S02-RFP Attachment 13-Drawings-Dublin_Part4.pdf
PDF 2 MB Posted
- Solicitation number
- 36C77626R0031_1
About this file
This document package comprises architectural and construction drawings for the renovation of Building 9A at Carl Vinson VA Medical Center in Dublin, Georgia, to establish EHRM (Employee Health Records Management) administrative space. The project is designated as Phase I and Phase II renovation work with a project number of 557-21-703 and building number 009A, prepared by SPEES DESIGN BUILD as the design-build contractor.
The renovation includes comprehensive finishing plans, door and assembly schedules, specialty equipment specifications, and signage requirements for multiple functional spaces totaling approximately 7,000 square feet. Key spaces include IV testing rooms (103, 106), IV support (104), staff break room (107), change management office (108), restrooms (110-113), storage (114), mechanical rooms (101, 109), electrical closet (115), electrical room (116), and corridor areas (CR11-9, CR11-10). Room finishes specify combinations of acoustic ceiling tiles, ceramic floor tiles, luxury vinyl tiles, gypsum board, carpet tiles, epoxy coating, and painted surfaces with accent colors, rubber or premium rubber base, and ceramic wall tile in restroom areas. The specialty equipment schedule itemizes 89 workstations with accessories, multiple chairs, televisions (60-65 inches), refrigeration units, coffee makers, microwaves, and various restroom fixtures and accessories. Fire protection design includes light hazard level sprinkler systems with new quick response and standard response heads coordinated throughout the facility. Structural and concrete details provide specifications for light-gauge metal stud framing, typical opening details, slab-on-grade construction with #4 rebar reinforcement at 12-inch spacing, and equipment anchorage requirements. All work complies with 2021 International Building Code standards, VA Design Guidelines, and NFPA 13 sprinkler installation requirements, with the contractor responsible for field verification of dimensions and coordination among architectural, mechanical, and structural systems.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64
17 18 19 20 21 25 26 27 28 29 30 31 32
CHANGE
MGMT
USER
IV
SUPPORT
MECHANICAL
HAC
STORAGE
IV
TESTING
IV
TESTING
TR
STAFF
BREAK
WAITING
ALCOVE
RESTROOM
ELECTRICAL
ROOM
CORRIDOR
CR11-9
RESTROOM
RESTROOM
RESTROOM
MECHANICAL
ELECTRICAL
CLOSET
LVT-1
LVT-1
LVT-1
LVT-1
LVT-1
LVT-2
LVT-2
LVT-2
LVT-2
ACT ACOUSTICAL CEILING TILE
CBT CERAMIC BASE TILE
CFT CERAMIC FLOOR TILE
CPT CARPET TILE
CWT CERAMIC WALL TILE
GYP GYPSUM BOARD
LVT LUXURY VINYL TILE
PT PAINT
EP EPOXY
EXP EXPOSED
RB RUBBER BASE
PRB PREMIUM RUBBER BASE
WC WALL COVERING
PLAM PLASTIC LAMINATE
SDSF SOLID SURFACE
FINISH ABBREVIATIONS
FINISH PLAN LEGEND
LVT-1
LVT-2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
A-601
FINISH SCHEDULE
009A
MC EB
CONSTRUCTION
DOCUMENT
6/14/2024
557-21-703
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
Revisions: Date:
PHASE I - ROOM FINISH SCHEDULE
ROOM # ROOM NAME
CEILING
FINISH
FLOOR
FINISH
BASE WAINSCOT WALL FINISH
COMMENTSMAT HT MAT HT EAST NORTH SOUTH WEST
100 TR -- EXP RB-1 4" -- -- PT-2 PT-2 PT-2 PT-2 APPLY ANTI-STATIC COATING TO EXPOSED CONCRETE FLOORING
101 MECHANICAL -- EXP RB-1 4" -- -- PT-2 PT-2 PT-2 PT-2
102 HAC ACT-1 EP-1 RB-1 4" -- -- PT-2 PT-2 PT-2 PT-2
103 IV TESTING ACT-1 CPT-1 RB-1 4" -- -- PT-2 PT-2 PT-3 PT-2 PT-3 (ACCENT) ON SOUTH WALL
103A STG
104 IV SUPPORT ACT-1 CPT-1 RB-1 4" -- -- PT-2 PT-2 PT-3 PT-2 PT-3 (ACCENT) ON SOUTH WALL
105 WAITING ALCOVE GYP LVT-1 RB-1 4" -- -- PT-1 PT-1 PT-1 PT-1
106 IV TESTING ACT-1 CPT-1 RB-1 4" -- -- PT-2 PT-2 PT-3 PT-2 PT-3 (ACCENT) ON SOUTH WALL
107 STAFF BREAK ACT-1 LVT-2 RB-1 4" -- -- PT-3 PT-1 PT-1 PT-1 PLAM-1, SDSF-1, PT-3 (ACCENT) ON EAST WALL
108 CHANGE MGMT USER ACT-1 CPT-1 RB-1 4" -- -- PT-2 PT-2 PT-3 PT-2 PT-3, (ACCENT) ON SOUTH WALL
109 MECHANICAL -- EXP RB-1 4" -- -- PT-2 PT-2 PT-2 PT-2
110 RESTROOM ACT-1 CFT-1 CTB-1 4" CWT-1 4' - 0" WC-1 WC-1 WC-1 WC-1 REFERENCE AE424 FOR TILE ELEVATIONS
111 RESTROOM ACT-1 CFT-1 CTB-1 4" CWT-1 4' - 0" WC-1 WC-1 WC-1 WC-1 REFERENCE AE424 FOR TILE ELEVATIONS
112 RESTROOM ACT-1 CFT-1 CTB-1 4" CWT-1 4' - 0" WC-1 WC-1 WC-1 WC-1 REFERENCE AE424 FOR TILE ELEVATIONS
113 RESTROOM ACT-1 CFT-1 CTB-1 4" CWT-1 4' - 0" WC-1 WC-1 WC-1 WC-1 REFERENCE AE424 FOR TILE ELEVATIONS
114 STORAGE ACT-1 EP-1 RB-1 4" -- -- PT-2 PT-2 PT-2 PT-2
115 ELECTRICAL CLOSET -- EP-1 RB-1 4" -- -- PT-2 PT-2 PT-2 PT-2
116 ELECTRICAL ROOM -- EP-1 RB-1 4" -- -- PT-2 PT-2 PT-2 PT-2
CR11-9 CORRIDOR ACT-1 LVT-1 / LVT-2 PRB-1 4" -- -- PT-1 PT-1 PT-1 PT-1
CR11-10 CORRIDOR ACT-1 LVT-1 / LVT-2 PRB-1 4" -- -- PT-1 PT-1 PT-1 PT-1
1/8" = 1'-0"
FLOOR PLAN - PHASE I - FINISH PLAN
PROJECT
NORTH
TRUE NORTH
(DASHED)
Megan Matt's Stamp
Megan Text Box 6/14/24
01 03
5/8" 3 5/8" 5/8"
STRUCTURE ABV
5/8" 3 5/8" 5/8"
" FINISH CLG
FINISH FLOOR
TYPE 'X' GYP
STEEL STUD
FRAMING
TYPE 'X' GYP
TYPE 'X' GYP
STEEL STUD
FRAMING
TYPE 'X' GYP
TYPE 'X' GYP
STEEL STUD
FRAMING
5/8" 3 5/8"
1A
9" 4"
2A
GLAZING
1B
LOUVER PER
SCHEDULE
DOOR HEIGHTS AND WIDTHS PER SCHEDULE
9" 9"
2B
9" 9"
GLAZING
TYPE 'X' GYP
CT-3
CT-2
CONCRETE
BACKER BOARD
STEEL STUD
FRAMING
CT-1
EXISTING WALL
CT-3
CT-2
CONCRETE
BACKER BOARD
TYPE 'X' GYP
CT-1
STEEL STUD
FRAMING
TYPE 'X' GYP
TYPE 'X' GYP
STRUCTURE ABV
FINISH CEILING
FINISH FLOOR
5/8" 5 5/8" 5/8" 5/8" 5/8" 3 5/8" 5/8"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
A-602
DOOR AND ASSEMBLY SCHEDULE
009A
MC EB
CONSTRUCTION
DOCUMENT
6/14/2024
557-21-703
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
GENERAL NOTES
2. ROOM FINISHES WILL NOT BE IMPACTED BY PHASE II
SCOPE OF WORK. CONTRACTORS SHOULD BE CAREFUL
NOT TO DAMAGE ROOM FINISHES WHEN TRANSITIONING TO
PHASE II.
