S02-RFP Attachment 18-Drawings-Dublin_Part9.pdf

PDF 2 MB Posted

Attached to
Y1DZ--Renovate Building 9A for EHRM Administration- EHRM Project 557-21-703 Carl Vinson VA Medical Center Dublin, GA 31021
Solicitation number
36C77626R0031_1
Issued by

About this file

These are construction documents for the renovation of Building 9A at Carl Vinson VA Medical Center in Dublin, Georgia, prepared by SPEES Design Build. The project (557-21-703) involves renovating administrative space for the EHRM (Electronic Health Records Management) program across two construction phases. The documents include electrical power plans, special systems plans, fire alarm systems plans, and telecommunications plans for Building 9A Level 01. Key electrical infrastructure includes relocated panels (9LNA1, 9LNA2, 9LCA2, 9LNA3, 9LNA4, 9LNA6, 9LCA1), pull boxes, a power supply expander, and FA equipment. The facility is fully sprinklered and contains multiple rooms including classrooms, restrooms, break areas, a telecommunications room (TR 100), and an electrical room (116).

The special systems and telecommunications work encompasses installation of Category 6A cabling, work area outlets (WAOs), wireless access points (WAPs), fiber-optic cabling, cable tray systems, and data racks within the telecommunications room. The fire alarm systems plan depicts fire alarm device locations throughout the building connected to fire alarm panels in Room 116. Detailed notes address conduit sizing per ANSI/TIA-569 standards, segregation of data cabling from other building systems, fire-stopping requirements, pull box installation at 100-foot intervals, and coordination with architectural extendable walls. The construction documents are dated June 14, 2024, and are prepared at 1" = 10'-0" scale with multiple cross-referenced sheets for demolition, revised layouts, overhead plans, and telecommunications details.

View the file

Other files

File Type Posted
S05-Tech Questions w responses-Amendment 0006-Dublin.pdf PDF
S06- Addendum 2-Dublin - Specifications.pdf PDF
S06-Amendment 0006 SF 30-Dublin.pdf PDF
S06-Amendment 0005-SF30-Dublin.pdf PDF
S06-Amendment 0004-Addendum-1-Specifications.pdf PDF
S06-Amendment 0004-Addendum-1-Drawings.pdf PDF
S06 - Amendment 0004-Additional Technical Responses -Dublin.pdf PDF
S06-Amendment 0004-SF30.pdf PDF
S06- Amendment 0004-Technical Responses - Dublin.pdf PDF
S06-Amendment 0004- Addendum 1 - Hazardous Materials Survey.pdf PDF
S06-Amendment 0003-due date ext-Dub.pdf PDF
S04-Site Visit Sign In Sheet-Dublin.pdf PDF
S06-36C77626R0031-Amendment 0002.pdf PDF
S06-36C77626R0031-Amendment 0001.pdf PDF
S02-RFP Attachment 24-Specifications- Part 2 of 5 - Section 09 06 00.pdf PDF
S02-RFP Attachment 5- Specifications part 1 of 5.pdf PDF
S02-RFP Attachment 7- Specifications part 3 of 5.pdf PDF
S02-RFP Attachment 15-Drawings-Dublin_Part6.pdf PDF
S02-RFP Attachment 21-Drawings-Dublin_Part12.pdf PDF
S02-RFP Attachment 22-Drawings-Dublin_Part13.pdf PDF
S02 - RFP Attachment 3 - Limitations on Subcontracting - Dublin.docx DOCX document
S02-RFP Attachment 9- Specifications part 5 of 5.pdf PDF
S02-RFP Attachment 12-Drawings-Dublin_Part3.pdf PDF
S02-RFP Attachment 14-Drawings-Dublin_Part5.pdf PDF
S02-RFP Attachment 17-Drawings-Dublin_Part8.pdf PDF
S02-RFP Attachment 20-Drawings-Dublin_Part11.pdf PDF
S02-RFP Attachment 2 Site Visit Information-Dublin.docx DOCX document
S02-RFP Attachment 4 Campus Map-Dublin.pdf PDF
S02-RFP Attachment 8- Specifications part 4 of 5.pdf PDF
S02-RFP Attachment 10- Drawings-Dublin_Part1.pdf PDF
S02-RFP Attachment 11-Drawings-Dublin_Part2.pdf PDF
S02-RFP Attachment 23-Drawings-Dublin_Part14.pdf PDF
S02-36C77626R0031_1-final.pdf PDF
S02-RFP Attachment 1 DBA Rates-Laurens County-Dublin.pdf PDF
S02-RFP Attachment 6- Specifications part 2 of 5.pdf PDF
S02-RFP Attachment 13-Drawings-Dublin_Part4.pdf PDF
S02-RFP Attachment 16-Drawings-Dublin_Part7.pdf PDF
S02-RFP Attachment 19-Drawings-Dublin_Part10.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AREA OF WORK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64

