TYPE
M-MASTER S-SUBSTATION
KEYBOARD
KEYPAD DEVICE; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
MONITOR; LETTER INDICATES AS FOLLOWS:
M=MOUNT
C-CEILING D-DESK F-FLUSH H-HIDDEN M-MULLION
P-PEDESTAL R-RACK S-SURFACE W-WALL
SECURITY ACCESS, ANNUNCIATOR PANEL
SECURITY ACCESS, BUZZER. MTD 1'-6" [457mm] AFF
UNLESS OTHERWISE NOTED
SECURITY ACCESS, CONTROL UNIT WITH
CLOSED CIRCUIT TELEVISION CAMERA
SECURITY ACCESS, GENERIC "X" INDICATES THE
TYPE, PROVIDE SCHEDULE OR LEGEND
SECURITY ACCESS, HORN OR SIREN
SECURITY ACCESS, OUTDOOR MICROWAVE TRANSMISSION UNIT
SECURITY ACCESS, PANIC ALARM
SECURITY ACCESS, VIDEO CAMERA WITH LENS
M = MOTION DETECTOR
PZ = MOTION DETECTOR WITH PAN AND ZOOM
PTZ= MOTION DETECTOR WITH PAN, TILT, AND ZOOM
SECURITY ACCESS, VOLUMETRIC SENSOR
SECURITY SCREEN WITH ALARM; LETTER INDICATES ASFOLLOWS:
T=TECHNOLOGY/TYPE
B-BLIND S-SHADE
SECURITY WINDOW SCREEN; LETTER INDICATES ASFOLLOWS:
T=TECHNOLOGY/TYPE
B-BLIND
VIDEO CONTROL KEYBOARD
VIDEO MOTION DETECTOR
SECURITY ACCESS, PANNING CAMERA TRAVERSE ANGLE
C = CEILING MOUNTED
SECURITY ACCESS, SENSOR, BURIED VEHICULAR
SECURITY ACCESS, SWITCH, BALANCED MAGNETIC CONTROL
SECURITY ACCESS, TELEPHONE HANDSET
SECURITY ACCESS, VIDEO CAMERA WITH LENS, ANGLE OF VIEW
ALARM, CHECK VALVE
ALARM, FIRE, COMMUNICATOR
ALARM, FIRE, PANEL; LETTERS INDICATE AS FOLLOWS:
FACC = CENTRAL CONSOLE FACP = CONTROL PANEL
MFACP= MASTER CONTROL PANEL FAAP = ANNUNCIATORPANEL
ALARM, FIRE, MANUAL PULL STATION
ALARM, GONG
ALARM, HORN/LIGHT, ONE ASSEMBLY WITH CHIME
ALARM, HORN/LIGHT, SEPARATE ASSEMBLY
ALARM, LAMP LIGHT, SIGNAL LIGHT, STROBE
ALARM, MANUAL CONTROL
ALARM, MINI HORN
ALARM, SPRINKLER SYSTEM WATER FLOW BELL
ALARM, TAMPER SWITCH
DETECTION, SMOKE CONTROL AND PRESSURE PANEL
DETECTION SWITCH, ABORT
DETECTION SWITCH, VALVE TAMPER
DETECTOR, FLAME FLICKER
DETECTOR, FLOW SWITCH
DETECTOR, HEAT
DETECTOR, HEAT; LETTER INDICATES AS FOLLOWS:
R/T = COMBINATION F = FIXED TEMPERATURERISE
R/C = RATE COMPENSATION R = RATE OF
DETECTOR; LETTER INDICATES AS FOLLOWS:
BLANK = SMOKE DETECTOR
CODE ONE CONTROL AND ALARM STATION. MTD 5'-0"
AFF UNLESS OTHERWISE NOTED.
CODE ONE TERMINAL CABINET.
CODE ONE ANNUNCIATOR PANEL.
CODE ONE BEDSIDE STATION.
CODE ONE DUTY STATION, MTD 5'-0" AFF UNLESS
OTHERWISE NOTED.
ALARM, FIRE; LETTERS INDICATE AS FOLLOWS:
BATT =BATTERIESCHR = CHARGER FAR = RECORDER
ALARM, FIRE, VALVE SUPERVISORY SWITCH.
ALARM, FIRE, TERMINAL CABINET.
ALARM, FIRE, POST INDICATOR VALVE.