Revisions: Date:
PHASE I - DOOR SCHEDULE
MARK ROOM # ROOM NAME
DOOR SIZE DOOR
TYPE
GLAZING
TYPE
HW
SET
MATERIAL FIRE
RATING
STC
RATING COMMENTSWIDTH HT DOOR FRAME
100 100 TR 3' - 0" 7' - 0" 1A 11 HM HM
101 101 MECHANICAL 3' - 0" 7' - 0" 1B 11 HM HM
102 102 HAC 3' - 6" 7' - 0" 1A 5D WOOD HM
103A 103 IV TESTING 3' - 0" 7' - 0" 2A 4 WOOD HM
103B 103 IV TESTING 3' - 0" 7' - 0" 2A 4 WOOD HM
104A 104 IV SUPPORT 3' - 0" 7' - 0" 2A 4 WOOD HM
104B 104 IV SUPPORT 3' - 0" 7' - 0" 2A 4 WOOD HM
106A 106 IV TESTING 3' - 0" 7' - 0" 2A 4 WOOD HM
106B 106 IV TESTING 3' - 0" 7' - 0" 2A 4 WOOD HM
107 107 STAFF BREAK 3' - 0" 7' - 0" 2A 1 WOOD HM
108 108 CHANGE MGMT USER 5' - 0" 7' - 0" 2A 4 WOOD HM
109 109 MECHANICAL 3' - 0" 7' - 0" 1B 11 HM HM
110 110 RESTROOM 3' - 0" 7' - 0" 1A 2 WOOD HM
111 111 RESTROOM 3' - 0" 7' - 0" 1A 2 WOOD HM
112 112 RESTROOM 3' - 0" 7' - 0" 1A 2 WOOD HM
113 113 RESTROOM 3' - 10" 7' - 0" 1A 2 WOOD HM
114 114 STORAGE 3' - 8" 7' - 0" 1A 5 WOOD HM
115 115 ELECTRICAL CLOSET 5' - 0" 7' - 0" 1A 11 HM HM
116 116 ELECTRICAL ROOM 3' - 0" 7' - 0" 1A 11 HM HM
117 103A STG 5' - 0" 7' - 0" 1A 5D WOOD HM
118 CR11-9 CORRIDOR 1' - 8" 7' - 0" 1A EXST HM HM REPLACE DOOR LEAF, USE EXISTING DOOR HARDWARE OR REPLACE WITH LIKE
119 CR11-9 CORRIDOR 1' - 6" 7' - 0" 1A EXST HM HM REPLACE DOOR LEAF, USE EXISTING DOOR HARDWARE OR REPLACE WITH LIKE
120 CR11-9 CORRIDOR 3' - 8" 7' - 0" 2B EXST HM HM REPLACE DOOR LEAF, USE EXISTING DOOR HARDWARE OR REPLACE WITH LIKE
121 CR11-9 CORRIDOR 7' - 4" 7' - 0" 2B FR EXST HM HM 1-1/2 HR REPLACE DOOR LEAF, USE EXISTING DOOR HARDWARE OR REPLACE WITH LIKE, DOUBLE EGRESS
1. EXAMPLE PARTITION CODE: 09P4107b
09 - SPECIFICATION CATEGORY
P - DETAIL TYPE CATEGORY
4 - NOMINAL SIZE
1 - PARTITION CATEGORY
07 - SEQUENCE NUMBER
b - FIRE / SMOKE RATING
SPECIFICATION CATEGORY
03 CONCRETE
04 MASONRY
09 METAL STUD
DETAIL TYPE CATEGORY
P PARTITION
NOMINAL SIZE
1 SIZE 1"
2 SIZE 2"
4 SIZE 4"
6 SIZE 6"
8 SIZE 8"
PARTITION CATEGORY
1 WITHOUT INSULATION
2 WITH INSULATION
3 TILE
4 LEAD LINED
5 SECURITY MESH
6 USER DEFINED/COMBOS
7 USER DEFINED/COMBOS
FIRE / SMOKE / SOUND RATING
a SMOKE RATED b 1HR FIRE RATED c 1HR FIRE & SMOKED RATED d 2HR FIRE RATED e 2HR FIRE & SMOKE RATED f SOUND RATED g SOUND & SMOKE RATED h SOUND & 1HR FIRE RATED i SOUND & 1HR FIRE & SMOKE RATED j SOUND & 2HR FIRE RATED k SOUND & 2HR FIRE & SMOKE RATED
WALL SCHEDULE
MARK
PARTITION
CODE DESCRIPTION WIDTH
FIRE RATING SOUND RATING
COMMENTSFR SOURCE STC SOURCE
01 09P4101 3-5/8" MTL STUD, 5/8" GYP EA SIDE, "6 ABV CLG 0' - 4 7/8"
03 09P4103 3-5/8" MTL STUD, 5/8" GYP EA SIDE, FULL HEIGHT 0' - 4 7/8"
04 09P4104 3-5/8" MTL STUD, 5/8" GYP ONE SIDE, FULL
HEIGHT
0' - 4 1/4"
05 09P4103 5-5/8" MTL STUD, 5/8" GYP EA SIDE, FULL HEIGHT 0' - 6 7/8"
90 09P4101 EXISTING WALL, 5/8" GYP ONE SIDE, TILE ONE
SIDE, "6 ABV CLG
<varies>
93 09P4101 3-5/8" MTL STUD, 5/8" GYP EA SIDE, TILE ONE
SIDE, "6 ABV CLG
0' - 5 3/16"
1" = 1'-0"
WALL TYPES
1/4" = 1'-0"
DOOR TYPES
1" = 1'-0"
WALL TYPES CONT.
Megan Matt's Stamp
Megan
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
A-603
SPECIALTY EQUIPMENT
SCHEDULE 009A
MK MC
CONSTRUCTION
DOCUMENT
6/14/2024
557-21-703
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
1. VV - VA FURNISHED, VA INSTALLED
CC - CONTRACTOR FURNISHED, CONTRACTOR INSTALLED
VC - VA FURNISHED, CONTRACTOR INSTALLED
CV - CONTRACTOR FURNISHED, VA INSTALLED
R - RELOCATED
2. CONTRACTOR TO CONFIRM QUANTITIES OF EACH ITEM
PRIOR TO PURCHASE OR INSTALLATION.
3. SEE TYP MOUNTING HEIGHTS ON TYP INTERIOR
ELEVATIONS SHEET FOR INSTALLATION HEIGHTS, UNO.
SPECIALTY EQUIPMENT SCHEDULE
MARK EQUIPMENT QUANTITY
POWER
/ DATA
FURN /
INSTALL
BY DESCRIPTION
A0001 ACCORDIAN WALL 3 NO / NO VV Operable Partition
A1067 MIRROR - ADA 4 NO / NO CC A HIGH QUALITY 1/4" POLISHED FLOAT GLASS MIRROR WITH A STAINLESS STEEL FRAME. FRAME HOLDS MIRROR IN A TILTED POSITION FOR ACCESSIBILITY AND COMPLIANCE WITH ADA REQUIREMENTS. MIRROR HAS A GALVANIZED STEEL BACK SECURED TO FRAME WITH CONCEALED SCREWS WITH INTEGRAL HORIZONTAL HANGING BRACKETS. MIRROR SHALL BE APPROXIMATELY 18" WIDE AND 36" HIGH. OTHER SIZES ARE
AVAILABLE.
A5075 SOAP 6 NO / NO VC DISPOSABLE SOAP DISPENSER. ONE-HANDED DISPENSING OPERATION. DESIGNED TO ACCOMMODATE DISPOSABLE SOAP CARTRIDGE AND VALVE.
A5082 PAPER TOWELS - AUTO 6 NO / NO VC DISPENSER, PAPER TOWEL, SENSOR, HANDS FREE
A5090 SANITARY NAPKIN 4 NO / NO CC A SURFACE MOUNTED, SATIN FINISH STAINLESS STEEL, SANITARY NAPKIN DISPOSAL. DISPOSAL FEATURES A FLIP-UP COVER, SECURED TO THE CONTAINER BY A HEAVY DUTY STAINLESS STEEL PIANO-HINGE. DISPOSAL MAY BE SECURED TO WALL OR TOILET PARTITION. FOR GENERAL
PURPOSE USE IN FEMALE TOILET STALLS OR ROOMS AND UNI-SEX TOILET ROOMS.
A5107 GLOVES DISPENSER 1 NO / NO VC EXAMINATION GLOVE DISPENSER BOX FOR WALL MOUNTING. FABRICATED OF EITHER COLD ROLLED STEEL WITH A WHITE BAKED ENAMEL FINISH, PLASTIC OR ACRYLIC. PROVIDED WITH WALL BRACKET TO FACILITATE MOUNTING AND DEMOUNTING.
A5109 GRAB BAR 4 NO / NO CC A 1-1/4" DIAMETER, SATIN FINISH STAINLESS STEEL, PEENED GRIPPING SURFACE, 2 WALL TOILET STALL/ ROOM, GRAB BAR WITH CONCEALED MOUNTING FLANGES. SNAP OVER FLANGES ARE PROVIDED TO CONCEAL MOUNTING SCREWS. A SELECTION OF MOUNTING KITS AND CONCEALED ANCHOR DEVICES ARE AVAILABLE FROM THE MANUFACTURERS FOR DIFFERENT TYPES OF INSTALLATIONS.
A5135 UTILITY SHELF 1 NO / NO VC A SURFACE MOUNTED, SATIN FINISH, STAINLESS STEEL SHELF WITH A MINIMUM DEPTH OF 8". MOUNTING BRACKETS ARE WELDED TO SHELF.
SHELF IS AVAILABLE IN VARIOUS WIDTHS. FOR GENERAL PURPOSE USE IN SCRUB AREAS/ROOMS OR OTHER AREAS OF THE FACILITY WHERE A SS
SHELF IS REQUIRED. PRICING BASED UPON A 36" WIDTH.
A5200 TOILET TISSUE 4 NO / NO VC A CONCEALED SURFACE MOUNTED, DOUBLE ROLL, SATIN FINISH STAINLESS STEEL, TOILET TISSUE DISPENSER. UNIT ACCOMMODATES TWO STANDARD-CORE TOILET TISSUE ROLLS THROUGH 5" IN DIAMETER. SPINDLES ARE CHROME PLATED PLASTIC WITH A HEAVY-DUTY INTERNAL SPRING AND TURN FREELY FOR NON-CONTROLLED DELIVERY. FOR GENERAL PURPOSE USE IN RESTROOMS.
E0042 WORKSTATION 89 NO / NO VV THIS TYPICAL INCLUDES: 1 TOOL RAIL 2 PAPER TRAY 1 DIAGONAL TRAY 1 FREESTANDING WORK SURFACE 1 MOBILE PEDESTAL, BOX/FILE 1
ADJUSTABLE KEYBOARD TRAY
F0225 CHAIR 8 NO / NO VV DINING ROOM CHAIR WITH GLIDES. CHAIR HAS STRAIGHT LEGS WITH CUSHIONED CLOTH OR VINYL SEAT.
F0275 CHAIR 89 NO / NO VV HIGHBACK CONTEMPORARY SWIVEL CHAIR, 41" HIGH x 23" WIDE x 23" DEEP WITH FIVE CASTER SWIVEL BASE AND ARMS. BACK AND SEAT ARE FOAM
PADDED AND UPHOLSTERED WITH EITHER WOVEN TEXTILE FABRIC OR VINYL.
F0305 CHAIR 7 NO / NO VV SINGLE SEAT WAITING ROOM CHAIR WITH FOAM PADDED SEAT AND BACK. UPHOLSTERED WITH EITHER WOVEN FABRIC TEXTILE OR VINYL. ARMS AND FLOOR GLIDES INCLUDED.. Upholstered with either woven fabric textile or vinyl. Arms and floor glides included.
F0500 JANITOR'S CART 1 NO / NO VV UTILITY CART, 32-39" HIGH X 36" WIDE X 24" DEEP, WITH 4 (FOUR) HEAVY DUTY CASTER WHEELS.