17 18 19 20 21 25 26 27 28 29 30 31 32

ELECTRICAL

MECH

CHANGE MGMT USER

RESTROOM

TR ROOM

HAC

CLASSROOM

103A

CLASSROOM

103B

CLASSROOM

104A

CLASSROOM

106A

CLASSROOM

106B

STAFF BREAK

RESTROOM

RESTROOM

RESTROOM

STORAGE

CORRIDOR

CR11-9

FA EQUIPMENT

PANEL '9LCA1'

PANEL '9LNA1'

PULL BOX

PULL BOX

POWER SUPPLY EXPANDER

PANEL '9LNA2'

FACP (ABOVE)

FACP BATTERY BOX (BELOW)

1 1

P-418

P-103

P-418

P-103 P-418

P-103

PANEL '9LNC1'

CLASSROOM

104B

MECHANICAL

102A

PNL '9LCA2'

PNL '9LNA6'

PNL '9LNA4'

PNL '9LNA3'

BLDG 09A

BLDG 03BLDG 11

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:1

P

M

A u to d e s k D o c s /5

-2

-7

V A

G A

D u b lin

E H

R M

T A

S S

/V A

D U

C

E N

T R

A L

E

L

S D

B .r v t

EP102

BLDG 09A - LEVEL 01 - POWER

PLAN - PHASE 2 09A

JPB/WNM BCL

CONSTRUCTION

DOCUMENTS

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

KEY PLAN

GENERAL NOTES

TRUE

NORTH

KEY NOTES

1. SHEET INCLUDED TO DEPICT FINAL ELECTRICAL LAYOUT WITH ARCHITECTURAL

EXTENDABLE WALLS.

- 1" = 10'-0"

1 BLDG 09A - LEVEL 01 - POWER PLAN - PHASE 2

ARCHITECTURAL EXTENDABLE WALL.1

Revisions: Date:

0 10' 20'

PROJECT

NORTH

TRUE NORTH

(DASHED)

CONSTRUCTION

DOCUMENTS

WAP

WAP

360°

4 4 4 44 4 4 4

W

WWW

W

WWW

W

W

2 2

2 2 2 2 2 2 2 2

W

WAP

WAP

WAP

WAP WAP

WAP

W

4 4 4 4 4 4 4 4 4 4 44 4 4 4 4 44 4 4

44 4 4444 4

AREA OF WORK

BLDG 09A

BLDG 03BLDG 11

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64

17 18 19 20 21 25 26 27 28 29 30 31 32

PANEL '9LCA1'

RELOCATED PANEL '9LNA1'

RELOCATED PANEL '9LNA2'

RELOCATED PULL BOX

PULL BOX

RELOCATED POWER SUPPLY EXPANDER

TYP.

RELOCATED FA EQUIPMENT

CHANGE MGMT USER

IV SUPPORT

MECHANICAL

HAC

STORAGE

IV TESTING

IV TESTING

TR

STAFF BREAK

WAITING ALCOVE

RESTROOM

CORRIDOR

CR11-9

ELECTRICAL ROOM

RESTROOM

RESTROOM

RESTROOM

MECHANICAL

E-402

E-402

FACP BATTERY

BOX (BELOW)

FACP (ABOVE)

TYP.

ELECTRICAL

CLOSET

WORK AREA OUTLETS AND DEVICES IN THIS AREA SHALL

BE SERVED FROM TELECOMMUNICATIONS ROOM 100.

TYP.

E-501

E-503

E-505

STG

103A

E-505

TV

TVTVTVTVTVTVTV

TVTV

TVTV

F-01

2 22 2

TYP.

TYP.