ALARM, TRANSPONDER OR TRANSMITTER
ALARM, VOICE COMMUNICATION PANEL
ALARM, HORN/LIGHT, ONE ASSEMBLY C = WITH CHIME
360°
40°
X
M PTZ
AP
NIP
NIT
NIA
NI
NID
FAC
FACP
P
C
BATT
OSY
FATC
PIV
M
TS
FTR
SCCP
HD
R/T
HD
H
PB
T
S
WB
C
S
M
T
M
F
T
M
T
T
M
M
M
M
T
T
M
T
M
T
M
T
M
T
M
M
T
T
T
CP
EPO
CONDUIT OR EQUIPMENT TO BE REMOVED
CONDUIT 3/4"C, 3#12 PHASE, 1#12 N, & 1#12 GND UNLESS
SHOWN OTHERWISE. (EXAMPLE SHOWN: TO PANEL P1,
CIRCUIT 1,3,5). LONG TICK FOR NEUTRAL WIRE; ONE SHORT
TICK FOR EACH PHASE WIRE; GROUND SIZED PER NEC. NOTE
THAT A SECOND SHORT TICK FOR LUMINAIRES IS FOR A
TRAVELER WIRE.
CONDUIT HOME RUN - SEE CONDUIT AND WIRE SCHEDULE
CONDUIT CONCEALED IN WALL, CEILING, UNDER FLOOR,
IN FLOOR SLAB, OR ROUTED UNDERGROUND
CONDUIT CONCEALED WHERE POSSIBLE, OTHERWISE
EXPOSED
EXTRA-HARD USAGE FLEXIBLE CORD
FLEXIBLE CONDUIT
CONDUIT TURNED UP OR TOWARD
CONDUIT TURNED DOWN OR AWAY
CONDUIT CAPPED
P1-1,3,5
J
M
A
V
W
WH
P
S
RECEPTACLE, DUPLEX FLOOR MOUNTED
PE
DS
X
X
X
ALL INTERIOR AREAS TO HAVE MANUAL "ON"/AUTO OFF LIGHTING
CONTROL WITH THE USE OF DUAL TECHNOLOGY OCCUPANCY
SENSORS. EXCEPT WHERE A WALL SWITCH OCCUPANCY SENSOR
IS NOTED.
PHOTO ELECTRIC SENSOR
DAYLIGHT SENSOR FOR DAYLIGHT HARVESTING CONTROL. SENSOR
SHALL BE CEILING MOUNTED.
LIGHT TRACK WITH HEADS AS SHOWN
LIGHT FIXTURE, BOLLARD
OS
J
EXIT SIGN, ABOVE DOOR, CEILING MOUNTED
RECEPTACLE, DUPLEX CEILING MOUNTEDC
PP
X
POWER PACK FOR COMPLEX LIGHTING CONTROL. "X" DENOTES THE
LIGHTING ZONE.
METERING POINT##
OUTLET, COMBINATION TELEPHONE/DATA COMMUNICATION
CABLE TELEVISION LINE = CATV
CLOSED CIRCUIT TELEVISION LINE = CCTV. MINIMUM 1" [25mm] CONDUIT
FIBEROPTICS LINE = FO
SPEAKER, CEILING MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE ON
LEGEND.
SPEAKER, WALL MOUNTED, "X" INDICATES THE TYPE, PROVIDE SCHEDULE
ON LEGEND. MTD. 7'-6" [2286mm] AFF UNLESS OTHERWISE NOTED.
OUTLET DATA OR TELEPHONE, "X" INDICATES NUMBER OF OUTLET PORTS. BOX
AROUND SYMBOL INDICATES FLOOR MOUNTED.
P = POLE/PEDESTAL MOUNTED
TELEPHONE LINE = T
INTERCOM LINE = I. MINIMUM 3/4" [19mm] CONDUIT.
SOUND LINE = S
NURSE CALL LINE = NC. MINIMUM 3/4" [19mm] CONDUIT.
OUTLET; LETTER INDICATES AS FOLLOWS:
A = AUDIO V = VIDEO I = INTERCOM
RADIO CONDUIT RUN, MINIMUM 3/4" [19mm] CONDUIT.
RADIO CHANNEL SELECTOR FACILITIES, MTD. 4'-6" [1372mm] AFF UNLESS
OTHERWISE NOTED.
SPEAKER PROGRAM SELECTOR SWITCH & VOLUME
CONTROL MTD. 4'-6" [1372mm] AFF UNLESS OTHERWISE NOTED.
OUTLET, TELEVISION
BLANK = 4 11/16" [119mm] MASTER ANTENNA OUTLET BOX W/BLANK
COVER, MTD. 18" [457mm] AFF UNLESS OTHERWISE NOTED.
C = CAMERA (CCTV SYSTEM), MTD 18" [457mm] AFF
M = MONITOR (CTTV SYSTEM).
NURSE'S CALL MASTER STATION MTD ON
NURSE'S COUNTER TOP UNLESS OTHERWISE NOTED.
NURSE CALL TERMINAL CABINET.
NURSE CALL STATION.
2 = DUPLICATE FACILITIES FOR TWO BEDS (SEPARATE INDICATORS AT MASTER
STATION) MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.