F0505 MOP BUCKET 1 NO / NO VV ROUND WASTEPAPER BASKET, APPROXIMATELY 18" HIGH X 16" DIAMETER. THIS METAL UNIT IS USED TO COLLECT AND TEMPORARILY STORE SMALL QUANTITIES OF PAPER REFUSE IN PATIENT ROOMS, ADMINISTRATIVE AREAS AND NURSING STATIONS.
NSN: 7520002051857
JSN: F2000
F0795 TABLE 2 NO / NO VV DINING TABLE. ROUND 42" DIAMETER OR SQUARE 42" X 42". USED IN DINING FACILITIES AND CAN COMFORTABLY SEAT UP TO FOUR (4) PERSONS.
F2010 WASTEPAPER 4 NO / NO VV STEP-ON WASTEPAPER BASKET WITH INNER LINER AND FOOT PETAL ACTIVATED FLIP TOP.
F2015 WASTEPAPER 1 NO / NO VV METAL RECEPTACLE FOR SOILED / USED TOWELS OR WASTE. EQUIPPED WITH A REMOVABLE TAPERED TOP WITH TWO INDEPENDENTLY
OPERATING SELF-CLOSING, SPRING HINGED DOORS.
K1552 COFFEE 1 YES / NO VV SPACE SAVING FRONT TO BACK AUTOMATIC COFFEE MAKER. INCLUDES A HEATING TANK, CONNECTION FOR A COLDWATER SUPPLY, DECANTER SERVICE WITH THREE BURNERS, FUNNEL AND A WATER FLOW CONTROLLER. AUTOMATICALLY SHUTS OFF THE WATER FLOW WHEN ENOUGH HAS PASSED THROUGH TO FILL THE POT. PROVIDE PLUMBED WITH A HOT WATER FAUCET TO THE SIDE FOR MAKING OTHER HOT DRINKS (TEA, CIDER, COCOA, ETC.).
K4665 MICROWAVE 1 YES / NO VV COUNTER MOUNTED MICROWAVE OVEN. THE EXTERIOR CABINET CAN BE METAL OR HEAVY-DUTY IMPACT RESISTANT PLASTIC. OVEN HAS TOUCH PAD CONTROLS, DIGITAL TIMER, POWER LEVEL SELECTOR AND PREPROGRAMMED SELECTORS FOR COMMONLY COOKED ITEMS.
M0512 TELEVISION, 60" 12 YES / YES VV A HIGH DEFINITION (HDTV) MULTIMEDIA, SLIM DESIGN, 60"W TO 65"W COLOR TELEVISION. THE TV WILL HAVE A 16.9 WIDE SCREEN ASPECT RATIO WITH FULL HD 1080P RESOLUTION AND HDMI CONNECTIONS. TV MAY BE LED, PLASMA OR LCD. TV WILL INCLUDE A STAND.
M2050 WIRE SHELF 2 NO / NO VC STORAGE SHELVING UNIT. UNIT IS CORROSION RESISTANT STAINLESS STEEL, GALVANIZED STEEL OR BAKED ENAMEL ON STEEL. IT CONTAINS 5 ADJUSTABLE SHELVES WITH 400 POUND LOAD CAPACITY. AVAILABLE IN OPEN OR CLOSED (END PANELS) DESIGNS. UNIT IS DESIGNED FOR
STORAGE AND LIGHT INDUSTRIAL APPLICATIONS.
R7250 REFRIGERATOR 1 YES / NO VV REFRIGERATOR/FREEZER UNIT. IT INCLUDES ROLL OUT WHEELS AND IS EQUIPPED FOR AN OPTIONAL AUTOMATIC ICEMAKER.
GENERAL NOTES
Revisions: Date: 35 OF 102
Megan Matt's Stamp
Megan
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64
17 18 19 20 21 25 26 27 28 29 30 31 32
IN-09.03-04
IN-04.02-12
IN-09.03-01
IN-04.02-11
IN-09.03-03
IN-09.03-02
IN-04.02-10
IN-04.02-09 IN-04.02-08 IN-04.02-07 IN-04.02-05 IN-04.02-04 IN-04.02-03 IN-04.02-02
IN-04.02-14
IN-04.02-00
CHANGE MGMT
USER
IV SUPPORT
MECHANICAL
HAC
STORAGE
IV TESTING
IV TESTING
TR
STAFF BREAK
WAITING ALCOVE
RESTROOM
CORRIDOR
CR11-9
ELECTRICAL ROOM
RESTROOM
RESTROOM
RESTROOM
MECHANICAL
IN-04.02-13
IN-04.02-06
IN-04.02-01
IN-15.51-01
IN-03.01-01
STG
103A
ELECTRICAL
CLOSET
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AW001
SIGNAGE LOCATION PLAN &
MESSAGE SCHEDULE 009A
MK MC
CONSTRUCTION
DOCUMENT
6/14/2024
557-21-703
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
GENERAL NOTES
1. ALL FINAL MESSAGES AND LOCATIONS ARE TO BE
REVIEWED AND APPROVED BY VA SIGNAGE MANAGER OR VA
COR PRIOR TO FABRICATON.
1/8" = 1'-0"
LEVEL 1 - SIGNAGE LOCATION PLAN
SIGNAGE MESSAGE SCHEDULE
MARK
ROOM
NUMBER ROOM NAME MESSAGE COMMENTS
IN-03.01 - NUMBER IDENTIFICATION
IN-03.01-01 103A STG ROOM NUMBER IDENTIFICATION ONLY
IN-04.02 - ROOM IDENTIFICATION WITH INSERT
IN-04.02-00 100 TR TR
IN-04.02-01 101 MECHANICAL MECHANICAL
IN-04.02-02 102 HAC HAC
IN-04.02-03 103 IV TESTING IV TESTING PHASE II - NUMBER CHANGES TO "103A", MESSAGE CHANGES TO "CLASSROOM"
IN-04.02-04 103 IV TESTING IV TESTING PHASE II - NUMBER CHANGES TO "103B", MESSAGE CHANGES TO "CLASSROOM"
IN-04.02-05 104 IV SUPPORT IV SUPPORT PHASE II - MESSAGE CHANGES TO "CLASSROOM"
IN-04.02-06 104 IV SUPPORT IV SUPPORT PHASE II - MESSAGE CHANGES TO "CLASSROOM"
IN-04.02-07 106 IV TESTING IV TESTING PHASE II - NUMBER CHANGES TO "106A", MESSAGE CHANGES TO "CLASSROOM"
IN-04.02-08 106 IV TESTING IV TESTING PHASE II - NUMBER CHANGES TO "106B", MESSAGE CHANGES TO "CLASSROOM"
IN-04.02-09 107 STAFF BREAK STAFF BREAK
IN-04.02-10 108 CHANGE MGMT USER CHANGE MGMT USER
IN-04.02-11 109 MECHANICAL MECHANICAL
IN-04.02-12 114 STORAGE STORAGE
IN-04.02-13 115 ELECTRICAL CLOSET ELECTRICAL CLOSET
IN-04.02-14 116 ELECTRICAL ELECTRICAL
IN-09.03 - RESTROOM IDENTIFICATION (ACCESSIBLE)
IN-09.03-01 110 RESTROOM SEE ENLARGED SIGNAGE FOR MESSAGE
IN-09.03-02 111 RESTROOM SEE ENLARGED SIGNAGE FOR MESSAGE
IN-09.03-03 112 RESTROOM SEE ENLARGED SIGNAGE FOR MESSAGE
IN-09.03-04 113 RESTROOM SEE ENLARGED SIGNAGE FOR MESSAGE
IN-15.51 - CEILING MOUNTED DIRECTIONAL
IN-15.51-01 105 WAITING ALCOVE WAITING FLAT INSERT
PROJECT
NORTH
TRUE NORTH
(DASHED)
Revisions: Date: 36 OF 102
Megan Matt's Stamp
Megan
IV Testing
LEFT ALIGN TEXT
& BRAILLE
3/4"
1/2"
3/4"
3/8"
3/4"
5/8"
5/8"
1/4" 3/8"
1 1/4"
1/2"
9"
MESSAGE INSERT
RESTROOM
LEFT ALIGN TEXT
& BRAILLE
3/4"
3/4"
5 3/8"
3/4"
1"
3/8" 1/4" 1/2"
5/8"
1/4" 3/8"
1 1/4"
1/2"
9"
CENTER ALIGN SYMBOL,
TEXT, & BRAILLE
IN-04.02
2" UNO ON LOCATION PLAN
A F
F
2" UNO ON LOCATION PLAN
A F
F
IN-09.03
2" UNO ON LOCATION PLAN
A F
F
IN-03.01
103A
LEFT ALIGN TEXT
& BRAILLE
3/4"
1/8" 5/8"
1/4" 3/8"
1 1/4"
1/2"
9"
1/8" 1 1/2"
3"
1 1/2" 1/8"
3' - 4"
CENTER TEXT
WAITING
5/8"
SIDE VIEW
STRUCTURE ABV
ANGLE BRACE
GYP. CEILING *GYP. SHALL NOT SUPPORT
WEIGHT OF CEILING MOUNTED
SIGNAGE AND INSTEAD SHALL
TIE INTO STRUCTURE ABOVE.
STEEL PLATE
RIGHT SIDELEFT SIDE
M A
X
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
AW002
ENLARGED SIGNAGE - IN-03.01,
IN-04.02, & IN-09.03 009A
MK AB
CONSTRUCTION
DOCUMENT
6/14/2024
557-21-703
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
GENERAL NOTES
1. SEE AW001 FOR SIGNAGE LOCATION PLAN.
2. SEE SPECIFICATION SECTION 10 14 00 SIGNAGE FOR
MATERIALS AND FINISHES.