PNL '9LNA3'

PNL '9LNA4'

PNL '9LNA6'

PNL '9LCA2'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:1

P

M

A u to d e s k D o c s /5

-2

-7

V A

G A

D u b lin

E H

R M

T A

S S

/V A

D U

C

E N

T R

A L

E

L

S D

B .r v t

ET101

BLDG 09A - LEVEL 01 - SPECIAL

SYSTEMS PLAN - PHASE 1 09A

JPB/WNM BCL

CONSTRUCTION

DOCUMENTS

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

2. SEAL ALL PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS AS REQUIRED.

3. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

4. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

5. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO SEAL

IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS FOR

PARTITION TYPES AND WALL HEIGHTS.

6. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES ON AS-BUILT DRAWINGS.

7. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY AND FIRE ALARM SYSTEMS. WHEN

ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN RACEWAY. WHEN

DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL SYSTEMS CABLE TRAY,

CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS; ADDITIONALLY, CABLE TRAYS

SHALL BE PROVIDED WITH TRAY DIVIDERS AS REQUIRED TO SEGREGATE SYSTEMS

FROM ONE ANOTHER.

8. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND ANY

OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

9. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL TELECOMMUNICATIONS AND ASSOCIATED CIRCUITRY AS

REQUIRED.

10. WHERE DATA OUTLETS ARE PROVIDED, PROVIDE (1) 1-1/4" CONDUIT FROM BACKBOX

TO ACCESSIBLE CEILING SPACE TO SECURELY ROUTE DATA CABLING FROM OUTLET

TO TR VIA EXISTING PATHWAYS.

11. EXISTING DEVICES SHALL NOT BE ORPHANED. PROVIDE CABLING TO TR 100 AS

REQUIRED TO MAINTAIN CONNECTIVITY.

0 10' 20'

PROJECT

NORTH

TRUE NORTH

(DASHED)

EACH SET OF (2) WORKSTATIONS SHALL BE PROVIDED WITH (1) WALL MOUNTED 4-

PORT WAO. EXACT LOCATION OF WAO SHALL BE COORDINATED WITH VA PRIOR TO

INSTALLATION TO CONFORM WITH VA WORKSTATION / FURNITURE LAYOUT. WAO

SHALL BE PROVIDED WITH CAT 6A CABLING.

PROVIDE CABLE TRAY AS INDICATED. SIZE CABLE TRAY PER "TELECOMMUNICATIONS

WAO, CABLE TRAY AND FIRE SLEEVE SCHEDULE" ON SHEET E-701.

REPLACE EXISTING WORK AREA OUTLET (WAO) CABLING AND PORT QUANTITY AS

INDICATED BY BLACK PORT QUANTITY TEXT. EXISTING WAO CONDUIT AND BOX SHALL

REMAIN AND BE UTILIZED TO FEED REPLACEMENT CABLING; REPLACEMENT CABLING

SHALL BE CAT 6A. PROVIDE NEW FACEPLATE, JACK MODULES/COVERS, AND

LABELING AS REQRUIED. FIELD VERIFY EXACT OUTLET PLACEMENT.

COORDINATE WITH ARCHITECT FOR TV DATA PORT ELEVATION. PROVIDE RECESSED

WALL BOX AND SPANNER SUPPORT FOR TV. PROVIDE ADDITIONAL 1" CONDUIT

STUBBED IN ACCESSIBLE CEILING SPACE TO ROUTE HDMI CABLE.

PROVIDE (2) CAT6A CABLES FOR WAP TO CABLE BACK TO TR DATA RACK IN ROOM

100.

APPROXIMATE LOCATION OF EXISTING FIBER-OPTIC CABLE ROUTED UNDERFLOOR IN

CRAWLSPACE. PROVIDE JUNCTION BOX "JB-TR100" (24"X24"X8"D, NEMA 3R) LOCATED

IN CRAWLSPACE TO INTERCEPT AND ROUTE CABLING TO TR RACK LOCATED IN TR

100. IF EXISTING FIBER-OPTIC CABLE IS NOT LONG ENOUGH TO EXTEND TO TR 100,

PROVIDE FUSION SPLICE IN "JB-TR100" AND EXTEND TO TR 100 THROUGH

CRAWLSPACE AS REQUIRED. REFERENCE SHEET ET601 FOR ADDITIONAL

INFORMATION.

PROVIDE (1) CAT6A CABLE FOR CAMERA TO CABLE BACK TO TR DATA RACK IN ROOM

100.