D = DUTY STATION. MTD 5'-0" [1524mm] AFF UNLESS NOTED OTHERWISE.
E = MTD 6'-0" [1829mm] AFF FOR SHOWER LOCATION, MTD 4'-6" [1372mm] AFF FOR TUB LOCATION, & MTD 3'-0" [914mm] AFF FOR TOILET LOCATION.
P = PSYCHIATRIC CORRIDOR STATION WITH KEY SWITCH
S = AUDIO VISUAL MALL STATION (STAFF) MTD 5'-0" [1524mm] AFF UNLESS
OTHERWISE NOTED
U = UTILITY CALL STATION, MTD 5'-0" [1524mm] AFF UNLESS OTHERWISE NOTED.
NURSE CALL STATION.
2 = NURSE'S CALL DOME LIGHT (SUFFIX INDICATES No OF
LAMP) MTD 6" [152mm] ABOVE DOOR.
D = CORRIDOR DOME LIGHT.
I = AUXILIARY INTERSECTIONAL DOME LIGHT.
TELEPHONE TERMINAL CABINET
TELEPHONE BACKBOARD (WALLMOUNTED)
3-POLE TWIST-LOCK RECEPTACLE FOR MICROPHONE, MTD. 4'-6" 1372mm]
AFF.
REMOTE DICTATING OUTLET MTD 1'-6" [457mm] AFF. UNLESS OTHERWISE NOTED.
INTERCOM STATION (REFER TO SPECS. FOR FUNCTIONAL
OPERATION OF INSTRUMENT & TYPE REQUIRED).
INTERCOM STAFF STATION.
TELECOMMUNICATIONS MANHOLE
DATA/COMMUNICATION
N X
TTB
A
S X
S X
X
N X
R M
C
R
R M
NCS
NCT
S
CATV
CCTV
FO
T
I
S
NC
R
= 3 - FUNCTION EMERGENCY STATION; FUNCTIONS SHALL INCLUDE "STAFF
EMERGENCY", "CODE BLUE", AND "CANCEL". MTD 5'-0" AFF.
WIRELESS ACCESS POINT.
"S" = STAFF; "G" = GUEST. IF NOTED LIKE THIS "S,G", CONTRACTOR SHALL PROVIDE
(2) SEPARATE WAPs, (1) WAP FOR EACH SERVICE.
X X
XWAP
1 = SINGLE PATIENT STATION. MTD 4'-0" AFF UNLESS OTHERWISE NOTED.
P
WIRELESS TRACKING MODULE, IR TECHNOLOGY
VW - INDICATES VIRTUAL WALL TYPE.
WT
VW
OUTLET TELEPHONE; "X" INDICATES NUMBER OF OUTLET PORTS. "Y" INDICATES AS
FOLLOWS:
BLANK=EXISTING CONDUIT WITH NEW CAT6A CABLE
P=POLE/ PEDESTAL MOUNTED
F=FURNITURE MOUNTED
C=OUTLET WITH NEW CONDUIT INSTALLED, 3/4" MINIMUM UNLESS OTHERWISE
STATED "Z" INDICATES AS FOLLOWS:
J = JACK TYPE W = WALL TYPE A = ANALOG PORT
Z Y
X
P/D POWER/DATA POLE
HARDWIRED
H =HDMI
C
EMERGENCY NORMAL
X X
X X
X X
X X
X X
X X
XX
X X
X X
X X
X X
X X
X X
X X
X X
X X
X X
X = DENOTES LUMINAIRE TAG NAME
RECESSED DOWNLIGHT
FIXTURE
LIGHT FIXTURE, RECESSED, 2'x4'
LIGHT FIXTURE, RECESSED,1'x4'
LIGHT FIXTURE, RECESSED, 1'x8'
LIGHT FIXTURE, RECESSED, 2'x2'
LIGHT FIXTURE, SURFACE MOUNTED, 2'x4'
LIGHT FIXTURE, SURFACE MOUNTED, 1'x4'
LIGHT FIXTURE, SURFACE MOUNTED, 1'x8'
LIGHT FIXTURE, SURFACE MOUNTED, 2'x2'
STRIP LIGHTING, 4' LONG
LIGHT FIXTURE, WALL MOUNTED
STREET LIGHT WITH BRACKET
LIGHT POLE, ONE LUMINAIRE
LIGHT POLE, TWO LUMINAIRES
LIGHT POLE, POST TOP MOUNT LUMINAIRE
LIGHTING WALL PACK, EXTERIOR BUILDING
CIRCUITING DESIGNATIONS
WHERE A PANEL NAME AND CORRESPONDING CIRCUIT ARE CALLED OUT ADJACENT TO A RECEPTACLE, LUMINAIRE, OR MISC LOAD, THAT LOAD SHALL BE CIRCUITED TO THE CORRESPONDING PANELBOARD CIRCUIT BREAKER. CONDUIT AND WIRE FOR CIRCUIT SHALL BE 3/4" CONDUIT WITH (2) 12 AWG AND (1) 12 AWG GND, UNLESS OTHERWISE NOTED; IF FURTHER THAN 70', PHASE AND GROUND WIRE SHALL BE UPSIZED TO 10 AWG TO ACCOUNT FOR VOLTAGE DROP.