6" = 1'-0"
IN-04.02 - ROOM ID WITH INSERT
Revisions: Date:
6" = 1'-0"
IN-04.02 - DIMENSIONS
6" = 1'-0"
IN-09.03 - RESTROOM ID
6" = 1'-0"
IN-09.03 - DIMENSIONS
1" = 1'-0"
SIGNAGE MOUNTING HEIGHTS
6" = 1'-0"
IN-03.01 - ROOM NUMBER IDENTIFICATION
6" = 1'-0"
IN-03.01 - DIMENSIONS
3" = 1'-0"
IN-15.51 - DIMENSIONS
3" = 1'-0"
IN-15.51 - CEILING MOUNTED DIRECTIONAL
1 1/2" = 1'-0"
CEILING MOUNTED SIGNAGE DETAIL
Megan Matt's Stamp
Megan
ABBREVIATIONS
PLYWOODPLWD
APA AMERICAN PLYWOOD ASSOCIATION
BLKG BLOCKING
PENNYWEIGHT (NAILS)d
BC
DS
BOF
CA
DRAG STRUT
CONCRETE (EXPANSION) ANCHOR
BOTTOM CHORD
BOTTOM OF FOOTING
PA
NLG
GRD
HDR
POWDER ACTUATED
GIRDER
NAILING
HEADER
TOW
TC
SHTHG
TOP OF WALL
SHEATHING
TOP CHORD
TWS THREADED WELDED STUD
THREADED RODTR
SJI STEEL JOIST INSTITUTE
POUNDS PER CUBIC FOOTPCF
MILES PER HOURMPH
IJ
ISOLATION JOINT
HIGH STRENGTH BOLTHSB
DEEPDP
DEMOLISH, DEMOLITIONDEMO
DIVIDER BEAM, DROPPED BEAMDB
AMERICAN SOCIETY OF CIVIL ENGINEERSASCE
AMERICAN IRON AND STEEL INSTITUTEAISI
ELEV ELEVATOR
JOIST
JOINT
JST
K
JT
POUND
LEVEL
KSI
LB, #
LEV
L
LL
LLH
LONGIT
LOC
LLV
LF
KSF
KIP (1,000 LB)
KIPS PER SQUARE FOOT
KIPS PER SQUARE INCH
LENGTH, ANGLE
LINEAL FOOT
LIVE LOAD
LONG LEG HORIZONTAL
LONG LEG VERTICAL
LONGITUDINAL
LOCATION, LOCATE
MATERIAL
MINIMUM
MAXIMUM
LSH
MATL
MB
MECH
MIN
MISC
MFR
MAX
NOMINAL
NUMBER
NF
NO, #
NOM
NIC
NS
NTS
OD
OC
N-S
MTL METAL
MECHANICAL
MANUFACTURER
MISCELLANEOUS
NEAR FACE
NOT IN CONTRACT
NORTH-SOUTH
NEAR SIDE
NOT TO SCALE
ON CENTER
OUTSIDE DIAMETER
MACHINE BOLT
LONG SLOTTED HOLE
OPENING
OPPOSITE
PANEL
PLACES
OPP
OPNG
PCC
OSH
PERP
PL
PNL
PLCS
PEN
RADIUS
PS
PSI
PSF
PT
PVC
RD
R, RAD
P.T.
PREFAB
PP, PJP
PRECAST CONCRETE
PENETRATION
PERPENDICULAR
PLATE, PROPERTY LINE
PARTIAL JOINT PENETRATION
PREFABRICATED
PRESTRESSED CONCRETE
POUNDS PER SQUARE INCH
POUNDS PER SQUARE FOOT
POINT, PRESSURE TREATED
POLYVINYL CHLORIDE
ROOF DRAIN
POST-TENSIONED
OVERSIZED HOLE
OUTSIDE FACEO.F.
LOW POINTLPT
AB
ACI
AND
AT
ANCHOR BOLT
ADJ
ANCH
ALT
AISC
AR
AWS
ASTM
ARCH
APPROX
ANCHOR ROD
APPROXIMATE
ANCHOR
ALTERNATE
ADDITIONALADDL
AMERICAN WELDING SOCIETY
AMERICAN SOCIETY FOR TESTING AND MATERIALS
ARCHITECT, ARCHITECTURAL
AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ADJACENT, ADJUSTABLE
AMERICAN CONCRETE INSTITUTE
BAL
B/
BLDG
BF
BOT
BRG
BTWN
BU
BM
BALANCE
BETWEEN
BEARING
BOTTOM
BEAM
BUILDING
BUILT-UP
BRACED FRAME, BOTTOM FLANGE
BOTTOM OF
C
CANTIL
CC
CAP
CIP
CJ
CLR
CL
CG
CAPACITY
CLEAR
CENTERLINE
CAST-IN-PLACE
CANTILEVER
CONTROL JOINT, CONSTRUCTION JOINT
CENTER OF GRAVITY
CENTER-TO-CENTER
CAMBER, CHANNEL
COL
CONC
CONT
CONN
CONST
CU YD
CTR
COORD
CONTR
CUBIC YARD
CENTER, CENTERED
COORDINATE
CONTRACTOR
CONSTRUCTION
CONNECTION
CONCRETE
COLUMN
DBA
DBL
DET
DEG,
DIAG
DIA
DIM
DICA
DIAPH
DIMENSION
DIAPHRAGM
DIAGONAL
DIAMETER
DETAIL
DEGREE
DOUBLE
DEFORMED BAR ANCHOR
CONTINUE, CONTINUOUS
DRILLED-IN CONCRETE ANCHOR
CONCRETE MASONRY UNITCMU
REQUIRED
RETURN
SCHEDULE
SECTION
SHEET
SIMILAR
REQD
REINF
RTN
SCHED
SIM
SHT
SECT
SQUARE
STIFFENER
STIRRUP
STEEL
SUPPORT
SPEC
SPC
SST
STD
SSH
SQ
STL
STIR
STIF
SYMM
SPRT
STRUCT
SOG SLAB ON GRADE
SPACE, SPACED, SPACING
SPECIFICATION
STAINLESS STEEL
SHORT SLOTTED HOLE
STANDARD
STRUCTURAL
SYMMETRICAL, SYMMETRY
REINFORCING
TOP OF
THROUGH
SW
T&B T/
THK
THRU
TOF
TOS
TOC
TEMP
TYPICAL
WIDTH, WIDE FLANGE
WITH
WOOD
VERTICAL
TYP
UNO
W
WD
WHS
W/
VERT
TRANS
THICK, THICKNESS
TRANSVERSE
UNLESS NOTED OTHERWISE
WELDED HEADED STUD
TOP OF CONCRETE
TOP OF STEEL
TOP OF FOOTING
TOP AND BOTTOM
TEMPERATURE
SHEAR WALL
WEIGHTWT
WP
WWR
WORK POINT
WELDED WIRE REINFORCEMENT
W/O WITHOUT
DO
DN
DWL
DWG
EA
EE
EJ
EL
EF
(E), EXIST
ELEVATION
EACH FACE
EACH END
EACH, EPOXY (ADHESIVE) ANCHOR
EXISTING
DOWEL
DRAWING
DITTO
DOWN
ENGR
ETC
ES
EQUIP
EQ
EMBED
EXP
EW
E-W
FD
EXT
ET CETERA
FLOOR DRAIN
EAST-WEST
EACH WAY
EXPANSION
EXTERIOR
EMBEDMENT
ENGINEER
EQUIPMENT
EACH SIDE
ELECTRICALELEC
EXPANSION JOINT
EARTHQUAKE, EQUAL
FF
FEMA
FDN
FIN
FLG
FLR
FS
FT, '
FTG
GALV
GA
FAR SIDE
GALVANIZED
FEET
FOOTING
GAGE, GAUGE
FOUNDATION
FAR FACE, FINISH FLOOR
FINISH
FLOOR
FLANGE
GEN
GB, GR BM
GRND
HGR
HPT
HK
HORIZ
HIGH POINT
HANGER
HOOK
HORIZONTAL
GROUND
GRADE BEAM
GENERAL
FEDERAL EMERGENCY MANAGEMENT AGENCY
INSIDE FACE
INCH
INCLUDE
INFORMATION
INTERIOR
HT
HSS
I.F.
IBC
ID
INFO
INCL
IN, "
INT
HEIGHT
INTERNATIONAL BUILDING CODE
HOLLOW STRUCTURAL SECTION
INSIDE DIAMETER
DEAD LOADDL
REFERENCEREF
PLF POUNDS PER LINEAR FOOT
LONG LEGS BACK TO BACKLLBB
COMPLETE JOINT PENETRATIONCJP, CP
REMAINDERREM
OPEN WEB JOISTOWJ
CONCRETE REINFORCED STEEL INSTITUTECRSI
STAG STAGGER, STAGGERED
MF MOMENT FRAME
CONTROL DENSITY FILLCDF
BP BASE PLATE
DESIGN-BUILDD-B
EXT GR EXTERIOR GRADE
GL, GLU LAM GLUE LAMINATED WOOD
GLB GLUE LAMINATED BEAM
HLDN HOLD DOWN
PRCST PRECAST
REBAR REINFORCING STEEL BARS
T&G TONGUE AND GROOVE
LVL LAMINATED VENEER LUMBER
PSL PARALLEL STRAND LUMBER
GWB
HF HEM-FIR
GYPSUM WALL BOARD
FL
FOS
FLUSH LEDGER
FACE OF STUD
OSB
GE GABLE END
ORIENTED STRAND BOARD
SWS SHEAR WALL SCHEDULE
WIJ WOOD I-JOIST
LSL LAMINATED STRAND LUMBER
DIST DISTANCE
THP TENDON HIGH POINT
HD HOLDOWN
AFF ABOVE FINISHED FLOOR
FB FLUSH BEAM
DOUGLAS FIRDF
COR CONTRACTING OFFICERS REPRESENTATIVE
GENERAL
CODES
DESIGN CRITERIA
SUBMITTALS
RENOVATION:
CONCRETE ANCHORAGE
STEEL
DRAWINGS INDICATE GENERAL AND TYPICAL DETAILS OF CONSTRUCTION. TYPICAL DETAILS AND NOTES SHOWN ON THESE DRAWINGS ARE PART OF THE CONSTRUCTION CONTRACT AND SHALL BE PROVIDED BY THE CONTRACTOR. TYPICAL DETAILS MAY NOT NECESSARILY BE INDICATED ON THE PLANS BUT SHALL APPLY AS SHOWN OR DESCRIBED IN THE DETAILS AND NOTES. WHERE CONDITIONS ARE NOT SPECIFICALLY INDICATED BUT ARE OF SIMILAR CHARACTER TO DETAILS SHOWN, SIMILAR DETAILS OF CONSTRUCTION SHALL BE USED.
STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH ARCHITECTURAL DRAWINGS AND ALL OTHER CONTRACT DOCUMENTS FOR BIDDING AND CONSTRUCTION. CONTRACTOR SHALL VERIFY DIMENSIONS AND CONDITIONS FOR COMPATIBILITY AND SHALL NOTIFY CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF ALL
DISCREPANCIES PRIOR TO CONSTRUCTION.