Revisions: Date:

- 1" = 10'-0"

1 BLDG 09A - LEVEL 01 - SPECIAL SYSTEMS PLAN - PHASE 1

WAP

360°

4 4 4 44 4 4 4

W

WWW

W

WWW

W

W

2 2

2 2 2 2 2 2 2 2

W

WAP

WAP

WAP

WAP WAP

WAP

W

4 4 4 4 4 4 4 4 4 4 44 4 4 4 4 44 4 4

44 4 4444 4

AREA OF WORK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64

17 18 19 20 21 25 26 27 28 29 30 31 32

CHANGE MGMT USER

CLASSROOM

104A

MECH

HAC

STORAGE

CLASSROOM

106B

CLASSROOM

103B

TR ROOM

STAFF BREAK

RESTROOM

CORRIDOR

CR11-9

ELECTRICAL

RESTROOM

RESTROOM

RESTROOM

CLASSROOM

103A

CLASSROOM

106A

PANEL '9LCA1'

RELOCATED PANEL '9LNA1'

RELOCATED PANEL '9LNA2'

PULL BOX

PULL BOX

POWER SUPPLY EXPANDER

RELOCATED FA EQUIPMENT

FACP BATTERY

BOX (BELOW)

FACP (ABOVE)

1 1

MECHANICAL

102A

1CLASSROOM

104B

WAITING ALCOVE

STG

2 22 2

ELECTRICAL

CLOSET

BLDG 09A

BLDG 03BLDG 11

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:2

P

M

A u to d e s k D o c s /5

-2

-7

V A

G A

D u b lin

E H

R M

T A

S S

/V A

D U

C

E N

T R

A L

E

L

S D

B .r v t

ET102

BLDG 09A - LEVEL 01 - SPECIAL

SYSTEMS PLAN - PHASE 2 09A

JPB/WNM BCL

CONSTRUCTION

DOCUMENTS

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

- 1" = 10'-0"

1 BLDG 09A - LEVEL 01 - SPECIAL SYSTEMS PLAN - PHASE 2 0 10' 20'

PROJECT

NORTH

TRUE NORTH

(DASHED)

ARCHITECTURAL EXTENDABLE WALL.1

1. SHEET INCLUDED TO DEPICT FINAL SPECIAL SYSTEMS LAYOUT WITH ARCHITECTURAL

EXTENDABLE WALLS.

Revisions: Date:

F S

FS

FS

AREA OF WORK

BLDG 09A

BLDG 03BLDG 11

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64

17 18 19 20 21 25 26 27 28 29 30 31 32

PANEL '9LCA1'

RELOCATED PANEL '9LNA1'

RELOCATED PANEL '9LNA2'

RELOCATED PULL BOX

PULL BOX

RELOCATED POWER SUPPLY EXPANDER

RELOCATED FA EQUIPMENT

CHANGE MGMT USER

IV SUPPORT

MECHANICAL

HAC

STORAGE

IV TESTING

IV TESTING

TR

STAFF BREAK

WAITING ALCOVE

RESTROOM

CORRIDOR

CR11-9

ELECTRICAL ROOM

RESTROOM

RESTROOM

RESTROOM

MECHANICAL

FACP BATTERY

BOX (BELOW)

FACP (ABOVE)

STG

103A

009A-AHU-1

PNL '9LNA3'

PNL '9LNA4'

PNL '9LNA6'

ELECTRICAL CLOSET

PNL '9LCA2'

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:2

P

M

A u to d e s k D o c s /5

-2

-7

V A

G A

D u b lin

E H

R M

T A

S S

/V A

D U

C

E N

T R

A L

E

L

S D

B .r v t

EF101

BLDG 09A - LEVEL 01 - FIRE ALARM

SYSTEMS PLAN - PHASE 1 09A

JPB/WNM BCL

CONSTRUCTION

DOCUMENTS

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

1. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

2. SEAL ALL PENETRATIONS TO MATCH EXISTING FIRE RATING OR NEW FIRE RATING, IF

REQUIRED. COORDINATE WITH ARCHITECTURAL DRAWINGS AS REQUIRED.

3. ALL FIRE ALARM DEVICE CABLING SHALL EXTEND AND TERMINATE TO FIRE ALARM

PANELS LOCATED IN ROOM 116 AS REQUIRED.

4. REFERENCE SHEET E-506 FOR ADDITIONAL INFORMATION.

0 10' 20'

PROJECT

NORTH

TRUE NORTH

(DASHED)

RELOCATED EQUIPMENT. REFERENCE SHEET ED103, KEY NOTE 6 FOR

ADDITIONAL INFORMATION.