SEE EXAMPLES BELOW:
RECEPTACLE:
PANELBOARD OR POWER SOURCE NAME = "P1"
CIRCUIT NUMBER OF POWER SOURCE = "2"
LUMINAIRE:
PANELBOARD OR POWER SOURCE NAME = "PP3"
CIRCUIT NUMBER OF POWER SOURCE = "4"
TYP LUMINIARE TAG NAME, REFERENCE LUMINAIRE SCHEDULE = "L1"
LIGHTING CONTROL SWITCH LEG = "a"
ALL LUMINAIRES IN SAME ROOM ARE CIRCUITED TO SAME CIRCUIT = PP3-4
ALL LUMINAIRES WITHIN DASHED BOX ARE CIRCUITED TO SAME CIRCUIT = PP3-4
MISC LOAD:
PANELBOARD OR POWER SOURCE NAME = "PP"
CIRCUIT NUMBER OF POWER SOURCE = "7"
P1-2 P1-2
HEAT PUMP
PP-7
L1 a
PP3-4
FACP
PP-7
XXXX
Revisions: Date:
L1 a
L1 a
PP3-4
DETECTOR, SMOKE, FOR DUCT
AREA OF WORK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64
17 18 19 20 21 25 26 27 28 29 30 31 32
E-401
HOUSEKEEPING
AID CLOSET
BLDG 09A
BLDG 03BLDG 11
PROSTHETICS
STOR
VERTICAL
SPACE CHASE
RCC103C
PROSTHETICS
WRK RM
PROSTHETICS
STOR
PROSTHETICS
PURCHASING
AGENT OFF
PROSTHETICS
PURCHASING
AGENT SUPV
PROSTHETICS
STOR
VERTICAL
SPACE PIPE
CHASE
RCC101C
PROSTHETICS
PIPE CLO
RCC101R
COMMON
MECH RM
PROSTHETICS
PGM ANALYST
NETWRK
EMPLOYEE
VERTICAL
SPACE PIPE
CHASE
RCC104C
COMMON TLT
PROSTHETICS
FILE RM
129A
VERTICAL
SPACE PIPE
CHASE
RCC105C
COMMON
FEMALE TLT
VERTICAL
SPACE PIPE
CHASE
RCC106C
GERIATRICS
COMM / NH
NRS GE AND C
OFF
GERIATRICS
PIPE CLO
131A
GERIATRICS
BRK RM
COMMON
CORR
CR15-9
GERIATRICS
SPECIAL
PGMS
CO-ORDER SCI
/ TBI / VISIT
OFF
GERIATRICS
SOC WRK
SUPV COMM
CARE PGMS
OFF
GERIATRICS
RECREATION
OFF
GERIATRICS G
AND EC PHY
GERIATRICS
EXTENDED
CARE OFF
GERIATRICS
ACOS AND
EXTENDED
CARE OFF
GERIATRICS
CLO
137B
GERIATRICS
TLT
137A
COMMON
MALE TLT
COMMON TEL
CLO
GERIATRICS
SOC WRK
EXTERNAL
CARE
VERTICAL
SPACE CHASE
RCC102C
GERIATRICS
MULTIPURPOSE
RM
GERIATRICS
STOR
COMMON FEC
142A
VERTICAL
SPACE ELEV
RCC102R
COMMON
VEST
ENVIR MGMT
HAC CLO
CANTEEN SVC
VENDING
AREA
ENGINEERING
MECH RM
NUTRITION/FOOD
DIETICIAN OFF
GERIATRICS
FEMALE TLT
GERIATRICS
OFF
GERIATRICS G
AND EC PSA
GERIATRICS
DIETICIAN AND
EXTENDED
CARE OFF
GERIATRICS
DIETICIAN AND
EXTENDED
CARE OFF
NUTRITION/FOOD
DIETICIAN OFF
GERIATRICS
OFF
GERIATRICS
COMM HEALTH
NRS CO-ORDR
COMMON
CORR
CR13-9
PROSTHETICS
OFF
PROSTHETICS
OFF
COMMON
CORR
CR12-9
PROSTHETICS
RECEPTION
AND WAIT
PROSTHETICS
PGM MGR
PROSTHETIC
PROSTHETICS
PURCHASING
116A
PROSTHETICS
CORR
CR14-9
PROSTHETICS
PURCHASING
116B
COMMON FEC
121A
VERTICAL
SPACE STAIR
ST11-9
COMMON
CORR
CR11-9
VERTICAL
SPACE CHASE
RCC107C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:5
:0
P
M
A u to d e s k D o c s /5
-2
-7
V A
G A
D u b lin
E H
R M
T A
S S
/V A
D U
C
E N
T R
A L
E
L
S D
B .r v t
ED101
09A
JPB/WNM BCL
CONSTRUCTION
DOCUMENTS
06/14/2024
557-21-703RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA
BLDG 09A - LEVEL 01 - LIGHTING
DEMOLITION PLAN - PHASE 1
KEY PLAN
GENERAL NOTES
TRUE
NORTH
KEY NOTES
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN. CONTRACTOR SHALL FIELD VERIFY
ALL LIGHTING, CONTROLS, AND ASSOCIATED CIRCUITRY AS REQUIRED. ALL
RACEWAYS AND CONDUCTORS ASSOCIATED WITH DEMOLISHED EQUIPMENT SHALL
BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE NOTED.