DISCREPANCIES: IN CASE OF DISCREPANCIES BETWEEN DRAWINGS, SPECIFICATIONS, REFERENCE STANDARDS, OR GOVERNING CODE, THE MORE STRINGENT REQUIREMENTS SHALL GOVERN. CONTRACTOR SHALL NOTIFY THE CONTRACTING OFFICER'S REPRESENTATIVE (COR) OF DISCREPANCIES AND OBTAIN DIRECTION PRIOR TO PROCEEDING. NOTES ON INDIVIDUAL STRUCTURAL DRAWINGS SHALL TAKE PRIORITY OVER GENERAL STRUCTURAL NOTES. DIMENSIONS NOTED IN THE DRAWINGS SHALL BE FOLLOWED. DO NOT SCALE DRAWINGS.
SPECIFICATIONS: REFER TO SPECIFICATIONS FOR INFORMATION IN ADDITION TO THESE NOTES AND DRAWINGS.
ARCHITECTURAL: REFER TO ARCHITECTURAL DRAWINGS FOR ELEVATIONS, SLOPES, DEPRESSIONS, NON- BEARING WALLS, FASCIA, ELEVATORS, STAIRS, CURBS, DRAINS, RAILINGS, WATERPROOFING, FINISHES, ETC.
CONTRACTOR-INITIATED CHANGES: SHALL BE SUBMITTED IN WRITING COR FOR APPROVAL AT LEAST 10 WORKING DAYS PRIOR TO FABRICATION AND CONSTRUCTION. CHANGES SHOWN ON SHOP DRAWINGS OR SUBMITTALS ONLY
WILL NOT SATISFY THIS REQUIREMENT.
CONTRACTOR RESPONSIBILITIES: DRAWINGS REPRESENT DESIGN OF STRUCTURE IN COMPLETED FORM.
CONTRACTOR SHALL BE RESPONSIBLE FOR METHODS, SEQUENCES, AND SAFETY PRECAUTIONS REQUIRED TO
PERFORM WORK.
CONTRACTOR SHALL DESIGN AND PROVIDE TEMPORARY SHORING AND BRACING OF ALL STRUCTURAL MEMBERS, EXISTING CONSTRUCTION, AND SOIL EXCAVATION AS REQUIRED. SHORING AND BRACING SHALL NOT BE REMOVED UNTIL ALL FINAL CONNECTIONS HAVE BEEN COMPLETED IN ACCORDANCE WITH THE DRAWINGS, AND MATERIALS
HAVE ACHIEVED DESIGN STRENGTH.
EXISTING CONDITIONS: CONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS, MEMBER SIZES, AND CONDITIONS PRIOR TO COMMENCING ANY WORK. ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS ARE INTENDED AS GUIDELINES ONLY AND MUST BE VERIFIED. EXISTING CONDITIONS SHOWN ON DRAWINGS ARE BASED EITHER ON SITE OBSERVATIONS, ORIGINAL DRAWINGS, OR WERE ASSUMED BASED ON EXPECTED CONDITIONS. IF EXISTING CONDITIONS DO NOT CLOSELY MATCH CONDITIONS SHOWN ON DRAWINGS, OR IF EXISTING MATERIALS ARE OF QUESTIONABLE OR SUBSTANDARD QUALITY, NOTIFY COR PRIOR TO COMMENCING
ANY WORK.
SPECIAL INSPECTION PER IBC SECTION 1704, SHALL BE PERFORMED BY AN SPECIAL INSPECTIONS AGENCY PROVIDED BY THE CONTRACTOR AND APPROVED BY THE COR. SEE SPECIFICATIONS AND STRUCTURAL
INSPECTION SCHEDULE ON SHEET S-002 FOR ADDITIONAL INFORMATION.
BUILDING CODE: ALL MATERIALS, WORKMANSHIP, DESIGN, AND CONSTRUCTION SHALL CONFORM TO THE DRAWINGS, SPECIFICATIONS AND THE INTERNATIONAL BUILDING CODE (IBC), 2021 EDITION (VA 18-8 STANDARDS).
RISK CATEGORY: IV (IBC TABLE 1604.5)
STANDARDS: REFERENCE TO ASTM AND OTHER STANDARDS SHALL MEAN THE LATEST EDITION REFERENCED IN THE 2021 IBC, UNLESS NOTED IN THESE DOCUMENTS OR DESIGNATED BY THE GOVERNING CODE.
EARTHQUAKE DESIGN DATA:
SEISMIC IMPORTANCE FACTOR Ie 1.5 (ASCE 7 TABLE 1.5-2)
COMPONENT IMPORTANCE FACTOR IP= 1.5 (ASCE 7 13.1.3)
SITE CLASS (ASSUMED) D
SS = 0.260 (ASCE 7 SECTION 11.4.1)
S1 = 0.088 (ASCE 7 SECTION 11.4.1)
SDS = 0.210 (ASCE 7 SECTION 11.4.4)
SD1 = 0.120 (ASCE 7 SECTION 11.4.4)
SEISMIC DESIGN CATEGORY C (ASCE 7 SECTION 11.6)
SHOP DRAWINGS SHALL BE SUBMITTED COR FOR REVIEW PRIOR TO FABRICATION OR
CONSTRUCTION OF THESE ITEMS:
POST INSTALLED ANCHORS
CONTRACTOR SHALL REVIEW AND STAMP SUBMITTALS PRIOR TO SUBMISSION. DIMENSIONS AND QUANTITIES ARE CONTRACTOR'S RESPONSIBILITY AND WILL NOT BE REVIEWED. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MATERIALS PLACED PRIOR TO RECEIPT OF REVIEWED SHOP DRAWINGS. CONTRACTOR SHALL ALLOW A MINIMUM
OF 10 WORKING DAYS FOR REVIEW.
SHOP DRAWING SUBMITTALS PROCESSED BY THE ENGINEER ARE NOT CHANGE ORDERS. THE PURPOSE OF SHOP DRAWING SUBMITTALS BY THE CONTRACTOR IS TO DEMONSTRATE TO THE ENGINEER THAT THE CONTRACTOR UNDERSTANDS THE DESIGN CONCEPT BY INDICATING WHICH MATERIAL IS INTENDED TO BE FURNISHED AND INSTALLED AND BY DETAILING THE INTENDED FABRICATION AND INSTALLATION METHODS. IF DEVIATIONS, DISCREPANCIES, OR CONFLICTS BETWEEN SHOP DRAWING SUBMITTALS AND THE CONTRACT DOCUMENTS ARE DISCOVERED EITHER PRIOR TO OR AFTER SHOP DRAWING SUBMITTALS ARE PROCESSED BY THE ENGINEER, THE
DESIGN DRAWINGS AND SPECIFICATIONS SHALL CONTROL AND SHALL BE FOLLOWED.
DEMOLITION: CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS BEFORE COMMENCING ANY DEMOLITION.
SHORING SHALL BE INSTALLED TO SUPPORT EXISTING CONSTRUCTION AS REQUIRED AND IN A MANNER SUITABLE TO THE WORK SEQUENCES. EXISTING REINFORCING SHALL BE SAVED WHERE POSSIBLE AND AS NOTED ON DRAWINGS. SAW-CUTTING, IF AND WHERE USED, SHALL NOT CUT EXISTING REINFORCING THAT IS TO BE SAVED.
DEMOLITION DEBRIS SHALL NOT BE ALLOWED TO DAMAGE OR OVERLOAD THE EXISTING STRUCTURE.
CONSTRUCTION LOADING (INCLUDING DEMOLITION DEBRIS) ON EXISTING FLOOR SYSTEMS SHALL BE LIMITED TO 20 PSF.
1. ALL NEW OPENINGS THROUGH EXISTING WALLS, SLABS, AND BEAMS SHALL BE ACCOMPLISHED BY SAWCUTTING WHEREVER POSSIBLE. ALL NEW OPENINGS SHALL BE SAWCUT NEAT AND CLEAN; NO OVERCUTTING AT OPENING CORNERS SHALL BE ALLOWED, UNLESS NOTED OTHERWISE. AS REQUIRED, CORE DRILL CORNERS AND CHIP, GRIND, OR CUT THE CORNERS TO PROVIDE REQUIRED DIMENSIONS.
2. CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND LOCATION OF MEMBERS PRIOR TO CUTTING ANY
OPENINGS.
3. SMALL ROUND OPENINGS SHALL BE ACCOMPLISHED BY CORE DRILLING.
POST-INSTALLED ANCHORS INTO NORMAL-WEIGHT CONCRETE SHALL BE THE FOLLOWING TYPES:
ADHESIVE ANCHORS SHALL BE HILTI HIT-RE 500-V3 (ESR-3814), HILTI HIT-HY 200 (ESR-4868), SIMPSON SET-XP
(ESR-2508), OR DEWALT PURE 110+ (ESR-3298).
REFERENCE STANDARDS: STRUCTURAL STEEL SHALL CONFORM TO ALL REQUIREMENTS OF THE FOLLOWING
DOCUMENTS:
AISC 360 "SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS"
AISC 303 "CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES"
AWS D1.1 "STRUCTURAL WELDING CODE - STEEL"
AISC 348 "SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS"
MATERIALS:
TYPE OF MEMBER ASTM SPECIFICATION YIELD
WIDE FLANGES (W), STRUCTURAL TEES (WT) A992 50 KSI
PLATES, ANGLES, CHANNELS A36 36 KSI
AND BARS
STEEL PIPES A53 (TYPE E OR S, GRADE B) 35 KSI
HOLLOW STRUCTURAL STEEL (HSS) A500 (GRADE B) 46 KSI
MACHINE BOLTS (MB) A307
CONNECTION BOLTS (HSB) A325
ANCHOR RODS (AR) AND THREADED RODS (TR) F1554 GRADE 55, WELDABLE
BOLTED CONNECTIONS NOT SPECIFIED AS SLIP-CRITICAL NEED ONLY BE TIGHTENED TO AISC SNUG-TIGHT CRITERIA, UNLESS NOTED OTHERWISE. CONNECTION PLATES SHALL HAVE AISC STANDARD ROUND HOLES UNLESS NOTED OTHERWISE. ALL OVERSIZED OR SLOTTED HOLES SHALL HAVE WASHERS PROVIDED IN ACCORDANCE WITH
AISC 360, UNLESS NOTED OTHERWISE.