DUCT SMOKE DETECTOR. COORDINATE EXACT INSTALLATION LOCATION WITH

MECHANICAL ENGINEER AND AHU MANUFACTURER AS REQUIRED.

- 1" = 10'-0"

1 BLDG 09A - LEVEL 01 - FIRE ALARM SYSTEMS PLAN - PHASE 1

Revisions: Date:

F S

FS

FS

AREA OF WORK

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64

17 18 19 20 21 25 26 27 28 29 30 31 32

CHANGE MGMT USER

CLASSROOM

104A

MECH

HAC

STORAGE

CLASSROOM

106B

CLASSROOM

103B

TR ROOM

STAFF BREAK

RESTROOM

CORRIDOR

CR11-9

ELECTRICAL

RESTROOM

RESTROOM

RESTROOM

CLASSROOM

103A

CLASSROOM

106A

PANEL '9LCA1'

RELOCATED PANEL '9LNA1'

RELOCATED PANEL '9LNA2'

PULL BOX

PULL BOX

POWER SUPPLY EXPANDER

RELOCATED FA EQUIPMENT

FACP (ABOVE)

FACP BATTERY BOX (BELOW)

MECHANICAL

102A

CLASSROOM

104B

WAITING ALCOVE

WAITING ALCOVE

ELECTRICAL CLOSET

STG

BLDG 09A

BLDG 03BLDG 11

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:2

P

M

A u to d e s k D o c s /5

-2

-7

V A

G A

D u b lin

E H

R M

T A

S S

/V A

D U

C

E N

T R

A L

E

L

S D

B .r v t

EF102

BLDG 09A - LEVEL 01 - FIRE ALARM

SYSTEMS PLAN - PHASE 2 09A

JPB/WNM BCL

CONSTRUCTION

DOCUMENTS

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

KEY NOTES

KEY PLAN

GENERAL NOTES

TRUE

NORTH

- 1" = 10'-0"

1 BLDG 09A - LEVEL 01 - FIRE ALARM SYSTEMS PLAN - PHASE 2 0 10' 20'

PROJECT

NORTH

TRUE NORTH

(DASHED)

ARCHITECTURAL EXTENDABLE WALL.1

Revisions: Date:

1. SHEET INCLUDED TO DEPICT FINAL FIRE ALARM SYSTEMS LAYOUT WITH

ARCHITECTURAL EXTENDABLE WALLS.

J

Mo a

Mo b

AREA OF WORK

TYP.

HOUSEKEEPING

AID CLOSET

TR

101 SF

E-503

E-503

DATA RACK,

TYP.

09A-FC-01

09A-HP-01

9LCA3

9LNA7

9LCA3-2

9LNA7-2

9LCA3-2

9LCA3-2

9LNA7-2

9LCA3-2

9LNA7-2

9LNA7-2

F F

E-504

09-P-03

09-P-10

09-P-TRB

09-P-TRA

ACCESS CONTROL PANEL

"09-ACP-100-1"

9LCA3-10

ACCESS CONTROL PANEL

"09-ACP-100-2"

9LCA3-10

DDC CONTROLLER

9LCA3-14

TYP.

HOUSEKEEPING

AID CLOSET

TR

101 SF

DATA RACK,

TYP.

9LNA7

9LCA3

b

9LNA7-4

L1 b

9LNA7-4

L1E a

9LCA3-4

L1E a

9LCA3-4

L1

E-401

E-502 TYP.

TYP.

CANTEEN SVC

VENDING AREA

95 SF

CANTEEN SVC

VENDING AREA

95 SF

TR 100

A SIDE POWER

B SIDE POWER

SHEET SHALL PRINTED

IN COLOR TO PROVIDE

ALL INFORMATION.

LEGEND:

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:2

P

M

A u to d e s k D o c s /5

-2

-7

V A

G A

D u b lin

E H

R M

T A

S S

/V A

D U

C

E N

T R

A L

E

L

S D

B .r v t

E-401

ENLARGED TR ROOM 100

ELECTRICAL PLANS 09A

JPB/WNM BCL

CONSTRUCTION

DOCUMENTS

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

KEY NOTES

KEY PLAN

GENERAL NOTES

PROJECT

NORTH

TRUE NORTH

(DASHED)

EXISTING EQUIPMENT TO BE DEMOLISHED. ASSOCIATED CONDUIT AND WIRE SHALL

BE DEMOLISHED BACK TO SOURCE.

SOURCE A POWER PANELBOARD "9LCA3".