2. ALL DEMOLITION OF ELECTRICAL SYSTEMS SHALL BE CLOSELY COORDINATED WITH
THE CONTRACTORS PHASING OF THE PROJECT. VERIFY DEMOLITION OF ELECTRICAL
WITH ALL TRADES PRIOR TO START OF DEMOLITION.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. ALL CIRCUITS AND RELATED DEVICES THAT ARE TO REMAIN ARE TO STAY
"ENERGIZED" IN THE DEMOLITION AND NEW CONSTRUCTION PHASES UNTIL THE
COMPLETION OF THE WORK INDICATED ON THESE PLANS.
5. THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL ASSOCIATED WITH WALLS BEING
REMOVED, AND IN ALL LOCATIONS WHERE JUNCTION BOXES WILL NOT REMAIN
ACCESSIBLE AFTER INSTALLATION OF MILLWORK.
6. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF DEVICES
SHALL COMPLY WITH ALL APPROPRIATE CODES. REUSE EXISTING CONDUITS AND
JUNCTION BOXES AS IS PRACTICAL.
7. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL
PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. CONTRACTOR SHALL ENSURE ALL EQUIPMENT INCLUDING, BUT NOT LIMITED TO
LIGHT BALLASTS THAT CONTAIN PCBs, SHALL BE PROPERLY REMOVED AND
DISPOSED.
- 1" = 10'-0"
1 BLDG 09A - LEVEL 01 - LIGHTING DEMOLITION PLAN - PHASE 1 0 10' 20'
PROJECT
NORTH
TRUE NORTH
(DASHED)
EXISTING LIGHTING AND CONTROLS TO BE DEMOLISHED. ALL ASSOCIATED CONDUIT
AND WIRING SHALL BE DEMOLISHED BACK TO SOURCE.
PANELBOARD AND CIRCUIT FEEDING EXISTING FIXTURE AT THIS LOCATION IS
UNKNOWN. TRACE CIRCUIT TO ORIGIN AND MAINTAIN CONTINUITY TO FIXTURE.
LUMINARIE FUNCTIONALITY SHALL BE MAINTAINED.
EXISTING TOGGLE LIGHT SWITCH TO BE DEMOLISHED AND REPLACED WITH WALL
MOUNTED OCCUPANCY SWITCH. REFERENCE SHEET EL101 FOR ADDITIONAL
INFORMATION.
Revisions: Date:
AREA OF WORK
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64
17 18 19 20 21 25 26 27 28 29 30 31 32
57PANEL '9LNA3'
PANEL '9LNA4'
TYP.