WELDING: ALL WELDS SHALL COMPLY WITH AWS D1.1. WELDS SHALL BE MADE USING LOW HYDROGEN E70XX ELECTRODES. ONLY AWS PREQUALIFIED WELDED JOINTS SHALL BE USED. SHOP DRAWINGS SHALL SHOW ALL WELDING WITH AWS A2.4 STANDARD SYMBOLS. WELDS SHOWN ON DRAWINGS ARE MINIMUM SIZES. INCREASE WELD SIZE TO AWS MINIMUM SIZES BASED ON PLATE THICKNESS. WELDS NOT SPECIFIED SHALL BE CONTINUOUS
1/4" FILLET WELDS.
WELDS SHOWN ON DRAWINGS ARE FOR FINAL CONNECTIONS. UNLESS FIELD WELD SYMBOLS ARE SHOWN, CONTRACTOR SHALL BE RESPONSIBLE FOR DETERMINING IF A WELD SHOULD BE SHOP OR FIELD WELDED IN
ORDER TO FACILITATE STEEL ERECTION.
CONTRACTOR SHALL BE RESPONSIBLE FOR ALL JOINT PREPARATIONS AND WELDING PROCEDURES, INCLUDING ROOT OPENINGS AND FACE DIMENSIONS, GROOVE ANGLES, BACKING BARS, COPES, TAPERS, AND SURFACE
ROUGHNESS.
DIMENSIONAL TOLERANCE FOR STRUCTURAL STEEL MEMBERS SHALL BE PER THE AISC CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES, SECTION 6.4 AND ASTM SPECIFICATION A6. UNLESS SPECIFICALLY ALLOWED BY THE ENGINEER, COLUMN MEMBERS SHALL NOT BE MODIFIED BY THE ROTARY STRAIGHTENING
PROCESS.
POST-INSTALLED ANCHORS SHALL NOT BE USED AS SUBSTITUTES FOR CAST-IN-PLACE ANCHOR BOLTS OR
REINFORCING STEEL UNLESS SPECIFICALLY APPROVED BY THE CONTRACTING OFFICER.
PRODUCT SUBSTITUTES PROPOSED BY THE CONTRACTOR SHALL BE SUBMITTED FOR REVIEW WITH IAPMO OR
ICC-ES REPORTS INDICATING EQUIVALENT OR GREATER LOAD CAPACITIES.
NO REINFORCING BARS SHALL BE CUT TO PLACE POST-INSTALLED ANCHORS. ALL DEFECTIVE ANCHOR HOLES SHALL
BE GROUTED WITH EPOXY ADHESIVE AND A NEW HOLE DRILLED A MINIMUM OF 3 BOLT DIAMETERS AWAY. NOTIFY
THE CONTRACTING OFFICER WHERE DEFECTIVE ANCHOR HOLES OCCUR PRIOR TO DRILLING IN NEW ANCHOR
LOCATION.
37358
A
A
F O
P R
N I
S E
S O
S T
WFO
A E T
E E
L
NE
I G
N
R
N
SH
I
O
N
G T
GNEAR
U T C
U R T S
E R
NI
E
P A U L
N
AT
HAN CRO
R E
K C
L
728 134th Street SW, Suite 200 Everett, Washington 98204 Ph: 425.741.3800 www.reidmiddleton.com © Copyright 2024 Reid Middleton, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
6/14/
S001
ABBREVIATIONS, SHEET INDEX &
GENERAL STRUCTURAL NOTES 009A
SAH EP
CONSTRUCTION
DOCUMENT
06/14/24
557-21-703
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
S001 ABBREVIATIONS, SHEET INDEX & GENERAL STRUCTURAL NOTES
S101 FLOOR PLAN - WEST
S102 FLOOR PLAN - EAST
S401 TYPICAL LIGHT-GAUGE FRAMING
S501 TYPICAL CONCRETE DETAILS
SHEET INDEX
Revisions: Date: 38 OF 102
86 SF
MECH
440 SF
CHANGE MGMT
USER
73 SF
RESTROOM
601 SF
CLASSROOM
106A
633 SF
CLASSROOM
106B
199 SF
STAFF BREAK
80 SF
RESTROOM
77 SF
RESTROOM
106 SF
RESTROOM
S
F
S T
O R
A G
E
51 SF
ELECTRICAL
CLOSET
106 SF
WAITING
ALCOVE
1 2 3 4 5 6 7 8
17 18 19 20 21
SEE NOTE 3
SEE NOTE 2
AREA SHOWN
PROJECT
NORTH
TRUE NORTH
(DASHED)
BUILDING 9A
37358
A
A
F O
P R
N I
S E
S O
S T
WFO
A E T
E E
L
NE
I G
N
R
N
SH
I
O
N
G T
GNEAR
U T C
U R T S
E R
NI
E
P A U L
N
AT
HAN CRO
R E
K C
L
728 134th Street SW, Suite 200 Everett, Washington 98204 Ph: 425.741.3800 www.reidmiddleton.com © Copyright 2024 Reid Middleton, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
6/14/
S101
FLOOR PLAN - WEST
009A
SAH EP
CONSTRUCTION
DOCUMENT
06/14/24
557-21-703
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
LEGEND
GENERAL NOTES
PLAN NOTES (THIS SHEET ONLY)
KEY PLAN
PROJECT
NORTH
TRUE NORTH
(DASHED)
3/16" = 1'-0"
FLOOR PLAN - PHASE II WEST
1. SEE DETAILS ON SHEET S401 AND ARCHITECTURAL DRAWINGS FOR
TYPICAL INTERIOR METAL WALLS STUD FRAMING DETAIL
2. EXISTING CONCRETE EQUIPMENT PAD TO REMAIN.
3. EXISTING MECHANICAL UNIT TO REMAIN.
A. CONTRACTOR TO COORDINATE WITH MECHANICAL AND
ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
Revisions: Date: 39 OF 102
121 SF
ELECTRICAL
101 SF
TR ROOM
99 SF
HAC
682 SF
CLASSROOM
103A
692 SF
CLASSROOM
103B
634 SF
CLASSROOM
104A
1677 SF
CORRIDOR
CR11-9
191 SF
MECHANICAL
102A
8 9 10 11 12 13 14 15 16 60 61 62 63 64
25 26 27 28 29 30 31 32 58
SEE NOTE 3
SEE NOTE 2
E10 S501
E10 S501
TYP
TYP
SEE NOTE 4
AREA SHOWN
PROJECT
NORTH
TRUE NORTH
(DASHED)
BUILDING 9A
37358
A
A
F O
P R
N I
S E
S O
S T
WFO
A E T
E E
L
NE
I G
N
R
N
SH
I
O
N
G T
GNEAR
U T C
U R T S
E R
NI
E
P A U L
N
AT
HAN CRO
R E
K C
L
728 134th Street SW, Suite 200 Everett, Washington 98204 Ph: 425.741.3800 www.reidmiddleton.com © Copyright 2024 Reid Middleton, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
6/14/
S102
FLOOR PLAN - EAST
009A
Checker Author
CONSTRUCTION
DOCUMENT
06/14/24
557-21-703
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
3/16" = 1'-0"
FLOOR PLAN - PHASE II EAST
LEGEND
GENERAL NOTES
PLAN NOTES (THIS SHEET ONLY)
KEY PLAN
PROJECT
NORTH
TRUE NORTH
(DASHED)
A. CONTRACTOR TO COORDINATE WITH MECHANICAL AND
ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
1. SEE DETAILS ON SHEET S401 AND ARCHITECTURAL DRAWINGS FOR
TYPICAL INTERIOR METAL WALLS STUD FRAMING DETAIL
2. 8" THICK CONCRETE SLAB WITH #4 REBAR AT 12" O.C SPACING AT MID-
DEPTH OF SLAB, EACH WAY. SEE E10/S501 FOR ADDITIONAL INFORMATION.
PROVIDE CONSTRUCTION / CONTROL JOINTS IN SLAB-ON-GRADE TO
DIVIDE SLAB INTO RECTANGULAR AREAS 144 SF OR LESS. AREAS SHALL
BE APPROXIMATELY SQUARE AND HAVE NO ACTUE ANGLES. SEE DETAIL
C9/S501 FOR ADDITIONAL INFORMATION.
3. MECHANICAL UNIT PER MECHANICAL DRAWINGS. MAXIMUM WEIGHT OF
UNIT NOT TO EXCEED 4300 LBS WITH MAXIMUM DIMENSIONS OF 30'-4" x 7'-2" x 5'-2" (L X W X H). SEE DETAILS ON SHEET S501 FOR ANCHORAGE
INFORMATION.
4. BIDDER TO DESIGN AND INSTALL CHAIN LINK FENCE AROUND MECHANICAL
UNIT. COORDINATE WITH ARCHITECTURAL AND MECHANICAL DRAWINGS
FOR ADDITIONAL INFORMATION.
Revisions: Date: 40 OF 102
METAL STUD WALL TYPES
DRIVE PIN SPACE
AT TRACKS, UNO
MAX WALL
HEIGHT
8'-0"
STUD
DEPTH
3-5/8" 362S137 - 33
362S137 - 33
362S137 - 33
362S137 - 33
STUD
SPACING
16" OC
STUD TYPE
12" OC
16" OC
13'-6"
24" OC
16" OC
24" OC
METAL FRAMING NOTES:
1. METAL FRAMING USED SHALL CONFORM TO THE SPECIFICATIONS OUTLINED IN THE GENERAL NOTES
IN ADDITION TO REQUIREMENTS NOTED HERE.
2. METAL FRAMING AND STRAP BRACING SHALL BE GALVANIZED UNLESS NOTED OTHERWISE
CONFORMING AS FOLLOWS:
12, 14, 16 GAGE ASTM A653, QUALITY SQUARE GRADE 50, CLASS 1
18, 20 GAGE ASTM A653, QUALITY SQUARE GRADE 33.
3. ALL STUDS AND STUD GROUPS SHALL BE LATERALLY SUPPORTED TO PREVENT WEAK AXIS BUCKLING BY CONNECTING EACH FLANGE TO GYPSUM WALLBOARD. WALLS WHICH HAVE SHEATHING CONNECTED
ON ONE SIDE ONLY SHALL HAVE UNSHEATHED FLANGES LATERALLY SUPPORTED PER DETAIL.