SOURCE B POWER PANELBOARD "9LNA7".

PROVIDE SECONDARY BONDING BUSBAR. REFERENCE TELECOMMUNICATIONS

BONDING RISER DIAGRAM ON SHEET ET601 FOR ADDITIONAL INFORMATION.

OVERHEAD TR RACK SOURCE A AND SOURCE B POWER RECEPTACLE.

FURNISH AND INSTALL BOXED POWER SUPPLIES AS INDICATED ABOVE ACCESSIBLE

CEILINGS. VERIFY LOCATIONS WITH ARCHITECT. PROVIDE (1) POWER SUPPLY FOR

EACH DOOR OPENING. PROVIDE 120V POWER TO ADEQUATE SERVE DOORS WITH

ELECTRIFIED DOOR HARDWARE AND MAKE CONNECTIONS AS REQUIRED. SEE

REQUIREMENTS IN 087100 - DOOR HARDWARE. COORDINATE WITH ARCHITECT AND

DOOR INSTALLER.

09A-FC-01-101 POWERED FROM 09A-HP-01-101, PROVIDE CONDUCTORS AND WIRE

PER MANUFACTURER'S REQUIREMENT. COORDINATE WITH MECHANICAL

CONTRACTOR AS REQUIRED.

REFERENCE EQUIPMENT SCHEDULE ON SHEET E-701 FOR ADDITIONAL CIRCUITING

INFORMATION.

DDC CONTROLLER. COORDINATE EXACT REQUIREMENTS AND LOCATION WITH

MECHANICAL CONTRACTOR AND ENGINEER AS REQUIRED.

FEEDER ROUTES FROM CRAWLSPACE. REFERENCE SHEET EP100 FOR ADDITIONAL

ROUTING INFORMATION.

1. DEMOLITION PLANS/NOTES ARE BASED ON SITE INVESTIGATIONS AND RECORD

DRAWINGS. IF DISCREPANCIES ARE FOUND THAT MAY IMPACT WORK, PROMPTLY

NOTIFY VA AND ENGINEER OF SAID DISCREPANCY.

2. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL POWER, LIGHTING AND ASSOCIATED CIRCUITRY AS REQUIRED.

ALL RACEWAYS AND CONDUCTORS ASSOCIATED WITH EQUIPMENT TO BE

DEMOLISHED SHALL BE DEMOLISHED BACK TO THEIR SOURCE, UNLESS OTHERWISE

NOTED.

3. CONTRACTOR SHALL DEMOLISH ALL ELECTRICAL EQUIPMENT, CONDUCTORS, AND

RACEWAYS ASSOCIATED WITH WALLS BEING REMOVED AND IN ALL LOCATIONS

WHERE JUNCTION BOXES WILL NOT REMAIN ACCESSIBLE AFTER INSTALLATION OF

MILLWORK, UNLESS OTHERWISE NOTED.

4. CONTRACTOR SHALL DISPOSE OF THE REMOVED DEVICES. DISPOSAL OF

DEVICES SHALL COMPLY WITH ALL APPROPRIATE CODES.

5. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, FINISHES AND THE LIKE, SHALL BE

REPAIRED OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE

ACCEPTANCE OF THE OWNER.

6. FIELD VERIFY ALL RACEWAY DEMOLITION AND INSTALLATIONS PRIOR TO

PERFORMING WORK.

7. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING, IF REQUIRED. COORDINATE WITH ARCHITECTURAL

DRAWINGS AS REQUIRED.

8. REFERENCE CORRESPONDING ONE-LINE DIAGRAM FOR ADDITIONAL INFORMATION.

9. CONTRACTOR SHALL PROVIDE UPDATED CIRCUIT PANEL DIRECTORIES FOR ALL

PANELS THAT CONTAIN CIRCUITS IMPACTED BY THIS PROJECT.

Revisions: Date:

1/2" = 1'-0"ED102

1 DEMO ELECTRICAL POWER FLOOR PLAN

1/2" = 1'-0"EP101

2 REVISED ELECTRICAL POWER FLOOR PLAN

1/2" = 1'-0"ED101

3 DEMO LIGHTING OVERHEAD PLAN

1/2" = 1'-0"

REVISED LIGHTING OVERHEAD PLAN

EL101

EL102

1'0 2' 4'

PROJECT

NORTH

TRUE NORTH

(DASHED)

1'0 2' 4'

PROJECT

NORTH

TRUE NORTH

(DASHED)

1'0 2' 4'

PROJECT

NORTH

TRUE NORTH

(DASHED)

1'0 2' 4'

PROJECT

NORTH

TRUE NORTH

(DASHED)

360°

C

S

X

W

X

W

HOUSEKEEPING

AID CLOSET

TR

101 SF

C

SECONDARY

BONDING BUSBAR

DATA RACK,

TYP.