E-401
FA EQUIPMENT
FACP BATTERY
BOX (BELOW)
PANEL '9LCA1'
PANEL '9LNA1'
PANEL '9LNA2'
PULL BOX
PULL BOX
POWER SUPPLY EXPANDER
FACP (ABOVE)
HOUSEKEEPING
AID CLOSET
PROSTHETICS
STOR
VERTICAL
SPACE CHASE
RCC103C
PROSTHETICS
WRK RM
PROSTHETICS
STOR
PROSTHETICS
PURCHASING
AGENT OFF
PROSTHETICS
PURCHASING
AGENT SUPV
PROSTHETICS
STOR
VERTICAL
SPACE PIPE
CHASE
RCC101C
PROSTHETICS
PIPE CLO
RCC101R
COMMON
MECH RM
PROSTHETICS
PGM ANALYST
NETWRK
EMPLOYEE
VERTICAL
SPACE PIPE
CHASE
RCC104C
COMMON TLT
PROSTHETICS
FILE RM
129A
VERTICAL
SPACE PIPE
CHASE
RCC105C
COMMON
FEMALE TLT
VERTICAL
SPACE PIPE
CHASE
RCC106C
GERIATRICS
COMM / NH
NRS GE AND C
OFF
GERIATRICS
PIPE CLO
131A
GERIATRICS
BRK RM
COMMON
CORR
CR15-9
GERIATRICS
SPECIAL
PGMS
CO-ORDER SCI
/ TBI / VISIT
OFF
GERIATRICS
SOC WRK
SUPV COMM
CARE PGMS
OFF
GERIATRICS
RECREATION
OFF
GERIATRICS G
AND EC PHY
GERIATRICS
EXTENDED
CARE OFF
GERIATRICS
ACOS AND
EXTENDED
CARE OFF
GERIATRICS
CLO
137B
GERIATRICS
TLT
137A
COMMON
MALE TLT
COMMON TEL
CLO
GERIATRICS
SOC WRK
EXTERNAL
CARE
VERTICAL
SPACE CHASE
RCC102C
GERIATRICS
MULTIPURPOSE
RM
GERIATRICS
STOR
COMMON FEC
142A
VERTICAL
SPACE ELEV
RCC102R
COMMON
VEST
ENVIR MGMT
HAC CLO
CANTEEN SVC
VENDING
AREA
ENGINEERING
MECH RM
NUTRITION/FOOD
DIETICIAN OFF
GERIATRICS
FEMALE TLT
GERIATRICS
OFF
GERIATRICS G
AND EC PSA
GERIATRICS
DIETICIAN AND
EXTENDED
CARE OFF
GERIATRICS
DIETICIAN AND
EXTENDED
CARE OFF
NUTRITION/FOOD
DIETICIAN OFF
GERIATRICS
OFF
GERIATRICS
COMM HEALTH
NRS CO-ORDR
COMMON
CORR
CR13-9
PROSTHETICS
OFF
PROSTHETICS
OFF
COMMON
CORR
CR12-9
PROSTHETICS
RECEPTION
AND WAIT
PROSTHETICS
PGM MGR
PROSTHETIC
PROSTHETICS
PURCHASING
116A
PROSTHETICS
CORR
CR14-9
PROSTHETICS
PURCHASING
116B
COMMON FEC
121A
VERTICAL
SPACE STAIR
ST11-9
COMMON
CORR
CR11-9
VERTICAL
SPACE CHASE
RCC107C
BLDG 09A
BLDG 03BLDG 11
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:5
:1
P
M
A u to d e s k D o c s /5
-2
-7
V A
G A
D u b lin
E H
R M
T A
S S
/V A
D U
C
E N
T R
A L
E
L
S D
B .r v t
ED102
09A
JPB/WNM BCL
CONSTRUCTION
DOCUMENTS
06/14/2024
557-21-703RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA
BLDG 09A - LEVEL 01 - POWER
DEMOLITION PLAN - PHASE 1
KEY PLAN
GENERAL NOTES
TRUE
NORTH
- 1" = 10'-0"
1 BLDG 09A - LEVEL 01 - POWER DEMOLITION PLAN - PHASE 1
WHERE WALL IS BEING DEMOLISHED, DEMOLISH EXISTING DEVICES,
CONDUCTORS, AND RACEWAYS WITHIN WALL BACK TO SOURCE.
EXISTING ELECTRICAL EQUIPMENT WITHIN TR TO BE DEMOLISHED; ASSOCIATED
CONDUIT AND WIRE TO BE DEMOLISHED BACK TO SOURCE. ALL TR DATA RACK
RELATED EQUIPMENT SHALL BE SALVAGED TO VA.
EXISTING EQUIPMENT TO BE RELOCATED. ALL EXISTING RACEWAYS AND
CABLING SHALL EXTEND TO REVISED LOCATION AS REQUIRED.
EXISTING EQUIPMENT TO BE DEMOLISHED. ALL ELECTRICAL CONDUCTORS AND
RACEWAYS SHALL BE DEMOLISHED BACK TO SOURCE. REFERENCE MECHANICAL
AND PLUMBING DRAWINGS FOR ALL EQUIPMENT TO BE DEMOLISHED.
EXISTING TELECOMMUNICATIONS BONDING BACKBONE TO BE DEMOLISHED.
PRESERVE CONTINUITY OUTSIDE OF DEMOLITION AREA. PREPARE CONNECTIONS
TO BE EXTENDED TO NEW TR LOCATION.
EXISTING PANEL TO BE RELOCATED. REFERENCE SHEET EP101 AND ONE-LINE
DIAGRAMS ON SHEET EP602 FOR ADDITIONAL INFORMATION.
EXISTING PANELBOARD TO BE DEMOLISHED. REFERENCE SHEET EP101 AND ONE-
LINE DIAGRAMS ON SHEET EP602 FOR ADDITIONAL INFORMATION.