4. TRACK SECTIONS SHALL BE UNPUNCHED WITH GAGE MATCHING STUDS, AND HAVE LEAST 1"
FLANGES.
5. SCREWS TO BE #8 SIZE, UNLESS NOTED OTHERWISE.
6. WALL FRAMING:
TWO STUD MINIMUM SHALL BE PROVIDED AT THE END OF ALL WALLS AND AT EACH
SIDE OF ALL OPENINGS. SEE B10/S401 FOR FRAMING OF OPENINGS, UNLESS NOTED
OTHERWISE.
7. SEE DETAIL E6/S401 FOR REQUIRED BRIDGING.
8. SEE ARCHITECTURAL DWGS FOR SIZING AND DETAILING OF INTERIOR NON-BEARING WALLS.
9. TRACK CONNECTED TO CONCRETE OR STRUCTURAL STEEL SHALL BE FASTENED WITH .157" MINIMUM DIAMETER DRIVE PINS AT SPACING PER TABLE. SEE E7/S401 FOR STUD CONNECTION AT BOTTOM.
10. SEE E8/S401 FOR STUD CONNECTION TO (E) STRUCTURE AT TOP.
17'-3"3-5/8" 362S200 - 43
362S162 - 4316" OC
10" OC
24" OC
C
/S
WALL STUDS PER
E10/S401, TYP
STUD GROUP, EACH SIDE
OF OPNG SEE D9/S401
HEADER & SILL C10/S401
3'-3" MAX
"H a"
"H b"
"H o"
NOTE:
• "Ha" = WALL HEIGHT ABOVE OPENING
• "Hb" = WALL HEIGHT BELOW OPENING
• "Ho" = OPENING HEIGHT
JAMB STUDS, PER D9/S401
L 1 1/2 x 5 LLH, SAME GAGE AS STUD, LENGTH = STUD WIDTH LESS 1/2"
TRACK SAME GAGE AS STUD W/
1-1/4" WIDE FLG MIN
USE (3) #8 SCREWS
TO ATTACH ANGLE TO STUD WEB
NOTES:
1. STUD WEBS SHALL BEAR AGAINST TRACK WEBS.
2. ATTACH ANGLE CLIP TO CONC SLAB WITH (2) 0.157" DIA DRIVE PINS, 3/4" MIN. EMBEDMENT
& 4" MIN SPACING REQD.
(E) WALL STUD FRAMING
TO REMAIN, TYP.
(E) JAMB STUD AT OPENING
TO REMAIN, TYP
(E) LIGHT GAUGE HEADER
TRACK/BEAM TO REMAIN.
MAX.
4'-0"
DETAIL A: INFILL DETAIL
AT EXISTING DOOR
DETAIL B: INFILL DETAIL
AT EXISTING WINDOW
(E) WALL FRAMING TO
REMAIN.
(E) JAMB STUD AT WALL
OPENING TO REMAIN, TYP
(E) SILL TRACK TO REMAIN
MAX.
4'-0"
WALL FINISH PER ARCH
V
IF
7' -0
M
A X
INFILL STUDS TO MATCH (E) STUD FRAMING,
362S162-33 STUDS @ 16" O.C SPACING (MIN.). ATTACH
STUD FLANGES TO TRACK W/ #8 SCREWS, TYP.
FRAMING NOTE:
• "XXX" REPRESENTS STUD/TRACK SIZE.
SIZE TO MATCH EXISTING STUD FRAMING.
PROVIDE XXXT150-33 TRACK AT TOP &
BOT. FASTEN TOP TRACK WEB TO (E)
TRACK W/ #8 SCREWS @ 8" O.C. CENTER
SCREWS ON TRACK.
(E) LIGHT GAUGE HEADER
TRACK/BEAM TO REMAIN.
PROVIDE XXXT150-33 TRACK AT TOP &
BOT. FASTEN TRACK WEB TO (E) TRACK
WEB AT TOP W/ #8 SCREWS @ 8" O.C.
ATTACH BOTTOM TRACK TO (E) SLAB W/
0.157" DIA. HILTI XU PAFS @ 8" O.C.
SPACING, 1" MIN. EMBED, 4" MIN CONC.
SLAB THICKNESS REQUIRED.
INFILL STUDS PER DETAIL A.
L 1-1/2" X 1-1/2"X 97 MIL ANGLE CLIP
LENGTH = STUD WIDTH LESS 1/2"
FASTEN EACH LEG TO STUD FRAMING
WITH (3) #8 SCREWS, EACH LEG
SEE NOTE FOR THICKNESS
HEADER TRACK
JAMB STUDS PER D9/S401
SILL TRACK SAME AS HEADER
TRACK WHERE OCCURS
L 1-1/2" X 1-1/2" X 43 MIL ANGLE CLIP
LENGTH = STUD WIDTH LESS 1/2"
FASTEN EACH LEG TO STUD FRAMING
WITH (3) #8 SCREWS, EACH LEG
FRAMING NOTES:
1. SEE C9/S401 FOR JAMB STUD TOP CONNECTION.
2. SEE D10/S401 FOR JAMB STUD BOTTOM CONNECTION.
HEADER TRACK SCHEDULE:
* WHERE "Ha" IN DETAIL B10/S401 IS
10'-3" MAX. MIN HEADER SIZE =
362T200-54 (50 KSI) SINGLE TRACK.
* WHERE "Ha" IN DETAIL B10/S401 IS
6'-6" MAX. MIN HEADER SIZE =
362T150-54 (50 KSI) SINGLE TRACK.
362S162-43 STUD
TYPE 2: JAMB STUD
LENGTH = 13'-6" MAX
TYPE 1: JAMB STUD
LENGTH = 17'-3" MAX
362S162-43 NESTED STUD + 362T150-43 TRACK
FASTEN TRACK FLANGES TO STUD W/ #8
SCREWS AT 8" OC ALONG STUD LENGTH
WALL STUD PER E10/S401
CONT XXXT125-33 W/ #8
SCREW EA SIDE TO EA STUD,
WHERE XXX = DEPTH OF STUD
(1) 0.157" DIA HILTI XU PAF W/ 3/4" EMBED,
SEE E10/401 FOR MAX SPACING
3/ 4"
G A
P
CONT 43T MIL (33 KSI) TRACK TO
MATCH STUD WIDTH, PROVIDE
LONG SLOTTED HOLE PER EL
#8 SCREW EACH,
SIDE, LOC AT CENTER OF SLOT
(1) 0.157" DIA HILTI XU PAFS AT EA
STUD W/ MIN 3/4" EMBED, LOC
WITHIN 2" OF STUD
T O
S C
R E
W
1/
2" M
IN
T
/ S T
U D
A T
T A
C G
E D
T O
W A
LK
3/
4" C
LR
O
F A
N Y
S H
T H
G
WALL STUD PER E10/S401
ELEVATION OF SLOTTED TRACK
NTS
NOTE:
1. DO NOT FASTEN ARCHITECTURAL
FINISHES TO DEFLECTION TRACK.
M
IN
1/
4"
1/
4"
3/
4"
1/ 2"
M
IN
(1) 0.157" DIA HILTI XU PAFS W/ MIN 3/4" EMBED
JAMB STUD PER D9/S401
CLIP DETAIL
NTS
3/
4"
3/ 4"
G A
P
FRAMING NOTES:
1. FOR WALL STUDS WITH 17'-3" HEIGHT:
MINIMUM CLIP THICKNESS = 68 MIL (50 KSI)
MINIMUM REQUIRED # OF CLIPS = 2 CLIPS, (1)
CLIP PER SIDE OF JAMB.
2. FOR WALL STUD WITH 13'-6" HEIGHT:
MINIMUM CLIP THICKNESS = 97 MIL (50 KSI)
MINIMUM REQUIRED # CLIPS = 1 CLIP
JAMB DEPTH - 1/2"
1'- 1"
3"
E Q
E Q
7/
8"
S
LO
T
EQ EQ
INSTALL (CLIPS) WITHIN DEFLECTION
TRACK, DO NOT FASTEN JAMB TO
DEFLECTION TRACK
DEFLECTION TRACK PER E8/S401
SEE FRAMING NOTE FOR CLIP THICKNESS
AND NUMBER OF CLIPS, FASTEN EACH CLIP TO
JAMB W/ (3) #8 SCREWS, CENTER SCREWS
IN SLOT, SEE CLIP DETAIL FOR ADDL INFO
L16 GA x 1 1/2 x 1 1/2
BRIDGE CLIP, TYP
NOTES:
1. BRIDGING IS REQUIRED FOR LOADINGS APPLIED BEFORE
SHEATHING IS ATTACHED TO BOTH FLANGES. BRIDGING
PROVIDES RESISTANCE TO ROTATION CAUSED BY WIND
LOADING, AND RESISTANCE TO BOTH ROTATIONAL AND MINOR
AXIS BENDING CAUSED BY AXIAL LOADING.
2. BRIDGING SHALL BE EITHER WELDED OR SCREWED AS SHOWN.
(4) SCREWS
18 GA BRIDGING
CHANNEL @ 4'-0" OC
VERT MAX, TYP
16 GA 1/2
37358
A
A
F O
P R
N I
S E
S O
S T
WFO
A E T
E E
L
NE
I G
N
R
N
SH
I
O
N
G T
GNEAR
U T C
U R T S
E R
NI
E
P A U L
N
AT
HAN CRO
R E
K C
L
728 134th Street SW, Suite 200 Everett, Washington 98204 Ph: 425.741.3800 www.reidmiddleton.com © Copyright 2024 Reid Middleton, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
6/14/
S401
TYPICAL LIGHT-GAUGE FRAMING
009A
SAH EP
CONSTRUCTION
DOCUMENT
06/14/24
557-21-703
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
NTS E10METAL FRAMING NOTES
NTS B10TYPICAL OPENING ELEVATION IN NON-BEARING WALL
NTS D10JAMB STUD CONNECTION TO CONCRETE SLAB
NTS B9TYPICAL OPENING INFILL IN NON-BEARING WALL
NTS C10TYPICAL NON-BEARING HEADER CONNECTION
NTS D9JAMB STUD CONFIGURATION
NOTE:
1. SEE D10/S401 FOR JAMB STUD ATTACHMENT TO SLAB.
NTS E7WALL STUD TYPICAL CONNECTION AT TOP
NTS E8WALL STUD TYPICAL CONNECTION AT TOP
NTS C9JAMB STUD CONNECTION AT TOP TO (E) STRUCTURE
NTS E6TYPICAL BRIDGING DETAILS
Revisions: Date: 41 OF 102
SCHEDULE *
1/4 3
ROD DIAMETER "D" (IN) "A" (IN)
4 1/2
5/8 5 5/8
3/4 6 1/2
7/8 6 1/2
1 6 1/2
ROD DIAMETER "D"
"A
(M
IN
IM
U
M
P R
O
JE
C T
IO
N
THREADED ROD W/ MATCHING NUT AND
WASHER AND CHEMICAL ADHESIVE. SEE
NOTES IN DETAIL C10/S501.