9LCA3

9LNA7

E-505

E-505

E-505

F-01

ACCESS CONTROL PANEL

"09-ACP-100-2"

ACCESS CONTROL PANEL

"09-ACP-100-1"

DDC CONTROLLER

HOUSEKEEPING

AID CLOSET

TR

101 SF

DATA RACK,

TYP.

E-501

E-501

E-503

TYP.

TYP.

CANTEEN SVC

VENDING AREA

95 SF

CANTEEN SVC

VENDING AREA

95 SF

AREA OF WORK

TR 100

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:2

P

M

A u to d e s k D o c s /5

-2

-7

V A

G A

D u b lin

E H

R M

T A

S S

/V A

D U

C

E N

T R

A L

E

L

S D

B .r v t

E-402

09A

JPB/WNM BCL

CONSTRUCTION

DOCUMENTS

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

ENLARGED TR ROOM 100

TELECOMMUNICATIONS PLANS

1/2" = 1'-0"ED103

1 DEMO TELECOMMUNICATIONS FLOOR PLAN

1/2" = 1'-0"

REVISED TELECOMMUNICATIONS FLOOR PLAN

ET101

1/2" = 1'-0"ED103

3 DEMO TELECOMMUNICATIONS OVERHEAD PLAN

1/2" = 1'-0"

REVISED TELECOMMUNICATIONS OVERHEAD PLAN

ET101

KEY NOTES

GENERAL NOTES

PROJECT

NORTH

TRUE NORTH

(DASHED)

PROVIDE RIGID CONDUIT SLEEVES WITH FIRE PROOFING AS REQUIRED. SIDE 'A' AND

SIDE 'B' SLEEVES SHALL BE SEPARATED BY AT LEAST 10-FT.

PROVIDE WIRE BASKET CABLE TRAY AS INDICATED.

PROVIDE ACCESS CONTROL PANEL(S) TO SERVE ALL PACS DOOR SECURITY

EQUIPMENT FOR THIS TR ROOM AND BUILDING LEVEL 01. PROVIDE ALL REQUIRED

CONNECTIONS, PROGRAMMING, POWER SUPPLIES, AND COMPONENTS TO PROVIDE A

COMPLETE AND FULLY FUNCTIONAL SYSTEM. REFERENCE SPECIFICATION "28 13 00 -

PHYSICAL ACCESS CONTROL SYSTEM" FOR ADDITIONAL INFORMATION. ALL

EQUIPMENT SHALL MATCH INSTALLED BASE. PROVIDE (1) CAT 6A CABLE FROM ACP

TO TR DATA RACK.

PROVIDE (1) CAT6A CABLE TO CONNECT SECURITY CAMERA TO TR DATA RACK.

KEY PLAN

1. ALL EXISTING EQUIPMENT MAY NOT BE SHOWN FOR CLARITY. CONTRACTOR SHALL

FIELD VERIFY ALL DEVICES AND ASSOCIATED CABLING AS REQUIRED. ALL

RACEWAYS AND CABLING ASSOCIATED WITH EQUIPMENT TO BE DEMOLISHED

SHALL BE DEMOLISHED BACK TO ITS SOURCE, UNLESS OTHERWISE NOTED.

2. PROTECT ALL EXISTING WORK FROM DAMAGE DURING CONSTRUCTION. ANY

DAMAGED MATERIALS, SYSTEMS, COMPONENTS, AND FINISHES SHALL BE REPAIRED

OR REPLACED AT THE EXPENSE OF THE CONTRACTOR TO THE ACCEPTANCE OF

THE OWNER.

3. SEAL ALL INTERIOR WALL AND CEILING PENETRATIONS TO MATCH EXISTING FIRE

RATING OR NEW FIRE RATING. COORDINATE WITH ARCHITECTURAL DRAWINGS AS

REQUIRED.

4. ALL TELECOMMUNICATIONS CABLING CATEGORY 6 AND BELOW SHALL BE REMOVED

AND REPLACED WITH CAT6A PORTS AND CABLE QUANTITIES INDICATED, UNLESS

NOTED OTHERWISE.

5. TELECOMMUNICATIONS CABLES SHALL BE ROUTED IN EXISTING PATHWAY VACATED

BY EXISTING CABLING AS CONDUIT FILL ALLOWS. PROVIDE ADDITIONAL RACEWAYS

TO EXTEND TO ASSOCIATED TR AS REQUIRED.

6. TELECOMMUNICATIONS WAO UPGRADE SHALL INCLUDE, BUT IS NOT LIMITED TO

REMOVING AND DISPOSING OF EXISTING CABLING, JACKS AND FACEPLATES AS

REQUIRED; PROVIDING ALL LABOR, MATERIALS, TOOLS, TEST INSTRUMENTS, AND

CONSUMABLES REQUIRED FOR INSTALLATION, TERMINATION, TESTING, LABELING,

AND CERTIFICATION OF A FULLY FUNCTIONAL CATEGORY 6A OUTLET WITH PORT

QUANTITY INDICATED.

7. WHEN PROVIDING A WAO IN LOCATIONS WHERE AN EXISTING WAO CURRENTLY

DOES NOT EXIST, PROVIDE (1) 4-INCH SQUARE BACKBOX WITH SINGLE-GANG

REDUCING MUD RING AND (1) 1-1/4" CONDUIT EXTENDING FROM BACKBOX TO

ACCESSIBLE CEILING SPACE. ONCE IN ACCESSIBLE CEILING SPACE, CABLING SHALL

EXTEND TO ITS ASSOCIATED TR VIA CABLE TRAY; UTILIZE J-HOOKS EVERY 48” WHEN

TRANSITIONING TO OR FROM CABLE TRAY. IF CABLE TRAY IS NON-EXISTENT,

EXTEND HORIZONTAL CABLING FROM WAO TO TR VIA J-HOOKS ONLY.

8. PROVIDE PULL BOXES SIZED PER ANSI/TIA-569 AT 100-FT INTERVALS IN STRAIGHT

CONDUIT RUNS, OR CONDUIT CONTAINING BENDS TOTALING MORE THAN 180

DEGREES.

9. PROVIDE CONDUITS AND SLEEVES AS REQUIRED FOR ROUTING AND INSTALLATION

OF HORIZONTAL AND BACKBONE CABLING. PROVIDE FIRE-STOP MATERIALS TO

SEAL IN AND AROUND CONDUIT PER CODE. REFER TO ARCHITECTURAL DRAWINGS

FOR PARTITION TYPES AND WALL HEIGHTS.

10. OUTLET LOCATIONS ARE APPROXIMATE. DETERMINE EXACT LOCATIONS IN FIELD;

DOCUMENT VARIANCES BASED ON AS-BUILT DRAWINGS.

11. ALL DATA CABLING SHALL BE SEGREGATED FROM OTHER SPECIAL SYSTEMS

INCLUDING, BUT NOT LIMITED TO, SECURITY, FIRE ALARM, AND NURSE CALL

SYSTEMS. WHEN ROUTED THROUGH CONDUIT, DATA CABLING SHALL HAVE ITS OWN

RACEWAY. WHEN DATA CABLING IS ROUTED THROUGH A COMMON SPECIAL

SYSTEMS CABLE TRAY, CABLING SHALL BE BUNDLED WITH LIKE SYSTEMS;

ADDITIONALLY, CABLE TRAYS SHALL BE PROVIDED WITH TRAY DIVIDERS AS

REQUIRED TO SEGREGATE SYSTEMS FROM ONE ANOTHER.

12. FIBER-OPTIC CABLING ROUTES AND ASSOCIATED RACEWAYS/CABLE TRAY ARE

DIAGRAMMATICAL. COORDINATE EXACT ROUTING WITH EXISTING CONDITIONS,

ARCHITECTURAL FEATURES, MECHANICAL DUCTWORK, PIPING, EQUIPMENT, AND

ANY OTHER OBSTRUCTIONS PRIOR TO INSTALLATION.

1'0 2' 4'

PROJECT

NORTH

TRUE NORTH

(DASHED)

1'0 2' 4'

PROJECT

NORTH

TRUE NORTH

(DASHED)

1'0 2' 4'

PROJECT

NORTH

TRUE NORTH

(DASHED)

Revisions: Date:

1'0 2' 4'

PROJECT

NORTH

TRUE NORTH

(DASHED)

File details come from the government source that posted it. Updated .