Revisions: Date:
0 10' 20'
PROJECT
NORTH
TRUE NORTH
(DASHED)
KEY NOTES
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN. CONTRACTOR SHALL FIELD VERIFY
ALL ELECTRICAL, LOW VOLTAGE DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH DEMOLISHED
EQUIPMENT SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. ALL DEMOLITION OF ELECTRICAL AND TELECOMMUNICATIONS SYSTEMS SHALL BE
CLOSELY COORDINATED WITH THE CONTRACTORS PHASING OF THE PROJECT.
VERIFY DEMOLITION OF ELECTRICAL WITH ALL TRADES PRIOR TO START OF
DEMOLITION.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. ALL CIRCUITS AND RELATED DEVICES THAT ARE TO REMAIN SHALL STAY
"ENERGIZED" IN THE DEMOLITION AND NEW CONSTRUCTION PHASES UNTIL
COMPLETION OF WORK INDICATED ON THESE PLANS.
5. THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL AND TELECOMMUNICATIONS
EQUIPMENT ASSOCIATED WITH WALLS BEING REMOVED, AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK.
6. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF DEVICES
SHALL COMPLY WITH ALL APPROPRIATE CODES. REUSE EXISTING CONDUITS AND
JUNCTION BOXES AS IS PRACTICAL.
7. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT DIRECTORIES FOR ALL
EQUIPMENT THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. REMOVED ALL ABANDONED WIRING AND RACEWAYS TO SOURCE.COORDINATE WITH
COR FOR REMOVING EXISTING TERMINATION.
S
W
2 2 2
FS
S
W
S
W
S
W
S
W
S
W
FS
W
S
WAP
WAP
S
W
WAP
WT
WTWTWT
WT
360°
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
C
S
2 2
2 2
WAP
WAP
WAP
WAP WAP
WAP
AREA OF WORK
BLDG 09A
BLDG 03BLDG 11
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64
17 18 19 20 21 25 26 27 28 29 30 31 32
FA EQUIPMENT
FACP BATTERY
BOX (BELOW)
PANEL '9LCA1'
PANEL '9LNA1'
PANEL '9LNA2'
FACP (ABOVE)
PULL BOX
PULL BOX
POWER SUPPLY EXPANDER
PANEL '9LNA3'
PANEL '9LNA4'
TYP.
TYP.
TYP.
TYP.
E-402
E-402
HOUSEKEEPING
AID CLOSET
TYP.
TYP.
PROSTHETICS
STOR
VERTICAL
SPACE CHASE
RCC103C
PROSTHETICS
WRK RM
PROSTHETICS
STOR
PROSTHETICS
PURCHASING
AGENT OFF
PROSTHETICS
PURCHASING
AGENT SUPV
PROSTHETICS
STOR
VERTICAL
SPACE PIPE
CHASE
RCC101C
PROSTHETICS
PIPE CLO
RCC101R
COMMON
MECH RM
PROSTHETICS
PGM ANALYST
NETWRK
EMPLOYEE
VERTICAL
SPACE PIPE
CHASE
RCC104C
COMMON TLT
PROSTHETICS
FILE RM
129A
VERTICAL
SPACE PIPE
CHASE
RCC105C
COMMON
FEMALE TLT
VERTICAL
SPACE PIPE
CHASE
RCC106C
GERIATRICS
COMM / NH
NRS GE AND C
OFF
GERIATRICS
PIPE CLO
131A
GERIATRICS
BRK RM
COMMON
CORR
CR15-9
GERIATRICS
SPECIAL
PGMS
CO-ORDER SCI
/ TBI / VISIT
OFF
GERIATRICS
SOC WRK
SUPV COMM
CARE PGMS
OFF
GERIATRICS
RECREATION
OFF
GERIATRICS G
AND EC PHY
GERIATRICS
EXTENDED
CARE OFF
GERIATRICS
ACOS AND
EXTENDED
CARE OFF
GERIATRICS
CLO
137B
GERIATRICS
TLT
137A
COMMON
MALE TLT
COMMON TEL
CLO
GERIATRICS
SOC WRK
EXTERNAL
CARE
VERTICAL
SPACE CHASE
RCC102C
GERIATRICS
MULTIPURPOSE
RM
GERIATRICS
STOR
COMMON FEC
142A
VERTICAL
SPACE ELEV
RCC102R
COMMON
VEST
ENVIR MGMT
HAC CLO
CANTEEN SVC
VENDING
AREA
ENGINEERING
MECH RM
NUTRITION/FOOD
DIETICIAN OFF
104GERIATRICS
FEMALE TLT
GERIATRICS
OFF
GERIATRICS G
AND EC PSA
GERIATRICS
DIETICIAN AND
EXTENDED
CARE OFF
GERIATRICS
DIETICIAN AND
EXTENDED
CARE OFF
NUTRITION/FOOD
DIETICIAN OFF
GERIATRICS
OFF
GERIATRICS
COMM HEALTH
NRS CO-ORDR
COMMON
CORR
CR13-9
PROSTHETICS
OFF
PROSTHETICS
OFF
COMMON
CORR
CR12-9
PROSTHETICS
RECEPTION
AND WAIT
PROSTHETICS
PGM MGR
PROSTHETIC
PROSTHETICS
PURCHASING
116A
PROSTHETICS
CORR
CR14-9
PROSTHETICS
PURCHASING
116B
COMMON FEC
121A
VERTICAL
SPACE STAIR
ST11-9
COMMON
CORR
CR11-9
VERTICAL
SPACE CHASE
RCC107C
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:5
:1
P
M
A u to d e s k D o c s /5
-2
-7
V A
G A
D u b lin
E H
R M
T A
S S
/V A
D U
C
E N
T R
A L
E
L
S D
B .r v t
ED103
09A
JPB/WNM BCL
CONSTRUCTION
DOCUMENTS
06/14/2024
557-21-703RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA
BLDG 09A - LEVEL 01 - SPECIAL SYSTEMS
DEMOLITION PLAN - PHASE 1
KEY PLAN
GENERAL NOTES
TRUE
NORTH
KEY NOTES
- 1" = 10'-0"
1 BLDG 09A - LEVEL 01 - SPECIAL SYSTEMS DEMOLITION PLAN - PHASE 1 0 10' 20'
PROJECT
NORTH
TRUE NORTH
(DASHED)
WHERE WALL IS BEING DEMOLISHED, DEMOLISH EXISTING DEVICES, CABLING,
AND RACEWAYS WITHIN WALL BACK TO SOURCE.
EXISTING DATA CABLING AND RACEWAYS ASSOCIATED WITH WAOs BEING
DEMOLISHED SHALL BE REMOVED IN ITS ENTIRETY. ALL TR DATA RACK RELATED
EQUIPMENT SHALL BE SALVAGED TO VA.
EXISTING WORK AREA OUTLET (WAO) TO BE RE-CABLED WITH CAT 6A.
REFERENCE SHEET ET101 FOR ADDITIONAL INFORMATION. FIELD VERIFY EXACT
OUTLET PLACEMENT.
EXISTING FIRE ALARM FIELD DEVICES SHALL BE SALVAGED TO VA. ASSOCIATED
CONDUIT AND WIRE SHALL BE DEMOLISHED BACK TO SOURCE.
EXISTING SPEAKERS TO BE SALVAGED TO VA. ASSOCIATED CONDUIT AND
CABLING SHALL BE DEMOLISHED BACK TO SOURCE.
EQUIPMENT TO BE RELOCATED. REFERENCE SHEET EF101 FOR LOCATIONS.
EXISTING FIBER-OPTIC CABLING SERVING TR SHALL BE PRESERVED AND
PROTECTED TO SERVE NEW TR. REFERENCE SHEET ET101 FOR ADDITIONAL
INFORMATION.
PRESERVE AND PROTECT EXISTING WIRELESS ACCESS POINTS (WAPs).
Revisions: Date:
1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN. CONTRACTOR SHALL FIELD VERIFY
ALL ELECTRICAL, LOW VOLTAGE DEVICES AND ASSOCIATED CIRCUITRY AS
REQUIRED. ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH DEMOLISHED
EQUIPMENT SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE
NOTED.
2. ALL DEMOLITION OF ELECTRICAL AND TELECOMMUNICATIONS SYSTEM SHALL BE
CLOSELY COORDINATED WITH THE CONTRACTORS PHASING OF THE PROJECT.
VERIFY DEMOLITION OF ELECTRICAL WITH ALL TRADES PRIOR TO START OF
DEMOLITION.
3. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY
DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES, AND THE LIKE, SHALL BE
REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE
ACCEPTANCE OF THE OWNER.
4. ALL CIRCUITS AND RELATED DEVICES THAT ARE TO REMAIN SHALL STAY
"ENERGIZED" IN DEMOLITION AND NEW CONSTRUCTION PHASES UNTIL COMPLETION
OF WORK INDICATED ON THESE PLANS.
5. THE CONTRACTOR SHALL REMOVE ALL ELECTRICAL AND TELECOMMUNICATIONS
EQUIPMENT ASSOCIATED WITH WALLS BEING REMOVED, AND IN ALL LOCATIONS
WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF
MILLWORK.
6. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF DEVICES
SHALL COMPLY WITH ALL APPROPRIATE CODES. REUSE EXISTING CONDUITS AND
JUNCTION BOXES AS IS PRACTICAL.
7. THE CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT DIRECTORIES FOR ALL
EQUIPMENT THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.
8. REMOVE ALL ABANDONED WIRING AND RACEWAYS TO SOURCE. COORDINATE WITH
COR FOR REMOVING EXISTING TERMINATION.