TOP OF
CONCRETE
GROUT (WHERE INDICATED)
1/2
VERIFY MINIMUM EMBEDMENT DEPTH "A"
WITH MANUFACTURER. THE GREATER
EMBEDMENT DEPTH SHALL GOVERN. DRILL
SIZE AND TYPE SHALL BE PER
MANUFACTURER'S RECOMMENDATION.
NOTES:
1. FINAL ANCHOR REQUIREMENTS TO BE DETERMINED AFTER ACCEPTANCE OF
CERTIFIED EQUIPMENT DRAWINGS.
2. FILL EACH HOLE IN EQUIPMENT BASE WITH AN ANCHOR. ADDITIONAL ANCHORS BEYOND
THE (4) MINIMUM MAY BE REQUIRED. VERIFY HOLE SIZE WITH THE EQUIPMENT DRAWINGS
PRIOR TO DRILLING ANCHORS. WHERE A LARGER HOLE SIZE IS USED, A LARGER ANCHOR
SHOULD BE PROVIDED. SEE B10/S501 FOR ADDITIONAL INFORMATION.
P E
R E
/S
1'-0"
(MIN)
EQUIPMENT
ANCHOR EQUIPMENT BASE TO CONC SLAB WITH
MINIMUM (4) 5/8" DIA (ASTM F1554 GR 36) HOT-DIPPED
GALVANIZED EPOXY ANCHORS, LOCATE (1) ANCHOR
AT EACH CORNER. HILTI HY-200 EPOXY OR EQUAL,
SEE S001. SEE NOTES 1 AND 2.
TOP OF
CONCRETE PAD
GRADE LEVEL
LOCATE ANCHOR IN
ACCORDANCE W/ EQUIPMENT
MANUFACTURER DRAWINGS
UNIT FRAME/CURB THICKNESS
ASSUMED TO BE 68 MIL (14 GA)
SEE PLAN & DETAIL
E10/S501 FOR CONC PAD
8" M
IN
B
ID
D
E R
D E
S
IG
N E
D
MIN
10"
GRADE LEVEL
4" M
IN
CHAIN LINK POST EMBEDMENT DEPTH & ADDL
FTG REINFORCING TO BE BIDDER-DESIGNED
(2) CONT #4 REBAR AT BOT (MIN)
CHAIN LINK FENCE & ATTACHMENT TO SLAB TO
BE BIDDER DESIGNED, CONTRACTOR TO COORD
WITH ARCH & MECH DRAWINGS FOR ADDL INFO
#4 REBAR TO MATCH SLAB
REBAR SPACING HOOK &
EMBED 2'-0" MIN INTO SLAB
CONC PAD THICKNESS &
REINFORCEMENT PER PLAN
MIN f'c = 3500 PSI REQD
(S E
E N
O T
E
1' -0
M
IN
NOTES:
1. LAP #4 REINFORCING 2'-0" AS REQUIRED.
2. DEPTH AND WIDTH MAY BE INCREASED AS REQUIRED FOR
BIDDER-DEISGNED FENCE POST EMBEDMENT.
#3 X AT FENCE
POST LOCATIONS, TYPICAL
2'-0"
CONTROL JOINT
CONSTRUCTION JOINT
1/8" MIN SAWCUT OR FORMED
CONST JT TO BE FILLED
W/ JOINT FILLER
VAPOR BARRIER OVER
SUB BASE PER
GEOTECHNICAL REPORT
SEE PLAN FOR
SLAB REINF
CUT HALF OF REINF AT CJ
NOTES:
1. CONSTRUCTION JOINT MAY BE USED AT ANY CONTROL JOINT SHOWN ON PLANS AT
CONTRACTORS OPTION.
2. REFER TO PLANS FOR SLAB THICKNESS AND REINFORCING.
3. CONTROL JOINTS TO BE SPACED AT 12'-0" ON CENTER MAXIMUM, EACH WAY. RATIO
OF DISTANCE BETWEEN CONTROL JOINTS IN EACH DIRECTION FOR A SLAB PANEL
SHALL NOT EXCEED 1.5. CONSTRUCTION JOINTS PER THIS DETAIL SHALL BE
CONSIDERED AS CONTROL JOINTS FOR CONTROL JOINT SPACING REQUIREMENTS.
S E
E P
LA
N
"t
2" CLR, TYP
D E
P T
H
1/
4" S
LA
B 1/8" MIN SAWCUT OR FORMED
CJ TO BE FILLED
W/ JOINT FILLER
1'-4" LONG SMOOTH DWL BAR @ 12"
W/ DIA = t/8, INSTALL FLUSH AGAINST
UNDERSIDE OR PERP SLAB REINF
VAPOR BARRIER OVER SUB
BASE PER GEOTECHNICAL
REPORT
37358
A
A
F O
P R
N I
S E
S O
S T
WFO
A E T
E E
L
NE
I G
N
R
N
SH
I
O
N
G T
GNEAR
U T C
U R T S
E R
NI
E
P A U L
N
AT
HAN CRO
R E
K C
L
728 134th Street SW, Suite 200 Everett, Washington 98204 Ph: 425.741.3800 www.reidmiddleton.com © Copyright 2024 Reid Middleton, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
6/14/
S501
TYPICAL CONCRETE DETAILS
009A
SAH EP
CONSTRUCTION
DOCUMENT
06/14/24
557-21-703
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
SPEES DESIGN BUILD
625 1ST AVE, STE 301
SEATTLE, WA 98104
(206) 590-2118
RAY SPEES
NTS B10TYPICAL CONCRETE ANCHOR
NTS C10TYPICAL EQUIPMENT ANCHORAGE
1" = 1'-0" E10EQUIPMENT PAD DETAIL
NTS C9TYPICAL SLAB ON GRADE JOINT DETAILS
Revisions: Date: 42 OF 102
32 5831302928272625
382120191817
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 60 61 62 63 64
IV TESTING
STAFF BREAK
CHANGE MGMT
USER
MECHANICAL
STORAGE
ELECTRICAL
CLOSET
RESTROOM
RESTROOM
RESTROOM
RESTROOM
IV SUPPORT
IV TESTING
MECHANICAL
HAC
STG
103A
TR
CORRIDOR
CR11-9
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:3
:3
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /M
E C
H B
L D
G
A
.r v t
FP101
FIRE PROTECTION - OVERALL
009A
MGH/JW NBH
CONSTRUCTION
DOCUMENTS
06/14/2024
557-21-703
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
1/8" = 1'-0"
LEVEL 1 - FIRE PROTECTION - OVERALL
Revisions: Date:
PROJECT
NORTH
TRUE NORTH
(DASHED)
SEE SHEETS FP103 FOR ENLARGED PLAN
SEE SHEETS FP102 FOR ENLARGED PLAN
6/14/2024 43 OF 102
DETAIL AREA
PROJECT
NORTH
TRUE NORTH
(DASHED)
2120191817
1 2 3 4 5 6 7
IV TESTING
STAFF BREAK
CHANGE MGMT
USER
MECHANICAL
STORAGE
ELECTRICAL
CLOSET
RESTROOM
RESTROOM
RESTROOM
RESTROOM
M A
T C
H L
IN
E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:3
:3
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /M
E C
H B
L D
G
A
.r v t
FP102
FIRE PROTECTION - WEST
009A
MGH/JW NBH
CONSTRUCTION
DOCUMENTS
06/14/2024
557-21-703
RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER - DUBLIN, GA
GENERAL NOTES
1. COMPLY WITH THE REQUIREMENTS OF THE MOST CURRENT VERSION OF NFPA 13:
STANDARD FOR INSTALLATION OF SPRINKLER SYSTEMS.
2. COMPLY WITH VA DESIGN GUIDE LINES
3. FIRE PROTECTION TO BE A DEFERRED DESIGN.
4. COORDINATE EXACT LOCATION OF PIPING & FIXTURES WITH OTHER TRADES
5. FOR THE PURPOSES OF CLEARNESS AND LEGIBILITY, DRAWINGS ARE
DIAGRAMMATIC AND FOR DESIGN INTENT ONLY. DESIGN BUILD CONTRACTOR MUST
VERIFY ALL DIMENSIONS BY FIELD MEASUREMENT BEFORE BEGINNING ANY
FABRICATION OR CONSTRUCTION.
6. CONTRACTOR SHALL INSTALL ALL EQUIPMENT IN STRICT ACCORDANCE WITH
MANUFACTURERS RECOMMENDATIONS.
7. CONTRACTOR SHALL GET APPROVAL FOR ANY EXPOSED PIPE BY VA COR PRIOR TO
INSTALLATION
KEYNOTES
1 LIGHT HAZARD LEVEL FIRE PROTECTION REQUIRED IN THIS
AREA.
NEW QUICK RESPONSE FIRE PROTECTION HEADS TO TIE INTO EXISTING FIRE
PROTECTION LINE. FINAL LOCATION AND QUANTITY WILL BE DETERMINED IN THE
IN COMPLIANCE WITH APPLICABLE NFPA CODES.
KEY PLAN
3/16" = 1'-0"
LEVEL 1 - FP NEW RCP - WEST
PROJECT
NORTH
TRUE NORTH
(DASHED)
Revisions: Date:
6/14/2024 44 OF 102
DETAIL AREA
PROJECT
NORTH
TRUE NORTH
(DASHED)
32 5831302928272625
9 10 11 12 13 14 15 16 60 61 62 63 64
IV SUPPORT
IV TESTING
103 MECHANICAL
HAC
STG
103A
TR
CORRIDOR
CR11-9
21 21
CORRIDOR
CR11-9
M A
T C
H L
IN
E
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .